ML14324A327
| ML14324A327 | |
| Person / Time | |
|---|---|
| Site: | Summer |
| Issue date: | 07/30/2012 |
| From: | Feehan M South Carolina Electric & Gas Co |
| To: | Office of Nuclear Reactor Regulation |
| Shared Package | |
| ML14324A264 | List:
|
| References | |
| LAR-13-02396, RC-14-0179 DC00040-122, Rev. 0 | |
| Download: ML14324A327 (162) | |
Text
ES-0412 ATTACHMENT I PAGE 1 OF 2 REVISION 5 Subject Code SOUTH CAROLINA ELECTRIC AND GAS COMPANY 004 CALCULATION RECORD Page 1 of 155 Calculation Title Calculation Number Revision Status Loss of Coolant Accident - TSC D000040-122 0
A Parent Document System Safety Class qPartial Calc. Revision ECR 50786 N/A q NN q QR SR Complete Calc. Revision Originator Discipline Organization Date XREF Number Michael Feehan AE WorleyParsons 07/30/2012 N/A CALCULATION INFORMATION Content
Description:
The calculation determines the impact of the Alternate Source Term (AST) on the new Nuclear Operations Building (NOB) VC Summer Unit 1 Technical Support Center (TSC) dose following a postulated Loss of Coolant Accident (LOCA). This analysis is performed in accordance with the requirements of Appendix A of the USNRC Regulatory Guide 1.183.
Affected Components/Calculations/Documents: FSAR Section 15.4.1 Piping Reconciliation Completed per QA-CAR-0089-18:
qThis Revision q Previous Revision N/A Contains Preliminary Data/Assumptions:
No q Yes, Affected Pages:
Computer Program Used:
q No Yes, Validated per WorleyParsons computer program validation process (others) vendors name q Yes, Validated in accordance with SAP-1040/ES-413 (ref. 3.4 & 3.5) q Yes, Validated [ES-0412]
q Computer Program Validation Calculation VERIFICATION q Continued, Attachment Scope:
Verify input, methodology, output and assure that the calculation is in compliance with ES-412 and addresses the work scope and deliverables documented in CGGS-11-114.
Verifier: M. Waselus Assigned by: P. Bunker O7/-46/C/Z-Enineerin Personnel /Date Own s Acceptance Review
/1/'
^) a.atJ -L 1-31-- Zo I Z-
- y^
?^
Verifier/Date Responsible Engineer/Date Required for all engineering work performed by contractor personnel not enrolled in the VCSNS Engineering Training Program RECORDS ct" 9 /b f7 To Records Mgmt:
AA 14AJ
/6-Z-1(4 Approval/Date Initials/Date A
Distribution: Calc File (Original)
ES-0412 ATTACHMENT I PAGE 2 OF 2 REVISION 5 SOUTH CAROLINA ELECTRIC & GAS COMPANY REVISION
SUMMARY
Calculation Number DC00040-122 Revision Number.
Summary Description Page 2 of 155 0
Initial Revision
D000040-122, Revision 0 Page 3 of 155 TABLE OF CONTENTS DESCRIPTION PAGE
1.0 INTRODUCTION
............................................................................................................................... 5 1.1 Purpose................................................................................................................................................ 5 1.2 Objective.............................................................................................................................................. 5 1.3 Acceptance Criteria............................................................................................................................. 5 1.4 Approach.............................................................................................................................................. 5 2.0 ASSUMPTIONS.................................................................................................................................. 6 3.0 COMPUTER CODES.......................................................................................................................... 8
4.0 REFERENCES
....................................................................................................................................9 5.0 DESIGN INPUTS.............................................................................................................................. 11 6.0 METHODOLOGY............................................................................................................................ 20 7.0 COMPUTATIONS............................................................................................................................ 21 7.1 Elemental and Particulate Iodine Spray Removal Coefficient Timing.............................................. 21 7.1.1 - Determination of Maximum Elemental & Particulate Iodine Concentration.......... 22 7.1.2 - Determination of Elemental & Particulate Removal Coefficient Timing................ 23 7.2 TSC Operator Dose Due to Containment Release............................................................................. 24 7.2.1 TSC Operator Dose Due to Containment Release (Design Basis Source Terms) Attachment 7......24 7.3 TSC Operator Dose Due to ESF Leakage......................................................................................... 26 7.3.1 TSC Operator Dose Due to ESF Leakage (Design Basis Source Terms) Attachment 8................... 26 7.4 TSC Operator Dose - Containment Shine......................................................................................... 27 7.5 TSC Operator Dose - External Cloud Shine..................................................................................... 27 8.0
SUMMARY
OF RESULTS.............................................................................................................. 28 9.0 DISPOSITION OF RESULTS...........................................................................................................28
D000040-122, Revision 0 Page 4 of 155 TABLE OF CONTENTS ATT. #
DESCRIPTION PAGE 1
RADTRAD Models........................................................................................................................ 29 2
RADTRAD: Containment Source File: Cont.nif........................................................................... 32 3
RADTRAD: ESF Leakage Source File: ESF_Halogen.nif............................................................42 4
RADTRAD Release Fraction File: Pwrdba.rft............................................................................. 52 5
RADTRAD Input/Output File: Base Case No Spray - DBA......................................................... 54 6
RADTRAD Input/Output File: Base Case Elemental & Particulate DF Timing Determination - DBA..................................................................................................................... 79 7
RADTRAD Input/Output File: Containment Release - TSC.......................................................111 8
RADTRAD Input/Output File: Sump Release -TSC...................................................................129 9
RADTRAD Dose Conversion Coefficient File: FGRI1&12.inp................................................. 144 TABLE #
DESCRIPTION PAGE 1
Core Activity Available for Release (Reference 4.14)...................................................................11 2
Fraction of Fission Product Inventory Released During the Gap & Early In-Vessel Phases......... 12 3
LOCA Release Phases....................................................................................................................12 4
Ground Level Offsite and TSC X/Qs (sec/m3)...............................................................................13 5
Offsite and TSC Breathing Rates................................................................................................... 15 6
LOCA Offsite and TSC Doses....................................................................................................... 28
D000040-122, Revision 0 Page 5 of 155
1.0 INTRODUCTION
1.1 PURPOSE The purpose of this analysis is to calculate the radiological dose consequences of a loss of coolant accident (LOCA) in the Technical Support Center (TSC) located in the new Nuclear Operations Building (NOB) for the V. C. Summer Nuclear Station (VCSNS), based on the uprated power level of 2958 MW(t) and a cycle length of 480 days. The Alternate Source Term (AST) methodology, in accordance with the requirements of Appendix A of the USNRC Regulatory Guide 1.183 is utilized in this analysis.
1.2 OBJECTIVE The objective of this analysis is to demonstrate that the VCSNS design features, following the design basis LOCA, provide sufficient margin to ensure that the post accident TSC dose satisfies the 10CFR50.67 Accident Source Term criteria (Reference 4.1), 10CFR50 Appendix A, General Design Criteria (GDC) 19 (Reference 4.2), and the guidance in USNRC Regulatory Guide (RG) 1.183 (Reference 4.3).
. 1.3 ACCEPTANCE CRITERIA The TSC is to provide direct management and technical support to the control room during an accident; consequently it shall have the same radiological habitability as the control room under accident conditions. TSC personnel shall be protected from radiological hazards, including direct radiation and airborne radioactivity from in-plant sources under accident conditions, to the same degree as control room personnel.
The TSC acceptance criteria for the radiological consequences of this accident are the same as the control room radiation exposures; within the 10CFR50.67 limits; specifically:
Adequate radiation protection is provided to permit access to and occupancy of the TSC under accident conditions without personnel receiving radiation exposures in excess of 0.05 Sv (5 rem) total effective dose equivalent (TEDE) for the duration of the accident.
1.4 APPROACH To demonstrate the margin provided by the plant's design features in complying with the regulatory guidelines and requirements, a design basis analysis is evaluated. The dose models used to calculate the TSC radiological consequences are based on those presented in RG 1.183. The RADTRAD computer code (Reference 4.4) is used to calculate the TSC dose. This code was developed for the NRC and is used to calculate radiation doses by simulating the movement of radioactivity through various regions of the reactor building, its removal by various processes, and its leakage to the environment. The protected TSC personnel doses from the inleakage of radioactive materials into the TSC envelope are calculated based upon a whole body geometry factor as described by Murphy-Campe (Reference 4.5).
The direct dose from the external radioactive cloud in the atmosphere and the direct whole body dose from the shine of radioactive material in the reactor building are not included in this calculation because the TSC envelope is located underground and the resulting doses are negligible.
D000040-122, Revision 0 Page 6 of 155 2.0 ASSUMPTIONS 2.1 This analysis is consistent with the guidance provided in USNRC Regulatory Guide 1.183 (Reference 4.3).
2.2 Acceptable assumptions regarding core inventory and the release of radionuclides from the fuel are provided in Regulatory Position 3 (Reference 4.3, Appendix A.1).
2.3 If the sump pH is controlled at values of 7 or greater, the chemical form of the radioiodine released to the containment should be assumed to be 95% cesium iodide (CsI), 4.85% elemental iodine, and 0.15% organic iodide. With the exception of elemental and organic iodine and noble gases, fission products should be assumed to be in particulate form (Reference 4.3, Appendix A.2).
Maintenance of sump pH above 7.0 is described in Section 5.14.
2.4 The radioactivity released from the fuel should be assumed to be mixed instantaneously and homogeneously throughout the free air volume of the primary containment. The release into the containment is assumed to terminate at the end of the early in-vessel phase (Reference 4.3, Appendix A.3.1).
2.5 Reduction in airborne radioactivity in the containment by natural deposition within the containment may be credited. Acceptable models or user defined time-dependent removal coefficients for removal of iodine and aerosols are incorporated into the RADTRAD Computer Code (Reference 4.3, Appendix A.3.2). Based on recommendations of Reference 4.7, an acceptable natural deposition removal coefficient is 0.1 hr'. This value for natural deposition removal of particulates has been accepted by the NRC for Indian Point Unit 2 in their SER (Reference 4.8) for the application of the AST methodology. For this analysis it is assumed that natural deposition only occurs when the sprays are not operational.
2.6 The reduction in airborne radioactivity in the containment by containment spray systems that have been designed and maintained in accordance with Chapter 6.5.2 of the SRP (Reference No. 4.9) may be credited. Acceptable models for the removal of iodine and aerosols are described in Chapter 6.5.2 of the SRP and NUREG/CR-5966, "A Simplified Model of Aerosol Removal by Containment Spray" (Reference No. 4.10). This simplified model is incorporated into RADTRAD (Reference 4.3, Appendix A.3.3).
The evaluation of the containment sprays should address areas in the primary containment that are not covered by the spray drops. The mixture rate attributed to natural convection between sprayed and unsprayed regions of the containment building, provided that adequate flow exists between these regions, is assumed to be two turnovers for the unsprayed regions per hour, unless other rates are justified (see Section 5.19). The containment building atmosphere may be considered a single, well-mixed volume if the sprays cover at least 90% of the volume and if adequate mixing of the unsprayed compartments can be shown (Reference 4.3, Appendix A.3.3). See Sections 5.19 and 5.20.
The SRP sets forth a maximum decontamination factor for elemental iodine based on the maximum iodine activity in the primary containment atmosphere when the sprays actuate, divided by the activity of iodine remaining at some time after decontamination. The SRP also states that the particulate iodine removal rate should be reduced by a factor of 10 when a DF of 50 is reached. The reduction in the removal rate is not required if the removal rate is based on the calculated time-dependent airborne aerosol mass. There is no specified maximum DF for aerosols removal by sprays. The maximum activity to be used in determining the DF is defined as the total iodine activity from Table 2 of Reference 4.3, multiplied by 0.05 for elemental iodine and by 0.95 for particulate iodine (aerosol)
(Reference 4.3, Appendix A.3.3). See Section 5.15.
D000040-122, Revision 0 Page 7 of 155 2.7 Reduction in airborne radioactivity in the containment by in-containment recirculation filter systems may be credited if these systems meet the requirements of RG 1.52 and Generic Letter 99-02 (Reference 4.3, Appendix A.3.4). Per Section 5.19, the containment recirculation HEPA filter efficiency is assumed to be 90 percent, although 99 percent is justified per RG 1.52.
2.8 The primary containment should be assumed to leak at the peak pressure technical specification leak rate for the first 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. For PWRs, the leak rate may be reduced after the first 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> to 50% of the technical specification leak rate (Reference 4.3, Appendix A.3.7). See Section 5.12.
2.9 The radiological consequences from post-LOCA primary containment purging as a combustible gas or pressure control measure should be analyzed. If the installed containment purging capabilities are maintained for purposes of severe accident management and are not credited in any design basis analysis, radiological consequences need not be evaluated. Routine containment purge is not considered (see Section 5,. 13) in this calculation (Reference 4.3, Appendix A.3.8).
2.10 ESF systems that recirculate sump water outside the primary containment are assumed to leak during their intended operation.
With the exception of the noble gases, all the fission products released from the fuel to the containment should be assumed to instantaneously and homogeneously mix in the primary containment sump water at the time of release from the core. In lieu of this deterministic approach, suitably conservative mechanistic models for transport of airborne radioactivity in containment to the sump water may be used. Note, that many of the parameters that make spray and deposition models conservative with regard to containment airborne leakage are non-conservative with regard to the buildup of sump activity (Reference 4.3, Appendix A.5.1). For this calculation, the deterministic approach is utilized.
2.11 Leakage from the ESF system should be taken as two times the sum of the simultaneous leakage from all components in the ESF recirculation system above which the technical specifications, or licensee commitments to item III.D.1.1 of NUREG-0737, would require declaring such systems inoperable.
The leakage should be assumed to start at the earliest time the recirculation flow occurs in these systems and end at the latest time the releases from these systems are terminated. (Reference 4.3, Appendix A.5.2). ESF system leakage is addressed in Section 5.6.
2.12 With the exception of the non-particulate iodines, all radioactive materials in the recirculating liquid should be assumed to be retained in the liquid phase (Reference 4.3, Appendix A.5.3).
2.13 If the temperature of the leakage exceeds 212° F, the fraction of total iodine in the liquid that becomes airborne should be assumed equal to the fraction of the leakage that flashes to vapor. The flash fraction should be determined using a constant enthalpy (h) process, based on the maximum time-dependent temperature of the sump water circulating outside the containment (Reference 4.3, Appendix A.5.4).
If the temperature of the leakage is < 212° F, or the calculated flash fraction is < 10%, the amount of iodine that becomes airborne should be assumed to be 10% of the total iodine activity in the leaked fluid, unless a smaller amount can be justified based on the actual sump pH history and area ventilation rates (Reference 4.3, Appendix A.5.5). Flash fraction is addressed in Section 5.16.
2.14 The radioiodine that is postulated to be available for release from the sump to the environment is assumed to be 97% elemental and 3% organic. Reduction in release activity by dilution or holdup within buildings, or by ESF ventilation filtration systems, may be credited, where applicable (Reference 4.3, Appendix A.5.6). For this calculation, no reduction for dilution or holdup within buildings, or by ESF ventilation filtration systems is credited.
D000040-122, Revision 0 Page 8 of 155 2.15 For the ESF leak, only the iodines and bromine isotopes are considered per Sections 2.10 and 2.12.
The density of the sump water is conservatively assumed to equal 1.0 gram/cc (maximizes sump specific activity).
2.16 As noted in the text.
3.0 COMPUTER CODES 3.1 RADTRAD version 3.03, validated by WorleyParsons.
D000040-122, Revision 0 Page 9 of 155
4.0 REFERENCES
4.1 Title 10, Code of Federal Regulations Part 50.67, "Accident Source Term."
4.2 Title 10 Code of Federal Regulations Part 50 Appendix A, "General Design Criteria for Nuclear Power Plants", Criterion 19.
4.3 USNRC Regulatory Guide 1.183, July 2000, "Alternate Radiological Source Terms for Evaluating Design Basis Accidents at Nuclear Power Reactors."
4.4 NUREG/CR-6604, "RADTRAD: A Simplified Model for Radionuclide Transport and Removal and Dose Estimation", December 1997 and NUREG/CR-6604 (SAND98-0272/1), Supplement 1, "RADTRAD: A Simplified Model for Radionuclide Transport and Removal and Dose Determination", June 8, 1999.
4.5 "Nuclear Power Plant Control Room Ventilation System Design for Meeting General Design Criteria GDC 19", K. G. Murphy and K. M. Campe, USAEC, 13`h AEC Air Cleaning Conference, August 1974.
4.6 GMK Associates, Inc. drawings for VC Summer Nuclear Operations Building.
a.
I MS-82-202 (A2.0) - "Basement Floor Plan", RO b.
I MS-82-213 (A4.0) - "Building Sections", RO c.
1MS-82-700 (M2.0) - "Basement Plan HVAC Ductwork", RO d.
1MS-82-717 (M7.2) - "HVAC Schedules", RO 4.7 NUREG/CR-6189, "A Simplified Model of Aerosol Removal by Natural Processes in Reactor Containments", July 1996.
4.8 Letter for Patrick D. Milano, USNRC, to Mr. A. Alan Blind, ConEd, "Indian Point Nuclear Generating Unit No. 2 - Re: Issuance of Amendment Affecting Containment Air Filtration, Control Room Air Filtration, and Containment Integrity During Fuel Handling Operations (TAC NO.
MA6955)", dated July 27, 2000.
4.9 NUREG-0800, "Standard Review Plan For The Review Of Safety Analysis Reports For Nuclear Power Plants", Section 6.5.2, "Containment Spray as a Fission Product Cleanup System", Revision 4.
4.10 NUREG/CR-5966, "A Simplified Model of Aerosol Removal by Containment Spray."
4.11 Title 10 Code of Federal Regulations, Part 50, Appendix K, "ECCS Evaluation Models."
4.12 USNRC Regulatory Guide 1.49, "Power Levels of Nuclear Power Plants", Revision 1.
4.13 NUREG-1465, "Accident Source Terms for Light-Water Nuclear Power Plants", February 1995.
4.14 Westinghouse Radiation Analysis Manual, Revision 1 for VCSNS Uprating updated 12/98 (attachment to letter CGE-98-036).
4.15 VC Summer Nuclear Operations Building, A/E Project #07023.05, "Project Manual Including Specifications Issued for Construction", GMK Associates, Inc., May 6, 2011.
4.16 VCSNS Calculation DC00030-021, Revision 3, "VCSNS Containment Spray Iodine Removal Constants."
D000040-122, Revision 0 Page 10 of 155 4.17 License Amendment 170 to NPF-12, Docket No. 50-395, dated February 3, 2005.
4.19 VCSNS Design Basis Document, "Reactor Building Spray System", Revision 2, Section 3.10.4, As Built System.
4.20 VCSNS Calculation D000040-111, Revision 0, "Short Term Accident X/Qs."
4.21 VCSNS Calculation D000040-079, Revision 3, "Atmospheric Dispersion Coefficients for Control Room."
4.22 VCSNS Calculation D000020-208, Revision 1, "Sump Recirculation Time."
4.23 ASME Steam Tables, 1997.
4.24 NRC Letter Virgil C. Summer Nuclear Station - NRC Receipt of response to Generic Letter 2003-01 "Control Room Habitability" (TAC NO. MB9860), from Robert E. Martin to Jeffery Archie, 10/24/2006.
4.25 VCSNS Calculation DC01380-002, Revision 3, "Sump Volume."
4.26 VCS Technical Specification 4.6.3, Amendment 159.
4.27 USNRC Regulatory Guide 1.52, "Design, Inspection, and Testing Criteria for Air Filtration and Adsorption Units of Post-Accident Engineered-Safety-Feature Atmosphere Cleanup Systems in Light-Water-Cooled Nuclear Power Plants", Revision 2, DG-1102, Proposed Revision 3, issued 10/00.
4.28 VCSNS Calculation D000040-097, Revision 1, "Loss of Coolant Accident - AST."
D000040-122, Revision 0 Page 11 of 155 5.0 DESIGN INPUTS 5.1 Consistent with References 4.3, 4.11, and 4.12, the AST LOCA dose analysis is performed at 102% of the core thermal power level (1.02 x the Licensed Thermal Power of 2900 MW(t) before Appendix K Power Uprate), or 2958 MWth (Reference 4.14).
5.2 The inventory of fission products in the reactor core available for release to the containment is based on the maximum full power operation of the core, current licensed values of fuel enrichment, fuel burnup, and an assumed core power equal to the current licensed rated thermal power (Reference 4.3, Section 3.1). Please note, only the 60 isotopes required per References 4.3, 4.4, and 4.13 are included. Core inventories for the design basis source term are taken from Reference 4.14.
Table No. 1: Core Activity Available for Release - Design Basis (Reference 4.14A)
Isotopes Curies Isotopes Curies
'isotopes Curies Co-58 7.55E+05 Ru-103 1.06E+08 Cs-136 3.08E+06 Co-60 5.78E+05 Ru-105 6.92E+07 Cs-137 5.66E+06 Kr-85 8.30E+05 Ru-106 2.42E+07 Ba-139 1.47E+08 Kr-85m 2.72E+07 Rh-105 4.79E+07 Ba-140 1.46E+08 Kr-87 4.96E+07 Sb-127 6.53E+06 La-140 1.49E+08 Kr-88 6.71E+07 Sb-129 2.31E+07 La-141 1.37E+08 Rb-86 4.43E+04 Te-127 6.31E+06 La-142 1.32E+08 Sr-89 8.41E+07 Te-127m 8.35E+05 Ce-141 1.32E+08 Sr-90 4.54E+06 Te-129 2.17E+07 Ce-143 1.29E+08 Sr-91 1.08E+08 Te-129m 5.72E+06 Ce-144 7.98E+07 Sr-92 1.13E+08 Te-131m 1.10E+07 Pr-143 1.26E+08 Y-90 4.87E+06 Te-132 1.09E+08 Nd-147 5.65E+07 Y-91 1.02E+08 1-131 8.20E+07 N p-239 1.51E+09 Y-92 1.13E+08 1-132 1.20E+08 Pu-238 8.58E+04 Y-93 1.28E+08 1-133 1.68E+08 Pu-239 1.94E+04 Zr-95 1.29E+08 1-134 1.80E+08 Pu-240 2.44E+04 Zr-97 1.35E+08 1-135 1.54E+08 Pu-241 4.11E+06 Nb-95 1.22E+08 Xe-133 1.70E+08 Am-241 2.72E+03 MO-99 1.43E+08 Xe-135 3.70E+07 Cm-242 1.04E+06 Tc-99m 1.23E+08 Cs-134 1.01E+07 Cm-244 6.08E+04 A. Please note, for conservative reasons, for all isotopes not included in Reference 4.14, the default core inventories from Table 1.4.3.2-2 of Reference 4.4, corrected to a core thermal power of 2958MWt, are included in this analysis. In addition, the noble gas and iodine core inventories from Reference 4.14 and the corrected core inventories from Reference 4.4 were compared and the larger of the two concentrations is used in this analysis.
With the exception of the noble gases, all the fission products released from the fuel to the containment should be assumed to instantaneously and homogeneously mix in the primary containment sump water at the time of release from the core (Reference 4.3, Appendix A.5.1, see Section 2.10). With the exception of the non-particulate iodines, all radioactive materials in the recirculating liquid should be assumed to be retained in the liquid phase (Reference 4.3, Appendix A.5.3, see Section 2.12).
D000040-122, Revision 0 Page 12 of 155 5.3 The core inventory release fractions, by radionuclide groups, for the gap release and early in-vessel damage phases of the LOCA, are based on Regulatory Position 3.2, Table 2 of Reference 4.3 (reproduced below as Table No. 2).
Table No. 2: Fraction of Fission Product Inventory Released During the Gal) & Early In-Vessel Phases Group Isotopes Gap Release Phase Early
. In-Vessel Phase Total Noble Gases Xe, Kr 0.05 0.95 1.00 Halogens I, Br 0.05 0.35 0.40 Alkali Metals Cs, Rb 0.05 0.25 0.30 Tellurium Metals Te, Sb, Se 0.00 0.05 0.05 Ba, Sr Ba, Sr 0.00 0.02 0.02 Noble Metals Ru, Rh, Pd, Mo, Tc, Co 0.00 0.0025 0.0025 Cerium Group Ce, Pu, Np 0.00 0.0005 0.0005 Lanthanides La, Zr, Nd, Eu, Nb, Pm, Pr, Sm, Y, Cm, Am 0.00 0.0002 0.0002 5.4 Reference 4.3, Section 3.3, Table 4, provides the onset and duration of each sequential release phase of the LOCA. The specified onset is the time following the initiation of the accident. The early in-vessel phase immediately follows the gap release phase. The activity released from the core during each release phase is modeled as increasing in a linear fashion over the duration of the phase. This is accomplished with the RADTRAD default RFT file Pwr dba.rft (Attachment 4).
Table No. 3: LOCA Release Phases Phase Onset Duration Gap Release 30 seconds 0.5 hours5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br /> Early In-Vessel 0.5 hours5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br /> 1.3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> 5.5 Reference 4.20 provides post-accident offsite X/Q's (sec/m3) at the EAB and LPZ. These values were utilized in other calculations to determine the offsite doses as a result of FSAR Chapter 15 design basis accidents. These X/Q's are included in the RADTRAD files as a "check" for model correctness.
Reference 4.21, Appendix 2 provides the post-accident X/Q's at the TSC. TSC atmospheric dispersion factors are not adjusted to reflect the anticipated post-accident occupancy factors of Reference 4.3. Results are summarized in Table 4 below.
D000040-122, Revision 0 Page 13 of 155 Table No. 4: Ground Level Offsite and TSC X/O's (sec/m3)
Time Period EAB LEZ TSG(I)(z) 0 - 2 hour2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> 1.24E-04 3.9E-05 0 - 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> 2.42E-05 2 - 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> 3.3E-05 8 - 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> 1.68E-05 1.6E-05 1 - 4 days 7.55E-06 1.2E-05 4 - 30 days 2.40E-06 8.7E-06 (1) Not adjusted for TSC occupancy (2) Intermediate Building nearest point (southwest corner) 5.6 The effect of leakage of the sump fluid from engineered safety features (ESF) equipment located outside of containment is considered in evaluating the radiological consequences of a LOCA. In accordance with Reference 4.3, Appendix A, Section 5.2 "Leakage from the ESF system should be taken as two times the sum of the simultaneous leakage from all components in the ESF recirculation system above which the technical specifications, or licensee commitments to item III.D.1.1 of NUREG-0737, would require declaring such systems inoperable" (see Section 2.11). The VCSNS technical specifications do not provide a specific limitation on the quantity of operational leakage that is allowed from the RHR and RB spray Systems. However, FSAR Tables 6.2-52b and 6.3-4 provide estimates of 870 and 2,060 cc/hr for the RB Spray and RHR Systems respectively.
Consistent with the current FSAR value (FSAR section 15.4.1.4.2), an assumed conservative post LOCA recirculation leakage of 12,000 cc/hr (4.238E-01 cfh or 7.063E-03 cfm) is used herein as the design basis case. This is more than four times the combined leakage of 2,930 cc/hr [870 cc/hr +
2,060 cc/hr] provided in FSAR Tables 6.2-52b and 6.3-4.
The accident analysis leakage starts at the earliest time the recirculation mode is entered, which is 1,460 seconds (0.41 hours4.74537e-4 days <br />0.0114 hours <br />6.779101e-5 weeks <br />1.56005e-5 months <br />) per Reference 4.22, and continues for the duration of the accident.
No credit is taken for holdup or filtration of this leakage in the Auxiliary Building, i.e., the iodine released by the recirculation loop leakage is assumed to be immediately available for release to the atmosphere (see Section 2.14).
5.7 The VCSNS TSC design features include post accident isolation with filtered supply and pressurization. The following parameters are utilized in accessing the post-accident dose consequences to TSC personnel.
The total free volume of the TSC envelope located in the basement of the new Nuclear Operations Building (elevation 100') is 207,000 ft3 per Reference 4.6. The TSC envelope consists of all the areas depicted on the basement floor plan (Reference 4.6.a) excluding the south stairwell and area way open to above (southwest corner). The area between column lines B and G.2 and 2 and the fire wall running north-south is approximately 80' by 110' or 8,800 ft2. The area between column lines B and V and the fire wall running north-south and 5 is approximately 36' by (200' - 12') or 6,768 ft2. The total area is 8,800 ft2 + 6,768 ft2 or 15,568 ft2.
D000040-122, Revision 0 Page 14of155 The height of the TSC envelope is determined per Reference 4.6.b, Cross Section 3. The basement and first floor finished elevations of 100' and 120' are used. A first floor thickness of 1' is assumed.
The total height is (120' - 1') - 100' or 19'. The total volume of the TSC envelope is 15,568 ft2
- 19' or 295,792 ft3. It is assumed that 30 percent of the volume consists of components and/or structures, thus the total available free air volume is:
VTSC Envelope - 295,792 ft3
- 0.7 or 2.07E+05 ft3 For this accident analysis, manual operator action is required for the TSC to function in the emergency mode of operation. Consequently, it is conservatively assumed that the TSC never enters the emergency mode of operation (no filtration of make-up air through through the filtered air handling unit FFU-1.
TSC Normal Air Handling System flow rates, flow path and potential unfiltered leakage are determined below.
The Basement plan HVAC ductwork is provided in Reference 4.6.c. During normal operation, supply air enters the TSC envelope through the fan filter unit (FFU-1). The filters are by-passed and the make-up air is distributed throughout the TSC envelope with air handling unit AHU-0-1. Per Reference 4.6.d, AHU-0-1 has a capacity of 12,000 cfm.
Per Reference 4.15, Section 15940 - HVAC sequence of operation is as follows:
3.09 Technical Support Center (TSC)
A.
Non-Emergency Mode of Operation.
1.
AHU-0-1 shall operate as specified for VAV air handling unit(s) with static pressure optimization.
2.
Modulate return air damper in TSC space to maintain 1/8" wg positive pressure between the TSC space and the adjacent corridor.
Flow Rates under TSC Normal Operation It is assumed that the TSC does not isolate for the duration of the accident. A total of 13,000 cfm of unfiltered outside air is assumed to flow into and out of the TSC. 13,000 cfm conservatively bounds the expected design flow rate (AHU-0-1) of 12,000 cfm. The doses are conservatively calculated assuming no credit for filtration for the duration of the accident.
D000040-122, Revision 0 Page 15 of 155 5.8 Manual operator action is required for the TSC to function in the emergency mode. It is further assumed the TSC personnel do not take any manual actions to isolate the TSC envelope and enter the emergency mode of operation.
5.9 Offsite and TSC breathing rates are given in Table No. 5 per Reference 4.3, Sections 4.1.3, and 4.2.6.
Table No. 5: Offsite and TSC Breathing Rates Offsite EAB and LPZ)
TSC Time Rate (m3/sec)
Reference 4.3, Item 4.1.3 Time Rate (m3/sec)
Reference 4.3, Item 4.2.6 0-8 hr 3.5E-04 0-30 days 3.5E-04 8-24 hr 1.8E-04 1-30 days 2.3E-04 5.10 Consistent with Reference 4.3, Section 4.2.6, TSC occupancy factors are as follows:
Occupancy Time Factor 0-24 hours 1.0 1-4 days 0.6 4-30 days 0.4 5.11 The dose conversion factors (DCFs) utilized in the AST LOCA analysis are from Reference 4.4, Table 1.4.3.3-2. For the design basis analysis, the RADTRAD default file FGR11&12.inp is utilized.
5.12 The design basis leakage rate for the Reactor Building is given in FSAR Table 6.2-1 as 0.2 percent/day for the first 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, reduced to 0.1 percent/day thereafter for the duration of the accident. Per RG 1.183, Appendix A, Section 3.7 (Reference 4.3), "for PWRs, the leak rate may be reduced after the first 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> to 50% of the Technical Specification leak rate."
Sump Volume: The minimum volume of water in the reactor building sump post-LOCA for recirculation is 1.578E+09 cc. or 5.573E+04 ft3 per Reference 4.25.
5.13 Reference 4.17, the Safety Evaluation associated with Licensing Amendment 170 deleted the Technical Specification requirements associated with the hydrogen recombiners and hydrogen monitors as a result of changes to IOCFR50.44, which eliminated the requirements for hydrogen recombiners and relaxed the requirements for hydrogen and oxygen monitoring. The NRC eliminated the design basis LOCA hydrogen release from I OCFR50.54. Consequently, post LOCA containment purge for hydrogen control is not required and is not considered in this evaluation (see Section 2.9).
5.14 The sump pH is maintained > 7.0 for the duration of the accident. Per FSAR Section 6.2.2.2.1.2, during post recirculation operations, the Reactor Building recirculation sump water can be sampled with the normal and Post-Accident Sampling System to monitor the pH. If additional sodium hydroxide is required, the sodium hydroxide feed line valve(s) from the sodium hydroxide storage tank is (are) opened and the sodium hydroxide solution is gravity fed into the Reactor Building spray pump suction line(s).
D000040-122, Revision 0 Page 16 of 155 5.15 Per References 4.3 and 4.9, when a decontamination factor of 50 for the particulate iodine spray removal coefficient is achieved, the removal coefficient must be reduced by a factor of 10, based on the maximum airborne particulate iodine concentration in the containment (see Section 2.6). The reduction in the removal rate is not required if the removal rate is based on the calculated time-dependent airborne aerosol mass. Per Reference 4.16 the elemental iodine spray removal coefficient is 20 hr' and the particulate iodine spray removal coefficient is 5.68 hr'. Per above, the removal rate for the particulate iodines is reduced by a factor of 10 (0.568 hr) when a DF of 50 is reached. There is no specified maximum DF for aerosols removed by sprays. No credit is taken for the removal of organic iodine by the spray system.
5.16 Per Reference 4.3, Appendix A, Section 5.4 (see Section 2.13) "If the temperature of the leakage exceeds 212° F, the fraction of total iodine in the liquid that becomes airborne should be assumed equal to the fraction of the leakage that flashes to vapor. The flash fraction should be determined using a constant enthalpy (h) process, based on the maximum time-dependent temperature of the sump water circulating outside the containment."
Based on FSAR Figure 6.2-7, the maximum sump temperature post-LOCA is < 245° F. Since this is above 212° F, the percent of coolant which flashes must be calculated (Reference 4.3, also see Section 2.13). Considering the following:
h(w)
= enthalpy of water at 245° F h(g)
= enthalpy of water at 212° F h(f)
= enthalpy of water at 212° F M(w) = mass of water at 245° F M(s)
= mass of water at 212° F M(2w) = mass of water at 212° F By conservation of mass:
M(w) = M(s) + M(2w).and M(2w) = M(w) - M(s)
By conservation of energy:
M(w)h(w) = M(2w)h(f) + M(s)h(g)
M(w)h(w) = [M(w) - M(s)]h(f) + M(s)h(g)
M(w)h(w) = [M(w)h(f) - M(s)h(f) + M(s)h(g)]
M(w)h(w) = M(w)h(f) + M(s)[(h(g) - h(f)]
M(w)[h(w) - h(f) = M(s)[(h(g) - h(f)]
M(s)[h(g) - h(f)] = M(w)[(h(w) - h(f)]
M(s)/M(w) = [h(w) -h(f)] / [h(g) - h(f)]
From Reference 4.23:
@ T = 245 ° F, h(w) = 213.5 BTU/lb(m)
@ T = 212 ° F, h(g) = 1150.5 BTU/lb(m)
@ T = 212 ° F, h(f) = 180.17 BTU/lb(m)
M(s)/M(w) = (213.5 - 180.17)/(1150.5 - 180.17)
- 100 = 3.43 percent
D000040-122, Revision 0 Page 17 of 155 Although the flash fraction is less than the 10 percent value required in Reference 4.3, Appendix A, Section 5.5, a value of 10 percent of the iodine in the operational recirculation system leakage is conservatively assumed to become airborne and immediately released to the environment.
5.17 Per References 4.3 and 4.9, the maximum decontamination factor for the elemental iodine spray removal coefficient is 200, based on the maximum airborne elemental iodine concentration in the containment. Based on the timing of the release phases provided in Table 4 of Reference 4.3, the expected maximum concentration should occur at 1.8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />. Attachment No. 5 is a RADTRAD run that provides the design basis elemental iodine concentration as a function of time. As expected, the maximum concentration is achieved at 1.8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> and consists of the concentration in Volume 1, or a total of X atoms of elemental iodines. The DF of 200 is reached when a total of X/200 elemental iodine atoms remain in Volume 1. To determine when this "end-point" is achieved, RADTRAD was rerun (Attachment No. 6) with the sprays and recirculation fans operating (elemental iodine fan filter DF equals zero). This timing is utilized in all subsequent RADTRAD runs.
Per References 4.3 and 4.9, the decontamination factor for the particulate iodine spray removal coefficient is 50, at which time the removal coefficient must be reduced by a factor of 10, based on the maximum airborne particulate iodine concentration in the containment. Based on the timing of the release phases provided in Table 4 of Reference 4.3, the expected maximum concentration should occur at 1.8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />. Attachment No. 5 is a RADTRAD run that provides the design basis particulate iodine concentration as a function of time. As expected, the maximum concentration is achieved at 1.8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> and consists of the concentration in Volume 1, or a total of Y atoms of particulate iodines.
The DF of 50 is reached when a total of Y/50 particulate iodine atoms remain in Volume 1. To determine when this "end-point" is achieved, RADTRAD was rerun (Attachment No. 6) with the sprays and recirculation fans operating (particulate iodine fan filter DF equals zero). This timing is utilized in all subsequent RADTRAD runs.
5.18 Natural deposition is credited in the containment sprayed volume when sprays are not operational.
100 percent of the containment is sprayed.
5.19 The Reactor Building Cooling System consists of 4 plenums arranged to discharge filtered and cooled air into a common air supply main. The cooling air is further distributed from the supply main to the upper portions of the Reactor Building through supply air outlets in the supply main and to the lower elevations of the Reactor Building through vertical supply ducts connected to the supply main.
The Reactor Building Cooling Units (RBCUs) and associated discharge ductwork supply cooling air flow to the unsprayed regions below the operating floor. This air flow establishes a convective flow path whereby the air/steam mixture from the unsprayed regions and from inside the secondary shield walls are directed upward into the suction of the RBCUs. Therefore, the required mixing and recirculation of the building atmosphere for the volumes between the lowest elevation of the reactor Building and the elevation of the RBCUs (approximately 67 feet above the operating floor) is provided.
The Reactor Building cooling unit fans operate at high speed during normal periods and at slow speeds during post LOCA periods. The units are serviced by cooling water from the Industrial Cooling System during normal periods and by service water during post LOCA or loss of offsite power conditions. For normal operation, 3 out of 4 fans operate. For LOCA, one fan in each train operates.
D000040-122, Revision 0 Page 18 of 155 The plenums are arranged along the perimeter of the Reactor Building with the base of each at elevation 514'. Two (2) of the Reactor Building cooling units are supplied with electrical power from the A channel and the other 2 from the B channel of the Class lE electric system.
The automatic change in operating mode from normal to emergency involves changing from motors operating at high speed to motors operating at slow speed, changing the unit cooling water from that supplied by the Industrial Cooling Water System to that from the Service Water System, and automatically closing the Reactor Building HEPA filter bypass damper. The active RBCU discharge valves will automatically align so that 2 of the 4 valves, one per train, will open when their associated RBCU fans are selected to run; the other two valves will close when their RBCU fans are not selected to run. The units, when operating in the normal mode, are tripped upon the receipt of a safety injection or loss of offsite power signal and are then automatically started at slow speed in accordance with the ESF actuation system and the ESF loading sequence of the related emergency diesel generator.
In the following discussion, the times given for the occurrence of events are referenced to the time at which the ESF loading sequence gives a start signal to the first electrical load.
The slow speed motors are energized at approximately 25 seconds after the referenced time. An additional 8 seconds are required after energizing the slow speed motor for air flow to reach operating values. Thus, the total "air-side" switchover from normal to emergency operation is completed approximately 33 seconds after the reference time. For this analysis, the RBCUs are assumed to be fully operational at T= 52 seconds post LOCA and run for the duration of the accident.
The Reactor Building Cooling System recirculation flow rate is rated at 60, 270 +/- 10% acfm per Technical Specification 4.6.3 (Reference 4.26). Therefore, the minimum allowable system flow is 54,243 acfin. 54, 200 cfm is used in the RADTRAD analyses.. The recirculation HEPA efficiency is assumed to be 90 percent for the removal of iodine particulates only. This is conservative since Regulatory Guide 1.52 (Reference 4.27) permits a 99 percent removal efficiency for particulates in accident dose evaluations.
5.20 The Reactor Building Spray System is utilized to remove iodine from the Reactor Building atmosphere. The following factors are used in assessing the impact of this system in mitigating the TSC doses.
As described in FSAR Section 6.2.2.2.1.1, three spray header and nozzle assemblies are provided for each of the two spray subsystems. Each spray subassembly has 165 spray nozzles. The spray nozzles are one piece, stainless steel units that deliver water at a nominal rate 15.2 gpm. A nominal spray flow of 2,500 gpm is provided by each spray subsystem.
The arrangement of the spray rings within the Reactor Building is such that essentially all of the free volume above the operating floor, elevation 463', is exposed to the spray. Below the operating floor elevation, areas outside the secondary shield walls are shielded from the spray. However, the atmosphere in this area is mixed with the rest of the volume inside the secondary shield walls (see Section 5.19). The volume inside the secondary shield walls with the exception of the pressurizer compartment, is open to the spray. The location of the Reactor Building Spray System ring headers within the Reactor Building dome and the position of the spray nozzles in the ring headers provide for 100% spray coverage of the operating floor with both spray loops operating. For the case of minimum engineered safety features, i.e., only one spray loop available, 93% of the Reactor Building at the operating floor level is covered by the spray. For this analysis, the containment building atmosphere is considered a single, well-mixed volume since the sprays cover at least 90% of the volume and there is adequate mixing of the unsprayed compartments (Reference 4.3, Appendix A.3.3).,
D000040-122, Revision 0 Page 19 of 155 During the injection phase following a LOCA, the spray pumps receive fluid from the RWST and sodium hydroxide storage tank. The solutions are carried through the pump discharge lines to the spray headers and are then sprayed into the Reactor Building atmosphere through the spray nozzles.
The spray is collected in the bottom of the Reactor Building with water from ECCS and the Reactor Coolant System in the Reactor Building recirculation sumps. Upon receipt of the RWST "lo-lo" level signal in conjunction with the safety injection signal, the Reactor Building recirculation sump isolation valves (3004A & B and 3005A & B) automatically open. During the recirculation phase, the spray pumps may take suction from the sumps in the Reactor Building.
Per FSAR Section 6.2.1.3.4.2, during normal plant operation, the Spray System is in standby condition with the suction aligned to receive water from the RWST. Operation of the system is initiated automatically following a LOCA by signals from the Engineered Safety Features (ESF)
Actuation System when the Reactor Building pressure increases to the actuation set point. If there is a spray actuation signal, the Reactor Building spray pumps are loaded onto the onsite diesel generators following a loss of offsite power. The total time for RB Spray water to start being delivered through the spray nozzles to the RB atmosphere is 47 seconds following LOCA initiation. This includes a 10 second start time for EDGs, 5 seconds for the spray pump to reach full capacity (during this 5 second pump acceleration time, no filling of lines is assumed), and 32 seconds to fill the RB spray line up to the nozzles. For conservatism, it is assumed that spray starts 52 seconds after the LOCA occurs.
For this analysis, it is conservatively assumed that the sprays will operate for only the first 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> of the accident (Reference 4.18).
5.21 Leakage through the RWST and NaOH Tank is neglected in this calculation based on plant procedures (EOPs) that require closure of the 20" RWST outlet valve (6700) and closure of the 3" NAOH outlet valve (3012) following the transition to CL recirculation. This results in 3 valve isolation and a minimum of 2 valve isolation in the long term with a single failure. The actions outlined above will be implemented via the AST ECR (Reference 4.18).
D000040-122, Revision 0 Page 20 of 155 6.0 METHODOLOGY Consistent with the current licensing basis, as discussed in the V. C. Summer UFSAR and RG 1.183, this analysis considers a LOCA event. The analysis consists of the release of activity from the containment via containment leakage. In addition, once the recirculation mode of the ECCS is established, activity in the sump solution is released to the environment by means of leakage from the ECCS equipment in the Reactor Auxiliary Building. Per Section 5.21, leakage through the RWST or NaOH Tank pathway is not considered. The total TSC doses are the sum of the doses resulting from each of the postulated release pathways.
For the containment leakage analysis, all activity released from the fuel is assumed to be in the containment atmosphere until removed by sprays, natural deposition, radioactive decay, or leakage from the containment. The Containment Building is modeled as a single sprayed volume, since the sprays meet the 90 percent criteria of Reference 4.3 Appendix A.3.3. Containment leakage is assumed to occur at the rates given in Section 5.12. The removal of elemental iodine from the containment atmosphere is accomplished by containment spray, the RBCUs, leakage, and radioactive decay. The removal of the particulates is accomplished by containment sprays, natural deposition, the RBCUs, leakage, and radioactive decay. The organic iodine are subject to removal by the RBCUs, leakage, and radioactive decay. The noble gases and other non-halogen isotopes are subject to removal by leakage and radioactive decay. It is assumed that only one spray train is utilized during the LOCA (Reference 4.19).
