ML20045F235
| ML20045F235 | |
| Person / Time | |
|---|---|
| Site: | Beaver Valley |
| Issue date: | 07/01/1993 |
| From: | Sieber J DUQUESNE LIGHT CO. |
| To: | NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM) |
| References | |
| RTR-NUREG-1394 NUDOCS 9307070118 | |
| Download: ML20045F235 (7) | |
Text
{{#Wiki_filter:-.u
- a
.a- _g Beaver Valley Power Station Shippmgport, PA 15077-0004 July 1, 1993 JOHN D. SILBER (412) 393-5255 Sernor Vice President and Fax (412) 643 8069 Ch+ef NWenr Omcer Nuclear Power Omsion U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555
Subject:
Beaver Valley Power Station, Unit No. 1 BV-1 Docket No. 50-334, License No. DPR-66 Emergency Response Data System (ERDS) In accordance with the requirements published in NUREG 1394, Revision 1, Section 3.6, " Administrative Implementation Requirements", the enclosed Data Point Library. (DPL) changes are i being submitted. The six (6) data points have undergone a change.in their unique system description. The changes were incorporated to e more closely match the Beaver Valley Power Station Operating Manual ' descriptions for these. particular data points. The change is currently in effect on the Beaver Valley Plant computers which provide the data to the ERDS computer. Any questions regarding this DPL change should be addressed to Glenn McKee at (412) 393-5778. sincerely, D. Sieber Attachments 1 cc: Mr. L. W. Rossbach, Sr. Resident Inspector l Mr. T. T. Martin, NRC Region I Administrator [ Mr. J. R. Jolicoeur, USNRC' Incident Response. Branch Mr. T. P. LaRosa, NUS Corporation /EI Division Mr. E. C. McCabe,'NRC Region 1,. Emergency Preparedness Mr. C. Z. Gordon, NRC Region 1, Emergency Preparedness Mr. G. E. Edison, Project ~ Manager Mr. M. L. Bowling (VEPCO) 1 l EUKTRK ] /} l, UTIUTYof 060077 O f"W 4 THEMMR 9307070118 930701 B 1 \\\\ PDR ADOCK 05000334 t; j F PDR
? t BEAVER VALLEY POWER STAT!DN ERDS DATA POINT LIBRARY l Dv1 ERDS INPUT Date: 06/14/93 i Reactor Unit: DV1 ~ Data feeder: PVC e NRC ERDS Parameter: CL TEMP A 7 Point ID: T0406A i Plant Spec Point Desc.: RCLA COLD TEMP TRS-RC410 Generic /Cond Dese.. STM CEN A DUTLET TEMPERATURE Analog / Digital: A 1 Engr Units / Dig States: DEGF j Engr Units Conversion: N/A i Minimum Instr Range: 0 Maximum Instr Range: 700 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: S Number Of Sensors: 1 How Processed: N/A Sensor Locations: SEE UNIQUE SYSTEM DESCRIPTION FIELD Alarm / Trip Set Points: HI ALM Q 650 DEGF/LO ALM @ 32 DEGF l 1 NI Detector Power Supply Cut-of f Power Level: N/A NI Detector Power Supply Turn-on Power Level N/A Instrument failure Mode: LOW j Temperature Compensation for DP Transmitters: N Level Reference Leg: N/A Unique System Desc.: RX. COOLANT LOOP A COLD LEG TEMPERATURE SIGNAL IS SENT TO THE MAIN CONTROL BOARD, REMOTE SHUTDOWN PANEL, AND THE PLANT AND PSMS COMPU ERS. TRB-RC-410 IS LOCATED BETWEEN RC-P 1A DISCHARGE AND THE A LOO - STOP VALVE. OP MANUAL CHAPTER 6, RM-406-1 i e
