Emergency Diesel Generator Appendix A - References Rev 3/16 1
USNRC HRTD APPENDIX A - REFERENCES Part A USNRC Regulatory Documents 1 Criteria and Regulations
- Atomic Energy Commission General Design Criteria Criteria 38, 39, 49
- U. S. Code of Federal Regulations Table 10 - Energy Part 50 - Domestic Licensing of Production Facilities Sections 10, 22, 23, 24, 36, 54, 55, 56, 57, 63, Appendix A & B Regulatory Guides 1.108 - Periodic Testing of Diesel Generator Units Used as Onsite Electric Power Systems at Nuclear Power Plants 1.118 - Periodic Testing of Electric Power and Power Protection Systems 1.137 - Fuel-Oil Systems for Standby Diesel Generators 1.155 - Station Blackout 1.160 - Monitoring the Effectiveness of Maintenance at Nuclear Power Plants 1.29 - Seismic Design Classification 1.32 - Criteria for Safety Related Electric Power Systems for Nuclear Power Plants 1.6 - Independence Between Redundant Standby (Onsite) Power Sources 1.75 - Physical Independence of Electric Systems 1.89 - Environment Qualifications of Certain Electric Equipment to Safety for Nuclear Power Plants 1.9 - Selection, Design, Qualification, and Testing of Emergency Diesel Generator Units 1.93 - Availability of Electric Power Sources Part B Categorical References and Case Histories
- 1. Diesel Engine - Mechanical Failures and Design Issues
- 10CFR21-0095 Report, 2008-10-21 Defective Ingersol-Rand Series 89 Air Start Motors
- Information Notice 2008-05 Fires Involving Emergency Diesel Generator Exhaust Manifolds (FM OPs)
Emergency Diesel Generator Appendix A - References Rev 3/16 2
USNRC HRTD
- Information Notice 2007-27 Recurring Events Involving Emergency Diesel Generator Operabiity (Various)
- 10CFR21 Report, 2007-04-09 FM OP Diesel Engine Cam Roller Bushing Failures (Incorrect Material Hardness)
- 10CFR21 Reports, 2006-12-22 and 2007-01-08 New Woodward Governor Digital Reference Unit (DRU) Setup to Address Unevaluated Failure Mode
- 10CFR21 Report, 2006-06-13 Defective Nordberg EDG Valve Seat Inserts (Improper Size Inserts May Drop from Head into Cylinder)
- 10CFR21 Report, 2005-09-16 Falling Isoprene EDG Governor Drive Couplings on Transamerica DeLaval EDGs at 6 Nuclear Power Plants
- Information Notice 98-43 Leaks in the Emergency Diesel Generator Lubricating Oil and Jacket Cooling Water Piping
- Information Notice 97-41 Potentially Undersized EDG Oil Coolers
- 2. Emergency Diesel Generator - Electrical and Controls Related Failures
- Information Notice 2010-23 Malfunctioning EDG Speed Switch Circuits
- Information Notice 2010-09 Importance of Understanding Circuit Breaker Control Power Indications
- Information Notice 2007-36 Emergency Diesel Generator Voltage Regulator Problems
- Information Notice 2007-09 (EDG) Service Equipment Operability under Degraded Voltage Conditions
- 10CFR21 Report, 2006-12-16 EDG MCC Circuit Breaker Design Set Point Low (Loss of Cooling Fans, etc, for SACM EDG)
Emergency Diesel Generator Appendix A - References Rev 3/16 3
USNRC HRTD
- 10CFR21 Report, 2005-04-12 Defective Woodward Governor Compensating-Type EG Series Actuators (Null Voltage Shift)
- 10CFR21 Report, 2004-04-23 and 2006-01-23 Defective IC Chips in Some Woodward Governor DRUs May Result in Erratic Speed Control
- 3. Emergency Diesel Generator Failures Resulting from Maintenance/ Painting/
Cleaning/ Miscellaneous
- Information Notice 2009-14 (Painting Activities, Cleaning Agents Render EDGs and Other Systems Inoperable)
- Information Notice 98-41 Spurious Shutdown of Emergency Diesel Generators from Air Start Design Oversight
- 4. Site Switchyard, Electrical Distribution Issues (Including Aging)
- Information Notice 2010-26 (Failures in Submerged Electrical Cables)
- Information Notice 2009-10 (Large) Transformer Failures - Recent Operating Experience
- Generic Letter 2007-01 (Underground Power Cable Failures that Disable Accident Mitigation Systems)
- Information Notice 2005-20 (Site Electrical Distribution Failures)
- Information Notice 2005-04 (Single Point Vulnerability of Redundant Electrical Safety Buses to Fire and Failure)
- Information Notice 2004-19 Problems with Back-Up Power Supplies of Emergency Response Facilities
- 5. Fires and Fire Protection Issues Potentially Affecting Emergency Systems
- Information Notice 2007-23 Inadvertent Discharge of Halon 1301TM Fire Suppression System (Incorrect or Outdated Procedures)
- Information Notice 2007-19 Fire Protection Equipment Recalls and Counterfeit Notices
Emergency Diesel Generator Appendix A - References Rev 3/16 4
USNRC HRTD
- Information Notice 2007-17 Fires at Nuclear Power Plants Involving Fire Protection Administration and Design Controls
- Information Notice 2005-32 Product Alert for Fire Hydrants (Hardened, Corrosive Grease Issue)
- Information Notice 2002-27 Recent Fires at Commercial Nuclear Power Plants
- Information Notice 99-28 Recall of Star Brand Fire Protection Sprinkler Heads
- Information Notice 99-05 Inadvertent Discharge of CO2 Fire Protection System and Gas Migration (63 Deaths Since 1975)
- Information Notice 97-82 Inadvertent Halon Fire Suppression System Actuation Due to a Camera Flash
- Information Notice 97-72 Potential for Failure of Omega Series Sprinkler Heads
- 6. Grid Reliability and Potential Impact on Nuclear Power Plants
- Generic Letter 2006-02 Grid Reliability, Risk Assessment, NPP-TSO Communications, Maintenance Schedule Considerations
- Information Notice 2006-06 Loss of Offsite Power and Station Blackout More Probable during Summer
- Information Notice 2005-16 (LOOP 3-Unit Trip)
- 7. Fuel Oil and Lubricating Oil Issues
- Information Notice 2009-02 Biodiesel in Fuel Oil Could Adversely Impact Diesel Engine Performance
- Information Notice 2006-22 Potential Impact of Ultra-Low Sulfur Diesel Fuel on Diesel Engines
- Information Notice 96-67 Vulnerability of EDGs to Fuel Oil/Lubricating Oil Incompatibility
Emergency Diesel Generator Appendix A - References Rev 3/16 5
USNRC HRTD PART C U.S. Nuclear Regulation Commission Publications
- 1. Regulatory Guide 1.9, Rev. March 2007.
