ML17046A524
Text
SECTION 12 RADIATION PROTECTION The purpose of this section is to demonstrate that radiation exposure to plant personnel and persons at the site boundary, from sources contained within the plant and on the site, will be kept as low as practicable and within applicable limits.
12.1 SHIELDING 12.1.1 Design Objectives The overall design objectives for shielding during normal operation, maintenancet refueling, and anticipated operational occurrences are:
- 1.
To ensure that external radiation exposure to all onsite personnel remain below the limits set in 10CFR20.
- 2.
To reduce the possibility of radiation induced material damage and potential equipment activation.
In addition, the shielding provided ensures that in the unlikely event of a maximum design accident, the contained activity does not result in any harmful offsite radiation exposures.
All plant areas capable of personnel occupancy are classed as one of the five zones of radiation exposure listed in Table 12.1-1.
Typical Zone I areas are the Turbine Building, and turbine plant service areas and the Control Room.
Typical Zone II areas are the outer surfaces of the containment and Auxiliary Building.
Zone II areas include the local control spaces in the Auxiliary Building, and the operating deck of the containment during reactor shutdown.
Areas designated Zone III include the reactor cavity area after shutdown and the decontamination area.
Typical Zone IV areas 12.1-1 SGS-UFSAR Revision 6 February 15, 1987
include the Sampling Room, valve galleries within the Auxiliary Building and areas outside the crane wall of the containment at power operation.
Typical Zone V areas are within the regions adjacent to the Reactor Coolant System (RCS) at power operation and the demineralizers and Volume Control Tank Rooms within the Auxiliary Building.
Shielding for the Zone III areas defined above was designed to reduce radiation levels to below 15 mR per hour, and the areas are expected to have a general radiation level that is below 15 mR per hour.
However, these areas are classified as Zone IV because small segments of lines (ranging from instrument tubing to 2-inch piping) carrying radioactive liquids penetrate the shield walls, and at contact the dose rates can exceed 15 mR per hour locally, based on the activity associated with 1 percent failed fuel. These small segments of lines are located in such a position that it is not necessary for operating personnel to have contact with them.
As such, since these areas are designed for radiation levels of less than 15 mR per hour and fall in the category of periodic occupancy, they can be classified as Zone III areas.
Radiation shielding is designed for operation at maximum calculated thermal power and to limit the normal operation radiation levels at the site boundary to below those levels allowed for continuous nonoccupational exposure.
The plant is capable of continued safe operation with 1 percent fuel element defects.
The shielding is function.
These divided functions into five categories according include the primary shielding, to the secondary shielding, the accident shielding, the fuel transfer shielding, and the auxiliary shielding.
All radiation and high radiation areas are appropriately marked and isolated in accordance with 10CFR20 and other applicable regulations except as noted in Section 6. 12. 1 of the Technical Specifications.
12.1-2 SGS-UFSAR Revision 6 February 15, 1987
12.1.1.1 Primary Shielding The primary shielding is designed for the following:
- 1.
Reduce the neutron fluxes incident on the reactor vessel to limit the radiation induced increase in transition temperature.
- 2.
Attenuate the neutron flux sufficiently to prevent excessive activation of plant components.
- 3.
Limit the gamma flux in the reactor vessel and the primary concrete shielding to avoid excessive temperature gradients or dehydration of the primary shield.
- 4.
Reduce the residual radiation from the core, reactor internals and reactor vessel to levels which will permit access to the region between the primary and secondary shields after plant shutdown.
- 5.
Reduce the contribution of radiation leaking to obtain optimum division of the shielding between the primary and secondary shields.
12.1.1.2 Secondary Shielding The main function of the secondary shielding is to attenuate the radiation originating in the reactor and the reactor coolant.
The major source in the reactor coolant is the Nitrogen -16 activity, which is produced by neutron activation of oxygen during passage of the coolant through the core.
The secondary shielding will limit the full power dose rate outside the Containment Building from radioactivity inside the containment to less than 1.0 mR per hour.
12.1-3 SGS-UFSAR Revision 6 February 15, 1987
12.1.1.3 Accident Shielding The main purpose of the accident shielding is to ensure safe radiation levels outside the Containment Building following a maximum design accident.
12.1.1.4 Fuel Transfer Shielding The fuel transfer shielding permits the safe removal and transfer of spent fuel assemblies and control rod clusters from the reactor vessel to the spent fuel pool.
