Text
1 M I
So-~'1-9 1
. \\
D+
USAEC-HQS GTWN VU WSH
/
TLXA289 WAE197<2043JC1~032231C325002>PD 11/20/72 2039
- C
- ~wt
-~
ICS IPMVEIA MVN
~@.
~
..... J 2CZC 00222 TOVE MORRIS ILL 120 11-20 315P_CST
~i R'1S MR A GIAMBUSSO DEPUTY DIRECTOR OF REACTIV~ PROJECTS ~~
'"~
DIRECTOR APE OF
~ICENSING WUX ~ACHINE.
~
- S..
()tJf
- N L6 ATOMICH ENERGY COMMISSION W\\SH I NG TON DC M ~.*
~~} ' -
.9.J. BJEC T :.OP R. -2 5 DRESDEN NUCLEAR POWER' STAT I ON U_ N 1 T 3 n1-.
l1'f.l::'f:(J; *~, IJrc~
lHIS WILL CONF !RM A CONVERSATION wi TH MR ;i DANCE OF YOUR!
~- ~/.., $.
I A~. 1100 HOURS THIS DATE C~N<;:ERNING REACT,ORS LOW PRESSURE _sw1 TC. ~
-~~;~ \\ \\~ '.
~ING OUT.OF ~ALIBERATION~ ON
~l/L9/72 WHlLE UNIT i-WAS SHUT DOWN, I
AtAL)BERATION WAS MADE ON MAIN STEAM LINE LOW PRESSURE-SWITCHES.
CABLE 3.2.1 OF THE TECHNICAL SPE.CIFICATIONS STATE THAT THE TRIP
~VEL SETTING ON THESE SWITCHES SHOULD BE EQUAL TO OR GREATER lHAN 8 50 PS I G ** ALL FOUR PRESSURE SW I TC HES HAD TR IP SETTINGS BELOW 850 PSIG. PRESSURE SWITCHES 3-261-30A AND 308 HAD SETTING
. F 847 AND 848 PSIG *. PRESSURE SWITCHES 3-261-30C *AND 300
~D.SETTINGS OF 849 AND 848 PSIG. IN ORDER TO ELIMINATE.THIS PROBLEM*
I IN THE FUTURE.THE "AS LEFT" CALIBERATION SETTING ON THESE
~ITCHES HAS BEEN CHA~GED F~OM 85~ PLUS OR Ml~US PSIG Pl,.US OR i"11NUS 4PSIG.
W P WORDEN
~UPERINTENDENT COMMONWEALTH EDISON ORESD~N ~UCLEAR POWERSTATIQN RR 1 MORRIS ILLINOIS 430A 11-21-72
+.
l.SAEC HQS GTWN
. I