For the ECCS leakage, all iodine activity released from the fuel is assumed to be in the sump solution until removed by radioactive decay or leakage from the ECCS (Assumptions 2.12 & 2.14).
When ECCS recirculation is established following the LOCA, leakage is assumed to occur from ECCS equipment outside containment (directly into the Auxiliary Building). The fraction of the total iodine in the liquid that becomes airborne is assumed to be equal to the fraction of the leakage that flashes to vapor. (Reference 4.3).
For this accident analysis, manual operator action is required for the TSC to function in the emergency mode of operation. Consequently, it is conservatively assumed that the TSC never enters the emergency mode of operation (no filtration of make-up air through through the filtered air handling unit FFU-1.
Utilizing the Assumptions in Section 2.0 and the Design Input data in Section 5.0, the radioactive releases from the Containment and ECCS leakage in the Reactor Auxiliary Building following a LOCA, is calculated in compliance with RG 1. 183 (Reference 4.3). This evaluation is described in Section 7.0.
The applicable design inputs, as previously presented, are used to model the LOCA (see Attachment No. 1) utilizing the RADTRAD computer code (Reference 4.4). The detailed description of the RADTRAD inputs can be found in Section 7.0.
D000040-122, Revision 0 Page 21 of 155 7.0 COMPUTATIONS 7.1 ELEMENTAL AND PARTICULATE IODINE SPRAY REMOVAL COEFFICIENT TIMING Per Section 5.17, the time at which the elemental iodine spray removal coefficient meets the DF limit is when the maximum concentration of airborne elemental iodine atoms in containment before sprays is reduced by a factor of 200 utilizing the sprays. At this time, the removal of elemental iodine due to sprays is terminated.
Per Section 5.17, the time at which the particulate iodine spray removal coefficient meets the DF limit is when the maximum concentration of airborne particulate iodine atoms in containment before sprays is reduced by a factor of 50 utilizing the sprays. At this time, the particulate iodine spray removal coefficient is reduced by a factor of 10.
Attachment No. 5 determines the maximum design basis concentration of the elemental and particulate iodines in containment. Attachment No. 6 determines the time at which a DF of 200 occurs for design basis elemental iodine and the time at which a DF of 50 occurs for particulate iodine. The 2 RADTRAD models are developed in Sections 7.1.1 and 7.1.2.
For these runs, the filter efficiency of the RBCUs is set to zero.
Containment inventory is input as a user defined NIF file in Attachment Nos. 2 (Cont.nif) for the design basis case.
Release fractions and timing data for the LOCA are input as a RADTRAD default RFT file in Attachment No. 4 (Pwr dba.rft).
Dose conversion factors (DCFs) utilized in the AST LOCA analysis are input as a RADTRAD default RFT file FGR11&12.inp (Attachment 9).
D000040-122, Revision 0 Page 22 of 155 7.1.1 - Determination of Maximum Elemental & Particulate Iodine Concentration 7.1.1.1 RADTRAD Volume 1 represents the Containment Volume:'
Containment sprayed volume is modeled as 1.84E+06 ft3, containing 100% of the source Natural deposition is set to zero because it has an impact on the retention of particulate iodine in the Containment air. Natural deposition has no impact on elemental iodine No Containment sprays 7.1.1.2 RADTRAD Volume 2 represents the Environment:
No input required 7.1.1.3 RADTRAD Pathway 1 represents the Flow Rate from Volume 1 to Environment:
A "Dummy" flow rate was input as required by RADTRAD. A value if 1E-10 cfm from 0 to 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> is utilized to minimize the leakage of radioactive material from the Containment 7.1.1.4 RADTRAD Pathway 2 represents the Flow Rate from the RBCUs in Volume 1:
RBCU flow rate is 54,200 cfm, 1.44E-02 to 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> RBCU filter efficiency set to zero 7.1.1.5 RADTRAD Dose Location 1 - EAB:
A "Dummy" X/Q was input as required by RADTRAD. RADTRAD default breathing rates were utilized 7.1.1.6 RADTRAD Source Term:
Use the user defined source inventory file Cont.nif.
Modeled power level as 1 MWth, since the source is based on curies per core Model isotopic decay and daughter in-growth Use the RADTRAD default release fraction file, Pwrdba.rft.
Use the default RADTRAD FGR 11 & 12 dose conversion factors for the MACCS 60 isotope inventory, FGRl1&12.inp 7.1.1.7 RADTRAD Control Options:
Applicable Control Options are selected for the additional data supplied in the output printout The resulting RADTRAD output file is: Base Case No Spray DBA (Attachment 5)
Results of Attachment 5 indicate that the maximum elemental iodine concentration is 7.5001E+22 atoms at 1.8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />. The time a DF of 200 is reached is:
7.5001E+22 / 200 or when 3.75E+20 atoms of elemental iodine remains in Containment during spray "wash-out."
Results of Attachment 5 indicate that the maximum particulate (aerosol) iodine concentration is 2.3277E+01 atoms at 1.8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />. The time a DF of 50 is reached is:
2.3277E+01 / 50 or when 4.66E-01 atoms of elemental iodine remains in Containment during spray "wash-out."
D000040-122, Revision 0 Page 23 of 155 7.1.2 - Determination of Elemental & Particulate Removal Coefficient Timing This model is identical to the model described in Section 7.1.1, except the sprays are added.
7.1.2.1 RADTRAD Volume 1 represents the Containment Sprayed Volume:
Compartment Features include sprays Spray characteristics:- user defined elemental iodine removal coefficient is 20 hr' and particulate iodine removal coefficient is 5.68 hr' per Section 5.15 Sprays start at 1.44E-02 hours Detailed output button selected The resulting RADTRAD output file is:
Base Case Elemental -Particulate DF Timing Determination DBA.oO (Attachment 6)
Results of Attachment 5 indicate that the maximum elemental iodine concentration is 7.5001E+22 atoms at 1.8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />. The time a DF of 200 is reached is:
7.5001E+22 / 200 or when 3.75E+20 atoms of elemental iodine remains in Containment during spray "wash-out."
Per Attachment 6:
At 1.89 hours0.00103 days <br />0.0247 hours <br />1.471561e-4 weeks <br />3.38645e-5 months <br />, the elemental iodine concentration is 4.17E+20 atoms.
At 1.90 hours0.00104 days <br />0.025 hours <br />1.488095e-4 weeks <br />3.4245e-5 months <br />, the elemental iodine concentration is 3.42E+20 atoms.
Since the elemental DF of 200 is exceeded at 1.90 hours0.00104 days <br />0.025 hours <br />1.488095e-4 weeks <br />3.4245e-5 months <br />, the elemental iodine spray removal coefficient is terminated at 1.89 hours0.00103 days <br />0.0247 hours <br />1.471561e-4 weeks <br />3.38645e-5 months <br />. Spray will continue because there is no maximum particulate iodine DF.
Results of Attachment 5 indicate that the maximum particulate iodine concentration is 2.3277E+O 1 atoms at 1.8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />. The time a DF of 50 is reached is:
2.3277E+01 / 50 or when 4.66E-01 atoms of particulate iodine remains in Containment during spray "wash-out."
Per Attachment 6:
At 2.10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br />, the particulate iodine concentration is 4.83E-01 atoms.
At 2.11 hours1.273148e-4 days <br />0.00306 hours <br />1.818783e-5 weeks <br />4.1855e-6 months <br />, the particulate iodine concentration is 4.56E-01 atoms.
Since the elemental DF of 50 is exceeded at 2.11 hours1.273148e-4 days <br />0.00306 hours <br />1.818783e-5 weeks <br />4.1855e-6 months <br />, the particulate iodine spray removal coefficient is reduced by a factor of 10 at 2.10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br />. Spray will continue because there is no maximum particulate iodine DF.
D000040-122, Revision 0 Page 24 of 155 7.2 TSC OPERATOR DOSE DUE TO CONTAINMENT RELEASE A visual representation of the RADTRAD model used to calculate the TSC dose due to the radioactivity release from containment is provided as Attachment No. 1 (RADTRAD Model for Containment Source Release) and developed in Sections 2.0 and 5.0.
The activity released to the environment is assumed to be released as a ground level release from the Intermediate Building southwest corner to the TSC.
The RADTRAD model input consists of 3 volumes, 5 flow pathways, and 3 dose locations.
Containment inventory (activity available for release to the environment) is input as a user defined NIF file in Attachment No. 2 (Cont.nif) for the design basis case.
Release fractions and timing data for the LOCA analysis are input as a RADTRAD default RFT file (Pwr_dba.rft - Attachment No. 4).
Dose conversion factors (DCFs) utilized in the AST LOCA analysis are input as a RADTRAD default RFT file FGR11&12.inp (Attachment 9) for the design basis case.
7.2.1 TSC Operator Dose Due to Containment Release (Design Basis Source Terms) - Attachment 7 7.2.1.1 RADTRAD Volume I represents the Containment Volume:
Containment sprayed volume is modeled as 1.84E+06 ft3 containing 100% of the source Compartment features include sprays and natural deposition Natural deposition, user defined: 0.1 hr', 0 to 52 seconds and 4 to 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br />, only when the sprays are NOT functioning per Section 5.18 Spray characteristics:- user defined elemental and particulate iodine removal coefficients and timing per Section 5.15, Section 7.1, and Attachments 5 & 6. Elemental iodine removal coefficient is 20 hr', 52 seconds to 1.89 hours0.00103 days <br />0.0247 hours <br />1.471561e-4 weeks <br />3.38645e-5 months <br />. Particulate iodine removal coefficient is 5.68 hr', 52 seconds to 2.10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br />; 0.568 hr-' from 2.10 to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.
95% particulate (cesium iodide), 4.85% elemental iodine & 0.15% organic iodine (Section 2.3)
Detailed output button selected 7.2.1.2 RADTRAD Volume 2 represents the Environment:
No input required 7.2.1.3 RADTRAD Volume 3 represents the TSC:
TSC habitability volume equals 2.07E+05 ft3 (Section 5.7) 7.2.1.4 RADTRAD Pathway 1 represents the Containment sprayed volume leakage to the Environment:
Containment leakage is 0.2% weight/day for the first 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> and 0.1 % weight/day, for the remainder of the accident per Section 5.12 7.2.1.5 RADTRAD Pathway 2 represents the TSC Outside Air Makeup Pathway Normal Mode - Outside air makeup equals 12,000 cfm (Section 5.7)
No Emergency Mode or Filtration 7.2.1.6 RADTRAD Pathway 3 represents the TSC Unfiltered Air Inleakage Pathway:
TSC unfiltered air inleakage is conservatively assumed to be 1,000 cfm for the duration of the 30-day transient (Section 5.7)
D000040-122, Revision.0 Page 25 of 155 No filter is applied to this pathway (Section 5.7) 7.2.1.7 RADTRAD Pathway 4 represents the TSC Exhaust Air Pathway Exhaust air flow equals all incoming air (makeup and inleakage, 12,000 cfm plus 1,000 cfm )
13,000 cm for the duration of the 30 day transient (Section 5.7)
No filter is applied to this pathway (Section 5.7) 7.2.1.8 RADTRAD Pathway presents the Flow Rate from RBCUs in Volume 1 54,200 cfm RBCU recirculating flow rate, filters 90% efficient for aerosol species, beginning at 52 seconds through the duration of the accident (Section 5.19) 7.2.1.9 RADTRAD Dose Location 1 - EAB:
0-2 hour X/Q value per Table 4 used for entire 30-day transient 0-8 hour breathing rate per Table No. 5 for entire 30-day transient 7.2.1.10 RADTRAD Dose Location 2-LPZ:
X/Q value per Table 4 Use breathing rate values per Table No. 5 7.2.1.11 RADTRAD Dose Location 3 -Protected TSC:
X/Q values per Table 4 Use breathing rate and occupancy values per Table No. 5'& Section 5.10 7.2.1.12 RADTRAD Source Term:
Use the user defined source inventory file Cont DBA.nif.
Modeled power level as 1 MW(t), since the source is based on curies per core Model isotopic decay and daughter in-growth Use the RADTRAD default release fraction file, Pwr_dba.rft.
Use the default RADTRAD FGR 11 & 12 dose conversion factors for the MACCS 60 isotope inventory, FGR11&12.inp 7.2.1.13 RADTRAD Control Options:
Applicable Control Options are selected for the additional data supplied in the output printout The resulting RADTRAD output file is: Containment Release - TSC.oO (Attachment 7)
D000040-122, Revision 0 Page 26 of 155 7.3 TSC OPERATOR DOSE DUE TO ESF LEAKAGE A visual representation of the RADTRAD model used to calculate the TSC dose due to the radioactivity release from ESF leakage is provided as Attachment No. 1 (RADTRAD Model for ESF Leakage Source Release) and developed in the Sections 2.0 and 5.0.
The activity released to the environment is assumed to be released as a ground level release from the Intermediate Building southwest corner to the TSC.
The RADTRAD model input consists of 3 volumes, 4 flow pathways, and 3 dose locations.
ESF inventory (activity available for release to the environment) is input as a user defined NIF file in Attachment No. 3 (ESF Halogen.nif) for the design basis case.
Release fractions and timing data for the LOCA are input as a RADTRAD default RFT file (Pwr dba.rft - Attachment No. 4).
Dose conversion factors (DCFs) utilized in the AST LOCA analysis are input as a RADTRAD default RFT file FGR11&12.inp (Attachment 9) for the design basis case.
7.3.1 TSC Operator Dose Due to ESF Leakage (Design Basis Source Terms) - Attachment 8 7.3.1.1 RADTRAD Volume I represents the Sump Volume:
Sump volume is 5.573E+04 ft3 (Section 5.12).
97% elemental iodine & 3% organic iodine (Section 2.14) 7.3.1.2 RADTRAD Volume 2 represents the Environment:
No input required 7.3.1.3 RADTRAD Volume 3 represents the TSC:
TSC habitability volume equals 2.07E+05 ft3 (Section 5.7) 7.3.1.4 RADTRAD Pathway 1 represents the ESF leakage to the Environment:
ESF leakage is 7.063E-03 cfm starting at 0.41 hr. through the duration of the accident (Section 5.6). In order to model a flash fraction of 10% (Section 5.16), the source is released through filters with an efficiency of 90%
7.3.1.5 RADTRAD Pathwa 2 represents the TSC Outside Air Makeup Pathway:
Normal Mode - Outside air makeup equals 12,000 cfm 0 minutes through the duration of the 30-day transient (Section 5.7)
No Emergency Mode or Filtration (Section 5.7) 7.3.1.6 RADTRAD Pathway 3 represents the TSC Unfiltered Air Inleakage Pathway TSC unfiltered air inleakage is conservatively assumed to be 1,000 cfm from zero through the duration of the 30-day transient (Section 5.7)
No filter is applied to this pathway (Section 5.7)
D000040-122, Revision 0 Page 27 of 155 7.3.1.7 RADTRAD Pathway 4 represents the TSC Exhaust Air Pathway:
Exhaust air flow equals all incoming air (makeup and inleakage, 12,000 cfm plus 1,000 cfin) 13,000 cfm from 0 through the duration of the 30 day transient (Section 2.7)
No filter is applied to this pathway (Section 2.7) 7.3.1.8 RADTRAD Dose Location 1 - EAB:
0-2 hour X/Q value per Table 4 used for entire 30-day transient 0-8 hour breathing rate per Table No. 5 for entire 30-day transient 7.3.1.9 RADTRAD Dose Location 2 - LPZ:
X/Q value per Table 4 Use breathing rate values per Table No. 5 7.3.1.10 RADTRAD Dose Location 3 -Protected TSC:
X/Q values per Table 4 Use breathing rate and occupancy values per Table No. 5 & Section 5.10 7.3.1.11 RADTRAD Source Term:
Use the user defined source inventory file ESF-Halogen.nif.
Modeled power level as I MW(t), since the source is based on curies per core Model isotopic decay and daughter in-growth Use the RADTRAD default release fraction file, Pwrdba.rft.
Use the default RADTRAD FGR 11 & 12 dose conversion factors for the MACCS 60 isotope inventory, FGRI l & 12. inp 7.3.12 RADTRAD Control Options:
Applicable Control Options are selected for the additional data supplied in the output printout The resulting RADTRAD output files are: Sump Release - TSC.oO (Attachment 8) 7.4 TSC OPERATOR DOSE - CONTAINMENT SHINE The direct dose to the whole body from the shine of radioactive material in the reactor building is not included in this calculation because the TSC envelope is located underground and the resulting dose is negligible.
7.5 TSC OPERATOR DOSE - EXTERNAL CLOUD SHINE The direct dose from the external radioactive cloud in the atmosphere is not included in this calculation because the TSC envelope is located underground and the resulting dose is negligible.
D000040-122, Revision 0 Page 28 of 155 8.0
SUMMARY
OF RESULTS As a result of the LOCA, operation of the TSC HVAC system in the normal mode (no filtration) will not exceed regulatory dose requirements. The doses are summarized in Table 6.
Table 6 LOCA Offsite and TSC Doses Case Integrated Dose Rem - TEDE Attachment EAB LPZ TSC NRC Acceptance Criteria 25 25 5.0 Containment Release 1.37 0.535 0.409 7
Sump Leakage 0.11 0.293 0.484 8
Total 1.48 0.828 0.893 The EAB and LPZ doses are the same as those provided in the AST LOCA calculation D000040-097, Revision I (Reference 4.28).
9.0 DISPOSITION OF RESULTS As shown above the NRC acceptance criteria for the TSC is met. The results of this calculation are incorporated into the VCSNS FSAR Section 15.4.1.
DO00040-122, Revision 0 Page 29 of 155 RADTRAD Models
D000040-122, Revision 0 Page 30 of 155 RBCUs 90% aerosol, elemental &
organic Flow Diagram: RADTRAD Model for Containment Source Release 54,200 cfm FP5 Recirc. Fans (52 sec. to 720 hr.)
1 FP 2 - 12,000 cfm filtered makeup (0 - 720 hr.)
0 Volume 1 I
I I
No Filtration Containment (1.84E+06 ft3)
Sprays (52 sec. to 4 hr.)
95% aerosol 4.85% elemental 0.15% organic plus unfiltered inleakage elemental - 20 hr' (DF 200 stop) 13,000 cfm Xparfieulate = 5.68 hr-' (DF 50 reduce by 10%)
natural dep. = 0.1 hr' (stop when sprays operating)
FP 1 Containment Leakage 0.2%/day (0 - 24 hr.)
0.1%/day (24 -720 hr.)
N Volume 2 Environment 01 FP 3 - 1,000 cfm unfiltered inleakage (0 - 720 hr.)
unfiltered inleakage/damper leakage/
ingress/egress FP 4 - TSC Exhaust: makeup Volume 3 TSC Habitability Envelope (2.07E+05 ft3)
D000040-122, Revision 0 Page 31 of 155 Flow Diagram: RADTRAD Model for ESF Leakage Source Release Volume 1 FP 2 - 12,000 cfm filtered makeup (0 - 720 hr.)
No Filtration Volume 3 Sump Volume 2 FP 1 TSC ESF Leakage Environment Habitability 5.573E+04 ft3 7.063E-03 cfm@0.38-720 hr.
Envelope Filter 90% efff, to account for FP 3 - 1,000 cfm unfiltered inleakage (0 - 720 hr.)
(2.07E+05 ft3) 10% flash fraction unfiltered inleakage/damper leakage/
97% elemental ingress/egress 3% organic FP 4 - TSC exhaust: makeup plus unfiltered inleakage 13,000 cfm
DO00040-122, Revision 0 Page 32 of 155 RADTRAD:
Containment Source File:
Cont.nif
D000040-122, Revision 0 Page 33 of 155 Nuclide Inventory Name:
VC Summer Design Basis Source - 2958 MWth PWR Core Inventory Power Level:
0.1000E+01 Nuclides:
60 Nuclide 001:
Co-58 7
0.6117120000E+07 0.5800E+02 7.55E+05 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 002:
Co-60 7
0.1663401096E+09 0.6000E+02
- 5. 78E+05 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 003:
Kr-85 1
0.3382974720E+09 0.8500E+02
- 8. 30E+05 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 004:
Kr-85m 1
0.1612800000E+05 0.8500E+02 2.72E+07 Kr-85 0.2100E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 005:
Kr-87 1
0.4578000000E+04 0.8700E+02
- 4. 96E+07 Rb-87 0.1000E+01 none 0.0000E+00
.none 0.0000E+00 Nuclide 006:
Kr-88 1
0.1022400000E+05 0.8800E+02
- 6. 71E+07 Rb-88 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 007:
Rb-86 3
0.1612224000E+07
0.8600E+02 4.43E+04 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 008:
Sr-89 5
0.4363200000E+07 0.8900E+02 8.41E+07 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 009:
Sr-90 5
0.9189573120E+09 0.9000E+02 4.54E+06 Y-90 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 010:
Sr-91 5
0.3420000000E+05 0.9100E+02 1.08E+08 Y-91m 0.5800E+00 Y-91 0.4200E+00 none 0.0000E+00 Nuclide 011:
Sr-92 5
0.9756000000E+04 0.9200E+02 1.13E+08 Y-92 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 012:
Y-90 9
0.2304000000E+06 0.9000E+02 4.87E+06 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 013:
Y-91 9
0.5055264000E+07 0.9100E+02 1.02E+08 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 014:
Y-92 9
0.1274400000E+05 0.9200E+02
D000040-122, Revision 0 Page 35 of 155
- 1. 13E+08 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 015:
Y-93 9
0.3636000000E+05 0.9300E+02 1.28E+08 Zr-93 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 016:
Zr-95 9
0.5527872000E+07 0.9500E+02 1.29E+08 Nb-95m 0.7000E-02 Nb-95 0.9900E+00 none 0.0000E+00 Nuclide 017:
Zr-97 9
0.6084000000E+05 0.9700E+02 1.35E+08 Nb-97m 0.9500E+00 Nb-97 0.5300E-01 none 0.0000E+00 Nuclide 018:
Nb-95 9
0.3036960000E+07 0.9500E+02 1.22E+08 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 019:
Mo-99 7
0.2376000000E+06 0.9900E+02 1.43E+08 Tc-99m 0.8800E+00 Tc-99 0.1200E+00 none 0.0000E+00 Nuclide 020:
Tc-99m 7
0.2167200000E+05 0.9900E+02 1.23E+08 Tc-99 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 021:
Ru-103 7
0.3393792000E+07 0.1030E+03 1.06E+08
Rh-103m 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 022:
Ru-105 7
0.1598400000E+05 0.1050E+03 6.92E+07 Rh-105 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 023:
Ru-106 7
0.3181248000E+08 0.1060E+03 2.42E+07 Rh-106 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 024:
Rh-105 7
0.1272960000E+06 0.1050E+03 4.97E+07 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 025:
Sb-127 4
0.3326400000E+06 0.1270E+03 6.53E+06 Te-127m 0.1800E+00 Te-127 0.8200E+00 none 0.0000E+00 Nuclide 026:
Sb-129 4
0.1555200000E+05 0.1290E+03 2.31E+07 Te-129m 0.2200E+00 Te-129 0.7700E+00 none 0.0000E+00 Nuclide 027:
Te-127 4
0.3366000000E+05 0.1270E+03 6.31E+06 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 028:
Te-127m 4
0.9417600000E+07
- 0. 1270E+03
- 8. 35E+05 Te-127 0.9800E+00
none 0.0000E+00 none 0.0000E+00 Nuclide 029:
Te-129 4
0.4176000000E+04 0.1290E+03 2.17E+07 1-129 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 030:
Te-129m 4
0.2903040000E+07 0.1290E+03 5.72E+06 Te-129 0.6500E+00 1-129 0.3500E+00 none 0.0000E+00 Nuclide 031:
Te-131m 4
0.1080000000E+06 0.1310E+03 1.10E+07 Te-131 0.2200E+00 1-131 0.7800E+00 none 0.0000E+00 Nuclide 032:
Te-132 4
0.2815200000E+06 0.1320E+03 1.09E+08 1-132 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 033:
1-131 2
0.6946560000E+06 0.1310E+03 8.20E+07 Xe-131m 0.1100E-01 none 0.0000E+00 none 0.0000E+00 Nuclide 034:
1-132 2
0.8280000000E+04 0.1320E+03 1.20E+08 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 035:
1-133 2
0.7488000000E+05 0.1330E+03 1.68E+08 Xe-133m 0.2900E-01 Xe-133 0.9700E+00
none 0.0000E+00 Nuclide 036:
1-134 2
0.3156000000E+04 0.1340E+03 1.80E+08 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 037:
1-135 2
0.2379600000E+05 0.1350E+03 1.54E+08 Xe-135m 0.1500E+00 Xe-135 0.8500E+00 none 0.0000E+00 Nuclide 038:
Xe-133 1
0.4531680000E+06 0.1330E+03 1.70E+08 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 039:
Xe-135 1
0.3272400000E+05 0.1350E+03
- 3. 70E+07 Cs-135 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 040:
Cs-134 3
0.6507177120E+08 0.1340E+03 1.01E+07 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 041:
Cs-136 3
0.1131840000E+07 0.1360E+03
- 3. 08E+06 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 042:
Cs-137 3
0.9467280000E+09 0.1370E+03
- 5. 66E+06 Ba-137m 0.9500E+00 none 0.0000E+00 none 0.0000E+00
D000040-122, Revision 0 Page 39 of 155 Nuclide 043:
Ba-139 6
0.4962000000E+04 0.1390E+03 1.47E+08 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 044:
Ba-140 6
0.1100736000E+07
- 0. 1400E+03 1.46E+08 La-140 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 045:
La-140 9
0.1449792000E+06
- 0. 1400E+03 1.49E+08 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 046:
La-141 9
0.1414800000E+05
- 0. 1410E+03 1.37E+08 Ce-141 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 047:
La-142 9
0.5550000000E+04 0.1420E+03 1.32E+08 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 048:
Ce-141 8
0.2808086400E+07 0.1410E+03 1.32E+08 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 049:
Ce-143 8
0.1188000000E+06 0.1430E+03 1.29E+08 Pr-143 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 050:
Ce-144 8
0.2456352000E+08 0.1440E+03 7. 98E+07 Pr-144m 0.1800E-01 Pr-144 0.9800E+00 none 0.0000E+00 Nuclide 051:
Pr-143 9
0.1171584000E+07 0.1430E+03 1.26E+08 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 052:
Nd-147 9
0.9486720000E+06 0.1470E+03
- 5. 65E+07 Pm-147 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 053:
Np-239 8
0.2034720000E+06 0.2390E+03 1.51E+09 Pu-239 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 054:
Pu-238 8
0.2768863824E+10 0.2380E+03 8.58E+04 U-234 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 055:
Pu-239 8
0.7594336440E+12 0.2390E+03 1.94E+04 U-235 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 056:
Pu-240 8
0.2062920312E+12 0.2400E+03 2.44E+04 U-236 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 057:
Pu-241
8 0.4544294400E+09
- 0. 2410E+03 4.11E+06 U-237 0.2400E-04 Am-241 0.1000E+01 none 0.0000E+00 Nuclide 058:
Am-241 9
0.1363919472E+11 0.2410E+03 2.72E+03 Np-237 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 059:
Cm-242 9
0.1406592000E+08 0.2420E+03 1.04E+06 Pu-238 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 060:
Cm-244 9
0.571508136E+9 0.2440E+03
- 6. 08E+04 Pu-240 0.1000E+01 none 0.0000E+00 none 0.0000E+00 End of Nuclear Inventory File
DO00040-122, Revision 0 Page 42 of 155 RADTRAD:
ESF Leakage Source File:
ESF_Halogen.nif
D000040-122, Revision 0 Page 43 of 155 Nuclide Inventory Name:
VC Summer Design Basis Source - 2958 MWth PWR Core Inventory Power Level:
0.1000E+01 Nuclides:
60 Nuclide 001:
Co-58 7
0.6117120000E+07 0.5800E+02 0.00E+00 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 002:
Co-60 7
0.1663401096E+09 0.6000E+02 0.00E+00 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 003:
Kr-85 1
0.3382974720E+09 0.8500E+02 0.00E+00 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 004:
Kr-85m 1
0.1612800000E+05 0.8500E+02 0.00E+00 Kr-85 0.2100E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 005:
Kr-87 1
0.4578000000E+04 0.8700E+02 0.00E+00 Rb-87 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 006:
Kr-88 1
0.1022400000E+05 0.8800E+02 0.00E+00 Rb-88 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 007:
Rb-86 3
0.1612224000E+07
0.8600E+02 0.00E+00 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 008:
Sr-89 5
0.4363200000E+07 0.8900E+02 0.00E+00 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 009:
Sr-90 5
0.9189573120E+09 0.9000E+02 0.00E+00 Y-90 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 010:
Sr-91 5
0.3420000000E+05 0.9100E+02 0.00E+00 Y-91m 0.5800E+00 Y-91 0.4200E+00 none 0.0000E+00 Nuclide 011:
Sr-92 5
0.9756000000E+04 0.9200E+02 0.00E+00 Y-92 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 012:
Y-90 9
0.2304000000E+06 0.9000E+02 0.00E+00 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 013:
Y-91 9
0.5055264000E+07 0.9100E+02 0.00E+00 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 014:
Y-92 9
0.1274400000E+05 0.9200E+02
0.00E+00 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 015:
Y-93 9
0.3636000000E+05, 0.9300E+02 0.00E+00 Zr-93 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 016:
Zr-95 9
0.5527872000E+07 0.9500E+02 0.00E+00 Nb-95m 0.7000E-02 Nb-95 0.9900E+00 none 0.0000E+00 Nuclide 017:
Zr-97 9
0.6084000000E+05 0.9700E+02 0.00E+00 Nb-97m 0.9500E+00 Nb-97 0.5300E-01 none 0.0000E+00 Nuclide 018:
Nb-95 9
0.3036960000E+07 0.9500E+02 0.00E+00 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 019:
Mo-99 7
0.2376000000E+06 0.9900E+02 0.00E+00 Tc-99m 0.8800E+00 Tc-99 0.1200E+00 none 0.0000E+00 Nuclide 020:
Tc-99m 7
0.2167200000E+05 0.9900E+02 0.00E+00 Tc-99 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 021:
Ru-103 7
0.3393792000E+07 0.1030E+03 0.00E+00
DC00040-122, Revision 0 Page 46 of 155 Rh-103m 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 022:
RU-105 7
0.1598400000E+05 0.1050E+03 0.00E+00 Rh-105 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 023:
Ru-106 7
0.3181248000E+08 0.1060E+03 0.00E+00 Rh-106 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 024:
Rh-105 7
0.1272960000E+06 0.1050E+03 0.00E+00 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 025:
Sb-127 4
0.3326400000E+06 0.1270E+03 0.00E+00 Te-127m 0.1800E+00 Te-127 0.8200E+00 none 0.0000E+00 Nuclide 026:
Sb-129 4
0.1555200000E+05
- 0. 1290E+03 0.00E+00 Te-129m 0.2200E+00 Te-129 0.7700E+00 none 0.0000E+00 Nuclide 027:
Te-127 4
0.3366000000E+05 0.1270E+03 0.00E+00 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 028:
Te-127m 4
0.9417600000E+07 0.1270E+03 0.00E+00 Te-127 0.9800E+00
D000040-122, Revision 0 Page 47 of 155 none 0.0000E+00 none 0.0000E+00 Nuclide 029:
Te-129 4
0.4176000000E+04
- 0. 1290E+03 0.00E+00 1-129 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 030:
Te-129m 4
0.2903040000E+07 0.1290E+03 0.00E+00 Te-129 0.6500E+00 1-129 0.3500E+00 none 0.0000E+00 Nuclide 031:
Te-131m 4
0.1080000000E+06
- 0. 1310E+03 0.00E+00 Te-131 0.2200E+00 1-131 0.7800E+00 none 0.0000E+00 Nuclide 032:
Te-132 4
0.2815200000E+06 0.1320E+03 0.00E+00 1-132 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 033:
1-131 2
0.6946560000E+06
- 0. 1310E+03
- 8. 20E+07 Xe-131m 0.1100E-01 none 0.0000E+00 none 0.0000E+00 Nuclide 034:
1-132 2
0.8280000000E+04 0.1320E+03 1.20E+08 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 035:
1-133 2
0.7488000000E+05 0.1330E+03 1.68E+08 Xe-133m 0.2900E-01 Xe-133 0.9700E+00
none 0.0000E+00 Nuclide 036:
1-134 2
0.3156000000E+04 0.1340E+03 1.80E+08 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 037:
1-135 2
0.2379600000E+05 0.1350E+03 1.54E+08 Xe-135m 0.1500E+00 Xe-135 0.8500E+00 none 0.0000E+00 Nuclide 038:
Xe-133 1
0.4531680000E+06 0.1330E+03 0.00E+00 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 039:
Xe-135 1
0.3272400000E+05 0.1350E+03 0.00E+00 Cs-135 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 040:
Cs-134 3
0.6507177120E+08 0.1340E+03 0.00E+00 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 041:
Cs-136 3
0.1131840000E+07 0.1360E+03 0.00E+00.
none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 042:
Cs-137 3
0.9467280000E+09 0.1370E+03 0.00E+00 Ba-137m 0.9500E+00 none 0.0000E+00 none 0.0000E+00
D000040-122, Revision 0 Page 49 of 155 Nuclide 043:
Ba-139 6
0.4962000000E+04 0.1390E+03 0.00E+00 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 044:
Ba-140 6
0.1100736000E+07 0.1400E+03 0.00E+00 La-140 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 045:
La-140 9
0.1449792000E+06 0.1400E+03 0.00E+00 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 046:
La-141 9
0.1414800000E+05 0.1410E+03 0.00E+00 Ce-141 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 047:
La-142 9
0.5550000000E+04 0.1420E+03 0.00E+00 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 048:
Ce-141 8
0.2808086400E+07 0.1410E+03 0.00E+00 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 049:
Ce-143 8
0.1188000000E+06 0.1430E+03 0.00E+00 Pr-143 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 050:
Ce-144 8
0.2456352000E+08 0.1440E+03 0.00E+00 Pr-144m 0.1800E-01 Pr-144 0.9800E+00 none 0.0000E+00 Nuclide 051:
Pr-143 9
0.1171584000E+07 0.1430E+03 0.00E+00 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 052:
Nd-147 9
0.9486720000E+06 0.1470E+03 0.00E+00 Pm-147 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 053:
Np-239 8
0.2034720000E+06 0.2390E+03 0.00E+00 Pu-239 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 054:
Pu-238 8
0.2768863824E+10 0.2380E+03 0.00E+00 U-234 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 055:
Pu-239 8
0.7594336440E+12 0.2390E+03 0.00E+00 U-235 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 056:
Pu-240 8
0.2062920312E+12 0.2400E+03 0.00E+00 U-236 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 057:
Pu-241
D000040-122, Revision 0 Page 51 of 155 8
0.4544294400E+09 0.2410E+03 0.00E+00 U-237 0.2400E-04 Am-241 0.1000E+01 none 0.0000E+00 Nuclide 058:
Am-241 9
0.1363919472E+11 0.2410E+03 0.00E+00 Np-237 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 059:
Cm-242 9
0.1406592000E+08 0.2420E+03 0.00E+00 Pu-238 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 060:
Cm-244 9
0.571508136E+9 0.2440E+03 0.00E+00 Pu-240 0.1000E+01 none 0.0000E+00 none 0.0000E+00 End of Nuclear Inventory File
DO00040-122, Revision 0 Page 52 of 155 RADTRAD:
Release Fraction File:
Pwr dba.rft
D000040-122, Revision 0 Page 53 of 155 Release Fraction and Timing Name:
PWR, RG 1.183, Table 2 Section 3.2 Duration (h):
Design Basis Accident 0.5000E+00 0.1300E+01 0.0000E+00 0.0000E+00 Noble Gases:
0.5000E-01 0.9500E+00 0.0000E+00 0.0000E+00 Iodine:
0.5000E-01 0.3500E+00 0.0000E+00 0.0000E+00 Cesium:
0.5000E-01 0.2500E+00 0.0000E+00 0.0000E+00 Tellurium:
0.0000E+00 0.5000E-01 0.0000E+00 0.0000E+00 Strontium:
0.0000E+00 0.2000E-01 0.0000E+00 0.0000E+00 Barium:
0.0000E+00 0.2000E-01 0.0000E+00 0.0000E+00 Ruthenium:
0.0000E+00 0.2500E-02 0.0000E+00 0.0000E+00 Cerium:
0.0000E+00 0.5000E-03 0.0000E+00 0.0000E+00 Lanthanum:
0.0000E+00 0.2000E-03 0.0000E+00 0.0000E+00 Non-Radioactive Aerosols (kg):
0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 End of Release File
DC00040-122, Revision 0 Page 54 of 155 RADTRAD Input/Output File:
Base Case No Spray - DBA
D000040-122, Revision 0 Page 55 of 155 RADTRAD Version 3.03 (Spring 2001) run on 10/17/2007 at 7:24:34 File information Plant file
= C:\\Program Files\\radtrad3 03\\VCS LOCA\\Base Case No Spray DBA.psf Inventory file
= C:\\Program Files\\radtrad3 03\\VCS LOCA\\Cont.nif Release file
= c:\\program files\\radtrad3 03\\defaults\\pwr dba.rft Dose Conversion file = c:\\program files\\radtrad3 03\\defaults\\fgrll&12.inp Radtrad 3.03 4/15/2001 Base Case No Spray To Determine Elemental Iodine Maximum Concentration Nuclide Inventory File:
C:\\Program Files\\radtrad3 03\\VCS LOCA\\Cont.nif Plant Power Level:
1.0000E+00 Compartments:
2 Compartment 1:
Containment 3
1.8400E+06 0
0 0
0 0
Compartment 2:
Environment 2
0.0000E+00 0
0 0
0 0
Pathways:
2 Pathway 1:
Dummy Flow Rate - Containment to Environment 1
2 2
Pathway 2:
RBCU Flow Containment to Containment 1
DC00040-122, Revision 0 Page 56 of 155 1
2 End of Plant Model File Scenario Description Name:
Plant Model Filename:
Source Term:
1 1
1.0000E+00 c:\\program files\\radtrad3_ 03\\defaults\\fgrll&12.inp c:\\program files\\radtrad3 03\\defaults\\pwr dba.rft 0.0000E+00 1
9.5000E-01 4.8500E-02 1.5000E-03 1.0000E+00 Overlying Pool:
0 0.0000E+00 0
0 0
0 Compartments:
2 Compartment 1:
1 1
0 0
0 0
0 0
0 Compartment 2:
0 1
0 0
0 0
0 0
0 Pathways:
2 Pathway 1:
0 0
0 0
0 1
2 0.0000E+00 1.0000E-10 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0
0 0
0 0
0 Pathway 2:
0
DC00040-122, Revision 0 Page 57 of 155 1
3 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 1.4400E-02 5.4200E+04 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0
0 0
0 0
0 Dose Locations:
1 Location 1:
EAB 2
1 2
0.0000E+00 1.0000E-04 7.2000E+02 0.0000E+00 1
4 0.0000E+00 3.5000E-04 8.0000E+00 1.8000E-04 2.4000E+01 2.3000E-04 7.2000E+02 0.0000E+00 0
Effective Volume Location:
0 Simulation Parameters:
3 0.0000E+00 5.0000E-01 1.5000E+00 1.0000E-01 1.9000E+00 0.0000E+00 Output Filename:
C:\\Program Files\\radtrad3 03\\VCS LOCA\\Base Case No Spray DBA,.oO 1
1 1
1 0
End of Scenario File
D000040-122, Revision 0 Page 58 of 155 RADTRAD Version 3.03 (Spring 2001) run on 10/17/2007 at 7:24:34 Plant Description Number of Nuclides =
60 Inventory Power =
1.0000E+00 MWth Plant Power Level =
1.0000E+00 MWth Number of compartments
=
2 Compartment information Compartment number 1
(Source term fraction =
1.0000E+00 Name: Containment Compartment volume =
1.8400E+06 Compartment type is Normal (Cubic feet)
Pathways into and out of compartment 1 Inlet Pathway Number 2:
RBCU Flow Containment to Containment Exit Pathway Number 1:
Dummy Flow Rate - Containment to Environment Exit Pathway Number 2:
RBCU Flow Containment to Containment Compartment number 2 Name: Environment Compartment type is Environment Pathways into and out of compartment 2 Inlet Pathway Number 1:
Dummy Flow Rate - Containment to Environment Total number of pathways =
2
D000040-122, Revision 0 Page 59 of 155 RADTRAD Version 3.03 (Spring 2001) run on 10/17/2007 at 7:24:34 Scenario Description Radioactive Decay is enabled Calculation of Daughters is enabled Release Fractions and Timings GAP EARLY IN-VESSEL LATE RELEASE RELEASE MASS 0.500000 hr 1.3000 hrs 0.0000 hrs (gm)
NOBLES IODINE CESIUM TELLURIUM STRONTIUM BARIUM RUTHENIUM CERIUM LANTHANUM 5.0000E-02 5.0000E-02 5.0000E-02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 9.5000E-01 3.5000E-01 2.5000E-01 5.0000E-02 2.0000E-02 2.0000E-02 2.5000E-03 5.0000E-04 2.0000E-04 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 2.987E+03 3.488E+02 2.188E+04 3.416E+01 7.243E+02 4.007E+01 2.861E+01 2.502E+02 3.628E+00 Inventory Power =
1.