It is designed to attenuate radiation from spent fuel and control clusters to less than 2.5 mR per hour at the refueling cavity water surface and less than 1.0 mR per hour in the Auxiliary Building.
12.1.1.5 Auxiliary Shielding The function of the shielding is to protect personnel working near various system components in the Chemical and Volume Control System (CVCS), the Residual Heat Removal (RHR) System, the Waste Disposal System (WDS) and the Sampling System.
The shielding provided for the Auxiliary Building is designed to limit the dose rate to less than 2.5 mR per hour in normally occupied areas, and at or below 15.0 mR per hour in periodically occupied areas.
The design criteria for radiation protection in the Auxiliary Building following a
loss-of-coolant accident (LOCA) is as follows:
- 1.
The RHR compartment has sufficient shielding to assure that the 8-hour integrated dose outside the RHR compartment will not exceed 3 rem (after the first 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> following the accident).
- 2.
The RHR compartment shielding provides for access for manual isolation of pumps.
12.1-4 SGS-UFSAR Revision 6 February 15, 1987
12.1.2 Design Description 12.1.2.1 Primary Shielding The primary shielding consists of the reactor internals, the reactor vessel wall, and a concrete structure surrounding the reactor vessel.
The primary shielding immediately surrounding the reactor vessel consists of a reinforced concrete structure extending from the base of the containment to an elevation of 104 feet.
The lower portion of the shield is a minimum thickness of 7 feet of concrete and is an integral part of the main structural concrete support for the reactor vessel.
It extends upward to join the concrete cavity over the reactor.
This cavity is approximately rectangular in shape, and has concrete sidewalls which are 4 feet - 0 inches thick adjacent to areas in which fuel is transported.
The primary concrete shielding is air cooled to prevent overheating and dehydration from the heat generated by radiation absorption in the concrete.
Eight "windows" have been provided in the primary shield for insertion of the out-of-core nuclear instrumentation.
Cooling for the primary shield concrete, nuclear instrumentation, and vessel supports is provided by circulating 18,000 cfm of containment air between the reactor vessel wall and the surrounding concrete structure.
12.1.2.2 Secondary Shielding The secondary shielding surrounds the reactor coolant loops and the primary shielding.
It consists of interior walls within the Containment
- Building, the operating floor and the reactor containment building itself.
The Containment Building also serves as the accident shield.
The lower portion of the secondary shielding above grade consists of the 4 foot - 6 inch thick cylindrical portion of the reactor 12.1-5 SGS-UFSAR Revision 6 February 15, 1987
containment and a minimum of 3 feet thick concrete interior walls surrounding the reactor coolant loops.
The secondary shielding will reduce the radiation levels in the primary loop compartment to 15 mrem per hour outside the polar crane wall and to a level of less than 1. 0 mR per hour outside the Reactor Containment Building.
Penetrations in the secondary shielding are protected by supplemental shielding.
The secondary shielding design parameters are listed in Table 12.1-2.
12.1.2.3 Accident Shielding The accident shielding consists of the 4 foot -6 inch reinforced concrete cylinder capped by a shallow, reinforced concrete dome 3 feet -6 inches thick.
Supplemental shielding has been provided for the containment penetrations.
Shielding for the equipment access hatch is credited only for the inner access hatch which is modeled as a 1-1/4" steel plate for all postulated accident scenarios. Smaller penetrations associated with piping and electrical cables are directed into the penetration area which is shielded with a minimum of 24 inches of concrete.
The Control Room is protected with concrete sidewalls 24 inches thick, and a concrete roof 24 inches thick.
The accident shielding design parameters are listed in Table 12.1-3.
12.1.2.4 Fuel Transfer Shielding The refueling cavity is formed by the upper portions of the primary shield concrete, and other sidewalls of varying thicknesses.
is used for storing the 12.1-6 SGS-UFSAR A portion of the cavity Revision 29 January 30, 2017
upper and lower internals packages and is shielded with concrete walls 4 feet thick.
The remaining walls vary from 4 feet to 6 feet thick, and provide the shielding required for handling spent fuel.
The refueling cavity, flooded with borated water to elevation 128 feet-8 inches during refueling operations, provides a
temporary water shield above the components being withdrawn from the reactor vessel.