- 2. A Reliability Program for Emergency Diesel Generators at Nuclear Power Plants, NUREG/CR-5078, Vol. 2, Prepared by Science Applications International Corporation and Sandia National Laboratories, Pub. By USNRC.
- 3. NRC Inspection Manual, Part 9900, Technical Guidance Degraded Conditions, Operability, et.al; NUREG 0800, Standard Review Plan for the Review of Safety Analysis Reports for Nuclear Power Plants.
- 4. Performance of Emergency Diesel Generators in Restoring Power to Their Associated Safety Busses - A Review of Events Occurring at Power Plants, AEOD-591-01.
- 5. NRC Inspection Manual, Inspection Procedure 71707, Operational Safety Verification.
- 6. NRC Inspection Manual, Inspection Procedure 17710, Engineered Safety Feature Walkdown.
- 7. NRC Inspection Manual, Inspection Procedure 62703, Monthly Maintenance Observation.
- 8. NRC Inspection Manual, Inspection Procedure 61726, Surveillance Observation.
- 9. NRC Inspection Manual, Inspection Procedure 2515/93, Inspection for Verification of Quality Assurance Requests Regarding Diesel Generator Fuel Oil Multi-plant Action Item A-15.
- 10. Operating History Overview for Diesel Generators in Nuclear Service, USNRC Report AEOD/P401, February, 1984 PART D Commercial Codes, Standards, and Publications
- 1. IEEE Standard Criteria for Diesel Generator Units Applies as Standby Power Supplies for Nuclear Power Generating Stations, IEEE Standard 387-1995, Pub. By The Institute of Electrical Engineers, Inc., New York, NY 10017
- 2. IEEE Standard for Qualifying Class 1E Equipment for Nuclear Power Generating Stations, IEEE Standard 323-1983. Pub. By The Institute of Electrical Engineers, Inc.,
New York, NY 10017.
- 3. Standard Fuel Specifications for Diesel Fuel Oils, ASTM Designation D 975-93, Pub. By American Society for Testing and Materials, Philadelphia, PA 19103.
Emergency Diesel Generator Appendix A - References Rev 3/16 6
USNRC HRTD
- 4. Standard Test Method for Sulfur in Petroleum Products (High Temperature Method),
ASTM Designation D 1552-930 Pub. By American Society for Testing and Materials, Philadelphia, PA 19103.
Commercial codes/standards are available on the appropriate IEEE, ASTM, etc. web sites.
Part E Books and Manuals
- 1. Diesel Engineering Handbook, Karl W. Stinson, M.E.; Pub. by Business Journals Inc.,
Norwalk, CT 06855; 1980.
- 2. Fundamentals of Diesel Engines - U.S. Navy, NAVPERS; Pub. by Standards of Curriculum, Division Training, Bureau of Naval Personnel; 1951.
- 3. Diesel and High Compression Gas Engines, E. J. Kates and W. E. Luck, Pub. by American Technical Publishers, Inc., Alsip, IL 60658; 1974.
- 4. Principles of Energy Conversion, Archie W. Culp, Jr.; Pub. by McGraw-Hill Book Company; 1979.
- 5. Electric MACHINERY - The Dynamics and Statics of Electromechanical Energy Conversion, A. E. Fitzgerald and Charles Kingsley; Pub. by McGraw-Hill Book Company.
- 6. Standard Test Method for Particulate Contaminates in Aviation Fuel by Line Sampling, ASTM Designation D 2276-93; Pub by American Society for Testing and Materials, Philadelphia, PA 19103.
- 7. Standard Practice for Manual Sampling of Petroleum and Petroleum Products; ASTM Designation D 4057-88; Published by American Society for Testing and Materials, Philadelphia, PA 19103.
- 8. Standard Test Method for Free Water and Particulate Contamination in Distillate Fuels (Visual Inspection Procedures); ASTM Designation D 4176-93; Published by American Society for Testing and Materials, Philadelphia, PA 19103.
- 9. Guidelines for the Utilization of Commercial Grade Items in Nuclear Safety Related Applications (NCIG-07) EPRI Report NP-5652, Final Report, June 1988; Pub by Electric Power Research Institute, Palo Alto, CA 94304.
- 10. Diagnostic System Summary, Predictive Maintenance-Condition Monitoring Integration; Pub. by Electric Power Research, Eddystone, PA.
- 11. Woodward Controls for Generator Sets; Woodward Governor Company, Fort Collins, Co 80522; 1985.