MWt Nuclide Group Specific half Whole Body Inhaled Inhaled Name Inventory life DCF Thyroid Effective Co-58 7
(Ci/MWt) 7.550E+05 (s) 6.117E+06 (Sv-m3/Bq-s) 4.760E-14 (Sv/Bq) 8.720E-10 (Sv/Bq) 2.940E-09 Co-60 7
5.780E+05 1.663E+08 1.260E-13 1.620E-08 5.910E-08 Kr-85 1
8.300E+05 3.383E+08 1.190E-16 0.000E+00 0.000E+00 Kr-85m 1
2.720E+07 1.613E+04 7.480E-15 0.000E+00 0.000E+00 Kr-87 1
4.960E+07 4.578E+03 4.120E-14 0.000E+00 0.000E+00 Kr-88 1
6.710E+07 1.022.E+04 1.020E-13 0.000E+00 0.000E+00 Rb-86 3
4.430E+04 1.612E+06 4.810E-15 1.330E-09 1.790E-09 Sr-89 5
8.410E+07 4.363E+06 7.730E-17 7.960E-12 1.120E-08 Sr-90 5
4.540E+06 9.190E+08 7.530E-18 2.690E-10 3.510E-07 Sr-91 5
1.080E+08 3.420E+04 4.924E-14 9.930E-12 4.547E-10 Sr-92 5
1.130E+08 9.756E+03 6.790E-14 3.920E-12 2.180E-10 Y-90 9
4.870E+06 2.304E+05 1.900E-16 5.170E-13 2.280E-09 Y-91 9
1.020E+08 5.055E+06 2.600E-16 8.500E-12 1.320E-08 Y-92 9
1.130E+08 1.274E+04 1.300E-14 1.050E-12 2.110E-10 Y-93 9
1.280E+08 3.636E+04 4.800E-15 9.260E-13 5.820E-10 Zr-95 9
1.290E+08 5.528E+06 3.600E-14 1.440E-09 6.390E-09 Zr-97 9
1.350E+08 6.084E+04 4.432E-14 2.315E-11 1.171E-09 Nb-95 9
1.220E+08 3.037E+06 3.740E-14 3.580E-10 1.570E-09 Mo-99 7
1.430E+08 2.376E+05 7.280E-15 1.520E-11 1.070E-09 Tc-99m 7
1.230E+08 2.167E+04 5.890E-15 5.010E-11 8.800E-12 Ru-103 7
1.060E+08 3.394E+06 2.251E-14 2.570E-10 2.421E-09 Ru-105 7
6.920E+07 1.598E+04 3.810E-14 4.150E-12 1.230E-10 Ru-106 7
2.420E+07 3.181E+07 1.040E-14 1.720E-09 1.290E-07 Rh-105 7
4.970E+07 1.273E+05 3.720E-15 2.880E-12 2.580E-10 Sb-127 4
6.530E+06 3.326E+05 3.330E-14 6.150E-11 1.630E-09 Sb-129 4
2.310E+07 1.555E+04 7.140E-14 9.720E-12 1.740E-10 Te-127 4
6.310E+06 3.366E+04 2.420E-16 1.840E-12 8.600E-11 Te-127m 4
8.350E+05 9.418E+06 1.470E-16 9.660E-11 5.810E-09 Te-129 4
2.170E+07 4.176E+03 2.750E-15 5.090E-13 2.090E-11 Te-129m 4
5.720E+06 2.903E+06 3.337E-15 1.563E-10 6.484E-09 Te-131m 4
1.100E+07 1.080E+05 7.463E-14 3.669E-08 1.758E-09 Te-132 4
1.090E+08 2.815E+05 1.030E-14 6.280E-08 2.550E-09 1-131 2
8.200E+07 6.947E+05 1.820E-14 2.920E-07 8.890E-09 1-132 2
1.200E+08 8.280E+03 1.120E-13 1.740E-09 1.030E-10
D000040-122, Revision 0 Page 60 of 155 I-133 2
1.680E+08 7.488E+04 2.940E-14 4.860E-08 1.580E-09 I-134 2
1.800E+08 3.156E+03 1.300E-13 2.880E-10 3.550E-11 I-135 2
1.540E+08 2.380E+04 8.294E-14 8.460E-09 3.320E-10 Xe-133 1
1.590E+08 4.532E+05 1.560E-15 0.000E+00 0.000E+00 Xe-135 1
2.980E+07 3.272E+04 1.190E-14 0.000E+00 0.000E+00 Cs-134 3
1.010E+07 6.507E+07 7.570E-14 1.110E-08 1.250E-08 Cs-136 3
3.080E+06 1.132E+06 1.060E-13 1.730E-09 1.980E-09 Cs-137 3
5.660E+06 9.467E+08 2.725E-14 7.930E-09 8.630E-09 Ba-139 6
1.470E+08 4.962E+03 2.170E-15 2.400E-12 4.640E-11 Ba-140 6
1.460E+08 1.101E+06 8.580E-15 2.560E-10 1.010E-09 La-140 9
1.490E+08 1.450E+05 1.170E-13 6.870E-11 1.310E-09 La-141 9
1.370E+08 1.415E+04 2.390E-15 9.400E-12 1.570E-10 La-142 9
1.320E+08 5.550E+03 1.440E-13 8.740E-12 6.840E-11 Ce-141 8
1.320E+08 2.808E+06 3.430E-15 2.550E-11 2.420E-09 Ce-143 8
1.290E+08 1.188E+05 1.290E-14 6.230E-12 9.160E-10 Ce-144 8
7.980E+07 2.456E+07 2.773E-15 2.920E-10 1.010E-07 Pr-143 9
1.260E+08 1.172E+06 2.100E-17 1.680E-18 2.190E-09 Nd-147 9
5.650E+07 9.487E+05 6.190E-15 1.820E-11 1.850E-09 Np-239 8
1.510E+09 2.035E+05 7.690E-15 7.620E-12 6.780E-10 Pu-238 8
8.580E+04 2.769E+09 4.880E-18 3.860E-10 7.790E-05 Pu-239 8
1.940E+04 7.594E+11 4.240E-18 3.750E-10 8.330E-05 Pu-240 8
2.440E+04 2.063E+11 4.750E-18 3.760E-10 8.330E-05 Pu-241 8
4.110E+06 4.544E+08 7.250E-20 9.150E-12 1.340E-06 Am-241 9
2.720E+03 1.364E+10 8.180E-16 1.600E-09 1.200E-04 Cm-242 9
1.040E+06 1.407E+07 5.690E-18 9.410E-10 4.670E-06 Cm-244 9
6.080E+04 5.715E+08 4.910E-18 1.010E-09 6.700E-05 Nuclide Daughter Fraction Daughter Fraction Daughter Fraction Kr-85m Kr-85 0.21 none 0.00 none 0.00 Kr-87 Rb-87 1.00 none 0.00 none 0.00 Kr-88 Rb-88 1.00 none 0.00 none 0.00 Sr-90 Y-90 1.00 none 0.00 none 0.00 Sr-91 Y-91m 0.58 Y-91 0.42 none 0.00 Sr-92 Y-92 1.00 none 0.00 none 0.00 Y-93 Zr-93 1.00 none 0.00 none 0.00 Zr-95 Nb-95m 0.01 Nb-95 0.99 none 0.00 Zr-97 Nb-97m 0.95 Nb-97 0.05 none 0.00 Mo-99 Tc-99m 0.88 Tc-99 0.12 none 0.00 Tc-99m Tc-99 1.00 none 0.00 none 0.00 Ru-103 Rh-103m 1.00 none 0.00 none 0.00 Ru-105 Rh-105 1.00 none 0.00 none 0.00 Ru-106 Rh-106 1.00 none 0.00 none 0.00 Sb-127 Te-127m 0.18 Te-127 0.82 none 0.00 Sb-129 Te-129m 0.22 Te-129 0.77 none 0.00 Te-127m Te-127 0.98 none 0.00 none 0.00 Te-129 1-129 1.00 none 0.00 none 0.00 Te-129m Te-129 0.65 I-129 0.35 none 0.00 Te-131m Te-131 0.22 I-131 0.78 none 0.00 Te-132 1-132 1.00 none 0.00 none 0.00 1-131 Xe-131m 0.01 none 0.00 none 0.00 I-133 Xe-133m 0.03 Xe-133 0.97 none 0.00 1-135 Xe-135m 0.15 Xe-135 0.85 none 0.00 Xe-135 Cs-135 1.00 none 0.00 none 0.00 Cs-137 Ba-137m 0.95 none 0.00 none 0.00 Ba-140 La-140 1.00 none 0.00 none 0.00 La-141 Ce-141 1.00 none 0.00 none 0.00 Ce-143 Pr-143 1.00 none 0.00 none 0.00 Ce-144 Pr-144m 0.02 Pr-144 0.98 none 0.00 Nd-147 Pm-147 1.00 none 0.00 none 0.00 Np-239 Pu-239 1.00 none 0.00 none 0.00 Pu-238 U-234 1.00 none 0.00 none 0.00 Pu-239 U-235 1.00 none 0.00 none 0.00 Pu-240 U-236 1.00 none 0.00 none 0.00 Pu-241 U-237 0.00 Am-241 1.00 none 0.00
DC0004O-122, Revision 0 Page 61 of 155 Am-241 Np-237 1.00 none 0.00 none 0.00 Cm-242 Pu-238 1.00 none 0.00 none 0.00 Cm-244 Pu-240 1.00 none 0.00 none 0.00 Iodine fractions Aerosol
=
9.5000E-01 Elemental
=
4.8500E-02 Organic
=
1.5000E-03 COMPARTMENT DATA Compartment number 1:
Containment Compartment number 2: Environment PATHWAY DATA Pathway number 1: Dummy Flow Rate - Containment to Environment Pathway Filter: Removal Data Time (hr)
Flow Rate Filter Efficiencies (%)
(cfm)
Aerosol Elemental Organic 0.0000E+00 1.0000E-10 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Pathway number 2: RBCU.Flow Containment to Containment Pathway Filter: Removal Data Time (hr)
Flow Rate (cfm)
Filter Efficiencies (%)
Aerosol Elemental Organic 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 1.4400E-02 5.4200E+04 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 LOCATION DATA Location EAB is in compartment 2
Location X/Q Data Time (hr)
X/Q (s
- m^-3) 0.0000E+00 1.0000E-04 7.2000E+02 0.0000E+00 Location Breathing Rate Data Time (hr)
Breathing Rate (m^3
- sec^-1) 0.0000E+00 3.5000E-04 8.0000E+00 1.8000E-04 2.4000E+01 2.3000E-04 7.2000E+02 0.0000E+00 USER SPECIFIED TIME STEP DATA - SUPPLEMENTAL TIME STEPS Time Time step 0.0000E+00 5.0000E-01 1.5000E+00 1.0000E-01 1.9000E+00 0.0000E+00
DC0004O-122, Revision 0 Page 62 of 155 RADTRAD Version 3.03 (Spring 2001) run on 10/17/2007 at 7:24:34 Dose, Detailed model and Detailed Inventory Output EAB Doses:
Time (h) =
0.0144 Whole Body Thyroid TEDE Delta dose (rem) 8.3759E-16 1.4813E-13 6.2909E-15 Accumulated dose (rem) 8.3759E-16 1.4813E-13 6.2909E-15 Containment Compartment Nuclide Inventory:
Time (h) =
0.0144 Ci kg Atoms Decay Kr-85 1.1952E+03 3.0464E-03 2.1583E+22 2.1258E+15 1-131 1.1807E+05 9.5240E-04 4.3782E+21 2.1002E+17 1-133 2.4180E+05 2.1346E-04 9.6651E+20 4.3018E+17 Xe-133 2.2896E+05 1.2232E-03 5.5385E+21 4.0722E+17 Cs-134 1.4544E+04 1.1241E-02 5.0519E+22 2.5869E+16 Cs-137 8.1504E+03 9.3702E-02 4.1189E+23 1.4497E+16 Containment Transport Group Inventory:
Time (h) =
0.0144 Atmosphere Sump Noble gases (atoms) 2.7300E+22 0.0000E+00 Elemental I (atoms) 2.7864E+20 0.0000E+00 Organic I (atoms) 8.6179E+18 0.0000E+00 Aerosols (kg) 1.0620E-01 0.0000E+00 Dose Effective (Ci/cc) 1-131 (Thyroid) 3.1862E-06 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 4.0632E-06 Total I (Ci) 1.0097E+06 Dummy Flow Rate - Containment to Environment Transport Group Inventory:
Time (h) =
0.0144 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 6.4097E+05 Elemental I (atoms) 0.0000E+00 6.5441E+03 Organic I (atoms) 0.0000E+00 2.0240E+02 Aerosols (kg) 0.0000E+00 2.4933E-18 RBCU Flow Containment to Containment Transport Group Inventory:
Time (h) =
0.0144 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00
DC00040-122, Revision 0 Page 63 of 155 Aerosols (kg) 0.0000E+00 0.0000E+00 EAB Doses:
Time (h) =
0.5000 Whole Body Thyroid TEDE Delta dose (rem) 9.1276E-13 1.7761E-10 7.4475E-12 Accumulated dose (rem) 9.1360E-13 1.7776E-10 7.4538E-12 Containment Compartment Nuclide Inventory:
Time (h) =
0.5000 Ci kg Atoms Decay Kr-85 4.1501E+04 1.0578E-01 7.4943E+23 1.6446E+18 Kr-85m 1.2588E+06 1.5296E-04 1.0837E+21 5.1319E+19 Kr-87 1.8884E+06 6.6667E-05 4.6147E+20 8.2854E+19 Kr-88 2.9696E+06 2.3682E-04 1.6207E+21 1.2309E+20 Rb-86 2.2133E+03 2.7201E-05 1.9048E+20 8.7732E+16 I-131 4.0930E+06 3.3014E-02 1.5177E+23 1.6230E+20 I-132 5.4641E+06 5.2936E-04 2.4150E+21 2.2449E+20 I-133 8.2612E+06 7.2927E-03 3.3021E+22 3.2937E+20 I-134 6.0611E+06 2.2721E-04 1.0211E+21 2.7886E+20 I-135 7.3067E+06 2.0806E-03 9.2811E+21 2.9516E+20 Xe-133 7.9504E+06 4.2474E-02 1.9232E+23 3.1497E+20 Xe-135 1.6736E+06 6.5537E-04 2.9235E+21 6.2814E+19 Cs-134 5.0499E+05 3.9031E-01 1.7541E+24 2.0012E+19 Cs-136 1.5383E+05 2.0989E-03 9.2940E+21 6.0984E+18 Cs-137 2.8300E+05 3.2535E+00 1.4302E+25 1.1215E+19 Containment Transport Group Inventory:
Time (h) =
0.5000 Atmosphere Sump Noble gases (atoms) 9.4784E+23 0.0000E+00 Elemental I (atoms) 9.5791E+21 0.0000E+00 Organic I (atoms) 2.9626E+20 0.0000E+00 Aerosols (kg) 3.6870E+00 0.0000E+00 Dose Effective (Ci/cc) 1-131 (Thyroid) 1.0975E-04 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 1.3837E-04 Total I (Ci) 3.1186E+07 Dummy Flow Rate - Containment to Environment Transport Group Inventory:
Time (h) =
0.5000 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 7.7273E+08 Elemental I (atoms) 0.0000E+00 7.8435E+06 Organic I (atoms) 0.0000E+00 2.4258E+05 Aerosols (kg) 0.0000E+00 3.0058E-15 RBCU Flow Containment to Containment Transport Group Inventory:
Time (h) =
0.5000 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 4.1847E+23 Elemental I (atoms) 0.0000E+00 4.2476E+21 Organic I (atoms) 0.0000E+00 1.3137E+20 Aerosols (kg) 0.0000E+00 1.6278E+00 EAB Doses:
Time (h) =
1.0000 Whole Body Thyroid TEDE Delta dose (rem) 4.3043E-12 8.4211E-10 3.7951E-11 Accumulated dose (rem) 5.2179E-12 1.0199E-09 4.5405E-11 Containment Compartment Nuclide Inventory:
Time (h) =
1.0000
.Ci kg Atoms Decay
D000040-122, Revision 0 Page 64 of 155 Co-58 7.2567E+02 2.2821E-05 2.3695E+20 2.9000E+16 Co-60 5.5576E+02 4.9166E-04
- 4. 9347E+21 2.2208E+16 Kr-85 3.4478E+05 8.7880E-01 6.2262E+24 1.6528E+19 Kr-85m 9.6789E+06 1.1761E-03 8.3326E+21 4.8206E+20 Kr-87
- 1. 1946E+07 4.2173E.-04 2.9192E+21 6.5810E+20 Kr-88 2.1836E+07 1.7414E-03 1.1917E+22 1.1123E+21 Rb-86 6.4646E+03 7.9450E-05 5.5634E+20 4.0508E+17 Sr-89 6.4655E+05 2.2255E-02 1.5059E+23 2.5839E+19 Sr-90 3.4923E+04 2.5602E-01 1.7131E+24 1.3955E+18 Sr-91 7.7231E+05 2.1305E-04 1.4099E+21 3.1279E+19 Sr-92 6.7306E+05 5.3547E-05 3.5051E+20 2.8202E+19 Y-91 7.8921E+03 3.2181E-04 2.1297E+21
- 3. 1432E+17 Y-92 4.8483E+04 5.0386E-06 3.2982E+19 1.0724E+18 Y-93
- 9. 1931E+03 2.7555E-06 1.7843E+19
- 3. 7202E+17 Zr-95
- 9. 9186E+03 4.6170E-04 2.9267E+21
- 3. 9638E+17 Zr-97 9.9673E+03 5.2139E-06
- 3. 2370E+19 4.0131E+17 Nb-95 9.3850E+03 2.4001E-04 1.5214E+21 3.7500E+17 Mo-99 1.3606E+05 2.8369E-04 1.7257E+21
- 5. 4476E+18 Tc-99m 1.1857E+05 2.2549E-05 1.3717E+20 4.7087E+18 Ru-103 1.0185E+05
- 3. 1557E-03 1.8451E+22 4.0704E+18 Ru-105 5.6921E+04 8.4679E-06
- 4. 8566E+19
- 2. 3411E+18 Ru-106 2.3267E+04 6.9547E-03
- 3. 9511E+22
- 9. 2978E+17 Rh-105 4.8057E+04 5.6937E-05 3.2655E+20 1.9166E+18 Sb-127 1.2464E+05 4.6672E-04 2.2131E+21 4.9874E+18 Sb-129 3.7838E+05 6.7286E-05 3.1411E+20 1.5575E+19 Te-127 1.2116E+05
- 4. 5910E-05 2.1770E+20 4.8255E+18 Te-127m 1.6059E+04 1.7025E-03 8.0732E+21 6.4171E+17 Te-129 4.0790E+05 1.9477E-05
- 9. 0927E+19 1.5982E+19 Te-129m 1.0998E+05 3.6509E-03 1.7043E+22 4.3949E+18 Te-131m 2.0671E+05 2.5922E-04
- 1. 1917E+21 8.2951E+18 Te-132 2.0777E+06 6.8436E-03
- 3. 1222E+22
- 8. 3158E+19 1-131 1.5088E+07 1.2170E-01 5.5945E+23 8.7455E+20 1-132 1.9422E+07 1.8816E-03 8.5841E+21
- 1. 1682E+21 1-133 2.9999E+07 2.6482E-02
- 1. 1991E+23 1.7545E+21 1-134 1.5072E+07 5.6497E-04 2.5391E+21 1.1226E+21 1-135 2.5600E+07 7.2897E-03 3.2518E+22
- 1. 5297E+21 Xe-133 6.5989E+07 3.5254E-01 1.5963E+24 3.1642E+21 Xe-135 1.4643E+07
- 5. 7341E-03 2.5579E+22 6.7992E+20 Cs-134 1.4761E+06 1.1409E+00 5.1272E+24 9.2450E+19 Cs-136 4.4916E+05
- 6. 1285E-03 2.7137E+22 2.8151E+19 Cs-137 8.2723E+05
- 9. 5104E+00 4.1805E+25
- 5. 1810E+19 Ba-139 6.8387E+05 4.1809E-05 1.8114E+20 3.0030E+19 Ba-140 1.1205E+06 1.5306E-02 6.5839E+22 4.4795E+19 La-140 1.7175E+04 3.0899E-05 1.3291E+20 5.5907E+17 Ce-141 2.5380E+04 8.9073E-04 3.8043E+21 1.0142E+18 Ce-143 2.4292E+04 3.6580E-05 1.5405E+20 9.7446E+17 Ce-144 1.5345E+04 4.8110E-03 2.0120E+22
- 6. 1318E+17 Pr-143
- 9. 7019E+03 1.4408E-04 6.0675E+20
- 3. 8744E+17 Nd-147 4.3347E+03 5.3582E-05 2.1951E+20 1.7330E+17 Np-239 2.8685E+05 1.2364E-03 3.1155E+21
- 3. 7317E+00 6.0037E-02 1.5128E+23 1.4911E+14 Pu-240 4.6923E+00 2.0592E-02 5.1671E+22 1.8750E+14 Pu-241 7.9038E+02 7.6726E-03 1.9173E+22 3.1584E+16 Am-241 2.0931E-01 6.0986E-05 1.5239E+20
- 8. 3631E+12 Cm-242
- 7. 9986E+01 2.4134E-05
- 6. 0056E+19 3.1963E+15 Cm-244 4.6769E+00 5.7809E-05 1.4268E+20 1.8689E+14 Containment Transport Group Inventory:
Time (h) =
1.0000 Atmosphere Sump Noble gases (atoms) 7.8712E+24 0.0000E+00 Elemental I (atoms) 3.5066E+22 0.0000E+00 Organic I (atoms) 1.0845E+21 0.0000E+00 Aerosols (kg) 1.1223E+01 0.0000E+00
DC0004O-122, Revision 0 Page 65 of 155 Dose Effective (Ci/cc) 1-131 (Thyroid) 4.0214E-04 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 5.0272E-04 Total I
(Ci) 1.0518E+08 Dummy Flow Rate - Containment to Environment Transport Group Inventory:
Time (h) =
1.0000 Pathway Filtered Transported Noble gases Elemental I (atoms)
(atoms) 0.0000E+00 0.0000E+00 7.9633E+09 4.4337E+07 Organic I (atoms)
Aerosols (kg) 0.0000E+00 1.3712E+06 0.0000E+00 1.5161E-14 RBCU Flow Containment to Containment Transport Group Inventory:
Time (h) =
1.0000 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 4.3158E+24 Elemental I (atoms) 0.0000E+00 2.4027E+22 Organic I (atoms) 0.0000E+00 7.4310E+20 Aerosols (kg) 0.0000E+00 8.2160E+00 EAB Doses:
Time (h) =
1.5000 Whole Body Thyroid TEDE Delta dose (rem) 8.5936E-12 1.8074E-09 8.3065E-11 Accumulated dose (rem) 1.3812E-11 2.8273E-09 1.2847E-10 Containment Compartment Nuclide Inventory:
Time (h) =
1.5000 Ci kg Atoms Decay Co-58
- 1. 4510E+03 4.5633E-05 4.7381E+20 1.0632E+17 Co-60 1.1115E+03 9.8331E-04 9.8693E+21 8.1430E+16 Kr-85 6.4808E+05
- 1. 6518E+00 1.1703E+25 5.1609E+19 Kr-85m 1.6838E+07 2.0461E-03 1.4496E+22 1.4264E+21 Kr-87 1.7097E+07 6.0359E-04 4.1781E+21 1.7087E+21 Kr-88 3.6329E+07 2.8972E-03 1.9827E+22 3.1922E+21 Rb-86 1.0709E+04 1.3162E-04 9.2165E+20 1.0053E+18 Sr-89 1.2927E+06 4.4497E-02 3.0109E+23 9.4725E+19 Sr-90 6.9846E+04 5.1204E-01 3.4262E+24 5.1169E+18 Sr-91 1.4893E+06 4.1084E-04 2.7188E+21 1.1195E+20 Sr-92
- 1. 1845E+06 9.4239E-05 6.1687E+20 9.5096E+19 Y-90 1.1590E+03 2.1302E-06 1.4254E+19 7.1230E+16 Y-91 1.5858E+04 6.4664E-04 4.2793E+21 1.1562E+18 Y-92 1.4689E+05 1.5265E-05 9.9925E+19 6.7671E+18 Y-93 1.7766E+04 5.3250E-06 3.4482E+19 1.3334E+18 Zr-95 1.9833E+04 9.2319E-04 5.8522E+21 1.4532E+18 Zr-97 1.9530E+04 1.0216E-05 6.3426E+19 1.4515E+18 Nb-95 1.8770E+04 4.8002E-04 3.0429E+21 1.3750E+18 Mo-99 2.7070E+05 5.6441E-04 3.4333E+21 1.9905E+19 Tc-99m 2.3731E+05 4.5131E-05 2.7453E+20 1.7275E+19 Ru-103 2.0362E+05 6.3092E-03 3.6888E+22 1.4921E+19 Ru-105 1.0529E+05 1.5664E-05 8.9839E+19 8.1531E+18 Ru-106 4.6533E+04 1.3909E-02 7.9020E+22 3.4091E+18 Rh-105 9.6247E+04 1.1403E-04 6.5400E+20 7.0361E+18 Sb-127 2.4834E+05 9.2994E-04 4.4096E+21 1.8242E+19 Sb-129 6.9842E+05 1.2420E-04 5.7980E+20 5.4164E+19 Te-127 2.4210E+05
- 9. 1737E-05 4.3500E+20 1.7684E+19 Te-127m 3.2120E+04 3.4053E-03 1.6147E+22 2.3530E+18 Te-129 7.9184E+05
- 3. 7811E-05 1.7651E+20 5.7646E+19 Te-129m 2.1994E+05 7.3008E-03 3.4083E+22 1.6114E+19 Te-131m 4.0867E+05 5.1249E-04 2.3560E+21 3.0182E+19 Te-132 4.1369E+06 1.3627E-02 6.2168E+22 3.0401E+20 1-131 2.6045E+07 2.1008E-01 9.6576E+23 2.3177E+21
D000040-122, Revision 0 Page 66 of 155 1-132 3.1575E+07 3.0590E-03 1.3956E+22 2.9766E+21 1-133 5.1016E+07 4.5035E-02 2.0391E+23 4.6008E+21 1-134 1.7551E+07 6.5792E-04 2.9568E+21 2.2954E+21 1-135 4.2006E+07 1.1961E-02 5.3357E+22 3.9124E+21 Xe-133 1.2392E+08
- 6. 6205E-01 2.9977E+24 9.8750E+21 Xe-135 2.8801E+07 1.1278E-02 5.0310E+22 2.2056E+21 Cs-134 2.4472E+06 1.8914E+00 8.5003E+24 2.2956E+20 Cs-136 7.4384E+05 1.0149E-02 4.4941E+22 6..9849E+19 Cs-137 1.3715E+06 1.5767E+01 6.9308E+25 1.2865E+20 Ba-139 1.0637E+06 6.5028E-05 2.8173E+20 9.3654E+19 Ba-140 2.2385E+06 3.0577E-02 1.3153E+23 1.6412E+20 La-140 4.3798E+04 7.8798E-05 3.3895E+20 2.5130E+18 La-141 1.6177E+04 2.8606E-06 1.2217E+19 1.2618E+18 Ce-141 5.0751E+04 1.7811E-03 7.6073E+21 3.7184E+18 Ce-143 4.8077E+04 7.2395E-05 3.0488E+20 3.5481E+18 Ce-144 3.0688E+04 9.6215E-03 4.0237E+22 2.2483E+18 Pr-143 1.9419E+04 2.8838E-04 1.2144E+21 1.4214E+18 Nd-147 8.6581E+03 1.0702E-04 4.3844E+20 6.3488E+17 Np-239 5.7018E+05 2.4578E-03 6.1929E+21 4.1952E+19 Pu-238 3.3000E+01 1.9276E-03 4.8775E+21 2.4176E+15 Pu-239 7.4644E+00 1.2009E-01 3.0259E+23 5.4678E+14 Pu-240 9.3846E+00 4.1185E-02 1.0334E+23 6.8752E+14 Pu-241 1.5808E+03 1.5345E-02 3.8345E+22 1.1581E+17 Am-241 4.1873E-01 1.2200E-04 3.0486E+20 3.0670E+13 Cm-242 1.5996E+02 4.8263E-05 1.2010E+20 1.1719E+16 Cm-244 9.3538E+00 1.1562E-04 2.8536E+20 6.8526E+14 Containment Transport Group Inventory:
Time (h) =
1.5000 Atmosphere Sump Noble gases (atoms) 1.4790E+25 0.0000E+00 Elemental I (atoms) 6.0137E+22 0.0000E+00 Organic I (atoms) 1.8599E+21 0.0000E+00 Aerosols (kg) 1.8757E+01 0.0000E+00 Dose Effective (Ci/cc) 1-131 (Thyroid) 6.9014E-04 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 8.5626E-04 Total I (Ci) 1.6819E+08 Dummy Flow Rate - Containment to Environment Transport Group Inventory:
Time (h) =
1.5000 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 2.6439E+10 Elemental I (atoms) 0.0000E+00 1.2207E+08 Organic I (atoms) 0.0000E+00 3.7755E+06 Aerosols (kg) 0.0000E+00 3.9602E-14 RBCU Flow Containment to Containment Transport Group Inventory:
Time (h) =
1.5000 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 1.4329E+25 Elemental I (atoms) 0.0000E+00 6.6160E+22 Organic I (atoms) 0.0000E+00 2.0462E+21 Aerosols (kg) 0.0000E+00 2.1463E+01 EAB Doses:
Time (h) =
1.6000 Whole Body Thyroid TEDE Delta dose (rem) 2.1425E-12 4.7606E-10 2.1888E-11 Accumulated dose (rem) 1.5954E-11 3.3033E-09 1.5036E-10 Containment Compartment Nuclide Inventory:
Time (h) =
1.6000 Ci kg Atoms Decay
D000040-122, Revision 0 Page 67 of 155 Co-58 1.5961E+03
- 5. 0194E-05 5.2117E+20 1.2758E+17 Co-60 1.2227E+03 1.0816E-'03 1.0856E+22 9.7716E+16 Kr-85 7.0873Et05 1.8065E+00 1.2798E+25 6.1050E+19 Kr-85m 1.8132E+07 2.2032E-03 1.5610E+22 1.6698E+21 Kr-87 1.7705E+07 6.2507E-04 4.3267E+21 1.9511E+21 Kr-88 3.8771E+07 3.0920E-03 2.1159E+22 3.7150E+21 Rb-86 1.1557E+04 1.4204E-04 9.9464E+20 1.1593E+18 Sr-89 1.4219E+06 4.8944E-02 3.3118E+23 1.1367E+20 Sr-90 7.6830E+04 5.6324E-01 3.7688E+24 6.1403E+18 Sr-91 1.6263E+06 4.4864E-04 2.9690E+21 1.3369E+20 Sr-92 1.2701E+06 1.0104E-04 6.6142E+20 1.1223E+20 Y-90 1.3157E+03 2.4183E-06 1.6181E+19 8.7656E+16 Y-91 1.7460E+04 7.1194E-04 4.7114E+21 1.3883E+18 Y-92 1.7086E+05 1.7757E-05 1.1623E+20 8.7265E+18 Y-93 1.9409E+04
- 5. 8175E-06 3.7671E+19 1.5928E+18 Zr-95 2.1815E+04 1.0155E-03 6.4371E+21 1.7438E+18 Zr-97 2.1395E+04 1.1192E-05 6.9483E+19 1.7371E+18 Nb-95 2.0647E+04 5.2802E-04 3.3472E+21 1.6500E+18 Mo-99 2.9746E+05 6.2020E-04 3.7727E+21 2.3869E+19 Tc-99m 2.6107E+05 4.9650E-05 3.0202E+20 2.0733E+19 Ru-103 2.2397E+05 6.9396E-03 4.0574E+22 1.7904E+19 Ru-105 1.1403E+05 1.6964E-05 9.7292E+19 9.6839E+18 Ru-106 5.1186E+04 1.5300E-02 8.6921E+22 4.0909E+18 Rh-105 1.0589E+05 1.2545E-04 7.1952E+20 8.4450E+18 Sb-127 2.7297E+05 1.0222E-03 4.8470E+21 2.1879E+19 Sb-129 7.5603E+05 1.3444E-04 6.2763E+20 6.4316E+19 Te-127 2.6626E+05 1.0089E-04 4.7841E+20 2.1218E+19 Te-127m 3.5333E+04 3.7458E-03 1.7762E+22 2.8236E+18 Te-129 8.6496E+05 4.1302E-05 1.9281E+20 6.8908E+19 Te-129m 2.4193E+05 8.0307E-03 3.7490E+22 1.9336E+19 Te-131m 4.4849E+05 5.6244E-04 2.5856E+21 3.6163E+19 Te-132 4.5466E+06 1.4976E-02 6.8324E+22 3.6460E+20 1-131 2.8232E+07 2.2772E-01 1.0469E+24 2.6938E+21 1-132 3.3813E+07 3.2758E-03 1.4945E+22 3.4320E+21 1-133 5.5134E+07 4.8670E-02 2.2038E+23 5.3364E+21 1-134 1.7585E+07
- 6. 5918E-04 2.9624E+21 2.5391E+21 1-135 4.5074E+07, 1.2835E-02 5.7254E+22 4.5160E+21 Xe-133 1.3550E+08 7.2388E-01 3.2777E+24 1.1680E+22 Xe-135 3.1755E+07 1.2435E-02 5.5470E+22 2.6262E+21 Cs-134 2.6414E+06 2.0415E+00 9.1749E+24 2.6475E+20 Cs-136 8.0270E+05 1.0952E-02 4.8497E+22 8.0542E+19 Cs-137 1.4803E+06 1.7019E+01 7.4809E+25 1.4837E+20 Ba-139 1.1126E+06 6.8022E-05 2.9470E+20 1.0885E+20 Ba-140 2.4618E+06 3.3627E-02 1.4465E+23 1.9692E+20 La-140 5.0248E+04 9.0402E-05 3.8887E+20 3.1264E+18 La-141 1.7484E+04 3.0916E-06 1.3204E+19 1.4968E+18 Ce-141 5.5824E+04 1.9592E-03 8.3677E+21 4.4620E+18 Ce-143 5.2773E+04 7.9468E-05 3.3466E+20 4.2518E+18 Ce-144 3.3756E+04 1.0584E-02 4.4261E+22 2.6979E+18 Pr-143 2.1364E+04
- 3. 1727E-04 1.3361E+21 1.7058E+18 Nd-147 9.5214E+03 1.1770E-04 4.8216E+20 7.6172E+17 Np-239 6.2643E+05 2.7002E-03 6.8039E+21 5.0301E+19 Pu-238 3.6300E+01 2.1204E-03 5.3652E+21 2.9011E+15 Pu-239 8.2110E+00 1.3210E-01 3.3286E+23 6.5615E+14 Pu-240 1.0323E+01 4.5303E-02 1.1368E+23 8.2502E+14 Pu-241 1.7388E+03 1.6880E-02 4.2179E+22 1.3897E+17 Am-241 4.6063E-01 1.3421E-04 3.3536E+20 3.6805E+13 Cm-242 1.7595E+02 5.3088E-05 1.3211E+20 1.4063E+16 Cm-244 1.0289E+01 1.2718E-04 3.1389E+20 8.2231E+14 Containment Transport Group Inventory:
Time (h) =
1.6000 Atmosphere Sump Noble gases (atoms) 1.6173E+25 0.0000E+00 Elemental I (atoms) 6.5106E+22 0.0000E+00
D000040-122, Revision 0 Page 68 of 155 Organic I (atoms)
Aerosols (kg) 2.0136E+21 0.0000E+00 2.0264E+01 0.0000E+00 Dose Effective (Ci/cc) 1-131 (Thyroid) 7.4724E-04 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 9.2582E-04 Total I (Ci) 1.7984E+08 Dummy Flow Rate - Containment to Environment Transport Group Inventory:
Time (h) =
1.6000 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 3.1487E+10 Elemental I (atoms) 0.0000E+00 1.4251E+08 Organic I (atoms) 0.0000E+00 4.4076E+06 Aerosols (kg) 0.0000E+00 4.5964E-14 RBCU Flow Containment to Containment Transport Group Inventory:
Time (h) =
1.6000 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 1.7066E+25 Elemental I (atoms) 0.0000E+00 7.7238E+22 Organic I (atoms) 0.0000E+00 2.3888E+21 Aerosols (kg) 0.0000E+00 2.4911E+01 EAB Doses:
Time (h) =
1.7000 Whole Body Thyroid TEDE Delta dose (rem) 2.2687E-12 5.1400E-10 2.3621E-11 Accumulated dose (rem) 1.8223E-11 3.8173E-09 1.7398E-10 Containment Compartment Nuclide Inventory:
Time (h) =
1.7000 Ci kg Atoms Decay Co-58 1.7411E+03 5.4755E-05 5.6852E+20 1.5077E+17 Co-60 1.3338E+03 1.1800E-03 1.1843E+22 1.1548E+17 Kr-85 7.6939E+05 1.9611E+00 1.3894E+25
- 7. 1298E+19 Kr-85m 1.9381E+07 2.3551E-03 1.6686E+22 1.9299E+21 Kr-87 1.8201E+07 6.4257E-04 4.4479E+21 2.2002E+21 Kr-88 4.1074E+07 3.2757E-03 2.2417E+22 4.2688E+21 Rb-86 1.2405E+04 1.5246E-04 1.0676E+21 1.3245E+18 Sr-89 1.5511E+06 5.3390E-02 3.6126E+23 1.3433E+20 Sr-90 8.3815E+04 6.1445E-01
- 4. 1114E+24 7.2567E+18 Sr-91 1.7613E+06 4.8587E-04 3.2153E+21 1.5723E+20 Sr-92 1.3505E+06 1.0745E-04 7.0333E+20 1.3045E+20 Y-90 1.4798E+03 2.7199E-06 1.8200E+19 1.0617E+17 Y-91 1.9064E+04 7.7736E-04 5.1443E+21 1.6418E+18 Y-92 1.9596E+05 2.0365E-05 1.3330E+20 1.1002E+19 Y-93 2.1029E+04 6.3029E-06 4.0814E+19
- 1. 8738E+18 Zr-95 2.3797E+04 1.1077E-03 7.0220E+21 2.0607E+18 Zr-97 2.3245E+04 1.2159E-05 7.5489E+19 2.0473E+18 Nb-95 2.2525E+04 5.7603E-04 3.6515E+21 1.9501E+18 Mo-99 3.2416E+05 6.7588E-04 4.1113E+21 2.8189E+19 Tc-99m 2.8483E+05 5.4168E-05 3.2950E+20 2.4504E+19 Ru-103 2.4431E+05 7.5699E-03 4.4259E+22 2.1159E+19 Ru-105 1.2247E+05 1.8219E-05 1.0449E+20 1.1328E+19 Ru-106 5.5839E+04 1.6690E-02 9.4822E+22 4.8347E+18 Rh-105 1.1553E+05 1.3688E-04 7.8504E+20 9.9821E+18 Sb-127 2.9757E+05 1.1143E-03 5.2836E+21 2.5844E+19 Sb-129 8.1163E+05 1.4433E-04 6.7379E+20 7.5214E+19 Te-127 2.9041E+05 1.1004E-04 5.2181E+20 2.5073E+19 Te-127m 3.8545E+04 4.0864E-03 1.9377E+22 3.3371E+18 Te-129 9.3676E+05 4.4731E-05 2.0882E+20 8.1109E+19 Te-129m 2.6391E+05 8.7605E-03 4.0897E+22 2.2851E+19 Te-131m 4.8814E+05 6.1216E-04 2.8141E+21 4.2673E+19
D000040-122, Revision 0 Page 69 of 155 Te-132 4.9555E+06 1.6323E-02 7.4469E+22 4.3064E+20 1-131 3.0418E+07 2.4535E-01 1.1279E+24 3.0990E+21 1-132 3.5992E+07 3.4869E-03 1.5908E+22 3.9167E+21 1-133 5.9225E+07 5.2281E-02 2.3673E+23 6.1266E+21 1-134 1.7512E+07 6.5644E-04 2.9501E+21 2.7818E+21 1-135 4.8073E+07 1.3689E-02 6.1063E+22 5.1597E+21 Xe-133 1.4707E+08 7.8569E-01 3.5576E+24 1.3639E+22 Xe-135 3.4746E+07 1.3606E-02 6.0694E+22 3.0866E+21 Cs-134 2.8356E+06 2.1916E+00 9.8494E+24 3.0252E+20 Cs-136 8.6153E+05 1.1755E-02 5.2052E+22 9.2019E+19 Cs-137 1.5891E+06 1.8270E+01 8.0309E+25 1.6954E+20 Ba-139 1.1543E+06 7.0567E-05 3.0573E+20 1.2462E+20 Ba-140 2.6850E+06 3.6676E-02 1.5776E+23 2.3269E+20 La-140 5.7070E+04 1.0268E-04 4.4167E+20 3.8256E+18 La-141 1.8740E+04
- 3. 3137E-06 1.4153E+19 1.7486E+18 Ce-141 6.0896E+04 2.1372E-03 9.1280E+21 5.2732E+18 Ce-143 5.7450E+04 8.6510E-05 3.6432E+20 5.0178E+18 Ce-144 3.6824E+04 1.1546E-02 4.8284E+22 3.1884E+18 Pr-143 2.3310E+04 3.4616E-04 1.4578E+21 2.0162E+18 Nd-147 1.0384E+04 1.2836E-04 5.2586E+20 9.0005E+17 Np-239 6.8254E+05 2.9421E-03 7.4133E+21 5.9398E+19 Pu-238 3.9601E+01 2.3132E-03 5.8530E+21 3.4286E+15 Pu-239 8.9577E+00 1.4412E-01 3.6313E+23 7.7547E+14 Pu-240 1.1262E+01 4.9422E-02 1.2401E+23 9.7502E+14 Pu-241 1.8969E+03 1.8414E-02 4.6014E+22 1.6423E+17 Am-241 5.0253E-01 1.4642E-04 3.6587E+20 4.3498E+13 Cm-242 1.9194E+02 5.7913E-05 1.4412E+20 1.6620E+16 Cm-244 1.1225E+01 1.3874E-04 3.4243E+20 9.7182E+14 Containment Transport Group Inventory:
Time (h) =
1.7000 Atmosphere Sump Noble gases (atoms) 1.7556E+25 0.0000E+00 Elemental I (atoms) 7.0060E+22 0.0000E+00 Organic I (atoms) 2.1668E+21 0.0000E+00 Aerosols (kg) 2.1770E+01 0.0000E+00 Dose Effective (Ci/cc) 1-131 (Thyroid) 8.0416E-04 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 9.9502E-04 Total I (Ci) 1.9122E+08 Dummy Flow Rate - Containment to Environment Transport Group Inventory:
Time (h) =
1.7000 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 3.6987E+10 Elemental I (atoms) 0.0000E+00 1.6457E+08 Organic I (atoms) 0.0000E+00 5.0898E+06 Aerosols (kg) 0.0000E+00 5.2818E-14 RBCU Flow Containment to Containment Transport Group Inventory:
Time (h) =
1.7000 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 2.0046E+25 Elemental I (atoms) 0.0000E+00 8.9193E+22 Organic I (atoms) 0.0000E+00 2.7585E+21 Aerosols (kg) 0.0000E+00 2.8626E+01 EAB Doses:
Time (h) =
1.8000 Whole Body Thyroid TEDE Delta dose (rem) 2.3894E-12 5.5183E-10 2.5345E-11 Accumulated dose (rem) 2.0612E-11 4.3692E-09 1.9932E-10 Containment Compartment Nuclide Inventory:
D000040-122, Revision 0 Page 70 of 155 Time (h) _
1.8000 Ci kg Atoms Decay Co-58 1.8861E+03
- 5. 9316E-05