The water height during refueling is approximately 24 feet-8 inches above the reactor vessel flange.
This height ensures that a minimum of 10 feet-0 inch of water will be above the top of a withdrawn fuel assembly.
Under these conditions, the dose rate is less than 2. 5 mR per hour at the water surface.
The spent fuel assemblies and control rod clusters are remotely moved from the reactor containment through the horizontal spent fuel transfer tube and placed in the spent fuel pool.
- Concrete, 4 feet-6 inches thick on sides and bottom, and 5 feet thick on top shields the spent fuel transfer tube.
This shielding is designed to protect personnel from radiation during the time a spent fuel assembly is passing through the main concrete support of the reactor containment and the transfer tube.
Radial shielding during fuel transfer is provided by the water and concrete walls of the fuel transfer canal.
An equivalent of 6 feet of concrete is provided to insure a maximum dose value of
- 1. 0 mR per hour in the Auxiliary Building areas adjacent to the spent fuel pool from a spent fuel assembly in the fuel transfer tube.
Spent fuel is stored in the spent fuel pool which is located adjacent to the Containment Building.
Radial shielding for the spent fuel is provided by 6-foot thick concrete walls plus a
minimum of 10 1/2 inches of water.
The pool is flooded with borated water to a level such that the water height above the stored fuel assemblies is approximately 25 feet.
12.1-7 SGS-UFSAR Revision 6 February 15, 1987
The refueling shielding design parameters are listed in Table 12.1-4.
12.1.2.5 Auxiliary Shielding The auxiliary shielding consists of concrete walls around certain components and piping which process reactor coolant.
In some cases, the concrete block walls are removable to allow personnel access to equipment during maintenance periods.
Each equipment compartment is individually shielded so that compartments may be entered without having to shut down and, possibly, to decontaminate the adjacent system.
The shielding material provided throughout the Auxiliary Building is ordinary concrete, with some lead and steel supplemental shielding.
auxiliary shielding provided is tabulated in Table 12.1-5.
The principal 12.1.3 Source Terms The residual heat removal loop radiation sources and evaluation parameters are developed in Section 15. 4. 1.
The radiation sources which are assumed to be released to the containment following a
DBA LOCA with fuel failure per Regulatory Guide 1.183 are developed in Section 15.4.1.
12.1.3.1 Miscellaneous Materials The Salem operating licenses authorize PSE&G to receive, possess, and use in amounts required any byproduct, source, or special nuclear material without restriction to chemical or physical
- form, for sample analysis, instrument calibration, or other uses associated with radioactive apparatus or components.
This authorization is provided pursuant to 10CFR Parts 30, 40, and 70.
Radioactive sources are inventoried and leak checked as required by Technical Specification 3/4.7.8.
12.1-8 SGS-UFSAR Revision 29 January 30, 2017
A source locker under the control of Radiation Protection provides secure storage and administrative control for licensed and non-licensed sources.
Sources may be stored and secured in other station locations if they are too for the source locker or if their presence in the source locker would an unnecessary exposure hazard or if the source/ sources is/are installed as part of a system such as the RMS or for interim storage as directed by RP.
12.1.3.1.1 and Secondary Neutron Sources Neutron source assemblies may be utilized in the core.
These will consist of assemblies containing primary and secondary source rods.
The rods in each assembly will be fastened to a hold down plate at the top end.
The hold down is similar to that of the burnable poison and plugging device assemblies.
The secondary sources (Sb-Be) are initially nonradioactive, a neutron source only after activation in the core.
The secondary source
- rods, 0.381 inch in diameter contain Sb-Be with an overall height of 88 inches.
Primary source rod assemblies contain of 3 source material 1. 5 inches long and alumina rods to space the capsule and fill the remainder of the rod height.
Primary source assemblies are used for initial loading and as after long shutdown when source strength has decayed to unacceptably low levels.