- +
BEAVER VALLEY POWER STATION ERDS DATA PolWT LIBRARY SV1 ERDS INPUT Date: 06/14/93 Reactor Unit: BV1 L Data Feeder: PVC NRC ERDS Paraneter: CL TEMP B Point ID: TD426A Plant Spec Point Desc.: RCLB COLD TEMP TRB-RC420 4 Generic /Cond Dese. STM GEN 8 OUTLET TEMPERATURE Analog / Digital: A Engr Units / Dig States: DECF Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: 700 Zero Point
Reference:
N/A i Reference Point Notes: h/A PROC or SENS: S Number Of Sensors: 1 How Processed: N/A Sensor Locations: SEE UNIQUE SYSTEM DESCRIPTION FIELD Alarm / Trip Set Point ** H1 ALM Q 650 DECF/LO ALM S 32 DEGF N! Detector Power Supply Cut-of f Power Level; N/A hl Detector Fower Supply Turn-on Power Level: h/A Instrument Failure Mode: LOW Temperature Compensation For DP Transmitters: N Level Reference Leg: N/A Unique System Dese. RX. COOLANT LOOP B COLD LEG TEMPERATURE SIGNAL IS SENT TO THE MAIN g CDNTROL BOARD, REMOTE SHUTDOWN PANEL, AND THE PLANT AWD PSMS COMPUT L95. TRB-RC-420 IS LOCATED BETWEEN RC-P-1B DISCHARGE AMD THE B LOO STDP VALVE. OP P.AMUAL CHADTER 6, RM-406-1
i 4 i BEAVER VALLEY POWER STATION ERDS DATA PolNT LIBRARY BV1 ERDS INPUT l Pete: 06/14/93 Reactor Unit: BV1 Data feeder: PVC
- ?
NRC ERDS Parameter: CL TEMP C f Point ID: TD446A r* a Plant Spec Point Desc.: RCLC COLD TEMP TRB-RC430 Generic /Cond Desc.: STM GEN C OUTLET TEMPERATURE Analog / Digital: A Engr Units / Dig States: DEGF t Engr Units Conversion: N/A [ Minimum Instr Range: O P f maimum Instr Range: 700 i Zero Point
Reference:
N/A [ Reference Point Notes: N/A ~- t t PROC or SENS: S I Nuncer Of Sensors: 1 [ ? How Pe N M: N/A Sensor SEE UNIQUE SYSTEM DESCRIPTION FIELD i AlarnVTrip 5et Points: HI ALM @ 650 DECF/LO ALM @ 32 DEGF r N1 Latector Power Supply Cut-off Power Level: N/A i N1 Detector Power Supply Turn-on Power Level: N/A + Instrument Failure Mode: LOW 'i leppe!ature Compensation f or DP Transmitters: N 'I level Reference Legi N/A unique System Dese.: RX. COOLANT LOOP C COLD LEG TEMPERATURE SIGNAL 18 SENT TO THE MAIN CONTROL' BOARD, REMOTE SHUTDOWN PANEL, AND THE PLANT AND PSMS COMPUT ; ERS. TRB-RC-430 IS LOCATED BETWEEN RC P-1C DISCHARGE AND THE C LOO STOP VALVE. OP MANUAL CHAPTER 6, RM-406-1 I I t. g, ey +-> a
+. BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY BV1 ERDS INPUT Date: 06/14/93 i n: BV1 Reactor Unit: Data Feeder: PVC b NPC ERDS Parameter: HL TEMP A Point ID: !0419A Plant Spec Point Desc.? RCLA HOT TEMP TRB-RC413' Generic /Cond Dese.: STM GEN A INLET TEMPERATURE Analog / Digital: A Engr Units / Dig States: DEGF Engr Units conversion: N/A l Minimum Instr Range: 0 Maximum Instr Range: 700 Zero Point
Reference:
N/A Ref r. ence icint Notes: N/A F50C or SENS: S Number Of Sensors: 1 How Processed: N/A j l Sensor Locations: SEE UNIQUE SYSTEM DESCRIPTION FIELD Alarm /frip set Points: HI ALM @ 650 DEGF/LO ALM @ 32 DEGF N1 Detector Power Supply Cut-off Power Level: N/A W1 Detector Poser Supply Turn-on Power Level: N/A l fattrument Failure Mode: LOW Tempe, ature Compensation f or DP.Transmittern: N Level Reference Leg: N/A i Unique System Desc.: RX. COOLANT LOOP A HOT LEG TEMPERATURE SIGNAL IS SENT TO THE PAIN O, ONTROL BOARD, P. EMOTE SHUTDOWN PANEL, AND THE PLANT AND PSMS COMPUTE ' RS. TRB-RC-413 IS LOCATED BETWEEN A LOOP STOP VALVE AND COOLANT IN ' ! T 'l0 SG A. OP MANUAL CHAPTER 6, RM 406-1 l
_ ~ -. . -.. ~.. n ~.. 4 BEAVER VALLEY ' POWER STATION ERDS DATA POINT LIBRARY ~ BV1 ERDS INPUT Date: - 06/14/93 Reactor Unit: BV1 l I Data Feeder: PVC NRC ERDS Parameter: HL TEMP B I Point ID: T0439A ] s Plant Spec Point Dese.: RCLB HOT TEMP TRB-RC423 l Generic /Cond Dese.: STM GEN B INLET TEMPERATURE l t Analog / Digital: A l ) Engr Units / Dig States: DEGF i i Engr _ Units Conversion: N/A j Minimum Instr Range: 0 l Maxiasn Instr Ruige: 700 2ero Polnt
Reference:
N/A f* Reference Point Notes: N/A %j PROC or SENS: S e Number Of Sensors: 1 [ -ii How Processed: N/A f Sensor Locations: SEE UNIQUE SYSTEM DESCRIPTION FIELD [ Alarm / Trip Set Points: HI ALM G 650 DEGF/to ALM a 32 DEGF f NI Detector Power Supply Cut-off Power Level: N/A HI Detector Power Supply Turn-on Power Level: N/A t instrtruent Failure Mode: LOW Tepperature Compensation for DP Transmitters: N lj Level Reference Leg: N/A 5 Unique System Dese.: RX. COOLANT LOOP B HOT LEG TEMPERATURE $!GNAL 'IS SENT TO THE 'HAIN C' ONTROL BOARD, REMOTE SHUTDOWN PANEL, AND THE PLANT AND PSMS COMPUTE RS. TRB-RC-423 !S LOCATED BETWEEN B LOOP STOP VALVE AND COOLANT IN-T TO SG B. OP MANUAL CHAPTER 6, RM-4061 i i I l I e -4 .4-
b
- i t
BEAVER VALLEY POWER STAT 10N ERDS DATA PolNT LIBRARY l BV1 ERDS INPUT Date: 06/14/93 Reactor Unit: BV1 ~> Data Feeder: PVC i i hRC ERDS Paraneter: HL TEMP C -{ f Point ID: TD459A f Plant Spec Point Desc. RCLC HOT TEMP . TRB-RC433 Generic /Cond Dese.: STM GEN C INLET TEMPERATURE Analog / Digital: A i Engr Units / Dig States: DEGF Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: 700 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: Nteter of Sensors: 1 How Processed: N/A Sensor Locations: SEE UNIQUE SYSTEM DESCRIPTION FIELD i i AlarnvTrip Set Points: HI ALM @ 650 DEGF/LO ALM B 32 DEGF F N1 Detector Power Supply Cut-off Power level: N/A ? NI Detector Power Supply Turn on Power Level: .N/A k I instrument Failure Mode: LOW i Temperature Compensation For DP Transmitters: N Level Reference Leg: N/A .r unique System Dese.: RX. COOLANT LOOP C HOT LEG TEMPERATURE SIGNAL IS SENT TO THE MAIN C ONTRDL BOARD, REMOTE SHUTDOWN PANEL, AND THE PLANT AND PSMS COMPUTE' RS. TRB RC-43315 LOCATED BETWEEN C LOOP STOP VALVE AND COOLANT IN T TO SG C. OP MANUAL CHAPTER 6, RM-406-1 i i i l 1 l i ,--.____r - -. - -}}