- 6. 1587E+20 1.7589E+17 Co-60 1.4450E+03 1.2783E-03 1.2830E+22 1.3473E+17 Kr-85 8.3006E+05 2.1157E+00 1.4989E+25 8.2354E+19 Kr-85m 2.0588E+07 2.5018E-03 1.7725E+22 2.2063E+21 Kr-87 1.8594E+07 6.5645E-04 4.5440E+21 2.4548E+21 Kr-88 4.3244E+07 3.4487E-03 2.3601E+22 4.8519E+21 Rb-86 1.3253E+04 1.6288E-04 1.1406E+21 1.5011E+18 Sr-89 1.6803E+06 5.7836E-02
- 3. 9135E+23 1.5671E+20 Sr-90 9.0800E+04 6.6565E-01 4.4541E+24 8.4662E+18 Sr-91 1.8942E+06 5.2253E-04
- 3. 4580E+21 1.8256E+20 Sr-92 1.4261E+06
- 1. 1346E-04 7.4269E+20 1.4969E+20 Y-90 1.6513E+03 3.0351E-06 2.0309E+19 1.2686E+17 Y-91 2.0671E+04 8.4288E-04
- 5. 5780E+21 1.9166E+18 Y-92 2.2205E+05 2.3077E-05 1.5106E+20 1.3609E+19 Y-93 2.2625E+04 6.7815E-06 4.3913E+19 2.1763E+18 Zr-95 2.5779E+04 1.2000E-03 7.6068E+21 2.4041E+18 Zr-97 2.5078E+04 1.3119E-05
- 8. 1445E+19 2.3821E+18 Nb-95 2.4402E+04 6.2403E-04
- 3. 9558E+21 2.2751E+18 Mo-99
- 3. 5081E+05 7.3143E-04 4.4493E+21 3.2864E+19 Tc-99m 3.0859E+05 5.8687E-05 3.5699E+20 2.8591E+19 Ru-103 2.6465E+05 8.2001E-03 4.7944E+22 2.4684E+19 Ru-105 1.3062E+05 1.9432E-05 1.1145E+20 1.3081E+19 Ru-106
- 6. 0491E+04 1.8081E-02 1.0272E+23 5.6404E+18 Rh-105 1.2517E+05 1.4830E-04 8.5055E+20 1.1648E+19 Sb-127
- 3. 2212E+05 1.2062E-03
- 5. 7197E+21
- 3. 0136E+19 Sb-129 8.6527E+05 1.5387E-04 7.1832E+20 8.6832E+19 Te-127
- 3. 1455E+05 1.1919E-04
- 5. 6518E+20 2.9248E+19 Te-127m
- 4. 1758E+04 4.4270E-03 2.0992E+22 3.8933E+18 Te-129 1.0072E+06 4.8094E-05 2.2452E+20 9.4230E+19 Te-129m 2.8590E+05 9.4903E-03 4.4304E+22 2.6659E+19 Te-131m 5.2760E+05 6.6164E-04
- 3. 0416E+21
- 4. 9708E+19 Te-132 5.3637E+06 1.7668E-02 8.0603E+22 5.0212E+20 1-131 3.2602E+07 2.6297E-01 1.2089E+24 3.5334E+21 1-132
- 3. 8112E+07 3.6923E-03 1.6845E+22 4.4299E+21 1-133 6.3288E+07 5.5868E-02 2.5297E+23 6.9710E+21 1-134 1.7348E+07 6.5030E-04 2.9225E+21 3.0223E+21 1-135
- 5. 1004E+07 1.4523E-02 6.4787E+22 5.8426E+21 Xe-133 1.5863E+08 8.4748E-01 3.8373E+24 1.5752E+22 Xe-135 3.7772E+07 1.4791E-02 6.5980E+22 3.5872E+21 Cs-134 3.0298E+06 2.3417E+00 1.0524E+25 3.4287E+20 Cs-136 9.2034E+05 1.2557E-02 5.5604E+22 1.0428E+20 Cs-137 1.6980E+06
- 1. 9521E+01
- 8. 5810E+25 1.9215E+20 Ba-139 1.1891E+06 7.2698E-05 3.1496E+20 1.4086E+20 Ba-140 2.9081E+06 3.9724E-02 1.7087E+23 2.7143E+20 La-140 6.4265E+04 1.1562E-04 4.9734E+20 4.6156E+18 La-141 1.9947E+04
- 3. 5271E-06 1.5064E+19 2.0167E+18 Ce-141 6.5968E+04 2.3152E-03 9.8883E+21
- 6. 1519E+18 Ce-143
- 6. 2107E+04 9.3523E-05 3.9385E+20 5.8460E+18 Ce-144 3.9893E+04 1.2508E-02 5.2307E+22 3.7198E+18 Pr-143 2.5257E+04 3.7507E-04 1.5795E+21 2.3525E+18 Nd-147
- 1. 1247E+04 1.3902E-04 5.6953E+20 1.0499E+18 Np-239 7.3852E+05
- 3. 1834E-03 8.0212E+21
- 6. 9241E+19 Pu-238 4.2901E+01 2.5059E-03
- 6. 3408E+21 4.0000E+15 Pu-239 9.7044E+00 1.5613E-01 3.9340E+23 9.0473E+14 Pu-240 1.2200E+01 5.3540E-02 1.3434E+23 1.1375E+15 Pu-241 2.0550E+03 1.9949E-02 4.9848E+22 1.9161E+17 Am-241 5.4443E-01 1.5863E-04 3.9637E+20 5.0749E+13 Cm-242 2.0793E+02 6.2738E-05 1.5612E+20 1.9389E+16 Cm-244 1.2160E+01 1.5030E-04 3.7096E+20 1.1338E+15 Containment Transport Group Inventory:
Time (h) =
1.8000 Atmosphere Sump
DC0004O-122, Revision 0 Page 71 of 155 Noble gases (atoms) 1.8938E+25 0.0000E+00 Elemental I (atoms) 7.5001E+22 0.0000E+00 Organic I (atoms) 2.3196E+21 0.0000E+00 Aerosols (kg) 2.3277E+01 0.0000E+00 Dose Effective (Ci/cc) 1-131 (Thyroid) 8.6093E-04 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 1.0639E-03 Total I
(Ci)
I 2.0235E+08 Dummy Flow Rate - Containment to Environment Transport Group Inventory:
Time (h) =
1.8000 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 4.2937E+10 Elemental I (atoms) 0.0000E+00 1.8824E+08 Organic I (atoms) 0.0000E+00 5.8219E+06 Aerosols (kg) 0.0000E+00 6.0163E-14 RBCU Flow Containment to Containment Transport Group Inventory:
Time (h) =
1.8000 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 2.3272E+25 Elemental I (atoms) 0.0000E+00 1.0202E+23 Organic I (atoms) 0.0000E+00 3.1554E+21 Aerosols (kg) 0.0000E+00 3.2607E+01 EAB Doses:
Time (h) =
1.9000 Whole Body Thyroid TEDE Delta dose (rem) 2.4175E-12 5.7026E-10 2.6157E-11 Accumulated dose (rem) 2.3030E-11 4.9394E-09 2.2548E-10 Containment Compartment Nuclide Inventory:
Time (h) =
1.9000 Ci kg Atoms Decay Co-58 1.8860E+03 5.9313E-05 6.1585E+20 2.0102E+17 Co-60 1.4450E+03 1.2783E-03 1.2830E+22 1.5398E+17 Kr-85 8.3006E+05 2.1157E+00 1.4989E+25 9.3411E+19 Kr-85m 2.0272E+07 2.4633E-03 1.7452E+22 2.4784E+21 Kr-87 1.7608E+07 6.2163E-04
- 4. 3029E+21 2.6958E+21 Kr-88 4.2202E+07 3.3656E-03 2.3032E+22 5.4210E+21 Rb-86 1.3251E+04 1.6285E-04 1.1404E+21
- 1. 6776E+18 Sr-89 1.6802E+06 5.7833E-02
- 3. 9132E+23 1.7909E+20 Sr-90 9.0800E+04 6.6565E-01 4.4541E+24
- 9. 6756E+18 Sr-91 1.8804E+06 5.1873E-04
- 3. 4328E+21 2.0769E+20 Sr-92
- 1. 3901E+06 1.1060E-04 7.2394E+20 1.6845E+20 Y-90 1.7478E+03 3.2126E-06 2.1496E+19
- 1. 4885E+17 Y-91 2.0709E+04 8.4443E-04
- 5. 5882E+21 2.1919E+18 Y-92 2.4532E+05 2.5495E-05 1.6688E+20
- 1. 6538E+19 Y-93 2.2470E+04 6.7351E-06 4.3612E+19 2.4766E+18 Zr-95 2.5778E+04 1.1999E-03 7.6064E+21 2.7475E+18 Zr-97 2.4976E+04 1.3065E-05 8.1112E+19 2.7154E+18 Nb-95 2.4402E+04 6.2404E-04 3.9558E+21 2.6001E+18 Mo-99 3.5044E+05 7.3066E-04 4.4446E+21 3.7534E+19 Tc-99m
- 3. 0861E+05 5.8691E-05 3.5701E+20 3.2678E+19 Ru-103 2.6463E+05 8.1995E-03 4.7940E+22 2.8209E+19 Ru-105 1.2860E+05 1.9131E-05 1.0972E+20 1.4808E+19 Ru-106 6.0491E+04 1.8081E-02 1.0272E+23 6.4462E+18 Rh-105 1.2518E+05 1.4831E-04 8.5061E+20 1.3313E+19 Sb-127 3.2188E+05 1.2053E-03 5.7154E+21 3.4425E+19 Sb-129
- 8. 5150E+05 1.5142E-04 7.0688E+20 9.8266E+19 Te-127 3.1449E+05 1.1917E-04 5.6507E+20 3.3422E+19 Te-127m 4.1758E+04 4.4270E-03 2.0992E+22 4.4495E+18 Te-129 9.9937E+05 4.7720E-05 2.2277E+20 1.0725E+20
DC00040-122, Revision 0 Page 72 of 155 Te-129m 2.8589E+05 9.4900E-03 4.4303E+22
- 3. 0467E+19 Te-131m 5.2638E+05 6.6011E-04 3.0346E+21
- 5. 6728E+19 Te-132 5.3590E+06 1.7652E-02 8.0532E+22 5.7353E+20 1-131 3.2590E+07 2. 6288E-01 1.2085E+24
- 3. 9675E+21 1-132 3.7142E+07 3.5983E-03 1.6416E+22 4.9300E+21 1-133 6.3077E+07 5.5682E-02 2.5212E+23 7.8125E+21 1-134 1.6029E+07 6.0087E-04 2.7004E+21 3.2445E+21 1-135 5.0472E+07 1.4372E-02
- 6. 4111E+22 6.5184E+21 Xe-133 1.5858E+08 8.4719E-01 3.8360E+24 1.7865E+22 Xe-135 3.7814E+07 1.4807E-02 6.6053E+22 4.0885E+21 Cs-134 3.0298E+06 2.3417E+00 1.0524E+25 3.8323E+20 Cs-136 9.2014E+05 1.2555E-02 5.5592E+22 1.1654E+20 Cs-137 1.6980E+06 1.9521E+01
- 8. 5810E+25 2.1477E+20 Ba-139 1.1308E+06 6.9132E-05 2.9951E+20 1.5631E+20 Ba-140 2.9074E+06 3.9715E-02 1.7083E+23 3.1016E+20 La-140
- 6. 9159E+04 1.2443E-04 5.3522E+20 5.4709E+18 La-141 1.9598E+04 3.4654E-06 1.4801E+19 2.2800E+18 Ce-141 6.5964E+04 2.3151E-03
- 9. 8877E+21 7.0305E+18 Ce-143
- 6. 1977E+04 9.3327E-05 3.9303E+20 6.6724E+18 Ce-144 3.9892E+04 1.2507E-02 5.2307E+22 4.2511E+18 Pr-143 2.5264E+04 3.7518E-04 1.5800E+21 2.6888E+18 Nd-147 1.1244E+04 1.3898E-04 5.6938E+20 1. 1997E+18 Np-239 7.3761E+05
- 3. 1795E-03 8.0114E+21 7.9072E+19 Pu-238 4.2901E+01 2.5059E-03 6.3408E+21
- 4. 5715E+15 Pu-239 9.7047E+00 1.5613E-01 3.9341E+23 1.0340E+15 Pu-240 1.2200E+01 5.3540E-02 1.3434E+23 1.3000E+15 Pu-241 2.0550E+03 1.9949E-02 4.9848E+22 2.1898E+17 Am-241
- 5. 4447E-01 1.5864E-04 3.9640E+20 5.8001E+13 Cm-242 2.0793E+02 6.2737E-05 1.5612E+20 2.2159E+16 Cm-244 1.2160E+01 1.5030E-04 3.7096E+20 1.2958E+15 Containment Transport Group Inventory:
Time (h) =
1.9000 Atmosphere Sump Noble gases (atoms) 1.8936E+25 0.0000E+00 Elemental I (atoms) 7.4875E+22 0.0000E+00 Organic I (atoms) 2.3157E+21 0.0000E+00 Aerosols (kg) 2.3276E+01 0.0000E+00 Dose Effective (Ci/cc) 1-131 (Thyroid) 8.5960E-04 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 1.0606E-03 Total I (Ci) 1.9931E+08 Dummy Flow Rate - Containment to Environment Transport Group Inventory:
Time (h) =
1.9000 Pathway Filtered Transported Noble gases (atoms)
Elemental I (atoms)
Organic I (atoms)
Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 4.9113E+10 2.1270E+08 6.5783E+06 6.7753E-14 RBCU Flow Containment to Containment Transport Group Inventory:
Time (h) =
1.9000 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 2.6619E+25 Elemental I (atoms) 0.0000E+00 1.1528E+23 Organic I (atoms) 0.0000E+00 3.5653E+21 Aerosols (kg) 0.0000E+00 3.6721E+01 EAB Doses:
Time (h) =
8.0000 Whole Body Thyroid TEDE Delta dose (rem) 8.8788E-11 3.3340E-08 1.4844E-09 Accumulated dose (rem) 1.1182E-10 3.8280E-08 1.7098E-09
D000040-122, Revision 0 Page 73 of 155 Containment Compartment Nuclide Inventory:
Time (h) 8.0000 Ci kg Atoms Decay Co-58 1.8814E+03
- 5. 9166E-05 6.1432E+20
- 8. 3014E+05 2.1159E+00 1.4991E+25 7.6789E+20 Kr-85m 7.8889E+06
- 9. 5861E-04 6.7916E+21 1.3139E+22 Kr-87 6.3345E+05 2.2363E-05 1.5480E+20 6.8440E+21 Kr-88 9.5225E+06 7.5942E-04 5.1969E+21 2.3256E+22 Rb-86 1.3126E+04 1.6132E-04 1.1297E+21 1.2394E+19 Sr-89 1.6743E+06 5.7631E-02 3.8996E+23 1.5419E+21 Sr-90 9.0798E+04
- 6. 6564E-01 4.4540E+24 8.3451E+19 Sr-91 1.2049E+06 3.3239E-04 2.1997E+21 1.4408E+21 Sr-92 2.9205E+05 2.3235E-05 1.5209E+20 7.4030E+20 Y-90 7.4441E+03 1.3682E-05
- 9. 1552E+19
- 3. 8687E+18 Y-91 2.2563E+04 9.2003E-04
- 6. 0885E+21 1.9817E+19 Y-92 4.9964E+05 5.1925E-05 3.3989E+20 4.1538E+20 Y-93 1.4784E+04 4.4313E-06 2.8695E+19 1.7394E+19 Zr-95 2.5707E+04 1.1966E-03 7.5855E+21 2.3664E+19 Zr-97 1.9448E+04 1.0173E-05 6.3158E+19 2. 0669E+19 Nb-95 2.4407E+04 6.2417E-04
- 3. 9567E+21 2.2428E+19 Mo-99 3.2869E+05 6.8532E-04
- 4. 1688E+21
- 3. 1334E+20 Tc-99m 3.0392E+05 5.7799E-05
- 3. 5159E+20 2.8081E+20 Ru-103 2.6345E+05 8.1628E-03 4.7726E+22 2.4274E+20 RU-105
- 4. 9619E+04 7.3816E-06 4.2336E+19 8.2192E+19 Ru-106 6.0462E+04 1.8072E-02 1.0267E+23 5.5585E+19 Rh-105 1.2034E+05 1.4258E-04 8.1772E+20 1.1358E+20 Sb-127 3.0748E+05 1.1514E-03
- 5. 4597E+21 2.9007E+20 Sb-129
- 3. 1998E+05
- 5. 6901E-05 2.6563E+20 5.3952E+20 Te-127 3.0907E+05 1.1711E-04 5.5533E+20 2.8605E+20 Te-127m 4.1782E+04 4.4296E-03 2.1004E+22 3.8388E+19 Te-129 5.3503E+05 2.5548E-05 1.1927E+20 7.0131E+20 Te-129m 2.8502E+05 9.4612E-03 4.4168E+22 2.6244E+20 Te-131m 4.5718E+05 5.7334E-04 2.6357E+21 4.5565E+20 Te-132 5.0769E+06 1.6723E-02 7.6293E+22 4.8122E+21 1-131
- 3. 1892E+07 2.5725E-01 1.1826E+24 3.0163E+22 1-132 1.0327E+07 1.0005E-03 4.5644E+21 2.102.1E+22 1-133 5.1474E+07 4.5439E-02 2.0575E+23 5.4190E+22 1-134 1.2891E+05 4.8323E-06
- 2. 1717E+19 5.9231E+21 1-135 2.6622E+07 7.5807E-03 3.3816E+22 3.6813E+22 Xe-133 1.5517E+08 8.2898E-01 3.7535E+24 1.4533E+23 Xe-135 3.5293E+07 1.3820E-02 6.1650E+22 3.4242E+22 Cs-134 3.0291E+06 2.3412E+00 1.0522E+25 2.8447E+21 Cs-136 9.0785E+05 1.2387E-02 5.4850E+22
- 8. 5916E+20 Cs-137 1.6980E+06 1.9521E+01 8.5808E+25 1.5944E+21 Ba-139 5.2618E+04 3.2169E-06 1.3937E+19 4.4189E+20 Ba-140 2.8675E+06
- 3. 9169E-02 1.6849E+23 2.6563E+21 La-140 3.5026E+05 6.3016E-04 2.7107E+21 1.7613E+20 La-141 6.6829E+03 1.1817E-06 5.0471E+18 1.2034E+19 La-142 7.2361E+02 5.0549E-08 2.1437E+17 4.6230E+18 Ce-141 6.5672E+04 2.3048E-03 9.8439E+21 6.0513E+19 Ce-143 5.4523E+04 8.2103E-05 3.4576E+20 5.3937E+19 Ce-144 3.9868E+04 1.2500E-02 5.2274E+22 3.6654E+19 Pr-143 2.5689E+04 3.8149E-04 1.6066E+21 2.3391E+19 Nd-147 1.1065E+04 1.3677E-04 5.6031E+20 1.0262E+19 Np-239 6.8444E+05 2.9503E-03 7.4339E+21 6.5653E+20 Pu-238 4.2901E+01 2.5060E-03 6.3409E+21 3.9429E+16 Pu-239 9.7189E+00 1.5636E-01 3.9399E+23 8.9250E+15 Pu-240 1.2200E+01 5.3540E-02 1.3434E+23 1.1213E+16 Pu-241 2.0549E+03 1.9948E-02 4.9847E+22 1.8887E+18 Am-241 5.4676E-01 1.5930E-04 3.9807E+20 5.0131E+14 Cm-242 2.0771E+02 6.2669E-05 1.5595E+20 1.9101E+17 Cm-244 1.2160E+01 1.5030E-04 3.7095E+20 1.1176E+16
D000040-122, Revision 0 Page 74 of 155 Containment Transport Group Inventory:
Time (h) =
8.0000 Atmosphere Sump Noble gases (atoms) 1.8818E+25 0.0000E+00 Elemental I (atoms) 6.9196E+22 0.0000E+00 Organic I (atoms) 2.1401E+21 0.0000E+00 Aerosols (kg) 2.3249E+01 0.0000E+00 Dose Effective (Ci/cc) 1-131 (Thyroid) 7.9251E-04 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 9.2586E-04 Total I
(Ci) 1.2044E+08 Dummy Flow Rate - Containment to Environment Transport Group Inventory:
Time (h) =
8.0000 Pathway Filtered Transported Noble gases Elemental I (atoms)
(atoms) 0.0000E+00 4.2458E+ll 0.0000E+00 1.6417E+09 Organic I (atoms)
Aerosols (kg) 0.0000E+00 5.0775E+07 0.0000E+00 5.3046E-13 RBCU Flow Containment to Containment Transport Group Inventory:
Time (h) =
8.0000 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 2.3012E+26 Elemental I (atoms) 0.0000E+00 8.8982E+23 Organic I (atoms) 0.0000E+00 2.7520E+22 Aerosols (kg) 0.0000E+00 2.8751E+02 EAB Doses:
Time (h) =
24.0000 Whole Body Thyroid TEDE Delta dose (rem) 9.7107E-11 3.9997E-08 1.8103E-09 Accumulated dose (rem) 2.0892E-10 7.8277E-08 3.5202E-09 Containment Compartment Nuclide Inventory:
Time (h) =
24.0000 Ci kg Atoms Decay Co-58 1.8691E+03 5.8781E-05 6.1032E+20 5.7280E+18 Co-60 1.4445E+03 1.2779E-03 1.2826E+22 4.4068E+18 Kr-85 8.3012E+05 2.1158E+00 1.4990E+25 2.5371E+21 Kr-85m 6.6360E+05 8.0637E-05 5.7130E+20 1.9360E+22 Kr-87 1.0332E+02 3.6476E-09 2.5248E+16
- 6. 9987E+21 Kr-88 1.9178E+05 1.5295E-05 1.0467E+20 2.8348E+22 Rb-86 1.2805E+04 1.5738E-04 1.1020E+21 4.OQ25E+19 Sr-89 1.6591E+06 5.7107E-02 3.8641E+23
- 5. 0939E+21 Sr-90 9.0794E+04 6.6561E-01 4.4538E+24 2.7696E+20 Sr-91 3.7494E+05 1.0343E-04 6.8448E+20 2.9560E+21 Sr-92 4.8771E+03 3.8801E-07 2.5399E+18 8.8985E+20 Y-90 2.0764E+04 3.8164E-05 2.5537E+20 3.3557E+19 Y-91 2.4733E+04 1.0085E-03 6.6741E+21 7.0599E+19 Y-92 4.9126E+04 5.1054E-06 3.3419E+19 8.7140E+20 Y-93 4.9308E+03 1.4779E-06 9.5702E+18 3.6519E+19 Zr-95 2.5522E+04 1.1880E-03 7.5309E+21 7.8253E+19 Zr-97 1.0089E+04 5.2778E-06 3.2767E+19 5.1061E+19 Nb-95 2.4420E+04 6.2449E-04
- 3. 9587E+21 7.4443E+19 Mo-99 2.7785E+05 5.7932E-04 3.5240E+21 9.5816E+20 Tc-99m 2.7785E+05 5.2840E-05 3.2143E+20 8.7841E+20 Ru-103 2.6036E+05 8.0673E-03 4.7168E+22 8.0091E+20 Ru-105 4.0818E+03 6.0724E-07
- 3. 4827E+18 1.2105E+20 Ru-106 6.0386E+04 1.8050E-02 1.0254E+23 1.8436E+20 Rh-105 9.2587E+04 1.0969E-04 6.2913E+20
- 3. 4102E+20 Sb-127 2.7271E+05 1.0212E-03 4.8422E+21 9.0757E+20 Sb-129 2.4558E+04 4.3671E-06 2.0387E+19 7.8476E+20
D000040-122, Revision 0 Page 75 of 155 Te-127 2.9187E+05 1.1059E-04 5.2442E+20
- 9. 1061E+20 Te-127m 4.1826E+04 4.4342E-03 2.1026E+22 1.2748E+20 Te-129 2.7786E+05 1.3268E-05
- 6. 1938E+19 1.3399E+21 Te-129m 2.8147E+05 9.3434E-03 4.3618E+22 8.6622E+20 Te-131m 3.1589E+05 3.9615E-04 1.8211E+21 1.2702E+21 Te-132 4.4056E+06 1.4512E-02 6.6206E+22 1.4900E+22 I-131 3.0127E+07 2.4301E-01 1.1171E+24 9.6233E+22 1-132 5.2739E+06 5.1093E-04 2.3310E+21 3.3342E+22 I-133 3.0201E+07 2.6661E-02 1.2072E+23 1.3922E+23 I-134 4.1324E-01 1.5491E-11
- 6. 9618E+13
- 5. 9448E+21 I-135 4.9726E+06 1.4159E-03
- 6. 3163E+21
- 6. 4313E+22 Xe-133 1.4534E+08 7.7647E-01
- 3. 5158E+24 4.6557E+23 Xe-135 1.7134E+07 6.7093E-03 2.9929E+22 8.9338E+22 Cs-134 3.0272E+06 2.3397E+00 1.0515E+25
- 9. 2983E+21 Cs-136 8.7638E+05 1.1958E-02 5.2949E+22 2.7602E+21 Cs-137 1.6979E+06 1.9520E+01 8.5805E+25
- 5. 2130E+21 Ba-139 1.6854E+01 1.0304E-09 4.4642E+15 4.5582E+20 Ba-140 2.7654E+06 3.7774E-02 1.6249E+23
- 8. 6580E+21 La-140 9.4767E+05 1.7050E-03 7.3339E+21 1.5546E+21 La-141 3.9756E+02 7.0297E-08 3.0024E+17 1.6781E+19 La-142 5.4362E-01 3.7976E-11 1.6105E+14 4.8372E+18 Ce-141 6.4777E+04 2.2734E-03
- 9. 7097E+21 1.9953E+20 Ce-143 3.8961E+04 5.8669E-05 2.4707E+20 1.5263E+20 Ce-144 3.9803E+04 1.2479E-02 5.2189E+22 1.2155E+20 Pr-143 2.6380E+04 3.9174E-04 1.6497E+21 7.8900E+19 Nd-147 1.0609E+04 1.3114E-04 5.3722E+20 3.3354E+19 Np-239 5.6250E+05 2.4247E-03
- 6. 1094E+21 1.9810E+21 Pu-238 4.2904E+01 2.5061E-03 6.3412E+21 1.3086E+17 Pu-239 9.7516E+00 1.5689E-01
- 3. 9531E+23 2.9672E+16 Pu-240 1.2200E+01 5.3540E-02 1.3434E+23 3.7213E+16 Pu-241 2.0547E+03 1.9946E-02 4.9842E+22 6.2679E+18 Am-241 5.5277E-01 1.6106E-04 4.0245E+20 1.6727E+15 Cm-242 2.0712E+02 6.2492E-05 1.5551E+20
- 6. 3305E+17 Cm-244 1.2159E+01 1.5029E-04 3.7093E+20
- 3. 7089E+16 Containment Transport Group Inventory:
Time (h) = 24.0000 Atmosphere Sump Noble gases (atoms) 1.8537E+25 0.0000E+00 Elemental I (atoms) 6.0455E+22 0.0000E+00 Organic I (atoms) 1.8698E+21 0.0000E+00 Aerosols (kg) 2.3204E+01 0.0000E+00 Dose Effective (Ci/cc) 1-131 (Thyroid) 6.7807E-04 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 7.4476E-04 Total I (Ci) 7.0575E+07 Dummy Flow Rate - Containment to Environment Transport Group Inventory:
Time (h) = 24.0000 Pathway Filtered Transported Noble gases (atoms)
Elemental I (atoms) 0.0000E+00 0.0000E+00 1.3994E+12.
5.0123E+09 Organic I (atoms)
Aerosols (kg) 0.0000E+00 1.5502E+08 0.0000E+00 1.7422E-12 RBCU Flow Containment to Containment Transport Group Inventory:
Time (h) = 24.0000 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 7.5845E+26 Elemental I (atoms) 0.0000E+00 2.7166E+24 Organic I (atoms) 0.0000E+00 8.4020E+22 Aerosols (kg) 0.0000E+00 9.4428E+02 EAB Doses:
DC0004O-122, Revision 0 Page 76 of 155 Time (h) = 720.0000 Whole Body Thyroid TEDE Delta dose (rem) 7.7859E-10 6.5668E-07 4.5282E-08 Accumulated dose (rem) 9.8752E-10 7.3495E-07 4.8802E-08 Containment Compartment Nuclide Inventory:
Time (h) = 720.0000 Ci kg Atoms Decay Co-58 1.4071E+03 4.4252E-05 4.5947E+20 1.5658E+20 Co-60 1.4295E+03 1.2646E-03 1.2693E+22 1.3762E+20 Kr-85 8.2587E+05 2.1050E+00 1.4914E+25 7.9298E+22 Rb-86 4.3607E+03 5.3592E-05 3.7528E+20 7.6678E+20 Sr-89 1.1143E+06 3.8355E-02 2.5952E+23 1.3198E+23 Sr-90 9.0623E+04 6.6436E-01 4.4454E+24 8.6863E+21 Y-90 9.1100E+04 1.6744E-04 1.1204E+21 7.5778E+21 Y-91 1.8303E+04 7.4632E-04 4.9389E+21 2.0933E+21 Zr-95 1.8641E+04 8.6771E-04 5.5005E+21 2.1087E+21 Zr-97 4.0403E-09 2.1135E-18 1.3121E+07 8.3828E+19 Nb-95 2.3091E+04 5.9053E-04 3.7434E+21 2.2999E+21 Mo-99 1.8591E+02 3.8763E-07 2.3580E+18 4.4798E+21 Tc-99m 1.9061E+02 3.6249E-08 2.2050E+17 4.2986E+21 Ru-103 1.5608E+05 4.8360E-03 2.8275E+22 1.9694E+22 Ru-106 5.7178E+04 1.7091E-02 9.7096E+22 5.6325E+21 Rh-105 1.1068E-01 1.3113E-10 7.5207E+14 9.7364E+20 Sb-127 1.4730E+03 5.5157E-06 2.6154E+19 5.7236E+21 Te-127 3.8401E+04 1.4551E-05 6.8998E+19 8.9034E+21 Te-127m 3.6267E+04 3.8449E-03 1.8232E+22 3.7889E+21 Te-129 1.3382E+05 6.3901E-06 2.9831E+19 1.4154E+22 Te-129m 1.5476E+05 5.1373E-03 2.3982E+22 2.0506E+22 Te-131m 3.2783E-02 4.1112E-11 1.8899E+14 3.0913E+21 Te-132 9.2207E+03 3.0372E-05 1.3856E+20 8.0967E+22 1-131 2.4763E+06 1.9975E-02 9.1824E+22 1.1230E+24 1-132 1.1006E+04 1.0662E-06 4.8644E+18 1.0173E+23 1-133 2.5533E-03 2.2539E-12 1.0206E+13 2.5994E+23 Xe-133 3.2735E+06 1.7488E-02 7.9185E+22 4.0193E+24 Cs-134 2.9475E+06 2.2781E+00 1.0238E+25 2.8623E+23 Cs-136 1.8893E+05 2.5777E-03 1.1414E+22 4.4294E+22 C3-137 1.6948E+06 1.9484E+01 8.5648E+25 1.6248E+23 Ba-140 5.7085E+05 7.7975E-03 3.3541E+22 1.3760E+23 La-140 6.6310E+05 1.1930E-03 5.1317E+21 1.3270E+23 Ce-141 3.4900E+04 1.2249E-03 5.2314E+21 4.6781E+21 Ce-143 1.7443E-02 2.6267E-11 1.1062E+14 3.9970E+20 Ce-144 3.7086E+04 1.1627E-02 4.8627E+22 3.6841E+21 Pr-143 6.9901E+03 1.0380E-04 4.3715E+20 1.5386E+21 Nd-147 1.7006E+03 2.1021E-05 8.6116E+19 4.8446E+20 Np-239 1.1045E+02 4.7610E-07 1.1996E+18 8.0893E+21 Pu-238 4.2999E+01 2.5117E-03 6.3553E+21 4.1129E+18 Pu-239 9.9022E+00 1.5931E-01 4.0142E+23 9.4604E+17 Pu-240 1.2200E+01 5.3540E-02 1.3434E+23 1.1682E+18 Pu-241 2.0469E+03 1.9870E-02 4.9652E+22 1.9639E+20 Am-241 8.1383E-01 2.3712E-04 5.9251E+20 6.5010E+16 Cm-242 1.8306E+02 5.5233E-05 1.3745E+20 1.8696E+19 Cm-244 1.2122E+01 1.4983E-04 3.6980E+20 1.1626E+18 Containment Transport Group Inventory:
Time (h) = 720.0000 Atmosphere Sump Noble gases (atoms) 1.4993E+25 0.0000E+00 Elemental I (atoms) 4.4537E+21 0.0000E+00 Organic I (atoms) 1.3774E+20 0.0000E+00 Aerosols (kg) 2.2779E+01 0.0000E+00 Dose Effective (Ci/cc) 1-131 (Thyroid) 4.7529E-05 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 4.7535E-05 Total I (Ci) 2.4873E+06
D000040-122, Revision 0 Page 77 of 155 Dummy Flow Rate - Containment to Environment Transport Group Inventory:
Time (h) = 720.0000 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 3.7446E+13 Elemental I (atoms) 0.0000E+00 5.0931E+10 Organic I (atoms) 0.0000E+00 1.5752E+09 Aerosols (kg) 0.0000E+00.5.3780E-11 RBCU Flow Containment to Containment Transport Group Inventory:
Time (h) = 720.0000 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 2.0296E+28 Elemental I (atoms) 0.0000E+00 2.7605E+25 Organic I (atoms) 0.0000E+00 8.5376E+23 Aerosols (kg) 0.0000E+00 2.9149E+04 838 1-131 Summary Time (hr)
Containment 1-131 (Curies)
Environment 1-131 (Curies) 0.000 4.5555E+03 4.1264E-15 0.014 1.1807E+05 2.7722E-12 0.414 3.3932E+06 2.2933E-09 0.500 4.0930E+06 3.3380E-09 0.800 1.0694E+07 1.0571E-08 1.100 1.7282E+07 2.4253E-08 1.400 2.3856E+07 4.4373E-08 1.700 3.0418E+07 7.0917E-08 1.800 3.2602E+07 8.1190E-08 2.100 3.2567E+07 1.1306E-07 2.400 3.2532E+07 1.4490E-07 2.700 3.2498E+07 1.7670E-07 3.000 3.2463E+07 2.0847E-07 3.300 3.2429E+07 2.4020E-07 3.600 3.2394E+07 2.7190E-07 3.900 3.2360E+07 3.0357E-07 4.200 3.2325E+07 3.3520E-07 4.500 3.2291E+07 3.6680E-07 4.800 3.2256E+07 3.9837E-07 5.100 3.2222E+07 4.2990E-07 5.400 3.2188E+07 4.6140E-07 5.700 3.2154E+07 4.9287E-07 6.000 3.2119E+07 5.2430E-07 6.300 3.2085E+07 5.5570E-07 6.600 3.2051E+07 5.8707E-07 6.900 3.2017E+07 6.1840E-07 7.200 3.1983E+07 6.4970E-07 7.500 3.1949E+07 6.8096E-07 7.800 3.1915E+07 7.1219E-07 8.000 3.1892E+07 7.3300E-07 8.300 3.1858E+07 7.6417E-07 8.600 3.1824E+07 7.9532E-07 8.900 3.1790E+07 8.2643E-07 9.200 3.1756E+07 8.5750E-07 9.500 3.1722E+07 8.8855E-07 9.800 3.1689E+07 9.1956E-07 10.100 3.1655E+07 9.5054E-07 10.400 3.1621E+07 9.8148E-07
D000040-122, Revision 0 Page 78 of 155 24.000 3.0127E+07 2.3484E-06 720.000 2.4763E+06 2.7439E-05 Cumulative Dose Summary EAB Time (hr)
Thyroid (rem)
TEDE (rem) 0.000 0.0000E+00 0.0000E+00 0.014 1.4813E-13 6.2909E-15 0.414 1.2223E-10 5.1380E-12 0.500 1.7776E-10 7.4538E-12 0.800 5.6639E-10 2.4711E-11 1.100 1.3046E-09 5.8463E-11 1.400 2.3893E-09 1.0833E-10 1.700 3.8173E-09 1.7398E-10 1.800 4.3692E-09 1.9932E-10 2.100 6.0774E-09 2.7752E-10 2.400 7.7779E-09 3.5495E-10 2.700 9.4709E-09 4.3167E-10 3.000 1.1157E-08 5.0775E-10 3.300 1.2835E-08 5.8324E-10 3.600 1.4506E-08 6.5817E-10 3.900 1.6171E-08 7.3258E-10 4.200 1.7829E-08 8.0651E-10 4.500 1.9479E-08 8.7998E-10 4.800 2.1124E-08 9.5303E-10 5.100 2.2762E-08 1.0257E-09 5.400 2.4393E-08 1.0979E-09 5.700 2.6019E-08 1.1698E-09 6.000 2.7638E-08 1.2413E-09 6.300 2.9251E-08 1.3124E-09 6.600 3.0858E-08 1.3833E-09 6.900 3.2459E-08 1.4538E-09 7.200 3.4054E-08 1.5240E-09 7.500 3.5643E-08 1.5939E-09 7.800 3.7227E-08 1.6636E-09 8.000 3.8280E-08 1.7098E-09 8.300 3.9090E-08 1.7468E-09 8.600 3.9896E-08 1.7835E-09 8.900 4.0701E-08 1.8201E-09 9.200 4.1502E-08 1.8566E-09 9.500 4.2301E-08 1.8929E-09 9.800 4.3096E-08 1.9290E-09 10.100 4.3890E-08 1.9650E-09 10.400 4.4680E-08 2.0008E-09 24.000 7.8277E-08 3.5202E-09 720.000 7.3495E-07 4.8802E-08 Worst Two-Hour Doses EAB Time Whole Body Thyroid TEDE (hr)
(rem)
(rem)
(rem) 1.1 4.1472E-11 1.0411E-08 4.7445E-10
DC00040-122, Revision 0
.Page 79 of 155 RADTRAD Input/Output File:
Base Case Elemental & Particulate DF Timing Determination - DBA
DC00040-122, Revision 0 Page 80 of 155 RADTRAD Version 3.03 (Spring 2001) run on 10/17/2007 at 7:30:56 File information Plant file
= C:\\Program Files\\radtrad3 03\\VCS LOCA\\Base Case Elemental
- Particulate DF Timing Determination DBA.psf Inventory file
=
Release file
=
Dose Conversion file =
c:\\program files\\radtrad3 03\\vcs loca\\cont.nif c:\\program files\\radtrad3 03\\defaults\\pwr_dba.rft c:\\program files\\radtrad3 03\\defaults\\fgrll&12.inp Radtrad 3.03 4/15/2001 Base Case Elemental DF Timing Determination Nuclide Inventory File:
c:\\program files\\radtrad3_03\\vcs loca\\cont.nif Plant Power Level:
1.0000E+00 Compartments:
2 Compartment 1:
Containment 3
1.8400E+06 1
0 0
0 0
Compartment 2:
Environment 2
0.0000E+00 0
0 0
0 0
Pathways:
2 Pathway 1:
Dummy Flow Rate - Containment to Environment 1
2 2
Pathway 2:
RBCU Flow Containment to Containment 1
DC0004O-122, Revision 0 Page 81 of 155 1
2 End of Plant Model File Scenario Description Name:
Plant Model Filename:
Source Term:
1 1
1.0000E+00 c:\\program files\\radtrad303\\defaults\\fgrll&12.inp c:\\program files\\radtrad3_03\\defaults\\pwr_dba.rft 0.0000E+00 1
9.5000E-01 4.8500E-02 1.5000E-03 1.0000E+00 Overlying Pool:
0 0.0000E+00 0
0 0
0 Compartments:
2 Compartment 1:
1 1
1 0.0000E+00 3
0.0000E+00 0.0000E+00 1.4400E-02 5.6800E+00 7.2000E+02 0.0000E+00 1
0.0000E+00 3
0.0000E+00 0.0000E+00 1.4400E-02 2.0000E+01 7.2000E+02 0.0000E+00 1
0.0000E+00 0
0 0
0 0
Compartment 2:
0 1
0 0
0 0
0 0
0 Pathways:
2 Pathway 1:
0 0
0 0
0
DC00040-122, Revision 0 Page 82 of 155 1
2 0.0000E+00 1.0000E-10 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0
0 0
0 0
0 Pathway 2:
0 0
0 0
0 1
3 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 1.4400E-02 5.4200E+04 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0
0 0
0 0
0 Dose Locations:
1 Location 1:
EAB 2
1 2
0.0000E+00 1.0000E-04 7.2000E+02 0.0000E+00 1
4 0.0000E+00 3.5000E-04 8.0000E+00 1.8000E-04 2.4000E+01 2.3000E-04 7.2000E+02 0.0000E+00 0
Effective Volume Location:
0 Simulation Parameters:
6 0.0000E+00 1.8000E+00 1.8000E+00 5.0000E-02 1.8500E+00 1.0000E-02 1.9000E+00 1.0000E-01 2.1000E+00 1.0000E-02 2.1200E+00 0.0000E+00 Output Filename:
C:\\Program Files\\radtrad3 03\\VCS LOCA\\Base Case Elemental - Particulate DF Timing Determination DBA.oO 1
1 1
1 0
End of Scenario File
D000040-122, Revision 0 Page 83 of 155 RADTRAD Version 3.03 (Spring 2001) run on 10/17/2007 at 7:30:56 Plant Description Number of Nuclides = 60 Inventory Power =
1.0000E+00 MWth Plant Power Level =
1.0000E+00 MWth Number of compartments
=
2 Compartment information Compartment number 1 (Source term fraction =
1.0000E+00 Name: Containment Compartment volume =
1.8400E+06 (Cubic feet)
Compartment type is Normal Removal devices within compartment:
Spray(s)
Pathways into and out of compartment 1
Inlet Pathway Number 2:
RBCU Flow Containment to Containment Exit Pathway Number 1:
Dummy Flow Rate - Containment to Environment Exit Pathway Number 2:
RBCU Flow Containment to Containment Compartment number 2 Name: Environment Compartment type is Environment Pathways into and out of compartment 2 Inlet Pathway Number 1:
Dummy Flow Rate - Containment to Environment Total number of pathways =
2
D000040-122, Revision 0 Page 84 of 155 RADTRAD Version 3.03 (Spring 2001) run on 10/17/2007 at 7:30:56 Scenario Description Radioactive Decay is enabled Calculation of Daughters is enabled Release Fractions and Timings GAP EARLY IN-VESSEL LATE RELEASE RELEASE MASS 0.500000 hr 1.3000 hrs 0.0000 hrs (gm)
NOBLES IODINE CESIUM TELLURIUM STRONTIUM BARIUM RUTHENIUM CERIUM LANTHANUM 5.0000E-02 5.0000E-02 5.0000E-02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 9.5000E-01 0.0000E+00 3.5000E-01 0.0000E+00 2.5000E-01 0.0000E+00 5.0000E-02 0.0000E+00 2.0000E-02 0.0000E+00 2.0000E-02 0.0000E+00 2.5000E-03 0.0000E+00 5.0000E-04 0.0000E+00 2.0000E-04 0.0000E+00 2.987E+03 3.488E+02 2.188E+04 3.416E+01 7.243E+02 4.007E+01 2.861E+01 2.502E+02 3.628E+00 Inventory Power =
1.