12.1.3.1.2 Primary Source Rod Assembly Data Source used in Unit 1 1 and Unit 2 1 loadings:
Type -
Californium Pd-Cf2o3 cermet Mfg. -
Gamma Industries - Division of Nuclear Systems Neutrons/sec. - Approximately 4 x 108 Size -Approximately 1.5 inches 0.381 inch OD same as fuel rod Encapsulation:
12.1-9 SGS-UFSAR Revision 25 October 26, 2010
Pr~ry - Savannah River National Laboratories, Type SR-CP-lx Intermediate - Savannah River National Laboratoriee, Type SR-CF-100 outer -
Same design as fuel rod Isotope WT (\\)
Cf-252 79 Cf-251 4
Cf-250 15 Cf-249 2
Shipment -
Common carrier using Gamma Industries container SISC-1, DOT-Type A-7A Primary Source uaed in Salam Unit 1 cycle 13 loading:
Type-Mfg.-
Neutrons/sec-Adapter Body Size-Encapsulation:
Primary-Intermediate-(Adapter Body)
Outer-Shipment-Isotope Cf-252 Cf-251 Cf-250 Cf-249 Triple encapsulated Californium capsule General Electric - Vallecitos Nuclear Center Approxtmately 7.5 x 108 Approximately 1.5 inches long -
0.330 inch ID and OD same as fuel rod Welded inner capsule body, Special Form Certificate Number USA/0141/S, Rev.8 Model GEN-CF-lx Inner capsule body inserted into an adapter body and closed by a press-fit inner plug same design as fuel rod Wt(\\)
80.282 3.144 10.342 6.227 MRC Model 2511-C Radioactive Shipping Container, u.s.D.O.T. Specification 7A certification 12.1.3.1.3 Reactor Vessel Flux Dosimeters As part of the reactor vessel surveillance program, a number of doaimaters are located in specimen capsules which are located about 3 inches from the vessel wall directly opposite the center portion of the core. The dosimeters permit evaluation of the neutron flux seen by the specimens and vessel wall.
12.. 1-10 SGS-UFSAR Revision 16 January 31, 1998
Note:
Number of dosimeters Total amount of contained NP-237 Total amount of contained u -238 Length of encapsulation material, in.
Diameter of encapsulation material, in.
Material used to encapsulate u-238 Material used to encapsulate NP-237 11-Np-237 11-U-238 197 mg 132 mg 0.375 0.25 Brass Stainless Staal Eight material test capsules were inserted in salem Units 1 and 2 reactor pressure vessels prior to initial plant startup.
Salem Unit 1 contained 5 Type I and 3 Type II capsules.
Salem Unit 2 was provided with all 8 Type II capsules.
Only Type II capsules contain NP-237/U-238 dosimeter blocks.
Bence, a total of eleven dosimeters were loaded in Salem Units 1 and 2 reactor pressure vessels.
To date, 2 capsules have been removed from each of the Salem Units (i.e., 1 Type I and 1 Type II capsule from Salem 1; 2 Type II capsules from Salem 2).
12.1.3.1.4 Special Nuclear Materials (SNM)
The Salem Operating License authorizes PSE&G to receive, possess and use any SRK as reactor fuel and as fission detectors in any amounts as required.
This includes, but is not limited to, incore monitoring fission chamber detectors and excore fission chamber detectors.
These detectors are considered "Licensed Material" in accordance with (January 1995) 10CFR20.1003 Definitions.
These detectors are also considered "Sealed Sources" in accordance with (January 1995) 10CFR74.4.
Special nuclear material in the form of reactor fuel will be received, stored, used and shipped in the normal operation of the nuclear plant. The facilities provided to ensure safety during these transfer and storage operations are consistent with the as low as practicable exposure guidelines.
A separate Fuel Handling Building is provided for each nuclear unit. These buildings are provided with fire detection systems, flood protection, radiation monitoring systems and facilities for cask decontamination.
movement, additional equipment During fuel 12.1-11 SGS-UFSAR Revision 16 January 31, 1998
for radiation monitoring will be available in these areas.
Portable survey instruments for radiation dose rate measurements, contamination surveys and air activity measurement will be provided during these periods. Protective clothing will be provided to personnel in these areas as conditions require.
Special Nuclear Material in the form of incore monitor fission detectors is used to monitor the neutron flux distribution within the reactor core.
These detectors are sealed units that contain Special Nuclear Material {SRM) enriched in u-235. Unirradiated detectors will be stored in a secure area which prohibits unauthorized removal or access in accordance with (January 1995) 10CFR20.1801, "Security of Stored Material." Irradiated detectors which have been removed from service may be temporarily stored in the Seal Table Room shield wall pipes.