MWt Nuclide Group Specific half Whole Body Inhaled Inhaled Name Inventory life DCF Thyroid Effective Co-58 7
(Ci/MWt) 7.550E+05 (s) 6.117E+06 (Sv-m3/Bq-s) 4.760E-14 (Sv/Bq) 8.720E-10 (Sv/Bq) 2.940E-09 Co-60 7
5.780E+05 1.663E+08 1.260E-13 1.620E-08 5.910E-08 Kr-85 1
8.300E+05 3.383E+08 1.190E-16 0.000E+00 0.000E+00 Kr-85m 1
2.720E+07 1.613E+04 7.480E-15 0.000E+00 0.000E+00 Kr-87 1
4.960E+07 4.578E+03 4.120E-14 0.000E+00 0.000E+00 Kr-88 1
6.710E+07 1.022E+04 1.020E-13 0.000E+00 0.000E+00 Rb-86 3
4.430E+04 1.612E+06 4.810E-15 1.330E-09 1.790E-09 Sr-89 5
8.410E+07 4.363E+06 7.730E-17 7.960E-12 1.120E-08 Sr-90 5
4.540E+06 9.190E+08 7.530E-18 2.690E-10 3.510E-07 Sr-91 5
1.080E+08 3.420E+04 4.924E-14 9.930E-12 4.547E-10 Sr-92 5
1.130E+08 9.756E+03 6.790E-14 3.920E-12 2.180E-10 Y-90 9
4.870E+06 2.304E+05 1.900E-16 5.170E-13 2.280E-09 Y-91 9
1.020E+08 5.055E+06 2.600E-16 8.500E-12 1.320E-08 Y-92 9
1.130E+08 1.274E+04 1.300E-14 1.050E-12 2.110E-10 Y-93 9
1.280E+08 3.636E+04 4.800E-15 9.260E-13 5.820E-10 Zr-95 9
1.290E+08 5.528E+06 3.600E-14 1.440E-09 6.390E-09 Zr-97 9
1.350E+08 6.084E+04 4.432E-14 2.315E-11 1.171E-09 Nb-95 9
1.220E+08 3.037E+06 3.740E-14 3.580E-10 1.570E-09 Mo-99 7
1.430E+08 2.376E+05 7.280E-15 1.520E-11 1.070E-09 Tc-99m 7
1.230E+08 2.167E+04 5.890E-15 5.010E-11 8.800E-12 Ru-103 7
1.060E+08 3.394E+06 2.251E-14 2.570E-10 2.421E-09 Ru-105 7
6.920E+07 1.598E+04 3.810E-14 4.150E-12 1.230E-10 Ru-106 7
2.420E+07 3.181E+07 1.040E-14 1.720E-09 1.290E-07 Rh-105 7
4.970E+07 1.273E+05 3.720E-15 2.880E-12 2.580E-10 Sb-127 4
6.530E+06 3.326E+05 3.330E-14 6.150E-11 1.630E-09 Sb-129 4
2.310E+07 1.555E+04 7.140E-14 9.720E-12 1.740E-10 Te-127 4
6.310E+06 3.366E+04 2.420E-16 1.840E-12 8.600E-11 Te-127m 4
8.350E+05 9.418E+06 1.470E-16 9.660E-11 5.810E-09 Te-129 4
2.170E+07 4.176E+03 2.750E-15 5.090E-13 2.090E-11 Te-129m 4
5.720E+06 2.903E+06 3.337E-15 1.563E-10 6.484E-09 Te-131m 4
1.100E+07 1.080E+05 7.463E-14 3.669E-08 1.758E-09 Te-132 4
1.090E+08 2.815E+05 1.030E-14 6.280E-08 2.550E-09 1-131 2
8.200E+07 6.947E+05 1.820E-14 2.920E-07 8.890E-09 1-132 2
1.200E+08 8.280E+03 1.120E-13 1.740E-09 1.030E-10
D000040-122, Revision 0 Page 85 of 155 I-133 2
1.680E+08 7.488E+04 2.940E-14 4.860E-08 1.580E-09 1-134 2
1.800E+08 3.156E+03 1.300E-13 2.880E-10 3.550E-11 I-135 2
1.540E+08 2.380E+04 8.294E-14 8.460E-09 3.320E-10 Xe-133 1
1.590E+08 4.532E+05 1.560E-15 0.000E+00 0.000E+00 Xe-135 1
2.980E+07 3.272E+04 1.190E-14 0.000E+00 0.000E+00 Cs-134 3
1.010E+07 6.507E+07 7.570E-14 1.110E-08 1.250E-08 Cs-136 3
3.080E+06 1.132E+06 1.060E-13 1.730E-09 1.980E-09 Cs-137 3
5.660E+06 9.467E+08 2.725E-14 7.930E-09 8.630E-09 Ba-139 6
1.470E+08 4.962E+03 2.170E-15 2.400E-12 4.640E-11 Ba-140 6
1.460E+08 1.101E+06 8.580E-15 2.560E-10 1.010E-09 La-140 9
1.490E+08 1.450E+05 1.170E-13 6.870E-11 1.310E-09 La-141 9
1.370E+08 1.415E+04 2.390E-15 9.400E-12 1.570E-10 La-142 9
1.320E+08 5.550E+03 1.440E-13 8.740E-12 6.840E-11 Ce-141 8
1.320E+08 2.808E+06 3.430E-15 2.550E-11 2.420E-09 Ce-143 8
1.290E+08 1.188E+05 1.290E-14 6.230E-12 9.160E-10 Ce-144 8
7.980E+07 2.456E+07 2.773E-15 2.920E-10 1.010E-07 Pr-143 9
1.260E+08 1.172E+06 2.100E-17 1.680E-18 2.190E-09 Nd-147 9
5.650E+07 9.487E+05 6.190E-15 1.820E-11 1.850E-09 Np-239 8
1.510E+09 2.035E+05 7.690E-15 7.620E-12 6.780E-10 Pu-238 8
8.580E+04 2.769E+09 4.880E-18 3.860E-10 7.790E-05 Pu-239 8
1.940E+04 7.594E+11 4.240E-18 3.750E-10 8.330E-05 Pu-240 8
2.440E+04 2.063E+11 4.750E-18 3.760E-10 8.330E-05 Pu-241 8
4.110E+06 4.544E+08 7.250E-20 9.150E-12 1.340E-06 Am-241 9
2.720E+03 1.364E+10 8.180E-16 1.600E-09 1.200E-04 Cm-242 9
1.040E+06 1.407E+07 5.690E-18 9.410E-10 4.670E-06 Cm-244 9
6.080E+04 5.715E+08 4.910E-18 1.010E-09 6.700E-05 Nuclide Daughter Fraction Daughter Fraction Daughter Fraction Kr-85m Kr-85 0.21 none 0.00 none 0.00 Kr-87 Rb-87 1.00 none 0.00 none 0.00 Kr-88 Rb-88 1.00 none 0.00 none 0.00 Sr-90 Y-90 1.00 none 0.00 none 0.00 Sr-91 Y-91m 0.58 Y-91 0.42 none 0.00 Sr-92 Y-92 1.00 none 0.00 none 0.00 Y-93 Zr-93 1.00 none 0.00 none 0.00 Zr-95 Nb-95m 0.01 Nb-95 0.99 none 0.00 Zr-97 Nb-97m 0.95 Nb-97 0.05 none 0.00 Mo-99 Tc-99m 0.88 Tc-99 0.12 none 0.00 Tc-99m Tc-99 1.00 none 0.00 none 0.00 Ru-103 Rh-103m 1.00 none 0.00 none 0.00 Ru-l05 Rh-105 1.00 none 0.00 none 0.00 Ru-106 Rh-106 1.00 none 0.00 none 0.00 Sb-127 Te-127m 0.18 Te-127 0.82 none 0.00 Sb-129 Te-129m 0.22 Te-129 0.77 none 0.00 Te-127m Te-127 0.98 none 0.00 none 0.00 Te-129 1-129 1.00 none 0.00 none 0.00 Te-129m Te-129 0.65 I-129 0.35 none 0.00 Te-131m Te-131 0.22 I-131 0.78 none 0.00 Te-132 1-132 1.00 none 0.00 none 0.00 1-131 Xe-131m 0.01 none 0.00 none 0.00 I-133 Xe-133m 0.03 Xe-133 0.97 none 0.00 I-135 Xe-135m 0.15 Xe-135 0.85 none 0.00 Xe-135 Cs-135 1.00 none 0.00 none 0.00 Cs-137 Ba-137m 0.95 none 0.00 none 0.00 Ba-140 La-140 1.00 none 0.00 none 0.00 La-141 Ce-141 1.00 none 0.00 none 0.00 Ce-143 Pr-143 1.00 none 0.00 none 0.00 Ce-144 Pr-144m 0.02 Pr-144 0.98 none 0.00 Nd-147 Pm-147 1.00 none 0.00 none 0.00 Np-239 Pu-239 1.00 none 0.00 none 0.00 Pu-238 U-234 1.00 none 0.00 none 0.00 Pu-239 U-235 1.00 none 0.00 none 0.00 Pu-240 U-236 1.00 none 0.00 none 0.00 Pu-241 U-237 0.00 Am-241 1.00 none 0.00
DC0004O-122, Revision 0 Page 86 of 155 Am-241 Np-237 1.00 none 0.00 none 0.00 Cm-242 Pu-238 1.00 none 0.00 none 0.00 Cm-244 Pu-240 1.00 none 0.00 none 0.00 Iodine fractions Aerosol
=
9.5000E-01 Elemental
=
4.8500E-02 Organic
=
1.5000E-03 COMPARTMENT DATA Compartment number 1:
Aerosal Removal Data Time (hr)
Removal Coef. (hr^-1) 0.0000E+00 0.0000E+00 1.4400E-02 5.6800E+00 7
0000E+00 2000E+02 0
Sprays:
Elemental Removal Data Time (hr)
Removal Coef. (hr^-l) 0.0000E+00 0.0000E+00 1.4400E-02 2.0000E+01 7.2000E+02 0.0000E+00 Compartment number 2:
Environment PATHWAY DATA Pathway number 1: Dummy Flow Rate - Containment to Environment Pathway Filter: Removal Data Time (hr)
Flow Rate Filter Efficiencies (%)
(cfm)
Aerosol Elemental Organic 0.0000E+00 1.0000E-10 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Pathway number 2: RBCU Flow Containment to Containment Pathway Filter:
Removal Data Time (hr)
Flow Rate (cfm)
Filter Efficiencies (%)
Aerosol Elemental Organic 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 1.4400E-02 5.4200E+04 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 LOCATION DATA Location EAB is in compartment 2
Location X/Q Data Time (hr)
X/Q (s
- m^-3) 0.0000E+00 1.0000E-04 7.2000E+02 0.0000E+00 Location Breathing Rate Data Time (hr)
Breathing Rate (m^3
- sec^-1) 0.0000E+00 3.5000E-04 8.0000E+00 1.8000E-04 2.4000E+01 2.3000E-04 7.2000E+02 0.0000E+00 USER SPECIFIED TIME STEP DATA - SUPPLEMENTAL TIME STEPS
Time Time step 0.0000E+00 1.8000E+00 1.8000E+00 5.0000E-02 1.8500E+00 1.0000E-02 1.9000E+00 1.0000E-01 2.1000E+00 1.0000E-02 2.1200E+00 0.0000E+00
DC0004O-122, Revision 0 Page 88 of 155 RADTRAD Version 3.03 (Spring 2001) run on 10/17/2007 at 7:30:56 Dose, Detailed model and Detailed Inventory Output EAB Doses:
Time (h) =
0.0144 Whole Body Thyroid TEDE Delta dose (rem) 8.3759E-16 1.4813E-13 6.2909E-15 Accumulated dose (rem) 8.3759E-16 1.4813E-13 6.2909E-15 Containment Compartment Nuclide Inventory:
Time (h) =
0.0144 Ci kg Atoms Decay Kr-85 1.1952E+03 3.0464E-03 2.1583E+22 2.1258E+15 1-131 1.1807E+05 9.5240E-04 4.3782E+21 2.1002E+17 1-133 2.4180E+05 2.1346E-04 9.6651E+20 4.3018E+17 Xe-133 2.2896E+05 1.2232E-03 5.5385E+21 4.0722E+17 Cs-134 1.4544E+04 1.1241E-02 5.0519E+22 2.5869E+16 Cs-137 8.1504E+03 9.3702E-02 4.1189E+23 1.4497E+16 Containment Transport Group Inventory:
Time (h) =
0.0144 Atmosphere Sump Noble gases (atoms) 2.7300E+22 0.0000E+00 Elemental I (atoms) 2.7864E+20 0.0000E+00 Organic I (atoms) 8.6179E+18 0.0000E+00 Aerosols (kg) 1.0620E-01 0.0000E+00 Dose Effective (Ci/cc) 1-131 (Thyroid) 3.1862E-06 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 4.0632E-06 Total I (Ci) 1.0097E+06 Dummy Flow Rate - Containment to Environment Transport Group Inventory:
Pathway Time (h) =
0.0144 Filtered Transported Noble gases (atoms) 0.0000E+00 6.4097E+05 Elemental I (atoms) 0.0000E+00 6.5441E+03 Organic I (atoms) 0.0000E+00 2.0240E+02 Aerosols (kg) 0.0000E+00 2.4933E-18 RBCU Flow Containment to Containment Transport Group Inventory:
Pathway Time (h) =
0.0144 Filtered Transported Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00
DC0004O-122, Revision 0 Page 89 of 155 Aerosols (kg) 0.0000E+00 0.0000E+00 EAB Doses:
Time (h) =
0.5000 Whole Body Thyroid TEDE Delta dose (rem) 4.9645E-13 8.1367E-11 3.5027E-12 Accumulated dose (rem) 4.9729E-13 8.1515E-11 3.5090E-12 Containment Compartment Nuclide Inventory:
Time (h) =
0.5000 Ci kg Atoms Decay Kr-85 4.1501E+04 1.0578E-01 7.4943E+23 1.6446E+18 Kr-85m 1.2588E+06 1.5296E-04 1.0837E+21 5.1319E+19 Kr-87 1.8884E+06 6.6667E-05 4.6147E+20 8.2854E+19 Kr-88 2.9696E+06 2.3682E-04 1.6207E+21 1.2309E+20 Rb-86 7.3395E+02 9.0202E-06 6.3164E+19 3.8838E+16 1-131 1.3154E+06 1.0611E-02 4.8778E+22 6.9770E+19 1-132 1.8069E+06 1.7505E-04 7.9860E+20 9.8384E+19 1-133 2.6550E+06 2.3437E-03 1.0612E+22 1.4173E+20 1-134 1.9479E+06 7.3020E-05 3.2816E+20 1.2311E+20 1-135 2.3482E+06 6.6866E-04 2.9828E+21 1.2731E+20 Xe-133 7.9428E+06 4.2434E-02 1.9214E+23 3.1486E+20 Xe-135 1.5926E+06 6.2365E-04 2.7820E+21 6.1614E+19 Cs-134 1.6746E+05 1.2943E-01 5.8168E+23 8.8586E+18 Cs-136 5.1012E+04 6.9602E-04 3.0820E+21 2.6998E+18 Cs-137 9.3846E+04 1.0789E+00 4.7426E+24 4.9644E+18 Containment Transport Group Inventory:
Time (h) =
0.5000 Atmosphere Sump Noble gases (atoms) 9.4752E+23 0.0000E+00 Elemental I (atoms) 9.5856E+20 8.7589E+21 Organic I (atoms) 2.9626E+20 0.0000E+00 Aerosols (kg) 1.2227E+00 2.4674E+00 Dose Effective (Ci/cc) 1-131 (Thyroid) 3.5277E-05 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 4.4505E-05 Total I (Ci) 1.0073E+07 Dummy Flow Rate - Containment to Environment Transport Group Inventory:
Time (h) =
0.5000 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 7.7261E+08 Elemental I (atoms) 0.0000E+00 1.4346E+06 Organic I (atoms) 0.0000E+00 2.4258E+05 Aerosols (kg) 0.0000E+00 1.4190E-15 RBCU Flow Containment to Containment Transport Group Inventory:
Time (h) =
0.5000 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 4.1841E+23 Elemental I (atoms) 0.0000E+00 7.7402E+20 Organic I (atoms) 0.0000E+00 1.3137E+20 Aerosols (kg) 0.0000E+00 7.6776E-01 EAB Doses:
Time (h) =
1.8000 Whole Body Thyroid TEDE Delta dose (rem) 8.4342E-12 7.8958E-10 4.1821E-11 Accumulated dose (rem) 8.9315E-12 8.7109E-10 4.5330E-11 Containment Compartment Nuclide Inventory:
Time (h) =
1.8000 Ci kg Atoms Decay
DC00040-122, Revision 0 Page 90 of 155 Co-58 2.5527E+02 8.0280E-06 8.3355E+19
- 3. 9794E+16 Co-60 1.9557E+02 1.7301E-04 1.7365E+21 3.0479E+16 Kr-85 8.3006E+05 2.1157E+00 1.4989E+25
- 8. 2354E+19 Kr-85m 2.0588E+07 2.5018E-03 1.7725E+22 2.2063E+21 Kr-87 1.8594E+07 6.5645E-04 4.5440E+21 2.4548E+21 Kr-88 4.3244E+07 3.4487E-03 2.3601E+22 4.8519E+21 Rb-86 1.4952E+03 1.8376E-05 1.2868E+20 2.8478E+17 Sr-89 2.2741E+05 7.8278E-03 5.2966E+22 3.5455E+19 Sr-90 1.2289E+04 9.0092E-02 6.0283E+23
- 1. 9153E+18 Sr-91 2.5636E+05 7.0721E-05 4.6801E+20 4.1748E+19 Sr-92 1.9302E+05 1.5356E-05 1.0052E+20
- 3. 5194E+19 Y-91 2.7718E+03 1.1303E-04 7.4798E+20
- 4. 3106E+17 Y-92 1.1658E+04 1.2116E-06 7.9308E+18 1.1726E+18 Y-93 3.0622E+03
- 9. 1783E-07 5.9433E+18
- 4. 9736E+17 Zr-95 3.4890E+03 1.6241E-04 1.0295E+21
- 5. 4391E+17 Zr-97 3.3942E+03 1.7755E-06 1.1023E+19
- 5. 4217E+17 Nb-95 3.3026E+03 8.4459E-05 5.3539E+20
- 5. 1468E+17 Mo-99 4.7479E+04 9.8995E-05
- 6. 0218E+20 7.4463E+18 Tc-99m 4.1766E+04 7.9429E-06 4.8316E+19
- 6. 4665E+18 Ru-103 3.5819E+04 1.1098E-03
- 6. 4889E+21
- 5. 5848E+18 Ru-105 1.7678E+04 2.6299E-06 1.5084E+19
- 3. 0292E+18 Ru-106 8.1871E+03 2.4472E-03 1.3903E+22 1.2760E+18 Rh-105 1.6941E+04 2.0071E-05
- 1. 1512E+20 2.6338E+18 Sb-127 4.3597E+04 1.6325E-04 7.7412E+20
- 6. 8251E+18 Sb-129 1.1711E+05 2.0825E-05
- 9. 7220E+19 2.0120E+19 Te-127 4.2573E+04 1.6132E-05 7.6494E+19
- 6. 6183E+18 Te-127m 5.6517E+03 5.9917E-04
- 2. 8411E+21
- 8. 8074E+17 Te-129 1.3632E+05 6.5092E-06
- 3. 0387E+19 2.1491E+19 Te-129m 3.8695E+04 1.2845E-03 5.9963E+21
- 6. 0313E+18 Te-131m 7.1407E+04 8.9549E-05 4.1166E+20 1.1284E+19 Te-132 7.2595E+05 2.3912E-03 1.0909E+22 1.1374E+20 I-131*
3.7714E+06 3.0421E-02 1.3985E+23 6.7927E+20 1-132 5.0692E+06 4.9110E-04 2.2405E+21 9.3689E+20 1-133 7.3198E+06
- 6. 4616E-03 2.9258E+22 1.3469E+21 1-134 2.0064E+06 7.5213E-05 3.3802E+20 6.7222E+20 1-135 5.8991E+06 1.6798E-03 7.4931E+21
- 1. 1430E+21 Xe-133 1.5841E+08
- 8. 4628E-01 3.8319E+24 1.5739E+22 Xe-135 3.5563E+07 1.3926E-02 6.2122E+22
- 3. 4508E+21 Cs-134 3.4182E+05 2.6420E-01 1.1873E+24
- 6. 5032E+19 Cs-136 1.0383E+05 1.4167E-03
- 6. 2733E+21
- 1. 9786E+19 Cs-137 1.9157E+05 2.2024E+00
- 9. 6811E+24
- 3. 6445E+19 Ba-139 1.6094E+05 9.8392E-06 4.2628E+19
- 3. 4418E+19 Ba-140 3.9359E+05 5.3763E-03 2.3126E+22
- 6. 1425E+19 La-140 5.5701E+03 1.0021E-05
- 4. 3107E+19 7.3749E+17 Ce-141 8.9303E+03
- 3. 1341E-04 1.3386E+21 1.3919E+18 Ce-143 8.4058E+03 1.2658E-05 5.3305E+19 1.3266E+18 Ce-144 5.3992E+03 1.6928E-03 7.0794E+21
- 8. 4152E+17 Pr-143 3.4132E+03 5.0687E-05 2.1346E+20 5.3169E+17 Nd-147 1.5222E+03 1.8816E-05 7.7082E+19 2.3760E+17 Np-239 9.9954E+04 4.3085E-04
- 1. 0856E+21 1.5692E+19 Pu-238 5.8063E+00 3.3916E-04 8.5818E+20
- 9. 0491E+14 Pu-239 1.3134E+00
- 2. 1131E-02 5.3244E+22 2.0466E+14 Pu-240 1.6512E+00 7.2463E-03 1.8183E+22 2.5734E+14 Pu-241 2.7813E+02 2.6999E-03 6.7467E+21 4.3346E+16 Am-241 7.3671E-02 2.1465E-05
- 5. 3636E+19 1.1479E+13 Cm-242 2.8143E+01 8.4913E-06
- 2. 1130E+19 4.3865E+15 Cm-244 1.6458E+00 2.0343E-05
- 5. 0207E+19 2.5649E+14 Containment Transport Group Inventory:
Time (h) =
1.8000 Atmosphere Sump Noble gases (atoms) 1.8929E+25 0.0000E+00 Elemental I (atoms) 2.5295E+21 7.3817E+22 Organic I (atoms) 2.3192E+21 0.0000E+00 Aerosols (kg) 2.6523E+00 2.0635E+01
DC0004O-122, Revision 0 Page 91 of 155 Dose Effective (Ci/cc) 1-131 (Thyroid) 9.9664E-05 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 1.2352E-04 Total I
(Ci) 2.4066E+07 Dummy Flow Rate - Containment to Environment Transport Group Inventory:
Time (h) =
1.8000 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 4.2923E+10 Elemental I (atoms) 0.0000E+00 1.2042E+07 Organic I (atoms) 0.0000E+00 5.8216E+06 Aerosols (kg) 0.0000E+00 1.1849E-14 RBCU Flow Containment to Containment Transport Group Inventory:
Time (h) =
1.8000 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 2.3264E+25 Elemental I (atoms) 0.0000E+00 6.5231E+21 Organic I (atoms) 0.0000E+00 3.1552E+21 Aerosols (kg) 0.0000E+00 6.4209E+00 EAB Doses:
Time (h) =
1.8500 Whole Body Thyroid TEDE Delta dose (rem) 4.5121E-13 2.8806E-11 1.6779E-12 Accumulated dose (rem) 9.3827E-12 8.9990E-10 4.7008E-11 Containment Compartment Nuclide Inventory:
Time (h) =
1.8500 Ci kg Atoms Decay Co-58 1.9216E+02 6.0431E-06 6.2745E+19 4.1074E+16 Co-60 1.4722E+02 1.3024E-04 1.3072E+21 3.1460E+16 Kr-85 8.3006E+05 2.1157E+00 1.4989E+25 8.7883E+19 Kr-85m 2.0430E+07 2.4825E-03 1.7588E+22 2.3429E+21 Kr-87 1.8095E+07 6.3881E-04 4.4218E+21 2.5770E+21 Kr-88 4.2720E+07 3.4069E-03 2.3315E+22 5.1382E+21 Rb-86 1.1255E+03 1.3832E-05 9.6857E+19 2.9228E+17 Sr-89 1.7118E+05 5.8923E-03 3.9870E+22 3.6595E+19 Sr-90 9.2509E+03 6.7818E-02 4.5379E+23 1.9769E+18 Sr-91 1.9228E+05 5.3043E-05 3.5102E+20 4.3031E+19 Sr-92 1.4345E+05 1.1413E-05 7.4706E+19 3.6155E+19 Y-91 2.0885E+03 8.5162E-05 5.6358E+20 4.4496E+17 Y-92 1.0104E+04 1.0501E-06 6.8734E+18 1.2308E+18 Y-93 2.2972E+03 6.8854E-07 4.4586E+18 5.1269E+17 Zr-95 2.6264E+03 1.2225E-04 7.7498E+20 5.6140E+17 Zr-97 2.5498E+03 1.3338E-06 8.2809E+18 5.5917E+17 Nb-95 2.4861E+03 6.3578E-05 4.0303E+20 5.3124E+17 Mo-99 3.5722E+04 7.4481E-05 4.5306E+20 7.6842E+18 Tc-99m 3.1440E+04 5.9792E-06 3.6372E+19 6.6753E+18 Ru-103 2.6962E+04 8.3541E-04 4.8844E+21 5.7644E+18 Ru-105 1.3204E+04 1.9643E-06 1.1266E+19 3.1175E+18 Ru-106 6.1630E+03 1.8421E-03 1.0466E+22 1.3171E+18 Rh-105 1.2753E+04 1.5110E-05 8.6659E+19 2.7187E+18 Sb-127 3.2806E+04 1.2285E-04 5.8251E+20 7.0437E+18 Sb-129 8.7452E+04 1.5551E-05 7.2599E+19 2.0705E+19 Te-127 3.2044E+04 1.2142E-05 5.7576E+19 6.8313E+18 Te-127m 4.2544E+03 4.5103E-04 2.1387E+21 9.0908E+17 Te-129 1.0218E+05 4.8792E-06 2.2777E+19 2.2164E+19 Te-129m 2.9128E+04 9.6688E-04 4.5137E+21 6.2252E+18 Te-131m 5.3691E+04 6.7332E-05 3.0953E+20 1.1642E+19 Te-132 5.4623E+05 1.7992E-03 8.2084E+21 1.1738E+20 1-131 2.8301E+06 2.2828E-02 1.0494E+23 6.9812E+20 1-132 3.7559E+06 3.6387E-04 1.6601E+21 9.6204E+20
DC00040-122, Revision 0 Page 92 of 155 1-133 5.4846E+06 4.8416E-03 2.1922E+22 1.3835E+21 1-134 1.4475E+06 5.4262E-05 2.4386E+20 6.8206E+20 1-135 4.4043E+06 1.2541E-03
- 5. 5944E+21 1.1725E+21 Xe-133 1.5837E+08 8.4605E-01 3.8309E+24 1.6793E+22 Xe-135 3.5442E+07 1.3879E-02
- 6. 1910E+22
- 3. 6872E+21 Cs-134 2.5731E+05 1.9888E-01 8.9378E+23
- 6. 6745E+19 Cs-136 7.8154E+04 1.0664E-03 4.7218E+21 2.0307E+19 Cs-137 1.4421E+05 1.6579E+00 7.2876E+24 3.7405E+19 Ba-139 1.1814E+05 7.2227E-06
- 3. 1292E+19
- 3. 5215E+19 Ba-140 2.9625E+05 4.0467E-03 1.7407E+22
- 6. 3398E+19 La-140 4.4443E+03 7.9959E-06
- 3. 4394E+19 7.6541E+17 Ce-141 6.7222E+03 2.3592E-04 1.0076E+21 1.4367E+18 Ce-143 6.3210E+03 9.5183E-06 4.0084E+19 1.3687E+18 Ce-144 4.0643E+03 1.2743E-03 5.3291E+21
- 8. 6859E+17 Pr-143 2.5697E+03
- 3. 8162E-05 1.6071E+20 5.4880E+17 Nd-147 1.1457E+03 1.4162E-05 5.8017E+19 2.4523E+17 Np-239 7.5196E+04 3.2413E-04 8.1672E+20 1.6193E+19 Pu-238 4.3708E+00 2.5531E-04
- 6. 4601E+20
- 9. 3402E+14 Pu-239 9.8872E-01 1.5907E-02
- 4. 0081E+22 2.1125E+14 Pu-240 1.2430E+00 5.4548E-03 1.3687E+22 2.6562E+14 Pu-241 2.0937E+02 2.0324E-03 5.0787E+21 4.4741E+16 Am-241 5.5459E-02 1.6159E-05 4.0377E+19 1.1848E+13 Cm-242 2.1185E+01
- 6. 3919E-06 1.5906E+19
- 4. 5276E+15 Cm-244 1.2389E+00 1.5313E-05 3.7794E+19 2.6474E+14 Containment Transport Group Inventory:
Time (h) =
1.8500 Atmosphere Sump Noble gases (atoms) 1.8927E+25 0.0000E+00 Elemental I (atoms) 9.2975E+20 7.5391E+22 Organic I (atoms) 2.3172E+21 0.0000E+00 Aerosols (kg) 1.9965E+00 2.1291E+01 Dose Effective (Ci/cc) 1-131 (Thyroid) 7.4742E-05 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 9.2558E-05 Total I (Ci) 1.7922E+07 Dummy Flow Rate - Containment to Environment Transport Group Inventory:
Time (h) =
1.8500 Pathway Filtered Transported Noble gases Elemental I (atoms)
(atoms) 0.000"0E+00 0.0000E+00 4.6010E+10 1.2299E+07 Organic I (atoms)
Aerosols (kg) 0.0000E+00 6.1998E+06 0.0000E+00 1.2226E-14 RBCU Flow Containment to Containment Transport Group Inventory:
Time (h) =
1.8500 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 2.4937E+25 Elemental I (atoms) 0.0000E+00 6.6623E+21 Organic I (atoms) 0.0000E+00 3.3602E+21 Aerosols (kg) 0.0000E+00 6.6249E+00 EAB Doses:
Time (h) =
1.8600 Whole Body Thyroid TEDE Delta dose (rem) 8.6278E-14 4.8346E-12 2.9222E-13 Accumulated dose (rem) 9.4690E-12 9.0474E-10 4.7300E-11 Containment Compartment Nuclide Inventory:
Time (h) =
1.8600 Ci kg Atoms Decay Co-58 1.8155E+02 5.7094E-06 5.9280E+19 4.1316E+16 Co-60 1.3909E+02 1.2304E-04 1.2350E+21 3.1645E+16
DC00040-122, Revision 0 Page 93 of 155 Kr-85 8.3006E+05 2.1157E+00 1.4989E+25 8.8988E+19 Kr-85m 2.0398E+07 2.4786E-03 1.7561E+22 2.3701E+21 Kr-87 1.7996E+07 6.3533E-04 4.3978E+21 2.6010E+21 Kr-88 4.2616E+07 3.3986E-03 2.3258E+22
- 5. 1950E+21 Rb-86 1.0633E+03 1.3068E-05
- 9. 1508E+19 2.9370E+17 Sr-89 1.6173E+05 5.5669E-03 3.7668E+22
- 3. 6810E+19 Sr-90 8.7401E+03 6.4073E-02 4.2873E+23 1.9885E+18 Sr-91 1.8153E+05 5.0077E-05
- 3. 3140E+20 4.3273E+19 Sr-92 1.3518E+05 1.0755E-05 7.0401E+19
- 3. 6336E+19 Y-91 1.9735E+03 8.0474E-05 5.3256E+20 4.4758E+17 Y-92 9.7924E+03 1.0177E-06
- 6. 6615E+18 1.2435E+18 Y-93 2.1689E+03 6.5008E-07 4.2095E+18
- 5. 1558E+17 Zr-95 2.4813E+03 1.1550E-04 7.3218E+20 5.6471E+17 Zr-97 2.4080E+03 1.2597E-06 7.8204E+18
- 5. 6238E+17 Nb-95 2.3488E+03 6.0068E-05 3.8077E+20
- 5. 3436E+17 Mo-99 3.3746E+04 7.0361E-05 4.2800E+20 7.7292E+18 Tc-99m 2.9704E+04 5.6491E-06
- 3. 4363E+19
- 6. 7148E+18 Ru-103 2.5473E+04 7.8928E-04
- 4. 6147E+21
- 5. 7983E+18 Ru-105 1.2456E+04 1.8530E-06 1.0628E+19
- 3. 1341E+18 Ru-106 5.8227E+03 1.7404E-03
- 9. 8877E+21 1.3248E+18 Rh-105 1.2049E+04 1.4275E-05
- 8. 1874E+19 2.7347E+18 Sb-127 3.0992E+04 1.1605E-04
- 5. 5031E+20 7.0850E+18 Sb-129 8.2490E+04 1.4669E-05 6.8480E+19 2.0815E+19 Te-127 3.0274E+04 1.1471E-05
- 5. 4395E+19
- 6. 8717E+18 Te-127m 4.0195E+03 4.2613E-04 2.0206E+21
- 9. 1443E+17 Te-129 9.6450E+04 4.6055E-06 2.1500E+19 2.2292E+19 Te-129m 2.7519E+04 9.1349E-04 4.2645E+21
- 6. 2619E+18 Te-131m 5.0714E+04 6.3599E-05 2.9237E+20 1.1709E+19 Te-132 5.1602E+05 1.6997E-03 7.7545E+21 1.1807E+20 I-131 2.6739E+06 2.1568E-02
- 9. 9150E+22 7.0169E+20 I-132 3.5397E+06 3.4292E-04
- 1. 5645E+21 9.6676E+20 I-133 5.1804E+06 4.5731E-03 2.0707E+22 1.3904E+21 I-134 1.3569E+06 5.0866E-05 2.2860E+20 6.8387E+20 I-135 4.1571E+06 1.1837E-03
- 5. 2804E+21 1.1780E+21 Xe-133 1.5836E+08 8.4601E-01 3.8307E+24 1.7004E+22 Xe-135 3.5418E+07 1.3869E-02
- 6. 1868E+22 3.7344E+21 Cs-134 2.4310E+05 1.8790E-01 8.4443E+23 6.7069E+19 Cs-136 7.3837E+04 1.0074E-03 4.4610E+21 2.0405E+19 Cs-137 1.3624E+05 1.5663E+00 6.8852E+24
- 3. 7587E+19 Ba-139 1.1106E+05 6.7897E-06 2.9416E+19 3.5363E+19 Ba-140 2.7989E+05 3.8231E-03 1.6445E+22 6.3771E+19 La-140 4.2464E+03 7.6397E-06 3.2863E+19 7.7100E+17 Ce-141 6.3510E+03 2.2289E-04
- 9. 5198E+20 1.4452E+18 Ce-143 5.9707E+03 8.9909E-06 3.7863E+19 1.3767E+18 Ce-144 3.8399E+03 1.2039E-03
- 5. 0349E+21 8.7370E+17 Pr-143 2.4279E+03 3.6055E-05 1.5184E+20 5.5203E+17 Nd-147 1.0824E+03 1.3380E-05
- 5. 4812E+19 2.4667E+17 Np-239 7.1035E+04 3.0620E-04 7.7153E+20 1.6288E+19 Pu-238 4.1295E+00 2.4121E-04
- 6. 1034E+20 9.3952E+14 Pu-239 9.3413E-01 1.5029E-02 3.7868E+22 2.1249E+14 Pu-240 1.1743E+00 5.1536E-03 1.2932E+22 2.6718E+14 Pu-241 1.9781E+02 1.9202E-03 4.7982E+21 4.5004E+16 Am-241 5.2397E-02 1.5266E-05
- 3. 8148E+19 1.1918E+13 Cm-242 2.0015E+01 6.0389E-06 1.5028E+19 4.5542E+15 Cm-244 1.1705E+00 1.4468E-05
- 3. 5708E+19 2.6630E+14 Containment Transport Group Inventory:
Time (h) =
1.8600 Atmosphere Sump Noble gases (atoms) 1.8927E+25 0.0000E+00 Elemental I (atoms) 7.6109E+20 7.5560E+22 Organic I (atoms) 2.3168E+21 0.0000E+00 Aerosols (kg) 1.8863E+00 2.1401E+01 Dose Effective (Ci/cc) 1-131 (Thyroid) 7.0610E-05 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 8.7427E-05
D00004O-122, Revision 0 Page 94 of 155 Total I (Ci) 1.6908E+07 Dummy Flow Rate - Containment to Environment Transport Group Inventory:
Time (h) =
1.8600 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 4.6627E+10 Elemental I (atoms) 0.0000E+00 1.2326E+07 Organic I (atoms) 0.0000E+00 6.2753E+06 Aerosols (kg) 0.0000E+00 1.2289E-14 RBCU Flow Containment to Containment Transport Group Inventory:
Time (h) =
1.8600 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 2.5271E+25 Elemental I (atoms) 0.0000E+00 6.6772E+21 Organic I (atoms) 0.0000E+00 3.4011E+21 Aerosols (kg) 0.0000E+00 6.6592E+00 EAB Doses:
Time (h) =
1.8700 Whole Body Thyroid TEDE Delta dose (rem) 8.5246E-14 4.5677E-12 2.7981E-13 Accumulated dose (rem) 9.5543E-12 9.0930E-10 4.7580E-11 Containment Compartment Nuclide Inventory:
Time (h) =
1.8700 Ci kg Atoms Decay Co-58 1.7152E+02 5.3941E-06
- 5. 6007E+19 4.1544E+16 Co-60 1:3141E+02 1.1625E-04 1.1668E+21 3.1820E+16 Kr-85 8.3006E+05 2.1157E+00 1.4989E+25
- 9. 0094E+19 Kr-85m 2.0366E+07 2.4748E-03 1.7534E+22 2.3972E+21 Kr-87 1.7898E+07 6.3188E-04 4.3739E+21 2.6249E+21 Kr-88 4.2512E+07 3.3903E-03 2.3201E+22 5.2517E+21 Rb-86 1.0046E+03 1.2346E-05 8.6454E+19 2.9504E+17 Sr-89 1.5280E+05 5.2595E-03 3.5588E+22 3.7014E+19 Sr-90 8.2575E+03 6.0535E-02 4.0506E+23 1.9995E+18 Sr-91 1.7138E+05 4.7277E-05
- 3. 1287E+20 4.3501E+19 Sr-92 1.2739E+05 1.0135E-05
- 6. 6343E+19 3.6505E+19 Y-91 1.8649E+03 7.6045E-05 5.0324E+20 4.5007E+17 Y-92 9.4834E+03 9.8556E-07 6.4513E+18 1.2558E+18 Y-93 2.0477E+03
- 6. 1376E-07
- 3. 9744E+18 5.1831E+17 Zr-95 2.3443E+03 1.0912E-04
- 6. 9175E+20 5.6783E+17 Zr-97 2.2741E+03 1.1896E-06 7.3856E+18 5.6541E+17 Nb-95 2.2191E+03 5.6751E-05 3.5975E+20 5.3732E+17 Mo-99 3.1879E+04 6.6469E-05 4.0433E+20 7.7717E+18 Tc-99m 2.8064E+04 5.3372E-06 3.2466E+19 6.7522E+18 Ru-103 2.4066E+04 7.4569E-04 4.3599E+21 5.8303E+18 Ru-105 1.1750E+04 1.7479E-06 1.0025E+19 3.1497E+18 Ru-106 5.5012E+03 1.6443E-03 9.3418E+21 1.3322E+18 Rh-105 1.1384E+04 1.3487E-05 7.7354E+19 2.7499E+18 Sb-127 2,9279E+04 1.0964E-04 5.1988E+20 7.1240E+18 Sb-129 7.7810E+04 1.3837E-05
- 6. 4595E+19 2.0919E+19 Te-127 2.8602E+04 1.0838E-05
- 5. 1391E+19
- 6. 9097E+18 Te-127m 3.7976E+03 4.0260E-04 1.9091E+21 9.1949E+17 Te-129 9.1041E+04 4.3472E-06 2.0294E+19 2.2413E+19 Te-129m 2.6000E+04 8.6305E-04 4.0290E+21 6.2965E+18 Te-131m 4.7903E+04 6.0073E-05 2.7616E+20 1.1773E+19 Te-132 4.8748E+05 1.6057E-03 7.3257E+21 1.1872E+20 1-131 2.5269E+06 2.0382E-02 9.3697E+22 7.0505E+20 1-132 3.3365E+06 3.2324E-04 1.4747E+21 9.7121E+20 1-133 4.8941E+06 4.3203E-03 1.9562E+22 1.3969E+21 1-134 1.2723E+06 4.7692E-05 2.1433E+20 6.8557E+20
D00004O-122, Revision 0 Page 95 of 155 1-135 3.9245E+06 1.1175E-03 4.9850E+21 1.1832E+21 Xe-133 1.5835E+08 8.4596E-01 3.8305E+24 1.7215E+22 Xe-135 3.5393E+07 1.3860E-02 6.1825E+22 3.7816E+21 Cs-134 2.2968E+05 1.7752E-01 7.9780E+23 6.7375E+19 Cs-136 6.9758E+04 9.5180E-04 4.2146E+21 2.0498E+19 Cs-137 1.2872E+05 1.4799E+00 6.5051E+2-4 3.7758E+19 Ba-139 1.0440E+05 6.3826E-06 2.7652E+19 3.5503E+19 Ba-140 2.6443E+05 3.6119E-03 1.5537E+22 6.4123E+19 La-140 4.0567E+03 7.2985E-06 3.1395E+19 7.7634E+17 Ce-141 6.0003E+03 2.1058E-04 8.9941E+20 1.4532E+18 Ce-143 5.6398E+03 8.4926E-06 3.5765E+19 1.3842E+18 Ce-144 3.6279E+03 1.1374E-03 4.7569E+21 8.7854E+17 Pr-143 2.2939E+03 3.4066E-05 1.4346E+20 5.5509E+17 Nd-147 1.0226E+03 1.2641E-05 5.1784E+19 2.4804E+17 Np-239 6.7104E+04 2.8925E-04 7.2884E+20 1.6377E+19 Pu-238 3.9015E+00 2.2789E-04 5.7664E+20 9.4472E+14 Pu-239 8.8255E-01 1.4199E-02 3.5777E+22 2.1367E+14 Pu-240 1.1095E+00 4.8690E-03 1.2217E+22 2.6866E+14 Pu-241 1.8688E+02 1.8142E-03 4.5333E+21 4.5253E+16 Am-241 4.9504E-02 1.4424E-05 3.6042E+19 1.1984E+13 Cm-242 1.8910E+01 5.7055E-06 1.4198E+19 4.5794E+15 Cm-244 1.1058E+00 1.3669E-05 3.3736E+19 2.6778E+14 Containment Transport Group Inventory:
Time (h) =
1.8700 Atmosphere Sump Noble gases (atoms) 1.8927E+25 0.0000E+00 Elemental I (atoms) 6.2302E+20 7.5698E+22 Organic I (atoms) 2.3164E+21 0.0000E+00 Aerosols (kg) 1.7821E+00 2.1505E+01 Dose Effective (Ci/cc) 1-131 (Thyroid) 6.6719E-05 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 8.2596E-05 Total I (Ci) 1.5954E+07 Dummy Flow Rate - Containment to Environment Transport Group Inventory:
Time (h) =
1.8700 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 4.7244E+10 Elemental I (atoms) 0.0000E+00 1.2349E+07 Organic I (atoms) 0.0000E+00 6.3509E+06 Aerosols (kg) 0.0000E+00 1.2349E-14 RBCU Flow Containment to Containment Transport Group Inventory:
Time (h) =
1.8700 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 2.5606E+25 Elemental I (atoms) 0.0000E+00 6.6894E+21 Organic I (atoms) 0.0000E+00 3.4421E+21 Aerosols (kg) 0.0000E+00 6.6916E+00 EAB Doses:
Time (h) =
1.8800 Whole Body Thyroid TEDE Delta dose (rem) 8.4266E-14 4.3163E-12 2.6811E-13 Accumulated dose (rem) 9.6385E-12 9.1362E-10 4.7848E-11 Containment Compartment Nuclide Inventory:
Time (h) =
1.8800 Ci kg Atoms Decay Co-58 1.6205E+02 5.0962E-06 5.2914E+19 4.1760E+16 Co-60 1.2415E+02 1.0983E-04 1.1024E+21 3.1985E+16 Kr-85 8.3006E+05 2.1157E+00 1.4989E+25 9.1199E+19 Kr-85m 2.0335E+07 2.4710E-03 1.7507E+22 2.4243E+21
D000040-122, Revision 0 Page 96 of 155 Kr-87 1.7801E+07 6.2844E-04
- 4. 3501E+21 2.6487E+21 Kr-88 4.2408E+07 3.3820E-03 2.3144E+22
- 5. 3083E+21 Rb-86 9.4909E+02 1.1664E-05
- 8. 1679E+19 2.9630E+17 Sr-89 1.4436E+05 4.9691E-03 3.3623E+22
- 3. 7206E+19 Sr-90 7.8015E+03 5.7193E-02 3.8269E+23 2.0099E+18 Sr-91 1.6180E+05 4.4634E-05 2.9538E+20 4.3717E+19 Sr-92 1.2005E+05 9.5512E-06
- 6. 2520E+19 3.6666E+19 Y-91 1.7623E+03 7.1859E-05 4.7555E+20 4.5241E+17 Y-92 9.1776E+03 9.5378E-07
- 6. 2432E+18 1.2677E+18 Y-93 1.9333E+03 5.7947E-07
- 3. 7523E+18
- 5. 2088E+17 Zr-95 2.2149E+03 1.0310E-04 6.5355E+20
- 5. 7078E+17 Zr-97 2.1477E+03 1.1235E-06
- 6. 9749E+18 5.6827E+17 Nb-95 2.0966E+03 5.3617E-05 3.3988E+20
- 5. 4011E+17 Mo-99 3.0116E+04 6.2792E-05 3.8196E+20
- 7. 8118E+18 Tc-99m 2.6514E+04 5.0425E-06 3.0673E+19
- 6. 7875E+18 Ru-103 2.2737E+04 7.0451E-04
- 4. 1191E+21
- 5. 8606E+18 Ru-105 1.1084E+04 1.6488E-06
- 9. 4567E+18
- 3. 1645E+18 Ru-106 5.1974E+03 1.5535E-03 8.8259E+21 1.3391E+18 Rh-105 1.0755E+04 1.2743E-05 7.3083E+19 2.7642E+18 Sb-127 2.7660E+04 1.0358E-04 4.9114E+20