After the detectors have decayed to acceptable levels for handling and movement in accordance with radiation protection practice (ALARA), the detectors will be removed from the shield wall pipes and stored in an acceptable radiation storage area which limits access and prohibits unauthorized removal.
Special Nuclear Material in the form of excore fission chamber detectors are used aa an independent system to monitor the neutron flux level from shutdown to full power.
This system is required for post accident monitoring and for remote shutdown monitoring capability.
These detectors are sealed units that contain Special Nuclear Material (SNM) enriched in U-235.
Irradiated excore fission detectors will be stored in a locked high radiation area. unirradiated detectors will be stored in a secure area which prohibits unauthorized removal or access is accordance with (January 1995) 10CFR20.1801, "Security of Stored Material."
12.1.3.1.5 Fuel and Fuel Handling Shipment of the fuel assemblies from the fabricating plant to the Fuel Handling Building will be by truck trailers.
Not more than 16 fuel assemblies will be delivered in any one ahipment.
The new fuel assemblies will be removed one at a time from the shipping containers by the fuel handling crane and will be checked visually for integrity and numbering and surveyed for background radiation levels and possible contamination.
12.1-12 SGS-UFSAR Revision 16 January 31, 1998
All jacti vi ties of unloading, inspecting, moving, removing, and replacing the fuel assemblies will be performed in accordance with written procedures.
Asseinblies will not be handled during severe weather conditions; for example, during periods when a hurricane or tornado watch is in effect in the vicinity of the site.
A Geiger-Mueller, or equivalent, monitor is located on the operating deck floor (Elevation 130 feet) of each Fuel Handling Building.
These monitors are described in Section 11.4.2.4.
In lieu of maintaining a criticality monitoring system as described in 10 CFR 70.24, Salem complies with the requirements of 10 CFR 50.68(b}.
In addition, personnel authorized to enter the Fuel Handling Building shall carry personnel radiation monitoring devices.
Radiation monitoring of the facility area shall be conducted on a routine basis, and portable radiation surv~y instruments shall be used during all fuel handling *operations.
Comprehensive emergency procedures have_ been written to ensure that all personnel withdraw upon the *sounding of the alarm to a designated area of safety.
Procedures are approved.by the Plant Manager and include provisions for 1nstruction of personnel and conduct of drills to familiarize them with the evacbation plan.
Portable radiation survey meters are in accessible locations fbr use in such an emergency.
Before the receipt of new fuel, all personnel associated with the fuel handling operation will have received training in Health Physics and fuel handling procedures.
- 12. 11* 4 Area Moni taring and Radiation Surveys The_, primary purpose of. the area monitors is to prevent excessive personnel expo~ure by monitoring locations within the plant. A secondary purpose is for emer_gency response assessment and to provide ra~iation data in support of the as low as *is reasonably achievable (ALARA) program and Regulatory Guide 8. 8.
Area monitors are located in the station radiologically controlled area where dose rates may be used to indicate potentially degrading plant conditions. The moni_tors provide local indication and alarms and operate horns and flashing beac*ons upon high radiation conditions.
Control Room indications and alarms are also provided.
The area monitoring system is described in Section 11. 4.
Onsite areas external to plant buildings are monitored by thermoluminescent dosi_m~ters.
12.1-13 SGS-UFSAR Revision 21 December 6, 2004
Radiation surveys are conducted to identify and control radiation sources
-associated with the operation of the Salem station.
They are also performed to mark and verify radiation area boundaries, and to determine if abnormal radiation levels exist.
The location and frequency of these routine radiation surveys are defined in the station Radiation Protection procedures. Radiation, High Radiation, and Very High Radiation Areas are posted conspicuously to ensure compliance with 10CFR20.
Radiation survey instruments are calibrated using current industry standards and guidelines.
12.1.5 Estimates of Exposure The average annual onsite person-rem exposure resulting from plant operations is approximately 409 person-rem per year for Unit 1.
This is based on operational data from 1976 through 1982 with values ranging from a low of 117 person-rem in 1977 to a high of 1027 person-rem in 1982, which included two refueling outages.
The average annual onsite person-rem exposure resulting from plant operations is approximately 16 person-rem per year for Unit 2.
This is based on data for 1981-1982, during which time no major outages occurred.
Annual dose goals based on scheduled maintenance and/or refueling activities are established by station management.
12.1-14 SGS-UFSAR Revision 15 June 12, 1996