- 7. 1608E+18 Sb-129 7.3396E+04 1.3052E-05
- 6. 0931E+19
- 2. 1017E+19 Te-127 2.7022E+04 1.0239E-05 4.8552E+19
- 6. 9457E+18 Te-127m 3.5879E+03 3.8037E-04 1.8037E+21
- 9. 2427E+17 Te-129 8.5935E+04 4.1034E-06 1.9156E+19 2.2527E+19 Te-129m 2.4564E+04 8.1539E-04
- 3. 8065E+21
- 6. 3293E+18 Te-131m 4.5247E+04 5.6743E-05 2.6085E+20 1.1833E+19 Te-132 4.6053E+05 1.5169E-03
- 6. 9205E+21 1.1933E+20 1-131 2.3883E+06 1.9264E-02 8.8559E+22 7.0823E+20 1-132 3.1456E+06 3.0474E-04 1.3903E+21 9.7540E+20 1-133 4.6243E+06 4.0822E-03 1.8484E+22 1.4031E+21 1-134 1.1931E+06 4.4723E-05 2.0099E+20
- 6. 8717E+20 1-135 3.7055E+06 1.0551E-03 4.7068E+21 1.1882E+21 Xe-133 1.5834E+08 8.4592E-01 3.8302E+24 1.7426E+22 Xe-135 3.5369E+07 1.3850E-02
- 6. 1782E+22
- 3. 8287E+21 Cs-134 2.1700E+05 1.6772E-01 7.5375E+23 6.7664E+19 Cs-136 6.5905E+04 8.9922E-04
- 3. 9818E+21 2.0586E+19 Cs-137 1.2161E+05 1.3981E+00
- 6. 1459E+24 3.7920E+19 Ba-139 9.8140E+04 5.9999E-06 2.5994E+19 3.5634E+19 Ba-140 2.4982E+05 3.4124E-03 1.4679E+22 6.4456E+19 La-140 3.8751E+03 6.9717E-06 2.9989E+19 7.8145E+17 Ce-141 5.6689E+03 1.9895E-04 8.4974E+20 1.4607E+18 Ce-143 5.3273E+03 8.0220E-06
- 3. 3783E+19 1.3913E+18 Ce-144 3.4276E+03 1.0746E-03 4.4942E+21 8.8310E+17 Pr-143 2.1673E+03 3.2186E-05 1.3554E+20 5.5797E+17 Nd-147 9.6611E+02 1.1942E-05 4.8924E+19 2.4932E+17 Np-239 6.3391E+04 2.7325E-04
- 6. 8851E+20 1.6462E+19 Pu-238 3.6860E+00 2.1531E-04 5.4480E+20
- 9. 4963E+14 Pu-239 8.3382E-01 1.3415E-02 3.3802E+22 2.1478E+14 Pu-240 1.0482E+00 4.6002E-03 1.1543E+22 2.7005E+14 Pu-241 1.7656E+02 1.7140E-03 4.2830E+21
- 4. 5488E+16 Am-241 4.6771E-02 1.3627E-05 3.4052E+19 1.2046E+13 Cm-242 1.7865E+01 5.3904E-06 1.3414E+19
- 4. 6032E+15 Cm-244 1.0448E+00 1.2914E-05 3.1873E+19 2.6917E+14 Containment Transport Group Inventory:
Time (h) =
1.8800 Atmosphere Sump Noble gases (atoms) 1.8926E+25 0.0000E+00 Elemental I (atoms) 5.1000E+20 7.5811E+22 Organic I (atoms) 2.3160E+21 0.0000E+00 Aerosols (kg) 1.6837E+00 2.1604E+01 Dose Effective (Ci/cc) 1-131 (Thyroid) 6.3053E-05 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 7.8044E-05 Total I (Ci) 1.5057E+07
D000040-122, Revision 0 Page 97 of 155 Dummy Flow Rate - Containment to Environment Transport Group Inventory:
Time (h) =
1.8800 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 4.7861E+10 Elemental I (atoms) 0.0000E+00 1.2367E+07 Organic I (atoms) 0.0000E+00 6.4264E+06 Aerosols (kg) 0.0000E+00 1.2405E-14 RBCU Flow Containment to Containment Transport Group Inventory:
Time (h) 1.8800 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 2.5940E+25 Elemental I (atoms) 0.0000E+00 6.6994E+21 Organic I (atoms) 0.0000E+00 3.4830E+21 Aerosols (kg) 0.0000E+00 6.7222E+00 EAB Doses:
Time (h) =
1.8900 Whole Body Thyroid TEDE Delta dose (rem) 8.3334E-14 4.0794E-12 2.5707E-13 Accumulated dose (rem) 9.7219E-12 9.1770E-10 4.8105E-11 Containment Compartment Nuclide Inventory:
Time (h.) =
1.8900 Ci kg Atoms Decay Co-58 1.5310E+02 4.8148E-06 4.9992E+19
- 4. 1964E+16 Co-60 1.1730E+02 1.0377E-04 1.0415E+21
- 3. 2142E+16 Kr-85 8.3006E+05 2.1157E+00 1.4989E+25
- 9. 2305E+19 Kr-85m 2.0304E+07 2.4672E-03 1.7479E+22 2.4514E+21 Kr-87 1.7704E+07 6.2503E-04 4.3264E+21 2.6723E+21 Kr-88 4.2305E+07 3.3738E-03 2.3088E+22 5.3647E+21 Rb-86 8.9667E+02 1.1020E-05 7.7167E+19 2.9749E+17 Sr-89 1.3639E+05 4.6947E-03 3.1766E+22
- 3. 7388E+19 Sr-90 7.3707E+03 5.4035E-02 3.6156E+23 2.0197E+18 Sr-91 1.5275E+05 4.2139E-05 2.7887E+20 4.3921E+19 Sr-92 1.1313E+05 9.0007E-06 5.8917E+19
- 3. 6816E+19 Y-91 1.6653E+03 6.7904E-05 4.4937E+20 4.5463E+17 Y-92 8.8757E+03 9.2240E-07 6.0379E+18 1.2792E+18 Y-93 1.8253E+03 5.4710E-07 3.5427E+18
- 5. 2331E+17 Zr-95 2.0926E+03 9.7406E-05 6.1746E+20 5.7357E+17 Zr-97 2.0283E+03 1.0610E-06 6.5870E+18
- 5. 7097E+17 Nb-95 1.9808E+03 5.0657E-05 3.2112E+20
- 5. 4275E+17 Mo-99 2.8450E+04 5.9318E-05 3.6083E+20 7.8497E+18 Tc-99m 2.5050E+04 4.7640E-06 2.8979E+19
- 6. 8208E+18 Ru-103 2.1482E+04 6.6561E-04 3.8916E+21
- 5. 8892E+18 Ru-105 1.0455E+04 1.5554E-06 8.9206E+18
- 3. 1785E+18 Ru-106 4.9104E+03 1.4677E-03 8.3386E+21 1.3456E+18 Rh-105 1.0162E+04 1.2039E-05 6.9048E+19 2..7777E+18 Sb-127 2.6131E+04 9.7849E-05 4.6398E+20 7.1956E+18 Sb-129 6.9232E+04 1.2311E-05 5.7474E+19 2.1109E+19 Te-127 2.5529E+04 9.6735E-06 4.5870E+19
- 6. 9797E+18 Te-127m 3.3898E+03 3.5937E-04 1.7041E+21
- 9. 2878E+17 Te-129 8.1115E+04 3.8733E-06 1.8082E+19 2.2635E+19 Te-129m 2.3208E+04 7.7037E-04 3.5963E+21 6.3602E+18 Te-131m 4.2739E+04 5.3598E-05 2.4639E+20 1.1890E+19 Te-132 4.3506E+05 1.4330E-03 6.5378E+21 1.1991E+20 1-131 2.2577E+06 1.8211E-02 8.3716E+22 7.1124E+20 1-132 2.9660E+06 2.8735E-04 1.3109E+21 9.7936E+20 1-133 4.3701E+06 3.8578E-03 1.7468E+22 1.4089E+21 1-134 1.1190E+06 4.1946E-05 1.8851E+20 6.8866E+20 1-135 3.4993E+06 9.9643E-04 4.4449E+21
- 1. 1928E+21 Xe-133 1.5833E+08 8.4587E-01 3.8300E+24 1.7637E+22
D000040-122, Revision 0 Page 98 of 155 Xe-135 3.5344E+07 1.3840E-02 6.1739E+22 3.8758E+21 Cs-134 2.0502E+05 1.5846E-01 7.1213E+23 6.7937E+19 Cs-136 6.2264E+04 8.4955E-04 3.7619E+21 2.0669E+19 Cs-137 1.1490E+05 1.3209E+00 5.8065E+24 3.8073E+19 Ba-139 9.2256E+04 5.6402E-06 2.4436E+19 3.5757E+19 Ba-140 2.3602E+05 3.2239E-03 1.3868E+22 6.4770E+19 La-140 3.7011E+03 6.6587E-06 2.8643E+19 7.8632E+17 Ce-141 5.3558E+03 1.8797E-04 8.0281E+20 1.4678E+18 Ce-143 5.0321E+03 7.5775E-06 3.1911E+19 1.3980E+18 Ce-144 3.2383E+03 1.0153E-03 4.2460E+21 8.8741E+17 Pr-143 2.0477E+03 3.0409E-05 1.2806E+20 5.6070E+17 Nd-147 9.1274E+02 1.1283E-05 4.6221E+19 2.5054E+17 Np-239 5.9884E+04 2.5813E-04 6.5041E+20 1.6542E+19 Pu-238 3.4825E+00 2.0342E-04 5.1472E+20 9.5427E+14 Pu-239 7.8778E-01 1.2674E-02 3.1935E+22 2.1583E+14 Pu-240 9.9035E-01 4.3462E-03 1.0906E+22 2.7137E+14 Pu-241 1.6681E+02 1.6194E-03 4.0465E+21 4.5711E+16 Am-241 4.4189E-02 1.2875E-05 3.2172E+19 1.2105E+13 Cm-242 1.6879E+01 5.0928E-06 1.2673E+19 4.6257E+15 Cm-244 9.8709E-01 1.2201E-05 3.0113E+19 2.7048E+14 Containment Transport Group Inventory:
Time (h) =
1.8900 Atmosphere Sump Noble gases (atoms) 1.8926E+25 0.0000E+00 Elemental I (atoms) 4.1748E+20 7.5903E+22 Organic I (atoms) 2.3157E+21 0.0000E+00 Aerosols (kg) 1.5907E+00 2.1697E+01 Dose Effective (Ci/cc) 1-131 (Thyroid) 5.9597E-05 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 7.3756E-05 Total I (Ci) 1.4212E+07 Dummy Flow Rate - Containment to Environment Transport Group Inventory:
Time (h) =
1.8900 Pathway Filtered Transported Noble gases (atoms)
Elemental I (atoms)
Organic I (atoms)
Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 4.8478E+10 1.2382E+07 6.5019E+06 1.2458E-14 RBCU Flow Containment to Containment Transport Group Inventory:
Time (h) =
1.8900 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 2.6275E+25 Elemental I (atoms) 0.0000E+00 6.7075E+21 Organic I (atoms) 0.0000E+00 3.5239E+21 Aerosols (kg) 0.0000E+00 6.7511E+00 EAB Doses:
Time (h) =
1.9000 Whole Body Thyroid TEDE Delta dose (rem) 8.2446E-14 3.8560E-12 2.4664E-13 Accumulated dose (rem) 9.8043E-12 9.2156E-10 4.8352E-11 Containment Compartment Nuclide Inventory:
Time (h) =
1.9000 Ci kg Atoms Decay Co-58 1.4465E+02 4.5489E-06 4.7232E+19 4.2157E+16 Co-60 1.1082E+02 9.8037E-05 9.8398E+20 3.2289E+16 Kr-85 8.3006E+05 2.1157E+00 1.4989E+25 9.3411E+19 Kr-85m 2.0272E+07 2.4633E-03 1.7452E+22 2.4784E+21 Kr-87 1.7608E+07 6.2163E-04 4.3029E+21 2.6958E+21 Kr-88 4.2202E+07 3.3656E-03 2.3032E+22 5.4210E+21
DC00040-122, Revision 0 Page 99 of 155 Rb-86 8.4715E+02 1.0411E-05 7.2905E+19 2.9862E+17 Sr-89 1.2886E+05 4.4354E-03 3.0012E+22 3.7559E+19 Sr-90 6.9637E+03 5.1051E-02 3.4160E+23 2.0290E+18 Sr-91 1.4421E+05 3.9783E-05 2.6327E+20 4.4113E+19 Sr-92 1.0661E+05 8.4820E-06 5.5522E+19 3.6959E+19 Y-91 1.5736E+03
- 6. 4166E-05 4.2464E+20 4.5673E+17 Y-92 8.5782E+03 8.9149E-07 5.8355E+18 1.2904E+18 Y-93 1.7233E+03 5.1654E-07 3.3448E+18 5.2561E+17 Zr-95 1.9770E+03 9.2027E-05 5.8337E+20 5.7620E+17 Zr-97 1.9155E+03 1.0020E-06 6.2208E+18 5.7352E+17 Nb-95 1.8715E+03 4.7860E-05 3.0339E+20 5.4524E+17 Mo-99 2.6876E+04 5.6037E-05 3.4087E+20 7.8855E+18 Tc-99m 2.3667E+04 4.5010E-06 2.7379E+19 6.8523E+18 Ru-103 2.0295E+04 6.2885E-04 3.6767E+21 5.9163E+18 Ru-105 9.8625E+03 1.4672E-06 8.4149E+18 3.1916E+18 Ru-106 4.6393E+03 1.3867E-03 7.8781E+21 1.3518E+18 Rh-105 9.6006E+03 1.1374E-05 6.5236E+19 2.7905E+18 Sb-127 2.4686E+04 9.2439E-05 4.3833E+20 7.2285E+18 Sb-129 6.5305E+04 1.1613E-05 5.4213E+19 2.1196E+19 Te-127 2.4119E+04 9.1391E-06 4.3336E+19 7.0118E+18 Te-127m 3.2026E+03 3.3953E-04 1.6100E+21 9.3305E+17 Te-129 7.6565E+04 3.6560E-06 1.7067E+19 2.2737E+19 Te-129m 2.1926E+04 7.2783E-04 3.3977E+21 6.3894E+18 Te-131m 4.0370E+04 5.0626E-05 2.3273E+20 1.1944E+19 Te-132 4.1100E+05 1.3538E-03 6.1763E+21 1.2046E+20 1-131 2.1345E+06 1.7217E-02 7.9149E+22 7.1408E+20 1-132 2.7971E+06 2.7098E-04 1.2363E+21 9.8309E+20 1-133 4.1305E+06 3.6462E-03 1.6510E+22 1.4144E+21 1-134 1.0496E+06 3.9347E-05 1.7683E+20 6.9007E+20 1-135 3.3051E+06
- 9. 4112E-04 4.1982E+21 1.1972E+21 Xe-133 1.5832E+08 8.4583E-01 3.8298E+24 1.7848E+22 Xe-135 3.5319E+07 1.3831E-02 6.1696E+22 3.9228E+21 Cs-134 1.9370E+05 1.4971E-01 6.7281E+23 6.8195E+19 Cs-136 5.8825E+04 8.0262E-04 3.5541E+21 2.0747E+19 Cs-137 1.0855E+05 1.2480E+00 5.4859E+24 3.8218E+19 Ba-139 8.6725E+04 5.3020E-06 2.2971E+19 3.5873E+19 Ba-140 2.2298E+05 3.0458E-03 1.3102E+22 6.5067E+19 La-140 3.5345E+03 6.3590E-06 2.7353E+19 7.9098E+17 Ce-141 5.0601E+03 1.7759E-04 7.5848E+20 1.4746E+18 Ce-143 4.7532E+03 7.1576E-06 3.0143E+19 1.4043E+18 Ce-144 3.0595E+03 9.5924E-04 4.0116E+21 8.9149E+17 Pr-143 1.9347E+03 2.8731E-05 1.2100E+20 5.6328E+17 Nd-147 8.6232E+02 1.0659E-05 4.3668E+19 2.5169E+17 Np-239 5.6570E+04 2.4385E-04 6.1442E+20 1.6617E+19 Pu-238 3.2902E+00 1.9219E-04 4.8630E+20 9.5865E+14 Pu-239 7.4429E-01 1.1974E-02 3.0172E+22 2.1682E+14 Pu-240 9.3566E-01 4.1062E-03 1.0303E+22 2.7262E+14 Pu-241 1.5760E+02 1.5299E-03 3.8230E+21 4.5921E+16 Am-241 4.1749E-02 1.2164E-05 3.0396E+19 1.2161E+13 Cm-242 1.5947E+01 4.8116E-06 1.1973E+19 4.6469E+15 Cm-244 9.3259E-01 1.1527E-05 2.8450E+19 2.7172E+14 Containment Transport Group Inventory:
Time (h) =
1.9000 Atmosphere Sump Noble gases (atoms) 1.8926E+25 0.0000E+00 Elemental I (atoms) 3.4174E+20 7.5979E+22 Organic I (atoms) 2.3153E+21 0.0000E+00 Aerosols (kg) 1.5029E+00 2.1784E+01 Dose Effective (Ci/cc)
I-131.(Thyroid) 5.6339E-05 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 6.9713E-05 Total I (Ci) 1.3417E+07 Dummy Flow Rate - Containment to Environment Transport Group Inventory:
D000040-122, Revision 0 Page 100 of 155 Time (h) =
1.9000 Pathway Filtered Transported Noble gases Elemental I (atoms)
(atoms) 0.0000E+00 0.0000E+00 4.9095E+10 1.2394E+07 Organic I (atoms)
Aerosols (kg) 0.0000E+00 6.5775E+06 0.0000E+00 1.2509E-14 RBCU Flow Containment to Containment Transport Group Inventory:
Time (h) =
1.9000 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 2.6609E+25 Elemental I (atoms) 0.0000E+00 6.7142E+21 Organic I (atoms) 0.0000E+00 3.5649E+21 Aerosols (kg) 0.0000E+00 6.7785E+00 EAB Doses:
Time (h) =
2.0000 Whole Body Thyroid TEDE Delta dose (rem) 7.9270E-13 2.8753E-11 2.0152E-12 Accumulated dose (rem) 1.0597E-11 9.5031E-10 5.0367E-11 Containment Compartment Nuclide Inventory:
Time (h) =
2.0000 Ci kg Atoms Decay Co-58 8.1962E+01 2.5776E-06 2.6763E+19 4.3248E+l6 Co-60 6.2796E+01 5.5553E-05 5.5758E+20 3.3126E+16 Kr-85 8.3006E+05 2.1157E+00 1.4989E+25 1.0447E+20 Kr-85m 1.9961E+07 2.4255E-03 1.7185E+22 2.7464E+21 Kr-87 1.6674E+07 5.8865E-04 4.0747E+21 2.9241E+21 Kr-88 4.1184E+07 3.2844E-03 2.2476E+22 5.9763E+21 Rb-86 4.7997E+02 5.8988E-06 4.1306E+19
- 3. 0502E+17 Sr-89 7.3015E+04 2.5132E-03 1.7006E+22
- 3. 8532E+19 Sr-90 3.9461E+03 2.8929E-02 1.9357E+23 2.0816E+18 Sr-91 8.1126E+04 2.2380E-05 1.4810E+20 4.5197E+19 Sr-92 5.8888E+04 4.6850E-06 3.0667E+19
- 3. 7753E+19 Y-91 8.9334E+02 3.6427E-05 2.4107E+20 4.6860E+17 Y-92 5.9346E+03 6.1675E-07 4.0371E+18 1.3545E+18 Y-93 9.6986E+02 2.9070E-07 1.8824E+18 5.3857E+17 Zr-95 1.1202E+03 5.2145E-05 3.3055E+20 5.9112E+17 Zr-97 1.0810E+03 5.6546E-07 3.5106E+18 5.8795E+17 Nb-95 1.0605E+03 2.7120E-05 1.7192E+20 5.5937E+17 Mo-99
- 1. 5214E+04 3.1721E-05 1.9296E+20 8.0882E+18 Tc-99m 1.3412E+04 2.5506E-06 1.5516E+19 7.0299E+18 Ru-103 1.1500E+04 3.5632E-04 2.0833E+21 6.0695E+18 RU-105 5.5021E+03 8.1852E-07 4.6945E+18 3.2655E+18 Ru-106 2.6289E+03 7.8577E-04 4.4642E+21 1.3868E+18 Rh-105 5.4404E+03 6.4456E-06 3.6968E+19 2.8629E+18 Sb-127 1.3978E+04 5.2342E-05 2.4820E+20 7.4147E+18 Sb-129 3.6416E+04 6.4759E-06 3.0231E+19 2.1685E+19 Te-127 1.3665E+04 5.1777E-06 2.4552E+19 7.1932E+18 Te-127m 1.8148E+03 1.9240E-04 9.1231E+20 9.5722E+17 Te-129 4.3041E+04 2.0552E-06 9.5945E+18 2.3298E+19 Te-129m 1.2424E+04 4.1242E-04 1.9253E+21 6.5549E+18 Te-131m 2.2823E+04 2.8622E-05 1.3158E+20 1.2248E+19 Te-132 2.3269E+05 7.6645E-04 3.4967E+21 1.2356E+20 1-131 1.2271E+06 9.8984E-03 4.5503E+22 7.3043E+20 1-132 1.5679E+06 1.5190E-04 6.9299E+20 1.0042E+21 1-133 2.3676E+06 2.0900E-03 9.4634E+21 1.4460E+21 1-134 5.5777E+05 2.0908E-05 9.3965E+19 6.9780E+20 1-135 1.8810E+06 5.3560E-04 2.3892E+21 1.2224E+21 Xe-133 1.5824E+08 8.4537E-01 3.8278E+24 1.9956E+22 Xe-135 3.5063E+07 1.3730E-02 6.1249E+22 4.3915E+21 Cs-134 1.0976E+05 8.4833E-02 3.8125E+23 6.9657E+19
DC00040-122, Revision 0 Page 101 of 155 Cs-136 3.3326E+04 4.5471E-04 2.0135E+21 2.1191E+19 Cs-137 6.1513E+04 7.0719E-01 3.1086E+24 3.9037E+19 Ba-139 4.6733E+04 2.8571E-06 1.2378E+19 3.6511E+19 Ba-140 1.2633E+05 1.7256E-03 7.4225E+21 6.6750E+19 La-140 2.2169E+03 3.9884E-06 1.7156E+19 8.1764E+17 Ce-141 2.8672E+03 1.0063E-04 4.2977E+20 1.5128E+18 Ce-143 2.6878E+03 4.0474E-06 1.7045E+19 1.4402E+18 Ce-144 1.7337E+03 5.4355E-04 2.2732E+21 9.1458E+17 Pr-143 1.0967E+03 1.6286E-05 6.8584E+19 5.7788E+17 Nd-147 4.8851E+02 6.0386E-06 2.4738E+19 2.5820E+17 Np-239 3.2017E+04 1.3801E-04 3.4774E+20 1.7044E+19 Pu-238 1.8644E+00 1.0891E-04 2.7556E+20 9.8348E+14 Pu-239 4.2177E-01 6.7855E-03 1.7098E+22 2.2244E+14 Pu-240 5.3020E-01 2.3268E-03 5.8385E+21 2.7968E+14 Pu-241 8.9307E+01 8.6695E-04 2.1664E+21 4.7110E+16 Am-241 2.3659E-02 6.8933E-06 1.7225E+19 1.2476E+13 Cm-242 9.0363E+00 2.7265E-06 6.7847E+18 4.7673E+15 Cm-244 5.2846E-01 6.5320E-06 1.6122E+19 2.7876E+14 Containment Transport Group Inventory:
Time (h) =
2.0000 Atmosphere Sump Noble gases (atoms) 1.8922E+25 0.0000E+00 Elemental I (atoms) 4.6172E+19 7.6238E+22 Organic I (atoms) 2.3113E+21 0.0000E+00 Aerosols (kg) 8.5161E-01 2.2434E+01 Dose Effective (Ci/cc) 1-131 (Thyroid) 3.2351E-05 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 3.9969E-05 Total I (Ci) 7.6014E+06 Dummy Flow Rate - Containment to Environment Transport Group Inventory:
Time (h) =
2.0000 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 5.5267E+10 Elemental I (atoms) 0.0000E+00 1.2437E+07 Organic I (atoms) 0.0000E+00 7.3324E+06 Aerosols (kg) 0.0000E+00 1.2882E-14 RBCU Flow Containment to Containment Transport Group Inventory:
Time (h) =
2.0000 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 2.9954E+25 Elemental I (atoms) 0.0000E+00 6.7371E+21 Organic I (atoms) 0.0000E+00 3.9741E+21 Aerosols (kg) 0.0000E+00 6.9806E+00 EAB Doses:
Time (h) =
2.1000 Whole Body Thyroid TEDE Delta dose (rem) 7.3699E-13 1.6604E-11 1.4393E-12 Accumulated dose (rem) 1.1334E-11 9.6691E-10 5.1806E-11 Containment Compartment Nuclide Inventory:
Time (h) =
2.1000 Ci kg Atoms Decay Co-58 4.6442E+01 1.4605E-06 1.5165E+19 4.3867E+16 Co-60 3.5584E+01 3.1480E-05 3.1596E+20 3.3600E+16 Kr-85 8.3006E+05 2.1157E+00 1.4989E+25 1.1552E+20 Kr-85m 1.9654E+07 2.3883E-03 1.6921E+22 3.0102E+21 Kr-87 1.5789E+07 5.5743E-04 3.8585E+21 3.1403E+21 Kr-88 4.0191E+07 3.2052E-03 2.1934E+22 6.5182E+21 Rb-86 2.7193E+02 3.3421E-06 2.3403E+19 3.0864E+17 Sr-89 4.1372E+04 1.4241E-03 9.6358E+21 3.9083E+19
D000040-122, Revision 0 Page 102 of 155 Sr-90 2.2361E+03 1.6393E-02 1.0969E+23 2.1113E+18 Sr-91 4.5636E+04 1.2589E-05
- 8. 3313E+19
- 4. 5807E+19 Sr-92 3.2527E+04 2.5878E-06
- 1. 6939E+19
- 3. 8192E+19 Y-91 5.0714E+02 2.0680E-05 1.3685E+20 4.7535E+17 Y-92 3.9428E+03 4.0975E-07
- 2. 6821E+18 1.3989E+18 Y-93 5.4582E+02 1.6360E-07 1.0594E+18 5.4587E+17 Zr-95 6.3476E+02 2.9547E-05 1.8730E+20 5.9958E+17 Zr-97 6.1004E+02 3.1911E-07 1.9812E+18 5.9609E+17 Nb-95 6.0093E+02 1.5368E-05 9.7418E+19
- 5. 6737E+17 Mo-99 8.6119E+03 1.7956E-05 1.0922E+20 8.2030E+18 Tc-99m 7.6003E+03 1.4454E-06 8.7923E+18 7.1306E+18 Ru-103 6.5159E+03 2.0189E-04 1.1804E+21
- 6. 1563E+18 Ru-105 3.0695E+03 4.5663E-07 2.6190E+18
- 3. 3067E+18 Ru-106 1.4897E+03 4.4526E-04 2.5296E+21 1.4067E+18 Rh-105 3.0829E+03 3.6525E-06 2.0948E+19
- 2. 9039E+18 Sb-127 7.9148E+03 2.9638E-05 1.4054E+20 7.5202E+18 Sb-129 2.0307E+04 3.6112E-06
- 1. 6858E+19 2.1958E+19 Te-127 7.7415E+03 2.9334E-06 1.3910E+19 7.2960E+18 Te-127m 1.0284E+03 1.0902E-04
- 5. 1697E+20
- 9. 7092E+17 Te-129 2.4190E+04 1.1551E-06
- 5. 3924E+18 2.3613E+19 Te-129m 7.0400E+03 2.3369E-04 1.0909E+21
- 6. 6486E+18 Te-131m 1.2903E+04 1.6181E-05 7.4386E+19 1.2420E+19 Te-132 1.3174E+05 4.3393E-04
- 1. 9797E+21 1.2531E+20 1-131 7.1584E+05 5.7741E-03 2.6544E+22 7.3997E+20 1-132 8.9175E+05 8.6392E-05
- 3. 9414E+20 1.0162E+21 1-133 1.3770E+06 1.2155E-03 5.5039E+21 1.4643E+21 1-134 3.0074E+05 1.1273E-05
- 5. 0664E+19 7.0197E+20 1-135 1.0862E+06 3.0929E-04 1.3797E+21 1.2370E+21 Xe-133 1.5815E+08 8.4491E-01 3.8257E+24 2.2063E+22 Xe-135 3.4804E+07 1.3629E-02 6.0796E+22 4.8568E+21 Cs-134 6.2196E+04 4.8071E-02 2.1604E+23 7.0486E+19 Cs-136 1.8880E+04 2.5761E-04 1.1407E+21 2.1443E+19 Cs-137 3.4857E+04 4.0074E-01 1.7615E+24
- 3. 9502E+19 Ba-139 2.5183E+04 1.5396E-06
- 6. 6702E+18
- 3. 6855E+19 Ba-140 7.1568E+04 9.7758E-04 4.2051E+21
- 6. 7703E+19 La-140 1.3772E+03 2.4778E-06 1.0658E+19 8.3435E+17 Ce-141 1.6246E+03 5.7016E-05 2.4352E+20 1.5344E+18 Ce-143 1.5199E+03 2.2887E-06 9.6382E+18 1.4604E+18 Ce-144 9.8238E+02
- 3. 0801E-04 1.2881E+21
- 9. 2767E+17 Pr-143 6.2162E+02 9.2313E-06 3.8876E+19 5.8616E+17 Nd-147 2.7675E+02 3.4209E-06 1.4014E+19 2.6188E+17 Np-239 1.8120E+04 7.8107E-05 1.9681E+20 1.7285E+19 Pu-238 1.0565E+00
- 6. 1712E-05 1.5615E+20
- 9. 9756E+14 Pu-239 2.3900E-01 3.8452E-03
- 9. 6888E+21 2.2562E+14 Pu-240 3.0044E-01 1.3185E-03
- 3. 3084E+21 2.8368E+14 Pu-241 5.0607E+01 4.9127E-04 1.2276E+21 4.7784E+16 Am-241 1.3407E-02 3.9064E-06 9.7614E+18 1.2654E+13 Cm-242 5.1204E+00 1.5449E-06 3.8446E+18 4.8355E+15 Cm-244 2.9945E-01 3.7014E-06
- 9. 1354E+18 2.8275E+14 Containment Transport Group Inventory:
Time (h) =
2.1000 Atmosphere Sump Noble gases (atoms) 1.8919E+25 0.0000E+00 Elemental I (atoms) 6.2382E+18 7.6273E+22 Organic I (atoms) 2.3075E+21 0.0000E+00 Aerosols (kg) 4.8256E-01 2.2802E+01 Dose Effective (Ci/cc) 1-131 (Thyroid) 1.8849E-05 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 2.3253E-05 Total I (Ci) 4.3715E+06 Dummy Flow Rate - Containment to Environment Transport Group Inventory:
Pathway Time (h) =
2.1000 Filtered Transported
DC00040-122, Revision 0 Page 103 of 155 Noble gases (atoms) 0.0000E+00 6.1437E+10 Elemental I (atoms) 0.0000E+00 1.2442E+07 Organic I (atoms) 0.0000E+00 8.0861E+06 Aerosols (kg) 0.0000E+00 1.3093E-14 RBCU Flow Containment to Containment Transport Group Inventory:
Pathway Time (h) =
2.1000 Filtered Transported Noble gases (atoms) 0.0000E+00 3.3299E+25 Elemental I (atoms) 0.0000E+00 6.7402E+21 Organic I (atoms) 0.0000E+00 4.3826E+21 Aerosols (kq) 0.0000E+00 7.0951E+00 EAB Doses:
Time (h) =
2.1100 Whole Body Thyroid TEDE Delta dose (rem) 7.0588E-14 1.2197E-12 1.2194E-13 Accumulated dose (rem) 1.1405E-11 9.6813E-10 5.1928E-11 Containment Compartment Nuclide Inventory:
Time (h) =
2.1100 Ci kg Atoms Decay Co-58 4.3878E+01 1.3799E-06 1.4327E+19 4.3925E+16 Co-60 3.3619E+01 2.9741E-05 2.9851E+20 3.3644E+16 Kr-85 8.3006E+05 2.1157E+00 1.4989E+25 1.1663E+20 Kr-85m 1.9624E+07 2.3846E-03 1.6895E+22 3.0364E+21 Kr-87 1.5704E+07 5.5440E-04 3.8375E+21 3.1612E+21 Kr-88 4.0093E+07 3.1974E-03 2.1881E+22 6.5717E+21 Rb-86 2.5692E+02 3.1575E-06 2.2110E+19 3.0898E+17 Sr-89 3.9087E+04 1.3454E-03 9.1037E+21 3.9135E+19 Sr-90 2.1126E+03 1.5487E-02 1.0363E+23 2.1142E+18 Sr-91 4.3085E+04 1.1886E-05 7.8655E+19 4.5865E+19 Sr-92 3.0652E+04 2.4386E-06 1.5963E+19 3.8233E+19 Y-91 4.7923E+02 1.9541E-05 1.2932E+20 4.7599E+17 Y-92 3.7779E+03 3.9261E-07 2.5700E+18 1.4038E+18 Y-93 5.1533E+02 1.5446E-07 1.0002E+18 5.4655E+17 Zr-95 5.9971E+02 2.7916E-05 1.7696E+20 6.0038E+17 Zr-97 5.7612E+02 3.0137E-07 1.8710E+18 5.9686E+17 Nb-95 5.6775E+02 1.4519E-05 9.2039E+19 5.6813E+17 Mo-99 8.1355E+03 1.6963E-05 1.0318E+20 8.2138E+18 Tc-99m 7.1806E+03 1.3656E-06 8.3068E+18 7.1401E+18 Ru-103 6.1561E+03 1.9074E-04 1.1152E+21 6.1645E+18 Ru-105 2.8955E+03 4.3075E-07 2.4705E+18 3.3105E+18 Ru-106 1.4074E+03 4.2067E-04 2.3900E+21 1.4085E+18 Rh-105 2.9127E+03 3.4508E-06 1.9792E+19 2.9078E+18 Sb-127 7.4772E+03 2.7999E-05 1.3277E+20 7.5302E+18 Sb-129 1.9155E+04 3.4063E-06 1.5902E+19 2.1983E+19 Te-127 7.3139E+03 2.7713E-06 1.3141E+19 7.3057E+18 Te-127m 9.7160E+02 1.0300E-04 4.8843E+20 9.7221E+17 Te-129 2.2832E+04 1.0903E-06 5.0897E+18 2.3644E+19 Te-129m 6.6513E+03 2.2079E-04 1.0307E+21 6.6575E+18 Te-131m 1.2188E+04 1.5284E-05 7.0262E+19 1.2437E+19 Te-132 1.2445E+05 4.0994E-04 1.8702E+21 1.2548E+20 1-131 6.7896E+05 5.4766E-03 2.5176E+22 7.4087E+20 1-132 8.4368E+05 8.1734E-05 3.7289E+20 1.0173E+21 1-133 1.3057E+06 1.1526E-03 5.2188E+21 1.4661E+21 1-134 2.8301E+05 1.0609E-05 4.7677E+19 7.0235E+20 1-135 1.0292E+06 2.9306E-04 1.3073E+21 1.2383E+21 Xe-133 1.5814E+08 8.4486E-01 3.8255E+24 2.2274E+22 Xe-135 3.4778E+07 1.3619E-02 6.0751E+22 4.9031E+21 Cs-134 5.8761E+04 4.5417E-02 2.0411E+23 7.0564E+19 Cs-136 1.7838E+04 2.4338E-04 1.0777E+21 2.1466E+19 Cs-137 3.2932E+04 3.7861E-01 1.6643E+24 3.9545E+19
DC00040-122, Revision 0 Page 104 of 155 Ba-139 2.3673E+04 1.4473E-06 6.2703E+18 3.6887E+19 Ba-140 6.7614E+04 9.2358E-04 3.9728E+21 6.7793E+19 La-140 1.3126E+03 2.3615E-06 1.0158E+19 8.3609E+17 Ce-141 1.5349E+03 5.3868E-05 2.3007E+20 1.5365E+18 Ce-143 1.4356E+03 2.1618E-06 9.1041E+18 1.4624E+18 Ce-144 9.2814E+02 2.9100E-04 1.2170E+21 9.2890E+17 Pr-143 5.8732E+02 8.7219E-06 3.6730E+19 5.8694E+17 Nd-147 2.6146E+02 3.2319E-06 1.3240E+19 2.6223E+17 Np-239 1.7118E+04 7.3785E-05 1.8592E+20 1.7308E+19 Pu-238 9.9815E-01 5.8304E-05 1.4753E+20 9.9889E+14 Pu-239 2.2581E-01 3.6329E-03 9.1538E+21 2.2592E+14 Pu-240 2.8385E-01 1.2457E-03 3.1257E+21 2.8406E+14 Pu-241 4.7812E+01 4.6414E-04 1.1598E+21 4.7848E+16 Am-241 1.2667E-02 3.6907E-06 9.2225E+18 1.2671E+13 Cm-242 4.8376E+00 1.4596E-06 3.6323E+18 4.8419E+15 Cm-244 2.8292E-01 3.4970E-06 8.6310E+18 2.8313E+14 Containment Transport Group Inventory:
Time (h) =
2.1100 Atmosphere Sump Noble gases (atoms) 1.8918E+25 0.0000E+00 Elemental I (atoms) 5.1066E+18 7.6274E+22 Organic I (atoms) 2.3071E+21 0.0000E+00 Aerosols (kg) 4.5591E-01 2.2829E+01 Dose Effective (Ci/cc) 1-131 (Thyroid) 1.7876E-05 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 2.2049E-05 Total I (Ci) 4.1405E+06 Dummy Flow Rate - Containment to Environment Transport Group Inventory:
Time (h) =
2.1100 Pathway Filtered Transported Noble gases (atoms)
Elemental I (atoms)
Organic I (atoms)
Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 6.2054E+10 1.2442E+07 8.1614E+06 1.3108E-14 RBCU Flow Containment to Containment Transport Group Inventory:
Time (h) =
2.1100 Pathway Filtered Transported Noble gases (atoms)
O.0000E+00 3.3633E+25 Elemental I (atoms) 0.0000E+00 6.7403E+21 Organic I (atoms) 0.0000E+00 4.4234E+21 Aerosols (kg) 0.0000E+00 7.1034E+00 EAB Doses:
Time (h) =
2.1200 Whole Body Thyroid TEDE Delta dose (rem) 7.0229E-14 1.1567E-12 1.1888E-13 Accumulated dose (rem) 1.1475E-11 9.6929E-10 5.2047E-11 Containment Compartment Nuclide Inventory:
Time (h) =
2.1200 Ci kg Atoms Decay Co-58 4.1455E+01 1.3037E-06 1.3536E+19 4.3981E+16 Co-60 3.1763E+01 2.8099E-05 2.8203E+20 3.3687E+16 Kr-85 8.3006E+05 2.1157E+00 1.4989E+25 1.1773E+20 Kr-85m 1.9594E+07 2.3809E-03 1.6868E+22 3.0625E+21 Kr-87 1.5618E+07 5.5138E-04 3.8167E+21 3.1821E+21 Kr-88 3.9995E+07 3.1896E-03 2.1828E+22 6.6250E+21 Rb-86 2.4273E+02 2.9831E-06 2.0889E+19 3.0930E+17 Sr-89 3.6929E+04 1.2711E-03 8.6009E+21 3.9184E+19 Sr-90 1.9959E+03 1.4632E-02 9.7908E+22 2.1168E+18 Sr-91 4.0676E+04 1.1221E-05 7.4258E+19 4.5919E+19
D000040-122, Revision 0 Page 105 of 155 Sr-92 2.8886E+04 2.2981E-06 1.5043E+19 3.8271E+19 Y-91 4.5285E+02 1.8466E-05 1.2220E+20 4.7659E+17 Y-92 3.6189E+03 3.7609E-07 2.4618E+18 1.4086E+18 Y-93 4.8654E+02 1.4583E-07 9.4432E+17 5.4720E+17 Zr-95 5.6659E+02 2.6374E-05 1.6719E+20 6.0113E+17 Zr-97 5.4408E+02 2.8461E-07 1.7670E+18 5.9758E+17 Nb-95 5.3640E+02 1.3718E-05 8.6957E+19 5.6884E+17 Mo-99 7.6855E+03 1.6024E-05 9.7475E+19 8.2241E+18 Tc-99m 6.7841E+03 1.2902E-06 7.8481E+18 7.1492E+18 Ru-103 5.8161E+03 1.8021E-04 1.0536E+21 6.1722E+18 Ru-105 2.7313E+03 4.0633E-07 2.3304E+18 3.3142E+18 Ru-106 1.3297E+03 3.9744E-04 2.2580E+21 1.4103E+18 Rh-105 2.7518E+03 3.2603E-06 1.8699E+19 2.9115E+18 Sb-127 7.0638E+03 2.6451E-05 1.2543E+20 7.5396E+18 Sb-129 1.8068E+04 3.2131E-06 1.5000E+19 2.2007E+19 Te-127 6.9099E+03 2.6183E-06 1.2415E+19 7.3149E+18 Te-127m 9.1795E+02 9.7317E-05 4.6146E+20 9.7344E+17 Te-129 2.1551E+04 1.0291E-06 4.8040E+18 2.3672E+19 Te-129m 6.2840E+03 2.0860E-04 9.7379E+20 6.6659E+18 Te-131m 1.1512E+04 1.4437E-05 6.6367E+19 1.2452E+19 Te-132 1.1757E+05 3.8727E-04 1.7668E+21 1.2563E+20 1-131 6.4413E+05
- 5. 1957E-03 2.3885E+22 7.4173E+20 1-132 7.9836E+05 7.7345E-05 3.5286E+20 1.0184E+21 1-133 1.2383E+06 1.0931E-03 4.9496E+21 1.4677E+21 1-134 2.6638E+05 9.9856E-06 4.4877E+19 7.0270E+20 1-135 9.7538E+05 2.7774E-04 1.2390E+21 1.2396E+21 Xe-133 1.5813E+08
- 8. 4481E-01 3.8252E+24 2.2485E+22 Xe-135 3.4752E+07 1.3608E-02 6.0705E+22 4.9494E+21 Cs-134 5.5517E+04 4.2909E-02 1.9284E+23 7.0638E+19 Cs-136 1.6852E+04 2.2994E-04 1.0182E+21 2.1489E+19 Cs-137 3.1114E+04 3.5770E-01 1.5724E+24 3.9587E+19 Ba-139 2.2254E+04 1.3605E-06 5.8943E+18 3.6916E+19 Ba-140 6.3879E+04 8.7256E-04 3.7534E+21 6.7879E+19 La-140 1.2509E+03 2.2505E-06 9.6807E+18 8.3774E+17 Ce-141 1.4501E+03 5.0893E-05 2.1737E+20 1.5384E+18 Ce-143 1.3561E+03 2.0420E-06 8.5996E+18 1.4642E+18 Ce-144 8.7689E+02 2.7493E-04 1.1498E+21 9.3007E+17 Pr-143 5.5491E+02 8.2405E-06 3.4703E+19 5.8768E+17 Nd-147 2.4701E+02 3.0534E-06 1.2509E+19 2.6256E+17 Np-239 1.6170E+04 6.9703E-05 1.7563E+20 1.7330E+19 Pu-238 9.4304E-01 5.5085E-05 1.3938E+20 1.0001E+15 Pu-239 2.1334E-01 3.4323E-03 8.6484E+21 2.2621E+14 Pu-240 2.6818E-01 1.1769E-03 2.9531E+21 2.8442E+14 Pu-241 4.5172E+01 4.3851E-04 1.0958E+21 4.7908E+16 Am-241 1.1968E-02 3.4870E-06 8.7133E+18 1.2687E+13 Cm-242 4.5705E+00 1.3790E-06 3.4317E+18 4.8480E+15 Cm-244 2.6730E-01 3.3039E-06 8.1544E+18 2.8349E+14 Containment Transport Group Inventory:
Time (h) =
2.1200 Atmosphere Sump Noble gases (atoms) 1.8918E+25 0.0000E+00 Elemental I (atoms) 4.1802E+18 7.6275E+22 Organic I (atoms) 2.3067E+21 0.0000E+00 Aerosols (kg) 4.3074E-01 2.2854E+01 Dose Effective (Ci/cc) 1-131 (Thyroid) 1.6957E-05 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 2.0912E-05 Total I (Ci) 3.9226E+06 Dummy Flow Rate - Containment to Environment Transport Group Inventory:
Time (h) =
2.1200 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 6.2671E+10 Elemental I (atoms) 0.0000E+00 1.2443E+07
DC0004O-122, Revision 0 Page 106 of 155 Organic I (atoms)
Aerosols (kg) 0.0000E+00 8.2366E+06 0.0000E+00 1.3123E-14 RBCU Flow Containment to Containment Transport Group Inventory:
Time (h) =
2.1200 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 3.3967E+25 Elemental I (atoms) 0.0000E+00 6.7404E+21 Organic I (atoms) 0.0000E+00 4.4641E+21 Aerosols (kg) 0.0000E+00 7.1112E+00 EAB Doses:
Time (h) =
8.0000 Whole Body Thyroid TEDE Delta dose (rem) 2.1879E-11 6.4913E-11 2.4119E-11 Accumulated dose (rem) 3.3354E-11 1.0342E-09 7.6166E-11 Containment Compartment Nuclide Inventory:
Time (h) =
8.0000 Ci kg Atoms Decay Co-58 1.2936E-13 4.0681E-21 4.2239E+04 4.4703E+16 Co-60 9.9343E-14 8.7885E-20 8.8209E+05 3.4240E+16 Kr-85 8.3014E+05 2.1159E+00 1.4991E+25 7.6789E+20 Kr-85m 7.8889E+06 9.5861E-04 6.7916E+21 1.3139E+22 Kr-87 6.3345E+05 2.2363E-05 1.5480E+20 6.8440E+21 Kr-88 9.5225E+06 7.5942E-04 5.1969E+21 2.3256E+22 Rb-86 7.5235E-13 9.2464E-21 6.4747E+04 3.1353E+17 Sr-89 1.1512E-10 3.9626E-18 2.6813E+07 3.9827E+19 Sr-90 6.2431E-12 4.5768E-17 3.0625E+08 2.1516E+18 Sr-91 8.2847E-11 2.2854E-20 1.5124E+05 4.6618E+19 Sr-92 2.0081E-11 1.5976E-21 1.0458E+04 3.8752E+19 Y-91 1.5383E-12 6.2727E-20 4.1511E+05 4.8449E+17 Y-92 3.1573E-11 3.2812E-21 2.1478E+04 1.4813E+18 Zr-95 1.7676E-12 8.2278E-20 5.2156E+05.
6.1100E+17 Nb-95 1.6782E-12 4.2917E-20 2.7205E+05 5.7819E+17 Mo-99 2.2600E-11 4.7121E-20 2.8664E+05 8.3577E+18 Tc-99m 2.0896E-11 3.9740E-21 2.4174E+04 7.2667E+18 Ru-103 1.8114E-11 5.6126E-19 3.2815E+06 6.2735E+18 Ru-106 4.1572E-12 1.2426E-18 7.0596E+06 1.4335E+18 Rh-105 8.2744E-12 9.8032E-21 5.6225E+04 2.9594E+18 Sb-127 2.1142E-11 7.9167E-20 3.7540E+05 7.6625E+18 Sb-129 2.2001E-11 3.9124E-21 1.8264E+04 2.2313E+19 Te-127 2.1251E-11 8.0523E-21 3.8183E+04 7.4348E+18 Te-127m 2.8729E-12 3.0457E-19 1.4442E+06 9.8942E+17 Te-129m 1.9597E-11 6.5053E-19 3.0369E+06 6.7753E+18 Te-131m 3.1435E-11 3.9421E-20 1.8122E+05 1.2652E+19 Te-132 3.4908E-10 1.1498E-18 5.2458E+06 1.2768E+20 1-131 4.7744E+04 3.8511E-04 1.7704E+21 7.8988E+20 1-132 1.0498E+04 1.0170E-06 4.6398E+18 1.0532E+21 1-133 7.7061E+04 6.8027E-05 3.0802E+20 1.5542E+21 1-134 1.9299E+02 7.2345E-09 3.2513E+16 7.0982E+20 1-135 3.9856E+04 1.1349E-05 5.0626E+19 1.2982E+21 Xe-133 1.5310E+08 8.1792E-01 3.7035E+24 1.4436E+23 Xe-135 2.2217E+07 8.6997E-03 3.8808E+22 2.6897E+22 Cs-134 1.7361E-10 1.3419E-16 6.0305E+08 7.1605E+19 Cs-136 5.2034E-11 7.0996E-19 3.1437E+06 2.1782E+19 Cs-137 9.7320E-11 1.1189E-15 4.9182E+09 4.0129E+19 Ba-140 1.9716E-10 2.6932E-18 1.1585E+07 6.8991E+19 La-140 2.2655E-11 4.0759E-20 1.7533E+05 8.6195E+17 Ce-141 4.5164E-12 1.5851E-19 6.7699E+05 1.5636E+18 Ce-143 3.7489E-12
- 5. 6453E-21 2.3774E+04 1.4877E+18 Ce-144 2.7412E-12
- 8. 5945E-19 3.5943E+06 9.4535E+17 Pr-143 1.7638E-12 2.6192E-20 1.1030E+05 5.9735E+17
DC0004O-122, Revision 0 Page 107 of 155 Nd-147 7.6079E-13 9.4042E-21 3.8526E+04 2.6686E+17 Np-239 4.7061E-11 2.0286E-19 5.1114E+05 1.7611E+19 Pu-238 2.9498E-15 1.7231E-19 4.3599E+05 1.0166E+15 Pu-239 6.6825E-16 1.0751E-17 2.7090E+07 2.2992E+14 Pu-240 8.3885E-16 3.6813E-18 9.2372E+06 2.8909E+14 Pu-241 1.4129E-13 1.3716E-18 3.4273E+06 4.8695E+16 Am-241 3.7587E-17 1.0951E-20 2.7365E+04 1.2896E+13 Cm-242 1.4281E-14 4.3090E-21 1.0723E+04 4.9276E+15 Cm-244 8.3607E-16 1.0334E-20 2.5506E+04 2.8814E+14 Containment Transport Group Inventory:
Time (h) =
8.0000 Atmosphere Sump Noble gases (atoms) 1.8745E+25 0.0000E+00 Elemental I (atoms) 3.2680E-33 7.6278E+22 Organic I (atoms) 2.1337E+21 0.0000E+00 Aerosols (kg) 1.3457E-15 2.3283E+01 Dose Effective (Ci/cc) 1-131 (Thyroid) 1.1859E-06 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 1.3826E-06 Total I (Ci) 1.7535E+05 Dummy Flow Rate - Containment to Environment Transport Group, Inventory:
Time (h) =
8.0000 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 4.2369E+ll Elemental I (atoms) 0.0000E+00 1.2443E+07 Organic I (atoms) 0.0000E+00 5.0695E+07 Aerosols (kg) 0.0000E+00 1.3369E-14 RBCU Flow Containment to Containment Transport Group Inventory:
Time (h) =
8.0000 Pathway Filtered Transported Noble gases (atoms) 0.0000E+00 2.2964E+26 Elemental I (atoms) 0.0000E+00 6.7407E+21 Organic I (atoms) 0.0000E+00 2.7477E+22 Aerosols (kg) 0.0000E+00 7.2449E+00 EAB Doses:
Time (h) =
24.0000 Whole Body Thyroid TEDE Delta dose (rem) 1.2948E-11 5.7937E-11 1.4738E-11 Accumulated dose (rem) 4.6301E-11 1.0921E-09 9.0904E-11 Containment Compartment Nuclide Inventory:
Time (h) =
24.0000 Ci kg Atoms Decay Kr-85 8.3012E+05 2.1158E+00 1.4990E+25 2.5371E+21 Kr-85m 6.6360E+05 8.0637E-05 5.7130E+20 1.9360E+22 Kr-87 1.0332E+02 3.6476E-09 2.5248E+16 6.9987E+21 Kr-88 1.9178E+05 1.5295E-05 1.0467E+20 2.8348E+22 1-131 4.5077E+04 3.6360E-04 1.6715E+21 8.8877E+20 1-132 8.4522E+01 8.1884E-09 3.7358E+16 1.0578E+21 1-133 4.5214E+04 3.9913E-05 1.8072E+20 1.6815E+21 1-134 6.1866E-04 2.3191E-14 1.0422E+ll 7.0985E+20 1-135 7.4444E+03 2.1198E-06 9.4561E+18 1.3394E+21 Xe-133 1.4019E+08 7.4897E-01 3.3913E+24 4.5669E+23 Xe-135 6.5687E+06 2.5722E-03 1.1474E+22 5.4265E+22 Containment Transport Group Inventory:
Time (h) =
24.0000 Atmosphere Sump Noble gases (atoms) 1.8394E+25 0.0000E+00 Elemental I (atoms) 3.0244-172 7.6278E+22 Organic I (atoms) 1.8617E+21 0.0000E+00
DC0004O-122, Revision 0 Page 108 of 155 Aerosols (kg) 4.5631E-55 2.3283E+01 Dose Effective (Ci/cc) 1-131 (Thyroid) 1.0137E-06 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 1.1091E-06 Total I (Ci) 9.7820E+04 Dummy Flow Rate - Containment to Environment Transport Group Inventory:
Pathway Time (h) = 24.0000 Filtered Transported Noble gases (atoms) 0.0000E+00 1.3926E+12 Elemental I (atoms) 0.0000E+00 1.2443E+07 Organic I (atoms) 0.0000E+00 1.5454E+08 Aerosols (kg) 0.0000E+00 1.3369E-14 RBCU Flow Containment to Containment Transport Group Inventory:
Pathway Time (h) = 24.0000 Filtered Transported Noble gases (atoms) 0.0000E+00 7.5477E+26 Elemental I (atoms) 0.0000E+00 6.7407E+21 Organic I (atoms) 0.0000E+00 8.3761E+22 Aerosols (kg) 0.0000E+00 7.2449E+00 EAB Doses:
Time (h) = 720.0000 Whole Body Thyroid TEDE Delta dose (rem) 4.8843E-11 9.5382E-10 7.7922E-11 Accumulated dose (rem) 9.5144E-11 2.0460E-09 1.6883E-10 Containment Compartment Nuclide Inventory:
Time (h) = 720.0000 Ci kg Atoms Decay Kr-85 8.2587E+05 2.1050E+00 1.4914E+25 7.9298E+22 1-131 3.6996E+03 2.9841E-05 1.3718E+20 2.4231E+21 1-133 3.8225E-06 3.3744E-15 1.5279E+10 1.8622E+21 Xe-133 3.0362E+06 1.6221E-02 7.3446E+22 3.7747E+24 Containment Transport Group Inventory:
Time (h) = 720.0000 Atmosphere Sump Noble gases (atoms) 1.4987E+25 0.0000E+00 Elemental I (atoms) 0.0000E+00 7.6278E+22 Organic I (atoms) 1.3718E+20 0.0000E+00 Aerosols (kg) 0.0000E+00 2.3283E+01 Dose Effective (Ci/cc) 1-131 (Thyroid) 7.1005E-08 Dose Effective (Ci/cc) 1-131 (ICRP2 Thyroid) 7.1005E-08 Total I (Ci) 3.6996E+03 Dummy Flow Rate - Containment to Environment Transport Group Inventory:
Pathway Time (h) = 720.0000 Filtered Transported Noble gases (atoms) 0.0000E+00 3.7298E+13 Elemental I (atoms) 0.0000E+00 1.2443E+07 Organic I (atoms) 0.0000E+00 1.5681E+09 Aerosols (kg) 0.0000E+00 1.3369E-14 RBCU Flow Containment to Containment Transport Group Inventory:
Pathway Time (h) = 720.0000 Filtered Transported Noble gases (atoms) 0.0000E+00 2.0216E+28 Elemental I (atoms) 0.0000E+00 6.7407E+21 Organic I (atoms) 0.0000E+00 8.4992E+23 Aerosols (kg) 0.0000E+00 7.2449E+00
D000040-122, Revision 0 Page 109 of 155 845 1-131 Summary Time (hr)
Containment 1-131 (Curies)
Environment 1-131 (Curies) 0.000 4.5555E+03 4.1264E-15 0.014 1.1807E+05 2.7722E-12 0.414 1.2648E+06 1.1691E-09 0.500 1.3154E+06 1.5297E-09 0.800 3.3164E+06 4.0661E-09 1.100 3.6792E+06 7.5346E-09 1.400 3.7502E+06 1.1176E-08 1.700 3.7682E+06 1.4855E-08 1.800 3.7714E+06 1.6084E-08 2.100 7.1584E+05 1.7863E-08 2.420 1.5691E+05 1.8234E-08 2.720 6.8324E+04 1.8332E-08 3.020 5.2180E+04 1.8389E-08 3.320 4.9203E+04 1.8438E-08 3.620 4.8619E+04 1.8486E-08 3.920 4.8470E+04 1.8534E-08 4.220 4.8400E+04 1.8581E-08 4.520 4.8345E+04 1.8628E-08 4.820 4.8292E+04 1.8676E-08 5.120 4.8240E+04 1.8723E-08 5.420 4.8188E+04 1.8770E-08 5.720 4.8136E+04 1.8817E-08 6.020 4.8084E+04 1.8864E-08 6.320 4.8033E+04 1.8911E-08 6.620 4.7981E+04 1.8958E-08 6.920 4.7929E+04 1.9005E-08 7.220 4.7878E+04 1.9052E-08 7.520 4.7826E+04 1.9099E-08 7.820 4.7775E+04 1.9145E-08 8.000 4.7744E+04 1.9173E-08 8.300 4.7692E+04 1.9220E-08 8.600 4.7641E+04 1.9267E-08 8.900 4.7590E+04 1.9313E-08 9.200 4.7538E+04 1.9360E-08 9.500 4.7487E+04 1.9406E-08 9.800 4.7436E+04 1.9453E-08 10.100 4.7385E+04 1.9499E-08 10.400 4.7334E+04 1.9545E-08 24.000 4.5077E+04 2.1591E-08 720.000 3.6996E+03 5.9085E-08 Cumulative Dose Summary EAB Time (hr)
Thyroid (rem)
TEDE (rem) 0.000 0.0000E+00 0.0000E+00 0.014 1.4813E-13 6.2909E-15 0.414 6.2338E-11 2.6788E-12 0.500 8.1515E-11 3.5090E-12 0.800 2.1916E-10 1.0199E-11 1.100 4.0796E-10 1.9936E-11 1.400 6.0567E-10 3.0544E-11
D000040-122, Revision 0 Page 110 of 155 1.700 8.0473E-10 4.1580E-11 1.800 8.7109E-10 4.5330E-11 2.100 9.6691E-10 5.1806E-11 2.420 9.8678E-10 5.4770E-11 2.720 9.9196E-10 5.6789E-11 3.020 9.9490E-10 5.8577E-11 3.320 9.9742E-10 6.0228E-11 3.620 9.9987E-10 6.1767E-11 3.920 1.0023E-09 6.3208E-11 4.220 1.0047E-09 6.4557E-11 4.520 1.0071E-09 6.5822E-11 4.820 1.0095E-09 6.7011E-11 5.120 1.0118E-09 6.8129E-11 5.420 1.0142E-09 6.9181E-11 5.720 1.0166E-09 7.0174E-11 6.020 1.0189E-09 7.1111E-11 6.320 1.0213E-09 7.1996E-11 6.620 1.0236E-09 7.2834E-11 6.920 1.0259E-09 7.3627E-11 7.220 1.0282E-09 7.4380E-11 7.520 1.0305E-09 7.5095E-11 7.820 1.0328E-09 7.5774E-11 8.000 1.0342E-09 7.6166E-11 8.300 1.0354E-09 7.6760E-11 8.600 1.0365E-09 7.7324E-11 8.900 1.0377E-09 7.7862E-11 9.200 1.0389E-09 7.8375E-11 9.500 1.0400E-09 7.8864E-11 9.800 1.0412E-09 7.9331E-11 10.100 1.0423E-09 7.9778E-11 10.400 1.0435E-09 8.0205E-11 24.000 1.0921E-09 9.0904E-11 720.000 2.0460E-09 1.6883E-10 Worst Two-Hour Doses EAB Time Whole Body Thyroid TEDE (hr)
(rem)
(rem)
(rem) 0.0 0.0000E+00 0.0000E+00 0.0000E+00
D000040-122, Revision 0 Page 111 of 155 RADTRAD Input/Output File:
Containment Release - TSC
D000040-122, Revision 0 Page 112 of 155 RADTRAD Version 3.03 (Spring 2001) run on 11/03/2011 at 13:16:04 File information Plant file
= C:\\Program Files\\radtrad3 03\\VCS TSC\\Cont.
Release\\Containment Release - TSC.psf Inventory file
= c:\\program files\\radtrad3 03\\vcs tsc\\cont.
release\\cont.nif Release file
= c:\\program files\\radtrad3 03\\vcs tsc\\cont.
release\\pwr dba.rft Dose Conversion file = c:\\program files\\radtrad3 03\\vcs tsc\\cont.
release\\fgrll&12.inp Radtrad 3.03 4/15/2001 Containment Release Nuclide Inventory File:
c:\\program files\\radtrad3 03\\vcs tsc\\cont. release\\cont.nif Plant Power Level:
1.0000E+00 Compartments:
3 Compartment 1:
Containment 3
1.8400E+06 1
0 0
1 0
Compartment 2:
Environment 2
0.0000E+00 0
0 0
0 0
Compartment 3:
TSC 1
2.0700E+05 0
0
DC00040-122, Revision 0 Page 113 of 155 0
0 0
Pathways:
5 Pathway 1:
Containment Leakage to Environment 1
2 4
Pathway 2:
Environment to TSC Makeup Flow Rate 2
3 2
Pathway 3:
Environment to TSC - Unfiltered Inleakage 2
3 2
Pathway 4:
TSC to Environment - Unfiltere Exhaust 3
2 2
Pathway 5:
RBCU Filters Containment to Containment 1
1 2
End of Plant Model File Scenario Description Name:
Plant Model Filename:
Source Term:
1 1
1.0000E+00 c:\\program files\\radtrad3 03\\vcs tsc\\cont. release\\fgrll&12.inp c:\\program files\\radtrad3 03\\vcs tsc\\cont. release\\pwr_dba.rft 0.0000E+00 1
9.5000E-01 4.8500E-02 1.5000E-03 1.0000E+00 Overlying Pool:
0 0.0000E+00 0
0 0
0 Compartments:
3 Compartment 1:
0 1
1 0.0000E+00 5
0.0000E+00 0.0000E+00 1.4400E-02 5.6800E+00 1.8900E+00 5.6800E+00 2.1000E+00 5.6800E-01 4.0000E+00 0.0000E+00 1
D000040-122, Revision 0 Page 114 of 155 0.0000E+00 5
0.0000E+00 0.0000E+00 1.4400E-02 2.0000E+01 1.8900E+00 0.0000E+00 2.1000E+00 0.0000E+00 4.0000E+00 0.0000E+00 1
0.0000E+00 0
0 0
1 4
0.0000E+00 1.0000E-01 1.4400E-02 0.0000E+00 4.0000E+00 1.0000E-01 7.2000E+02 0.0000E+00 0
Compartment 2:
0 1
0 0
0 0
0 0
0 Compartment 3:
0 1
0 0
0 0
0 0
0 Pathways:
5 Pathway 1:
0 0
0 0
0 0
0 0
0 0
1 3
0.0000E+00 2.0000E-01 2.4000E+01 1.0000E-01 7.2000E+02 0.0000E+00 0
Pathway 2:
0 0
0 0
0
D000040-122, Revision 0 Page 115 of 155 1
2 0.0000E+00 1.2000E+04 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0
0 0
0 0
0 Pathway 3:
0 0
0 0
0 1
2 0.0000E+00 1.0000E+03 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0
0 0
0 0
0 Pathway 4:
0 0
0 0
0 1
2 0.0000E+00 1.3000E+04 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0
0 0
0 0
0 Pathway 5:
0 0
0 0
0 1
3 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 1.4400E-02 5.4200E+04 9.0000E+01 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0
0 0
0 0
0 Dose Locations:
3 Location 1:
EAB 2
DC00040-122, Revision 0 Page 116 of 155 1
2 0.0000E+00 1.2400E-04 7.2000E+02 0.0000E+00 1
4 0.0000E+00 3.5000E-04 8.0000E+00 1.8000E-04 2.4000E+01 2.3000E-04 7.2000E+02 0.0000E+00 0
Location 2:
LPZ 2
1 5
0.0000E+00 2.4200E-05 8.0000E+00 1.6800E-05 2.4000E+01 7.5500E-06 9.6000E+01 2.4000E-06 7.2000E+02 0.0000E+00 1
4 0.0000E+00 3.5000E-04 8.0000E+00 1.8000E-04 2.4000E+01 2.3000E-04 7.2000E+02 0.0000E+00 0
Location 3:
TSC 3
0 1
2 0.0000E+00 3.5000E-04 7.2000E+02 0.0000E+00 1
4 0.0000E+00 1.0000E+00 2.4000E+01 6.0000E-01 9.6000E+01 4.0000E-01 7.2000E+02 0.0000E+00 Effective Volume Location:
1 6
0.0000E+00 3.9000E-05 2.0000E+00 3.3000E-05 8.0000E+00 1.6000E-05 2.4000E+01 1.2000E-05 9.6000E+01 8.7000E-06 7.2000E+02 0.0000E+00 Simulation Parameters:
1 0.0000E+00 0.0000E+00 Output Filename:
C:\\Program Files\\radtrad3 03\\VCS TSC\\Containment Release - TSC.oO 1
1 1
0 0
End of Scenario File
D000040-122, Revision 0 Page 117 of 155 RADTRAD Version 3.03 (Spring 2001) run on 11/03/2011 at 13:16:04 Plant Description Number of Nuclides = 60 Inventory Power =
1.0000E+00 MWth Plant Power Level =
1.0000E+00 MWth Number of compartments
=
3 Compartment information Compartment number 1 (Source term fraction =
1.0000E+00 Name: Containment Compartment volume =
1.8400E+06 (Cubic feet)
Compartment type is Normal Removal devices within compartment:
Spray(s)
Deposition Pathways into and out of compartment 1
Inlet Pathway Number 5: RBCU Filters Containment to Containment Exit Pathway Number 1:
Containment Leakage to Environment Exit Pathway Number 5:
RBCU Filters Containment to Containment Compartment number 2 Name: Environment Compartment type is Environment Pathways into and out of compartment 2 Inlet Pathway Number 1:
Containment Leakage to Environment Inlet Pathway Number 4:
TSC to Environment - Unfiltere Exhaust Exit Pathway Number 2:
Environment to TSC Makeup Flow Rate Exit Pathway Number 3: Environment to TSC - Unfiltered Inleakage Compartment number 3 Name: TSC Compartment volume =
2.0700E+05 Compartment type is Control Room (Cubic feet)
Pathways into and out of compartment 3 Inlet Pathway Number 2:
Environment to TSC Makeup Flow Rate Inlet Pathway Number 3: Environment to TSC - Unfiltered Inleakage Exit Pathway Number 4:
TSC to Environment - Unfiltere Exhaust Total number of pathways =
5
D000040-122,' Revision 0 Page 118 of 155 RADTRAD Version 3.03 (Spring 2001) run on 11/03/2011 at 13:16:04 Scenario Description Radioactive Decay is enabled Calculation of Daughters is enabled Release Fractions and Timings GAP EARLY IN-VESSEL LATE RELEASE RELEASE MASS 0.500000 hr 1.3000 hrs 0.0000 hrs (gm)
NOBLES IODINE CESIUM TELLURIUM STRONTIUM BARIUM RUTHENIUM CERIUM LANTHANUM 5.0000E-02 5.0000E-02 5.0000E-02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 9.5000E-01 3.5000E-01 2.5000E-01 5.0000E-02 2.0000E-02 2.0000E-02 2.5000E-03 5.0000E-04 2.0000E-04 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 3.049E+03 3.488E+02 2.188E+04 3.416E+01 7.243E+02 4.007E+01 2.861E+01 2.502E+02 3.628E+00 Inventory Power =
1.
MWt Nuclide Group Specific half Whole Body Inhaled Inhaled Name Inventory (Ci/MWt) life (s)
DCF (Sv-m3/Bq-s)
Thyroid (Sv/Bq)
Effective (Sv/Bq)
Co-58 7
7.550E+05 6.117E+06 4.760E-14 8.720E-10 2.940E-09 Co-60 7
5.780E+05 1.663E+08 1.260E-13 1.620E-08 5.910E-08 Kr-85 1
8.300E+05 3.383E+08 1.190E-16 0.000E+00 0.000E+00 Kr-85m 1
2.720E+07 1.613E+04 7.480E-15 0.000E+00 0.000E+00 Kr-87 1
4.960E+07 4.578E+03 4.120E-14 0.000E+00 0.000E+00 Kr-88 1
6.710E+07 1.022E+04 1.020E-13 0.000E+00 0.000E+00 Rb-86 3
4.430E+04 1.612E+06 4.810E-15 1.330E-09 1.790E-09 Sr-89 5
8.410E+07 4.363E+06 7.730E-17 7.960E-12 1.120E-08 Sr-90 5
4.540E+06 9.190E+08 7.530E-18 2.690E-10 3.510E-07 Sr-91 5
1.080E+08 3.420E+04 4.924E-14 9.930E-12 4.547E-10 Sr-92 5
1.130E+08 9.756E+03 6.790E-14 3.920E-12 2.180E-10 Y-90 9
4.870E+06 2.304E+05 1.900E-16 5.170E-13 2.280E-09 Y-91 9
1.020E+08 5.055E+06 2.600E-16 8.500E-12 1.320E-08 Y-92 9
1.130E+08 1.274E+04 1.300E-14 1.050E-12 2.110E-10 Y-93 9
1.280E+08 3.636E+04 4.800E-15 9.260E-13 5.820E-10 Zr-95 9
1.290E+08 5.528E+06 3.600E-14 1.440E-09 6.390E-09 Zr-97 9
1.350E+08 6.084E+04 4.432E-14 2.315E-11 1.171E-09 Nb-95 9
1.220E+08 3.037E+06 3.740E-14 3.580E-10 1.570E-09 Mo-99 7
1.430E+08 2.376E+05 7.280E-15 1.520E-11 1.070E-09 Tc-99m 7
1.230E+08 2.167E+04 5.890E-15 5.010E-11 8.800E-12 Ru-103 7
1.060E+08 3.394E+06 2.251E-14 2.570E-10 2.421E-09 Ru-105 7
6.920E+07 1.598E+04 3.810E-14 4.150E-12 1.230E-10 Ru-106 7
2.420E+07 3.181E+07 1.040E-14 1.720E-09 1.290E-07 Rh-105 7
4.970E+07 1.273E+05 3.720E-15 2.880E-12 2.580E-10 Sb-127 4
6.530E+06 3.326E+05 3.330E-14 6.150E-11 1.630E-09 Sb-129 4
2.310E+07 1.555E+04 7.140E-14 9.720E-12 1.740E-10 Te-127 4
6.310E+06 3.366E+04 2.420E-16 1.840E-12 8.600E-11 Te-127m 4
8.350E+05 9.418E+06 1.470E-16 9.660E-11 5.810E-09 Te-129 4
2.170E+07 4.176E+03 2.750E-15 5.090E-13 2.090E-11 Te-129m 4
5.720E+06 2.903E+06 3.337E-15 1.563E-10 6.484E-09 Te-131m 4
1.100E+07 1.080E+05 7.463E-14 3.669E-08 1.758E-09 Te-132 4
1.090E+08 2.815E+05 1.030E-14 6.280E-08 2.550E-09 1-131 2
8.200E+07 6.947E+05 1.820E-14 2.920E-07 8.890E-09 1-132 2
1.200E+08 8.280E+03 1.120E-13 1.740E-09 1.030E-10
D000040-122, Revision 0 Page 119 of 155 I-133 2
1.680E+08 7.488E+04 2.940E-14 4.860E-08 1.580E-09 I-134 2
1.800E+08 3.156E+03 1.300E-13 2.880E-10 3.550E-11 I-135 2
1.540E+08 2.380E+04 8.294E-14 8.460E-09 3.320E-10 Xe-133 1
1.700E+08 4.532E+05 1.560E-15 0.000E+00 0.000E+00 Xe-135 1
3.700E+07 3.272E+04 1.190E-14 0.000E+00 0.000E+00 Cs-134 3
1.010E+07 6.507E+07 7.570E-14 1.110E-08 1.250E-08 Cs-136 3-3.080E+06 1.132E+06 1.060E-13 1.730E-09 1.980E-09 Cs-137 3
5.660E+06 9.467E+08 2.725E-14 7.930E-09 8.630E-09 Ba-139 6
1.470E+08 4.962E+03 2.170E-15 2.400E-12 4.640E-11 Ba-140 6
1.460E+08 1.101E+06 8.580E-15 2.560E-10 1.010E-09 La-140 9
1.490E+08 1.450E+05 1.170E-13 6.870E-11 1.310E-09 La-141 9
1.370E+08 1.415E+04 2.390E-15 9.400E-12 1.570E-10 La-142 9
1.320E+08 5.550E+03 1.440E-13 8.740E-12 6.840E-11 Ce-141 8
1.320E+08 2.808E+06 3.430E-15 2.550E-11 2.420E-09 Ce-143 8
1.290E+08 1.188E+05 1.290E-14 6.230E-12 9.160E-10 Ce-144 8
7.980E+07 2.456E+07 2.773E-15 2.920E-10 1.010E-07 Pr-143 9
1.260E+08 1.172E+06 2.100E-17 1.680E-18 2.190E-09 Nd-147 9
5.650E+07 9.487E+05 6.190E-15 1.820E-11 1.850E-09 Np-239 8
1.510E+09 2.035E+05 7.690E-15 7.620E-12 6.780E-10 Pu-238 8
8.580E+04 2.769E+09 4.880E-18 3.860E-10 7.790E-05 Pu-239 8
1.940E+04 7.594E+11 4.240E-18 3.750E-10 8.330E-05 Pu-240 8
2.440E+04 2.063E+11 4.750E-18 3.760E-10 8.330E-05 Pu-241 8
4.110E+06 4.544E+08 7.250E-20 9.150E-12 1.340E-06 Am-241 9
2.720E+03 1.364E+10 8.180E-16 1.600E-09 1.200E-04 Cm-242 9
1.040E+06 1.407E+07 5.690E-18 9.410E-10 4.670E-06 Cm-244 9
6.080E+04 5.715E+08 4.910E-18 1.010E-09 6.700E-05 Nuclide Daughter Fraction Daughter Fraction Daughter Fraction Kr-85m Kr-85 0.21 none 0.00 none 0.00 Kr-87 Rb-87 1.00 none 0.00 none 0.00 Kr-88 Rb-88 1.00 none 0.00 none 0.00 Sr-90 Y-90 1.00 none 0.00 none 0.00 Sr-91 Y-91m 0.58 Y-91 0.42 none 0.00 Sr-92 Y-92 1.00 none 0.00 none 0.00 Y-93 Zr-93 1.00 none 0.00 none 0.00 Zr-95 Nb-95m 0.01 Nb-95 0.99 none 0.00 Zr-97 Nb-97m 0.95 Nb-97 0.05 none 0.00 Mo-99 Tc-99m 0.88 Tc-99 0.12 none 0.00 Tc-99m Tc-99 1.00 none 0.00 none 0.00 Ru-103 Rh-103m 1.00 none 0.00 none 0.00 Ru-105 Rh-105 1.00 none 0.00 none 0.00 Ru-106 Rh-106 1.00 none 0.00 none 0.00 Sb-127 Te-127m 0.18 Te-127 0.82 none 0.00 Sb-129 Te-129m 0.22 Te-129 0.77 none 0.00 Te-127m Te-127 0.98 none 0.00 none 0.00 Te-129 I-129 1.00 none 0.00 none 0.00 Te-129m Te-129 0.65 I-129 0.35 none 0.00 Te-131m Te-131 0.22 I-131 0.78 none 0.00 Te-132 I-132 1.00 none 0.00 none 0.00 1-131 Xe-131m 0.01 none 0.00 none 0.00 I-133 Xe-133m 0.03 Xe-133 0.97 none 0.00 I-135 Xe-135m 0.15 Xe-135 0.85 none 0.00 Xe-135 Cs-135 1.00 none 0.00 none 0.00 Cs-137 Ba-137m 0.95 none 0.00 none 0.00 Ba-140 La-140 1.00 none 0.00 none 0.00 La-141 Ce-141 1.00 none 0.00 none 0.00 Ce-143 Pr-143 1.00 none 0.00 none 0.00 Ce-144 Pr-144m 0.02 Pr-144 0.98 none 0.00 Nd-147 Pm-147 1.00 none 0.00 none 0.00 Np-239 Pu-239 1.00 none 0.00 none 0.00 Pu-238 U-234 1.00 none 0.00 none 0.00 Pu-239 U-235 1.00 none 0.00 none 0.00 Pu-240 U-236 1.00 none 0.00 none 0.00 Pu-241 U-237 0.00 Am-241 1.00 none 0.00
D000040-122, Revision 0 Page 120 of 155 Am-241 Np-237 1.00 none 0.00 none 0.00 Cm-242 Pu-238 1.00 none 0.00 none 0.00 Cm-244 Pu-240 1.00 none 0.00 none 0.00 Iodine fractions Aerosol
=
Elemental
=
Organic
=
9.5000E-01 4.8500E-02 1.5000E-03 COMPARTMENT DATA Compartment number 1:
Aerosal Removal Data Time (hr)
Removal Coef.
(hr^-l) 0.0000E+00 0.0000E+00 1.4400E-02 5.6800E+00 1.8900E+00 5.6800E+00 2.1000E+00 5.6800E-01 4.0000E+00 0.0000E+00 Sprays:
Elemental Removal Data Time (hr)
Removal Coef. (hr^-l) 0.0000E+00 0.0000E+00 1.4400E-02 2.0000E+01 1.8900E+00 0.0000E+00 2.1000E+00 0.0000E+00 4.0000E+00 0.0000E+00 Natural Deposition: Aerosol data Time (hr)
Removal Coef. (hr^-l) 0.0000E+00 1.0000E-01 1.4400E-02 0.0000E+00 4.0000E+00 1.0000E-01 7.2000E+02 0.0000E+00 Compartment number 2:
Environment Compartment number PATHWAY DATA 3:
TSC Pathway number 1: Containment Leakage to Environment Convection Data Time (hr)
Flow Rate (% / day) 0.0000E+00 2.0000E-01 2.4000E+01 1.0000E-01 7.2000E+02 0.0000E+00 Pathway number 2: Environment to TSC Makeup Flow Rate Pathway Filter: Removal Data Time (hr)
Flow Rate (cfm)
Filter Efficiencies (%)
Aerosol Elemental Organic 0.0000E+00 1.2000E+04 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Pathway number 3: Environment to TSC - Unfiltered Inleakage Pathway Filter: Removal Data Time (hr)
Flow Rate Filter Efficiencies (%)
D000040-122, Revision 0 Page 121 of 155 (cfm)
Aerosol Elemental Organic 0.0000E+00 1.0000E+03 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Pathway number 4: TSC to Environment - Unfiltere Exhaust Pathway Filter: Removal Data Time (hr)
Flow Rate Filter Efficiencies (%)
(cfm)
Aerosol' Elemental Organic 0.0000E+00 1.3000E+04 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Pathway number 5: RBCU Filters Containment to Containment Pathway Filter:
Removal Data Time (hr)
Flow Rate (cfm)
Filter Efficiencies (%)
Aerosol Elemental Organic 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 1.4400E-02 5.4200E+04 9.0000E+01 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 LOCATION DATA Location EAB Location X/Q Data is in compartment 2
Time (hr) 0.0000E+00 7.2000E+02 X/Q (s
- m^-3) 1.2400E-04 0.0000E+00 Location Breathing Rate Data Time (hr)
Breathing Rate (m^3
- sec^-l) 0.0000E+00 8.0000E+00 2.4000E+01 7.2000E+02 3.5000E-04 1.8000E-04 2.3000E-04 0.0000E+00 Location LPZ Location X/Q Data is in compartment 2
Time (hr)
X/Q (s
- m^-3) 0.0000E+00 8.0000E+00 2.4000E+01 9.6000E+01 7.2000E+02 2.4200E-05 1.6800E-05 7.5500E-06 2.4000E-06 0.0000E+00 Location Breathing Rate Data Time (hr)
Breathing Rate (m^3
- sec^-l) 0.0000E+00 8.0000E+00 2.4000E+01 7.2000E+02 3.5000E-04 1.8000E-04 2.3000E-04 0.0000E+00 Location TSC Location X/Q Data is in compartment 3
Time (hr)
X/Q (s
- m^-3) 0.0000E+00 3.9000E-05 2.0000E+00 3.3000E-05 8.0000E+00 1.6000E-05 2.4000E+01 1.2000E-05 9.6000E+01 8.7000E-06 7.2000E+02 0.0000E+00
DC0004O-122, Revision 0 Page 122 of 155 Location Breathing Rate Data Time (hr)
Breathing Rate (m^3
- sec^-1) 0.0000E+00 3.5000E-04 7.2000E+02 0.0000E+00 Location Occupancy Factor Data Time (hr)
Occupancy Factor 0.0000E+00 1.0000E+00 2.4000E+01 6.0000E-01 9.6000E+01 4.0000E-01 7.2000E+02 0.0000E+00 USER SPECIFIED TIME STEP DATA - SUPPLEMENTAL TIME STEPS Time Time step 0.0000E+00 0.0000E+00
DC00040-122, Revision 0 Page 123 of 155 RADTRAD Version 3.03 (Spring 2001) run on 11/03/2011 at 13:16:04 Dose Output EAB Doses:
Time (h) =
0.0144 Whole Body Thyroid TEDE Delta dose (rem) 2.6573E-05 4.6920E-03, 1.9930E-04 Accumulated dose (rem) 2.6573E-05 4.6920E-03 1.9930E-04 LPZ Doses:
Time (h) =
0.0144 Whole Body Thyroid TEDE Delta dose (rem) 5.1860E-06 9.1570E-04 3.8896E-05 Accumulated dose (rem) 5.1860E-06 9.1570E-04 3.8896E-05 TSC Doses:
Time (h) =
0.0144 Whole Body Thyroid TEDE Delta dose (rem) 1.1043E-08 3.6522E-05 1.3555E-06 Accumulated dose (rem) 1.1043E-08 3.6522E-05 1.3555E-06 EAB Doses:
Time (h) =
0.5000 Whole Body Thyroid TEDE Delta dose (rem) 1.4190E-02 2.2149E+00 9.5980E-02 Accumulated dose (rem) 1.4216E-02 2.2196E+00 9.6179E-02 LPZ Doses:
Time (h) =
0.5000 Whole Body Thyroid TEDE Delta dose (rem) 2.7693E-03 4.3226E-01 1.8731E-02 Accumulated dose (rem) 2.7744E-03 4.3318E-01 1.8770E-02 TSC Doses:
Time (h) =
0.5000 Whole Body Thyroid TEDE Delta dose (rem) 1.0933E-04 3.3871E-01 1.2613E-02 Accumulated dose (rem) 1.0934E-04 3.3875E-01 1.2614E-02 EAB Doses:
Time (h) =
1.8000 Whole Body Thyroid TEDE Delta dose (rem) 2.5263E-01 2.0108E+01 1.1029E+00 Accumulated dose (rem) 2.6685E-01 2.2328E+01 1.1990E+00
D000040-122, Revision 0 Page 124 of 155 LPZ Doses:
Time (h) =
1.8000 Whole Body Thyroid TEDE Delta dose (rem) 4.9304E-02 3.9243E+00 2.1524E-01 Accumulated dose (rem) 5.2079E-02 4.3575E+00 2.3401E-01 TSC Doses:
Time (h) =
1.8000 Whole Body Thyroid TEDE Delta dose (rem) 3.0708E-03 5.2965E+00 2.2489E-01 Accumulated dose (rem) 3.1801E-03 5.6352E+00 2.3751E-01 EAB Doses:
Time (h) =
1.8900 Whole Body Thyroid TEDE Delta dose (rem) 2.4349E-02 1.0919E+00 7.0742E-02 Accumulated dose (rem) 2.9120E-01 2.3420E+01 1.2698E+00 LPZ Doses:
Time (h) =
1.8900 Whole Body Thyroid TEDE Delta dose (rem) 4.7520E-03 2.1309E-01 1.3806E-02 Accumulated dose (rem) 5.6831E-02 4.5706E+00 2.4781E-01 TSC Doses:
Time (h) =
1.8900 Whole Body Thyroid TEDE Delta dose (rem) 3.6593E-04 4.4393E-01 1.9226E-02 Accumulated dose (rem) 3.5461E-03 6.0791E+00 2.5673E-01 EAB Doses:
Time (h) =
2.1000 Whole Body Thyroid TEDE Delta dose (rem) 5.0005E-02 9.5812E-01 9.0337E-02 Accumulated dose (rem) 3.4120E-01 2.4378E+01 1.3601E+00 LPZ Doses:
Time (h) =
2.1000 Whole Body Thyroid TEDE Delta dose (rem) 9.7591E-03 1.8699E-01 1.7630E-02 Accumulated dose (rem) 6.6590E-02 4.7576E+00 2.6544E-01 TSC Doses:
Time (h) =
2.1000 Whole Body Thyroid TEDE Delta dose (rem) 8.4086E-04 7.9609E-01 3.4638E-02 Accumulated dose (rem) 4.3869E-03 6.8752E+00 2.9137E-01 EAB Doses:
Time (h) =
4.0000 Whole Body Thyroid TEDE Delta dose (rem) 3.3636E-01 1.3925E+00 3.8941E-01 Accumulated dose (rem) 6.7756E-01 2.5770E+01 1.7495E+00 LPZ Doses:
Time (h) 4.0000 Whole Body Thyroid TEDE Delta dose (rem) 6.5644E-02 2.7176E-01 7.5997E-02 Accumulated dose (rem) 1.3223E-01 5.0293E+00 3.4144E-01 TSC Doses:
Time (h) =
4.0000 Whole Body Thyroid TEDE Delta dose (rem) 4.9652E-03 1.1028E+00 5.0372E-02
D000040-122, Revision 0 Page 125 of 155 Accumulated dose (rem) 9.3521E-03 7.9780E+00 3.4174E-01 EAB Doses:
Time (h) =
8.0000 Whole Body Thyroid TEDE Delta dose (rem) 3.7902E-01 1.1861E+00 4.1617E-01 Accumulated dose (rem) 1.0566E+00 2.6956E+01 2.1657E+00 LPZ Doses:
Time (h) =
8.0000 Whole Body Thyroid TEDE Delta dose (rem) 7.3970E-02 2.3149E-01 8.1221E-02 Accumulated dose (rem) 2.0620E-01 5.2608E+00 4.2266E-01 TSC Doses:
Time (h) =
8.0000 Whole Body° Thyroid TEDE Delta dose (rem) 5.3863E-03 3.2079E-01 1.5495E-02 Accumulated dose (rem) 1.4738E-02 8.2988E+00 3.5724E-01 EAB Doses:
Time (h) =
24.0000 Whole Body Thyroid TEDE Delta dose (rem) 4.3650E-01 2.1641E+00 5.0338E-01 Accumulated dose (rem) 1.4931E+00 2.9120E+01 2.6691E+00 LPZ Doses:
Time (h) =
24.0000 Whole Body Thyroid TEDE Delta dose (rem) 5.9139E-02 2.9320E-01 6.8200E-02 Accumulated dose (rem) 2.6534E-01 5.5540E+00 4.9086E-01 TSC Doses:
Time (h) =
24.0000 Whole Body Thyroid TEDE Delta dose (rem) 3.1253E-03 5.5343E-01 2.0231E-02 Accumulated dose (rem) 1.7864E-02 8.8522E+00 3.7747E-01 EAB Doses:
Time (h) =
96.0000 Whole Body Thyroid TEDE Delta dose (rem) 2.9384E-01 4.6451E+00 4.3594E-01 Accumulated dose (rem) 1.7869E+00 3.3766E+01 3.1050E+00 LPZ Doses:
Time (h) = 96.0000 Whole Body Thyroid TEDE Delta dose (rem) 1.7891E-02 2.8283E-01 2.6543E-02 Accumulated dose (rem) 2.8323E-01 5.8369E+00 5.1740E-01 TSC Doses:
Time (h) = 96.0000 Whole Body Thyroid TEDE Delta dose (rem) 9.2919E-04 4.1660E-01 1.3675E-02 Accumulated dose (rem) 1.8793E-02 9.2688E+00 3.9114E-01 EAB Doses:
p Time (h) = 720.0000 Whole Body Thyroid TEDE Delta dose (rem) 5.2850E-01 1.3000E+01 9.2435E-01 Accumulated dose (rem) 2.3154E+00 4.6766E+01 4.0294E+00 LPZ Doses:
D000040-122, Revision 0 Page 126 of 155 Time (h) = 720.0000 Whole Body Thyroid TEDE Delta dose (rem) 1.0229E-02 2.5161E-01 1.7891E-02 Accumulated dose (rem) 2.9346E-01 6.0885E+00 5.3529E-01 TSC Doses:
Time (h) = 720.0000 Whole Body Thyroid TEDE Delta dose (rem) 7.9283E-04 5.5565E-01 1.7713E-02 Accumulated dose (rem) 1.9586E-02 9.8245E+00 4.0885E-01 839
D000040-122, Revision 0 Page 127 of 155 1-131 Summary Time (hr)
Containment 1-131 (Curies)
Environment 1-131 (Curies)
TSC 1-131 (Curies) 0.000 4.5554E+03 1.0545E-04 2.5214E-08 0.014 1.1799E+05 7.0812E-02
- 1. 6641E-05 0.414 1.0426E+06 2.6055E+01 3.5919E-03 0.500 1.0676E+06 3.3589E+01 4.1426E-03 0.800 2.7390E+06 8.8329E+01 9.6702E-03 1.100 2.9301E+06 1.5996E+02 1.3439E-02 1.400 2.9578E+06 2.3363E+02 1.4900E-02 1.700 2.9672E+06 3.0769E+02 1.5420E-02 1.800 2.9696E+06 3.3242E+02 1.5506E-02 1.890 1.5476E+06 3.4875E+02 1.4296E-02 2.100 3.8096E+05 3.6312E+02 8.6304E-03 2.500 1.9365E+05 3.7225E+02 2.7871E-03 2.800 1.2859E+05 3.7619E+02 1.3588E-03 3.100 9.4549E+04 3.7894E+02 7.6152E-04 3.400 7.6725E+04 3.8105E+02 4.9736E-04 3.700 6.7378E+04 3.8284E+02 3.7470E-04 4.000 6.2462E+04 3.8446E+02 3.1546E-04 4.300 6.0281E+04 3.8599E+02 2.8686E-04 4.600 5.8944E+04 3.8748E+02 2.7265E-04 4.900 5.8115E+04 3.8894E+02 2.6499E-04 5.200 5.7592E+04 3.9039E+02 2.6059E-04 5.500 5.7252E+04 3.9182E+02 2.5794E-04 5.800 5.7022E+04 3.9325E+02 2.5626E-04 6.100 5.6859E+04 3.9467E+02, 2.5516E-04 6.400 5.6736E+04 3.9609E+02 2.5438E-04 6.700 5.6638E+04 3.9751E+02 2.5381E-04 7.000 5.6553E+04 3.9892E+02 2.5335E-04 7.300 5.6478E+04 4.0033E+02 2.5296E-04 7.600 5.6408E+04 4.0175E+02 2.5262E-04 7.900 5.6341E+04 4.0315E+02 2.5230E-04 8.000 5.6319E+04 4.0362E+02 2.5220E-04 8.300 5.6255E+04 4.0503E+02 1.6404E-04 8.600 5.6191E+04 4.0644E+02 1.3551E-04 8.900 5.6128E+04 4.0784E+02 1.2622E-04 9.200 5.6066E+04 4.0924E+02 1.2313E-04 9.500 5.6004E+04 4.1064E+02 1.2204E-04 9.800 5.5942E+04 4.1204E+02 1.2160E-04 10.100 5.5880E+04 4.1344E+02 1.2136E-04 10.400 5.5819E+04 4.1484E+02 1.2120E-04 24.000 5.3097E+04 4.7645E+02 1.1527E-04 96.000 4.0874E+04 6.1635E+02 3.3276E-05 720.000 4.2332E+03 1.0357E+03 2.4986E-06
D000040-122, Revision 0 Page 128 of 155 Cumulative Dose Summary EAB LPZ TSC Time (hr)
Thyroid (rem)
Thyroid (rem)
Thyroid (rem)
TEDE (rem) 0.000 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.014 4.6920E-03 1.9930E-04 9.1570E-04 3.8896E-05 3.6522E-05 1.3555E-06 0.414 1.7228E+00 7.4433E-02 3.3622E-01 1.4526E-02 2.3067E-01 8.5886E-03 0.500 2.2196E+00 9.6179E-02 4.3318E-01 1.8770E-02 3.3875E-01 1.2614E-02 0.800 5.9079E+00 2.7870E-01 1.1530E+00 5.4392E-02 1.0051E+00 3.9210E-02 1.100 1.0744E+01 5.3503E-01 2.0968E+00 1.0442E-01 2.1830E+00 8.8911E-02 1.400 1.5703E+01 8.1155E-01 3.0647E+00 1.5838E-01 3.6088E+00 1.5004E-01 1.700 2.0672E+01 1.1005E+00 4.0344E+00 2.1477E-01 5.1228E+00 2.1535E-01 1.800 2.2328E+01 1.1990E+00 4.3575E+00 2.3401E-01 5.6352E+00 2.3751E-01 1.890 2.3420E+01 1.2698E+00 4.5706E+00 2.4781E-01 6.0791E+00 2.5673E-01 2.100 2.4378E+01 1.3601E+00 4.7576E+00 2.6544E-01 6.8752E+00 2.9137E-01 2.500 2.4981E+01 1.4695E+00 4.8754E+00 2.8679E-01 7.5516E+00 3.2125E-01 2.800 2.5239E+01 1.5374E+00 4.9258E+00 3.0005E-01 7.7458E+00 3.3014E-01 3.100 2.5417E+01 1.5977E+00 4.9605E+00 3.1181E-01 7.8454E+00 3.3490E-01 3.400 2.5554E+01 1.6524E+00 4.9871E+00 3.2249E-01 7.9046E+00 3.3787E-01 3.700 2.5668E+01 1.7028E+00 5.0093E+00 3.3231E-01 7.9456E+00 3.4001E-01 4.000 2.5770E+01 1.7495E+00 5.0293E+00 3.4144E-01 7.9780E+00 3.4174E-01 4.300 2.5867E+01 1.7932E+00 5.0482E+00 3.4996E-01 8.0062E+00 3.4325E-01 4.600 2.5960E+01 1.8341E+00 5.0665E+00 3.5795E-01 8.0323E+00 3.4463E-01 4.900 2.6052E+01 1.8726E+00 5.0843E+00 3.6546E-01 8.0573E+00 3.4593E-01 5.200 2.6142E+01 1.9088E+00 5.1019E+00 3.7253E-01 8.0816E+00 3.4718E-01 5.500 2.6231E+01 1.9430E+00 5.1194E+00 3.7919E-01 8.1056E+00 3.4837E-01 5.800 2.6320E+01 1.9752E+00 5.1367E+00 3.8548E-01 8.1293E+00 3.4953E-01 6.100 2.6408E+01 2.0057E+00 5.1538E+00 3.9143E-01 8.1528E+00 3.5066E-01 6.400 2.6496E+01 2.0345E+00 5.1709E+00 3.9706E-01 8.1761E+00 3.5176E-01 6.700 2.6583E+01 2.0619E+00 5.1879E+00 4.0241E-01 8.1993E+00 3.5283E-01 7.000 2.6670E+01 2.0879E+00 5.2049E+00 4.0748E-01 8.2224E+00 3.5388E-01 7.300 2.6756E+01 2.1126E+00 5.2217E+00 4.1230E-01 8.2455E+00 3.5491E-01 7.600 2.6842E+01 2.1361E+00 5.2385E+00 4.1688E-01 8.2684E+00 3.5592E-01 7.900 2.6928E+01 2.1585E+00 5.2553E+00 4.2125E-01 8.2912E+00 3.5691E-01 8.000 2.6956E+01 2.1657E+00 5.2608E+00 4.2266E-01 8.2988E+00 3.5724E-01 8.300 2.7000E+01 2.1854E+00 5.2668E+00 4.2533E-01 8.3169E+00 3.5801E-01 8.600 2.7044E+01 2.2042E+00 5.2727E+00 4.2788E-01 8.3301E+00 3.5856E-01 8.900 2.7088E+01 2.2222E+00 5.2786E+00 4.3031E-01 8.3418E+00 3.5905E-01 9.200 2.7131E+01 2.2393E+00 5.2845E+00 4.3263E-01 8.3529E+00 3.5951E-01 9.500 2.7174E+01 2.2557E+00 5.2903E+00 4.3485E-01 8.3639E+00 3.5995E-01 9.800 2.7217E+01 2.2713E+00 5.2962E+00 4.3697E-01 8.3747E+00 3.6038E-01 10.100 2.7260E+01 2.2863E+00 5.3020E+00 4.3900E-01 8.3855E+00 3.6081E-01 10.400 2.7303E+01 2.3007E+00 5.3078E+00 4.4095E-01 8.3963E+00 3.6124E-01 24.000 2.9120E+01 2.6691E+00 5.5540E+00 4.9086E-01 8.8522E+00 3.7747E-01 96.000 3.3766E+01 3.1050E+00 5.8369E+00 5.1740E-01 9.2688E+00 3.9114E-01 720.000 4.6766E+01 4.0294E+00 6.0885E+00 5.3529E-01 9.8245E+00 4.0885E-01 Worst Two-Hour Doses EAB Time Whole Body Thyroid TEDE (hr)
(rem)
(rem)
(rem) 0.5 4.1190E-01 2.2762E+01 1.3733E+00
DC00040-122, Revision 0 Page 129 of 155 RADTRAD Input/Output File:
D000040-122, Revision 0 Page 130 of 155 RADTRAD Version 3.03 (Spring 2001) run on 11/04/2011 at 8:22:38 File information Plant file
= C:\\Program Files\\radtrad3_03\\VCS TSC\\ESF Release\\Sump Release - TSC.psf Inventory file
= c:\\program files\\radtrad3 03\\vcs tsc\\esf release\\esf_halogen.nif Release file
= c:\\program files\\radtrad3 03\\vcs tsc\\esf release\\pwr dba.rft Dose Conversion file = c:\\program files\\radtrad3 03\\vcs tsc\\esf release\\fgrll&12.inp Radtrad 3.03 4/15/2001 Sump Release - TSC Nuclide Inventory File:
c:\\program files\\radtrad3_03\\vcs tsc\\esf release\\esf_halogen.nif Plant Power Level:
1.0000E+00 Compartments:
3 Compartment 1:
Sump 3
5.5730E+04 0
0 0
0 0
Compartment 2:
Environment 2
0.0000E+00 0
0 0
0 0
Compartment 3:
TSC 1
2.0700E+05 0
0 0
D000040-122, Revision 0 Page 131 of 155 0
0 Pathways:
4 Pathway 1:
Sump Leakage to Environment 1
2 2
Pathway 2:
Environment to TSC Makeup Flow Rate 2
3 2
Pathway 3:
Environment to TSC - Unfiltered Inleakage 2
3 2
Pathway 4:
TSC to Environment - Unfiltered Exhaust 3
2 2
End of Plant Model File Scenario Description Name:
Plant Model Filename:
Source Term:
1 1
1.0000E+00 c:\\program files\\radtrad3 03\\vcs tsc\\esf release\\fgrll&12.inp c:\\program files\\radtrad3 03\\vcs tsc\\esf release\\pwr dba.rft 0.0000E+00 1
0.0000E+00 9.7000E-01 3.0000E-02 1.0000E+00 Overlying Pool:
0 0.0000E+00 0
0 0
0 Compartments:
3 Compartment 1:
0 1
0 0
0 0
0 0
0 Compartment 2:
0 1
0 0
0 0
0
D000040-122, Revision 0 Page 132 of 155 0
0 Compartment 3:
0 1
0 0
0 0
0 0
0 Pathways:
4 Pathway 1:,
0 0
0 0
0 1
3 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 4.1000E-01 7.0630E-03 9.0000E+01 9.0000E+01 9.0000E+01 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0
0 0
0 0
0 Pathway 2:
0 0
0 0
0 1
2 0.0000E+00 1.2000E+04 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0
0 0
0 0
0 Pathway 3:
0 0
0 0
0 1
2 0.0000E+00 1.0000E+03 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0
0 0
0 0
0 Pathway 4:
D000040-122, Revision 0 Page 133 of 155 0
0 0
0 0
1 2
0.0000E+00 1.3000E+04 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0
0 0
0 0
0 Dose Locations:
3 Location 1:
EAB 2
1 2
0.0000E+00 1.2400E-04 7.2000E+02 0.0000E+00 1
4 0.0000E+00 3.5000E-04 8.0000E+00 1.8000E-04 2.4000E+01 2.3000E-04 7.2000E+02 0.0000E+00 0
Location 2:
LPZ 2
1 5
0.0000E+00 2.4200E-05 8.0000E+00 1.6800E-05 2.4000E+01 7.5500E-06 9.6000E+01 2.4000E-06 7.2000E+02 0.0000E+00 1
4 0.0000E+00 3.5000E-04 8.0000E+00 1.8000E-04 2.4000E+01 2.3000E-04 7.2000E+02 0.0000E+00 0
Location 3:
TSC 3
0 1
2 0.0000E+00 3.5000E-04 7.2000E+02 0.0000E+00 1
4 0.0000E+00 1.0000E+00 2.4000E+01 6.0000E-01 9.6000E+01 4.0000E-01 7.2000E+02 0.0000E+00 Effective Volume Location:
1
DC00040-122, Revision 0 Page 134 of 155 6
0.0000E+00 3.9000E-05 2.0000E+00 3.3000E-05 8.0000E+00 1.6000E-05 2.4000E+01 1.2000E-05 9.6000E+01 8.7000E-06 7.2000E+02 0.0000E+00 Simulation Parameters:
1 0.0000E+00 0.0000E+00 Output Filename:
C:\\Program Files\\radtrad3 03\\VCS TSC\\ESF Release\\Sump Release - TSC.oO 1
1 1
0 0
End of Scenario File
D000040-122, Revision 0 Page 135 of 155 RADTRAD Version 3.03 (Spring 2001) run on 11/04/2011 at 8:22:38 Plant Description Number of Nuclides = 60 Inventory Power =
1.0000E+00 MWth Plant Power Level =
1.0000E+00 MWth Number of compartments
=
3 Compartment information Compartment number 1 (Source term fraction =
1.0000E+00 Name: Sump Compartment volume =
5.5730E+04 (Cubic feet)
Compartment type is Normal Pathways into and out of compartment 1 Exit Pathway Number 1:
Sump Leakage to Environment Compartment number 2 Name: Environment Compartment type is Environment Pathways into and out of compartment 2 Inlet Pathway Number 1:
Sump Leakage to Environment Inlet Pathway Number 4: TSC to Environment - Unfiltered Exhaust Exit Pathway Number 2:
Environment to TSC Makeup Flow Rate Exit Pathway Number 3: Environment to TSC - Unfiltered Inleakage Compartment number 3 Name: TSC Compartment volume =
2.0700E+05 (Cubic feet)
Compartment type is Control Room Pathways into and out of compartment 3 Inlet Pathway Number 2:
Environment to TSC Makeup Flow Rate Inlet Pathway Number 3: Environment to TSC - Unfiltered Inleakage Exit Pathway Number 4:
TSC to Environment - Unfiltered Exhaust Total number of pathways =
4
D00004O-122, Revision 0 Page 136 of 155 RADTRAD Version 3.03 (Spring 2001) run on 11/04/2011 at 8:22:38 Scenario Description Radioactive Decay is enabled Calculation of Daughters is enabled Release Fractions and Timings GAP EARLY IN-VESSEL LATE RELEASE RELEASE MASS 0.500000 hr 1.3000 hrs 0.0000 hrs (gm)
NOBLES 5.0000E-02 9.5000E-01 0.0000E+00 0.000E+00 IODINE 5.0000E-02 3.5000E-01 0.0000E+00 3.488E+02 CESIUM 5.0000E-02 2.5000E-01 0.0000E+00 0.000E+00 TELLURIUM 0.0000E+00 5.0000E-02 0.0000E+00 0.000E+00 STRONTIUM 0.0000E+00 2.0000E-02 0.0000E+00 0.000E+00 BARIUM 0.0000E+00 2.0000E-02 0.0000E+00 0.000E+00 RUTHENIUM 0.0000E+00 2.5000E-03 0.0000E+00 0.000E+00 CERIUM 0.0000E+00 5.0000E-04 0.0000E+00 0.000E+00 LANTHANUM 0.0000E+00 2.0000E-04 0.0000E+00 0.000E+00 Inventory Power =
1.
MWt Nuclide Name Group Specific Inventory (Ci/MWt) half life (s)
Whole Body DCF (Sv-m3/Bq-s)
Inhaled Thyroid (Sv/Bq)
Inhaled Effective (Sv/Bq)
I-131 2
8.200E+07 6.947E+05 1.820E-14 2.920E-07 8.890E-09 I-132 2
1.200E+08 8.280E+03 1.120E-13 1.740E-09 1.030E-10 I-133 2
1.680E+08 7.488E+04 2.940E-14 4.860E-08 1.580E-09 I-134 2
1.800E+08 3.156E+03 1.300E-13 2.880E-10 3.550E-11 I-135 2
1.540E+08 2.380E+04 8.294E-14 8.460E-09 3.320E-10 Nuclide Daughter Fraction Daughter Fraction Daughter Fraction 1-131 Xe-131m 0.01 none 0.00 none 0.00 I-133 Xe-133m 0.03 Xe-133 0.97 none 0.00 I-135 Xe-135m 0.15 Xe-135 0.85 none 0.00 Iodine fractions Aerosol
=
0.0000E+00 Elemental
=
9.7000E-01 Organic
=
3.0000E-02 COMPARTMENT DATA Compartment number 1:
Sump Compartment number 2: Environment Compartment number 3:
TSC PATHWAY DATA Pathway number 1: Sump Leakage to Environment Pathway Filter: Removal Data Time (hr)
Flow Rate Filter Efficiencies (%)
(cfm)
Aerosol Elemental Organic 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 4.1000E-01 7.0630E-03 9.0000E+01 9.0000E+01 9.0000E+01
DC00040-122, Revision 0 Page 137 of 155 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Pathway number 2: Environment to TSC Makeup Flow Rate Pathway Filter: Removal Data Time (hr)
Flow Rate Filter Efficiencies (%)
(cfm)
Aerosol Elemental Organic 0.0000E+00 1.2000E+04 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Pathway number 3: Environment to TSC - Unfiltered Inleakage Pathway Filter: Removal Data Time (hr)
Flow Rate Filter Efficiencies (%)
(cfm)
Aerosol Elemental Organic 0.0000E+00 1.0000E+03 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Pathway number 4: TSC to Environment - Unfiltered Exhaust Pathway Filter: Removal Data Time (hr)
Flow Rate Filter Efficiencies (%)
(cfm)
Aerosol Elemental Organic 0.0000E+00 1.3000E+04 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 LOCATION DATA Location EAB is in compartment 2
Location X/Q Data Time (hr)
X/Q (s
- m^-3) 0.0000E+00 1.2400E-04 7.2000E+02 0.0000E+00 Location Breathing Rate Data Time (hr)
Breathing Rate (m^3
- sec^-l) 0.0000E+00 3.5000E-04 8.0000E+00 1.8000E-04 2.4000E+01 2.3000E-04 7.2000E+02 0.0000E+00 Location LPZ is in compartment 2
Location X/Q Data Time (hr)
X/Q (s
- m^-3) 0.0000E+00 2.4200E-05 8.0000E+00 1.6800E-05 2.4000E+01 7.5500E-06 9.6000E+01 2.4000E-06 7.2000E+02 0.0000E+00 Location Breathing Rate Data Time (hr)
Breathing Rate (m^3
- sec^-l) 0.0000E+00 3.5000E-04 8.0000E+00 1.8000E-04 2.4000E+01 2.3000E-04 7.2000E+02 0.0000E+00 Location TSC is in compartment 3
Location X/Q Data Time (hr)
X/Q (s
- m^-3) 0.0000E+00 3.9000E-05
D000040-122, Revision 0 Page 138 of 155 2.0000E+00 3.3000E-05 8.0000E+00 1.6000E-05 2.4000E+01 1.2000E-05 9.6000E+01 8.7000E-06 7.2000E+02 0.0000E+00 Location Breathing Rate Data Time (hr)
Breathing Rate (m^3
- sec^-1) 0.0000E+00 3.5000E-04 7.2000E+02 0.0000E+00 Location Occupancy Factor Data Time (hr)
Occupancy Factor.
0.0000E+00 1.0000E+00 2.4000E+01 6.0000E-01
- 9. 6000E+01 4.0000E-01 7.2000E+02 0.0000E+00 USER SPECIFIED TIME STEP DATA - SUPPLEMENTAL TIME STEPS Time Time step 0.0000E+00 0.0000E+00
DC0004O-122, Revision 0 Page 139 of 155 RADTRAD Version 3.03 (Spring 2001) run on 11/04/2011 at 8:22:38 Dose Output EAB Doses:
Time (h) =
0.4100 Whole Body Thyroid TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 LPZ Doses:
Time (h) =
0.4100 Whole Body Thyroid TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 TSC Doses:
Time (h) =
0.4100 Whole Body Thyroid TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 EAB Doses:
Time (h) =
0.5000 Whole Body Thyroid TEDE Delta dose (rem) 6.8395E-05 1.6717E-02 5.9556E-04 Accumulated dose (rem) 6.8395E-05 1.6717E-02 5.9556E-04 LPZ Doses:
Time (h) =
0.5000 Whole Body Thyroid TEDE Delta dose (rem) 1.3348E-05 3.2626E-03 1.1623E-04 Accumulated dose (rem) 1.3348E-05 3.2626E-03 1.1623E-04 TSC Doses:
Time (h) =
0.5000 Whole Body Thyroid TEDE Delta dose (rem) 1.6609E-07 7.6033E-04 2.4142E-05 Accumulated dose (rem) 1.6609E-07 7.6033E-04 2.4142E-05 EAB Doses:
Time (h) =
1.8000 Whole Body Thyroid TEDE Delta dose (rem) 3.8940E-03 1.1775E+00 4.0891E-02 Accumulated dose (rem) 3.9624E-03 1.1942E+00 4.1486E-02
D000040-122, Revision 0 Page 140 of 155 LPZ Doses:
Time (h) =
1.8000 Whole Body Thyroid TEDE Delta dose (rem) 7.5996E-04 2.2980E-01 7.9803E-03 Accumulated dose (rem) 7.7331E-04 2.3306E-01 8.0965E-03 TSC Doses:
Time (h) =
1.8000 Whole Body Thyroid TEDE Delta dose (rem) 4.5631E-05 2.6420E-01 8.3453E-03 Accumulated dose (rem) 4.5797E-05 2.6496E-01 8.3695E-03 EAB Doses:
Time (h) =
8.0000 Whole Body Thyroid TEDE Delta dose (rem) 2.0121E-02 9.4919E+00 3.1614E-01 Accumulated dose (rem) 2.4084E-02 1.0686E+01 3.5763E-01 LPZ Doses:
Time (h) =
8.0000 Whole Body Thyroid TEDE Delta dose (rem) 3.9269E-03 1.8525E+00 6.1698E-02 Accumulated dose (rem) 4.7002E-03 2.0855E+00 6.9795E-02 TSC Doses:
Time (h) =
8.0000 Whole Body Thyroid TEDE Delta dose (rem) 2.8540E-04 2.5382E+00 7.9445E-02 Accumulated dose (rem) 3.3120E-04 2.8032E+00 8.7815E-02 EAB Doses:
Time (h) =
24.0000 Whole Body Thyroid TEDE Delta dose (rem) 2.8161E-02 1.1182E+01 3.7372E-01 Accumulated dose (rem) 5.2245E-02 2.1868E+01 7.3135E-01 LPZ Doses:
Time (h) = 24.0000 Whole Body Thyroid TEDE Delta dose (rem) 3.8153E-03 1.5150E+00 5.0633E-02 Accumulated dose (rem) 8.5156E-03 3.6005E+00 1.2043E-01 TSC Doses:
Time (h) = 24.0000 Whole Body Thyroid TEDE Delta dose (rem) 1.9734E-04 2.8596E+00 8.8573E-02 Accumulated dose (rem) 5.2854E-04 5.6628E+00 1.7639E-01 EAB Doses:
Time (h) =
96.0000 Whole Body Thyroid TEDE Delta dose (rem) 3.3807E-02 4.8091E+01 1.5050E+00 Accumulated dose (rem) 8.6052E-02 6.9959E+01 2.2363E+00 LPZ Doses:
Time (h) =
96.0000 Whole Body Thyroid TEDE Delta dose (rem) 2.0584E-03 2.9281E+00 9.1634E-02 Accumulated dose (rem) 1.0574E-02 6.5287E+00 2.1206E-01 TSC Doses:
Time (h) =
96.0000 Whole Body Thyroid TEDE Delta dose (rem) 1.0520E-04 4.2620E+00 1.3049E-01
D000040-122, Revision 0 Page 141 of 155 Accumulated dose (rem) 6.3374E-04 9.9248E+00 3.0688E-01 EAB Doses:
Time (h) = 720.0000 Whole Body Thyroid TEDE Delta dose (rem) 4.5132E-02 1.3570E+02 4.1771E+00 Accumulated dose (rem) 1.3118E-01 2.0565E+02 6.4134E+00 LPZ Doses:
Time (h) = 720.0000 Whole Body Thyroid TEDE Delta dose (rem) 8.7353E-04 2.6264E+00 8.0847E-02 Accumulated dose (rem) 1.1448E-02 9.1550E+00 2.9291E-01 TSC Doses:
Time (h) = 720.0000 Whole Body Thyroid TEDE Delta dose (rem) 6.7692E-05 5.7998E+00 1.7667E-01 Accumulated dose (rem) 7.0143E-04 1.5725E+01 4.8355E-01 838
D000040-122, Revision 0 Page 142 of 155 1-131 Summary Time (hr)
Sump 1-131 (Curies)
Environment 1-131 (Curies)
TSC 1-131 (Curies) 0.000 4.5555E+03 0.0000E+00 0.0000E+00 0.401 3.2844E+06 0.0000E+00 0.0000E+00 0.410 3.3571E+06 0.0000E+00 0.0000E+00 0.500 4.0926E+06 2.5488E-01
- 5. 2011E-05 0.800 1.0692E+07 1.9413E+00 2.7832E-04 1.100 1.7278E+07 5.1313E+00 5.6673E-04 1.400 2.3849E+07 9.8217E+00 8.7469E-04 1.700 3.0406E+07 1.6009E+01 1.1885E-03 1.800 3.2588E+07 1.8404E+01 1.2935E-03 2.100 3.2553E+07 2.5833E+01 1.4056E-03 2.400 3.2518E+07 3.3254E+01 1.3530E-03 2.700 3.2483E+07
- 4. 0667E+01 1.3351E-03 3.000 3.2448E+07 4.8071E+01 1.3283E-03 3.300 3.2413E+07 5.5468E+01 1.3252E-03 3.600 3.2378E+07 6.2857E+01 1.3232E-03 3.900 3.2343E+07 7.0238E+01 1.3216E-03 4.200 3.2308E+07 7.7611E+01 1.3201E-03 4.500 3.2273E+07 8.4976E+01 1.3186E-03 4.800 3.2238E+07 9.2333E+01 1.3172E-03 5.100 3.2204E+07 9.9682E+01 1.3158E-03 5.400 3.2169E+07 1.0702E+02 1.3144E-03 5.700 3.2134E+07 1.1436E+02 1.3129E-03 6.000 3.2099E+07 1.2168E+02 1.3115E-.03 6.300 3.2065E+07 1.2900E`+02 1.3101E-03 6.600 3.2030E+07 1.3631E+02 1.3087E-03 6.900 3.1996E+07 1.4361E+02 1.3073E-03 7.200 3.1961E+07 1.5090E+02 1.3059E-03 7.500 3.1927E+07 1..5819E+02 1.3045E-03 7.800 3.1892E+07 1.6547E+02
- 1. 3031E-03 8.000 3.1869E+07 1.7032E+02 1.3021E-03 8.300 3.1835E+07 1.7758E+02 8.4701E-04 8.600 3.1800E+07 1.8484E+02 6.9975E-04 8.900 3.1766E+07 1.9209E+02 6.5180E-04 9.200 3.1732E+07 1.9933E+02 6.3587E-04 9.500 3.1698E+07 2.0656E+02 6.3027E-04 9.800 3.1663E+07 2.1379E+02 6.2801E-04 10.100 3.1629E+07 2.2101E+02 6.2682E-04 10.400 3.1595E+07 2.2822E+02 6.2598E-04 24.000 3.0085E+07 5.4661E+02 5.9599E-04 96.000 2.3216E+07 1.9950E+03 3.4494E-04 720.000 2.4561E+06 6.3725E+03 2.6457E-05
D000040-122, Revision 0 Page 143 of 155 Cumulative Dose Summary EAB LPZ TSC Time (hr)
Thyroid (rem)
Thyroid (rem)
Thyroid (rem)
TEDE (rem) 0.000 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.401 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.410 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.500 1.6717E-02 5.9556E-04 3.2626E-03 1.1623E-04 7.6033E-04 2.4142E-05 0.800 1.2702E-01 4.4961E-03 2.4790E-02 8.7746E-04 1.6076E-02 5.0970E-04 1.100 3.3489E-01 1.1779E-02 6.5358E-02 2.2987E-03 5.6746E-02 1.7969E-03 1.400 6.3940E-01 2.2360E-02 1.2479E-01 4.36.39E-03 1.2618E-01 3.9912E-03 1.700 1.0396E+00 3.6174E-02 2.0290E-01 7.0597E-03 2.2530E-01 7.1189E-03 1.800 1.1942E+00 4.1486E-02 2.3306E-01 8.0965E-03 2.6496E-01 8.3695E-03 2.100 1.6725E+00 5.7865E-02 3.2640E-01 1.1293E-02 3.9795E-01 1.2560E-02 2.400 2.1486E+00 7.4084E-02 4.1933E-01 1.4458E-02 5.2903E-01 1.6685E-02 2.700 2.6226E+00 9.0156E-02 5.1184E-01 1.7595E-02 6.5658E-01 2.0696E-02 3.000 3.0946E+00 1.0610E-01 6.0394E-01 2.0706E-02 7.8263E-01 2.4656E-02 3.300 3.5645E+00 1.2191E-01 6.9565E-01 2.3792E-02 9.0783E-01 2.8586E-02 3.600 4.0324E+00 1.3761E-01 7.8697E-01 2.6856E-02 1.0324E+00 3.2494E-02 3.900 4.4984E+00 1.5320E-01 8.7791E-01 2.9899E-02 1.1564E+00 3.6381E-02 4.200 4.9624E+00 1.6869E-01 9.6847E-01 3.2922E-02 1.2799E+00 4.0250E-02 4.500 5.4246E+00 1.8409E-01 1.0587E+00 3.5926E-02 1.4029E+00 4.4101E-02 4.800 5.8849E+00 1.9939E-01 1.1485E+00 3.8912E-02 1.5254E+00 4.7934E-02 5.100 6.3433E+00 2.1460E-01 1.2380E+00 4.1881E-02 1.6474E+00 5.1750E-02 5.400 6.8000E+00 2.2972E-01 1.3271E+00 4.4833E-02 1.7690E+00 5.5549E-02 5.700 7.2549E+00 2.4477E-01 1.4159E+00 4.7770E-02 1.8900E+00 5.9332E-02 6.000 7.7080E+00 2.5973E-01 1.5043E+00 5.0690E-02 2.0106E+00 6.3098E-02 6.300 8.1594E+00 2.7462E-01 1.5924E+00 5.3596E-02 2.1308E+00 6.6849E-02 6.600 8.6092E+00 2.8944E-01 1.6802E+00 5.6487E-02 2.2504E+00 7.0584E-02 6.900 9.0572E+00 3.0418E-01 1.7676E+00 5.9363E-02 2.3697E+00 7.4303E-02 7.200 9.5036E+00 3.1885E-01 1.8547E+00 6.2226E-02 2.4885E+00 7.8008E-02 7.500 9.9484E+00 3.3344E-01 1.9415E+00 6.5076E-02 2.6068E+00 8.1697E-02 7.800 1.0392E+01 3.4798E-01 2.0280E+00 6.7912E-02 2.7248E+00 8.5373E-02 8.000 1.0686E+01 3.5763E-01 2.0855E+00 6.9795E-02 2.8032E+00 8.7815E-02 8.300 1.0913E+01 3.6540E-01 2.1162E+00 7.0849E-02 2.8966E+00 9.0725E-02 8.600 1.1138E+01 3.7314E-01 2.1468E+00 7..1897E-02 2.9651E+00 9.2855E-02 8.900 1.1363E+01 3.8084E-01 2.1773E+00 7.2940E-02 3.0253E+00 9.4730E-02 9.200 1.1588E+01 3.8850E-01 2.2077E+00 7.3978E-02 3.0828E+00 9.6518E-02 9.500 1.1811E+01 3.9613E-01 2.2379E+00 7.5011E-02 3.1392E+00 9.8274E-02 9.800 1.2034E+01 4.0372E-01 2.2681E+00 7.6039E-02 3.1952E+00 1.0002E-01 10.100 1.2256E+01 4.1127E-01 2.2982E+00 7.7063E-02 3.2509E+00 1.0175E-01 10.400 1.2477E+01 4.1879E-01 2.3281E+00 7.8081E-02 3.3064E+00 1.0347E-01 24.000 2.1868E+01 7.3135E-01 3.6005E+00 1.2043E-01 5.6628E+00 1.7639E-01 96.000 6.9959E+01 2.2363E+00 6.5287E+00 2.1206E-01 9.9248E+00 3.0688E-01 720.000 2.0565E+02 6.4134E+00 9.1550E+00 2.9291E-01 1.5725E+01 4.8355E-01 Worst Two-Hour Doses EAB Time Whole Body Thyroid TEDE (hr)
(rem)
(rem)
(rem) 1.7 8.1062E-03 3.1481E+00 1.0663E-01
DO00040-122, Revision 0 Page 144 of 155 RADTRAD Dose Conversion Coefficient File FGR11 & 12.inp
D000040-122, Revision 0 Page 145 of 155 FGRDCF 10/24/95 03:24:50 beta-test version 1.10, minor FORTRAN fixes 5/4/95 Implicit daughter halflives (m) less than 90 and less than 0.100 of parent 9 ORGANS DEFINED IN THIS FILE:
GONADS BREAST LUNGS RED MARR BONE SUR THYROID REMAINDER EFFECTIVE SKIN(FGR) 60 NUCLIDES DEFINED IN THIS FILE:
Co-58 Y
Co-60 Y
Kr-85 Kr-85m Kr-87 Kr-88 Rb-86 D
Sr-89 Y
Sr-90 Y
Sr-91 Y
Including:Y-91m Sr-92 Y
Y-90 Y
Y-91 Y
Y-92 Y
Y-93 Y
Zr-95 D
Zr-97 Y
Including:Nb-97m,
Including:Nb-97 Nb-95 Y
Mo-99 Y
Tc-99m Ru-103 D
Y Including:Rh-103m Ru-105 Y
Ru-106 Y
Including:Rh-106 Rh-105 Y
Sb-127 W
Sb-129 W
Te-127 W
Te-127m W
Te-129 W
Te-129m W
Including:Te-129 Te-131m W
Including:Te-131 Te-132 W
1-131 D
1-132 D
1-133 D
1-134 D
1-135 D
Including:Xe-135m Xe-133 Xe-135 Cs-134 D
Cs-136 D
Cs-137 D
Including:Ba-137m Ba-139 D
Ba-140 D
La-140 W
La-141 D
La-142 D
Ce-141 Y
Ce-143 Y
Ce-144 Y
Including:Pr-144m, Including:Pr-144 Pr-143 Y
D000040-122, Revision 0 Page 146 of 155 Nd-147 Y
Np-239 W
Pu-238 Y
Pu-239 Y
Pu-240 Y
Pu-241 Y
Am-241 W
Cm-242 W
Cm-244 W
CLOUDSHINE GROUND GROUND GROUND INHALED SHINE 8HR SHINE 7DAY SHINE RATE ACUTE INHALED CHRONIC INGESTION Co-58 GONADS 4.660E-14 2.867E-11 5.828E-10 9.970E-16-1.000E+00 6.170E-10 1.040E-09 BREAST 5.300E-14 2.737E-11 5.565E-10 9.520E-16-1.000E+00 9.370E-10 1.790E-10 LUNGS 4.640E-14 2.617E-11 5.319E-10 9.100E-16-1.000E+00 1.600E-08 8.530E-11 RED MARR 4.530E-14 2.671E-11 5.430E-10 9.290E-16-1.000E+00 9.230E-10 2.600E-10 BONE SUR 7.410E-14 3.795E-11 7.716E-10 1.320E-15-1.000E+00 6.930E-10 1.250E-10 THYROID 4.770E-14 2.720E-11 5.530E-10 9.460E-16-1.000E+00 8.720E-10 6.310E-11 REMAINDER 4.440E-14 2.585E-11 5.255E-10 8.990E-16-1.000E+00 1.890E-09 1.580E-09 EFFECTIVE 4.760E-14 2.732E-11 5.553E-10 9.500E-16-1.000E+00 2.940E-09 8.090E-10 SKIN(FGR) 5.580E-14 3.278E-11 6.664E-10 1.140E-15-1.000E+00 0.000E+00 0.000E+00 Co-60 GONADS 1.230E-13 7.056E-11 1.480E-09 2.450E-15-1.000E+00 4.760E-09 3.190E-09 BREAST 1.390E-13 6.739E-11 1.413E-09 2.340E-15-1.000E+00 1.840E-08 1.100E-09 LUNGS 1.240E-13 6.537E-11 1.371E-09 2.270E-15-1.000E+00 3.450E-07 8.770E-10 RED MARR 1.230E-13 6.710E-11 1.407E-09 2.330E-15-1.000E+00 1.720E-08 1.320E-09 BONE SUR 1.780E-13 8.956E-11 1.879E-09 3.110E-15-1.000E+00 1.350E-08 9.390E-10 THYROID 1.270E-13 6.480E-11 1.359E-09 2.250E-15-1.000E+00 1.620E-08 7.880E-10 REMAINDER 1.200E-13 6.508E-11 1.365E-09 2.260E-15-1.000E+00 3.600E-08 4.970E-09 EFFECTIVE 1.260E-13 6.768E-11 1.419E-09 2.350E-15-1.000E+00 5.910E-08 2.770E-09 SKIN(FGR) 1.450E-13 7.948E-11 1.667E-09 2.760E-15-1.000E+00 0.000E+00 0.000E+00 Kr-85 GONADS 1.170E-16 8.121E-14 1.704E-12 2.820E-18-1.000E+00 0.000E+00 0.000E+00 BREAST 1.340E-16 7.891E-14 1.656E-12 2.740E-18-1.000E+00 0.000E+00 0.000E+00 LUNGS 1.140E-16 7.056E-14 1.481E-12 2.450E-18-1.000E+00 0.000E+00 0.000E+00 RED MARR 1.090E-16 6.998E-14 1.469E-12 2.430E-18-1.000E+00 0.000E+00 0.000E+00 BONE SUR 2.200E-16 1.287E-13 2.702E-12 4.470E-18-1.000E+00 0.000E+00 0.000E+00 THYROID 1.180E-16 7.459E-14 1.565E-12 2.590E-18-1.000E+00 0.000E+00 0.000E+00 REMAINDER 1.090E-16 6.941E-14 1.457E-12 2.410E-18-1.000E+00 0.000E+00 0.000E+00 EFFECTIVE 1.190E-16 7.603E-14 1.596E-12 2.640E-18-1.000E+00 0.000E+00 0.000E+00 SKIN(FGR)
Kr-85m 1.320E-14 2.304E-11 4.835E-10 8.000E-16-1.000E+00 0.000E+00 0.000E+00 GONADS 7.310E-15 2.594E-12 3.653E-12 1.570E-16-1.000E+00 0.000E+00 0.000E+00 BREAST 8.410E-15 2.527E-12 3.560E-12 1.530E-16-1.000E+00 0.000E+00 0.000E+00 LUNGS 7.040E-15 2.379E-12 3.351E-12 1.440E-16-1.000E+00 0.000E+00 0.000E+00 RED MARR 6.430E-15 2.346E-12 3.304E-12 1.420E-16-1.000E+00 0.000E+00 0.000E+00 BONE SUR 1.880E-14 5.286E-12 7.446E-12 3.200E-16-1.000E+00 0.000E+00 0.000E+00 THYROID 7.330E-15 2.395E-12 3.374E-12 1.450E-16-1.000E+00 0.000E+00 0.000E+00 REMAINDER 6.640E-15 2.313E-12 3.257E-12 1.400E-16-1.000E+00 0.000E+00 0.000E+00 EFFECTIVE 7.480E-15 2.511E-12 3.537E-12 1.520E-16-1.000E+00 0.000E+00 0.000E+00 SKIN(FGR) 2.240E-14 2.247E-11 3.164E-11 1.360E-15-1.000E+00 0.000E+00 0.000E+00 Kr-87 GONADS 4.000E-14 4.962E-12 5.026E-12 7.610E-16-1.000E+00 0.000E+00 0.000E+00 BREAST 4.500E-14 4.740E-12 4.802E-12 7.270E-16-1.000E+00 0.000E+00 0.000E+00 LUNGS 4.040E-14 4.603E-12 4.663E-12 7.060E-16-1.000E+00 0.000E+00 0.000E+00 RED MARR 4.000E-14 4.708E-12 4.769E-12 7.220E-16-1.000E+00 0.000E+00 0.000E+00 BONE SUR 6.020E-14 6.514E-12 6.598E-12 9.990E-16-1.000E+00 0.000E+00 0.000E+00 THYROID 4.130E-14 4.473E-12 4.531E-12 6.860E-16-1.000E+00 0.000E+00 0.000E+00 REMAINDER 3.910E-14 4.590E-12 4.650E-12 7.040E-16-1.000E+00 0.000E+00 0.000E+00 EFFECTIVE 4.120E-14 4.773E-12 4.835E-12 7.320E-16-1.000E+00 0.000E+00 0.000E+00 SKIN(FGR) 1.370E-13 8.802E-11 8.916E-11 1.350E-14-1.000E+00 0.000E+00 0.000E+00 Kr-88 GONADS 9.900E-14 2.278E-11 2.655E-11 1.800E-15-1.000E+00 0.000E+00 0.000E+00 BREAST 1.110E-13 2.177E-11 2.537E-11 1.720E-15-1.000E+00 0.000E+00 0.000E+00
D000040-122, Revision 0 Page 147 of 155 LUNGS 1.010E-13 2.139E-11 2.493E-11 1.690E-15-1.000E+00 0.000E+00 O.000E+00 RED MARR 1.000E-13 2.190E-11 2.552E-11 1.730E-15-1.000E+00 0.000E+00 0.000E+00 BONE SUR 1.390E-13 2.886E-11 3.363E-11 2.280E-15-1.000E+00 0.000E+00 0.000E+00 THYROID 1..030E-13 2.012E-11 2.345E-11 1.590E-15-1.000E+00 0.000E+00 0.000E+00 REMAINDER 9.790E-14 2.139E-11 2.493E-11 1.690E-15-1.000E+00 0.000E+00 0.000E+00 EFFECTIVE 1.020E-13 2.202E-11 2.567E-11 1.740E-15-1.000E+00 0.000E+00 0.000E+00 SKIN(FGR) 1.350E-13 5.607E-11 6.534E-11 4.430E-15-1.000E+00 0.000E+00 0.000E+00 Rb-86 GONADS 4.710E-15 2.788E-12 5.187E-11 9.740E-17-1.000E+00 1.340E-09 2.150E-09 BREAST 5.340E-15 2.662E-12 4.953E-11 9.300E-17-1.000E+00 1.330E-09 2.140E-09 LUNGS 4.710E-15 2.553E-12 4.750E-11 8.920E-17-1.000E+00 3.300E-09 2.140E-09 RED MARR 4.640E-15 2.619E-12 4.873E-11 9.150E-17-1.000E+00 2.320E-09 3.720E-09 BONE SUR 7.050E-15 3.635E-12 6.764E-11 1.270E-16-1.000E+00 4.270E-09 6.860E-09 THYROID 4.840E-15 2.599E-12 4.836E-11 9.080E-17-1.000E+00 1.330E-09 2.140E-09 REMAINDER 4.520E-15 2.542E-12 4.729E-11 8.880E-17-1.000E+00 1.380E-09 2.330E-09 EFFECTIVE 4.810E-15 2.665E-12 4.958E-11 9.310E-17-1.000E+00 1.790E-09 2.530E-09 SKIN(FGR) 4.850E-14 2.210E-10 4.111E-09 7.720E-15-1.000E+00 0.000E+00 0.000E+00 Sr-89 GONADS 7.730E-17 7.155E-14 1.436E-12 2.490E-18-1.000E+00 7.950E-12 8.050E-12 BREAST 9.080E-17 7.212E-14 1.447E-12 2.510E-18-1.000E+00 7.960E-12 7.980E-12 LUNGS 7.080E-17 5.689E-14 1.142E-12 1.980E-18-1.000E+00 8.350E-08 7.970E-12 RED MARR 6.390E-17 5.345E-14 1.073E-12 1.860E-18-1.000E+00 1.070E-10 1.080E-10 BONE SUR 1.940E-16 1.560E-13 3.131E-12 5.430E-18-1.000E+00 1.590E-10 1.610E-10 THYROID 7.600E-17 6.063E-14 1.217E-12 2.110E-18-1.000E+00 7.960E-12 7.970E-12 REMAINDER 6.710E-17 5.603E-14 1.124E-12 1.950E-18-1.000E+00 3.970E-09 8.250E-09 EFFECTIVE 7.730E-17 6.523E-14 1.309E-12 2.270E-18-1.000E+00 1.120E-08 2.500E-09 SKIN(FGR) 3.690E-14 1.914E-10 3.841E-09 6.660E-15-1.000E+00 0.000E+00 0.000E+00 Sr-90 GONADS 7.780E-18 9.590E-15 2.014E-13 3.330E-19-1.000E+00 2.690E-10 5.040E-11 BREAST 9.490E-18 1.008E-14 2.116E-13 3.500E-19-1.000E+00 2.690E-10 5.040E-11 LUNGS 6.440E-18 6.307E-15 1.324E-13 2.190E-19-1.000E+00 2.860E-06 5.040E-11 RED MARR 5.440E-18 5.558E-15 1.167E-13 1.930E-19-1.000E+00 3.280E-08 6.450E-09 BONE SUR 2.280E-17 2.393E-14 5.025E-13 8.310E-19-1.000E+00 7.090E-08 1.390E-08 THYROID 7.330E-18 7.171E-15 1.506E-13 2.490E-19-1.000E+00 2.690E-10 5.040E-11 REMAINDER 6.110E-18 6.422E-15 1.348E-13 2.230E-19-1.000E+00 5.730E-09 6.700E-09 EFFECTIVE 7.530E-18 8.179E-15 1.717E-13 2.840E-19-1.000E+00 3.510E-07 3.230E-09 SKIN(FGR) 9.200E-15 4.032E-12 8.465E-11 1.400E-16-1.000E+00 0.000E+00 0.000E+00 Sr-91 GONADS 4.819E-14 2.155E-11 5.062E-11 1.026E-15-1.000E+00 5.669E-11 2.520E-10 BREAST 5.477E-14 2.059E-11 4.838E-11 9.806E-16-1.000E+00 1.775E-11 3.676E-11 LUNGS 4.803E-14 1.970E-11 4.626E-11 9.376E-16-1.000E+00 2.170E-09 1.055E-11 RED MARR 4.691E-14 2.011E-11 4.722E-11 9.570E-16-1.000E+00 2.275E-11 5.659E-11 BONE SUR 7.674E-14 2.852E-11 6.709E-11 1.360E-15-1.000E+00 1.306E-11 2.070E-11 THYROID 4.938E-14 2.035E-11 4.782E-11 9.693E-16-1.000E+00 9.930E-12 1.968E-12 REMAINDER 4.610E-14 1.948E-11 4.573E-11 9.268E-16-1.000E+00 5.802E-10 2.557E-09 EFFECTIVE 4.924E-14 2.057E-11 4.832E-11 9.793E-16-1.000E+00 4.547E-10 8.455E-10 SKIN(FGR) 9.938E-14 1.748E-10 3.987E-10 8.080E-15-1.000E+00 0.000E+00 0.000E+00 Sr-92 GONADS 6.610E-14 1.593E-11 1.830E-11 1.300E-15-1.000E+00 1.020E-11 8.180E-11 BREAST 7.480E-14 1.520E-11 1.745E-11 1.240E-15-1.000E+00 6.490E-12 1.700E-11 LUNGS 6.670E-14 1.483E-11 1.703E-11 1.210E-15-1.000E+00 1.050E-09 7.220E-12 RED MARR 6.620E-14 1.520E-11 1.745E-11 1.240E-15-1.000E+00 6.980E-12 2.290E-11 BONE SUR 9.490E-14 2.010E-11 2.308E-11 1.640E-15-1.000E+00 4.360E-12 8.490E-12 THYROID 6.820E-14 1.446E-11 1.661E-11 1.180E-15-1.000E+00 3.920E-12 1.300E-12 REMAINDER 6.450E-14 1.471E-11 1.689E-11 1.200E-15-1.000E+00 2.900E-10 1.720E-09 EFFECTIVE 6.790E-14 1.532E-11 1.759E-11 1.250E-15-1.000E+00 2.180E-10 5.430E-10 SKIN(FGR) 8.560E-14 2.280E-11 2.618E-11 1.860E-15-1.000E+00 0.000E+00 0.000E+00 Y-90 GONADS 1.890E-16 1.586E-13 1.601E-12 5.750E-18-1.000E+00 5.170E-13 1.430E-14 BREAST 2.200E-16 1.578E-13 1.593E-12 5.720E-18-1.000E+00 5.170E-13 1.270E-14 LUNGS 1.770E-16 1.313E-13 1.326E-12 4.760E-18-1.000E+00 9.310E-09 1.260E-14 RED MARR 1.620E-16 1.261E-13 1.273E-12 4.570E-18-1.000E+00 1.520E-11 3.700E-13 BONE SUR 4.440E-16 3.228E-13 3.259E-12 1.170E-17-1.000E+00 1.510E-11 3.670E-13 THYROID 1.870E-16 1.385E-13 1.398E-12 5.020E-18-1.000E+00 5.170E-13 1.260E-14
DC0004O-122, Revision 0 Page 148 of 155 REMAINDER 1.680E-16 1.291E-13 1.303E-12 4.680E-18-1.000E+00 3.870E-09 9.680E-09 EFFECTIVE 1.900E-16 1.468E-13 1.482E-12 5.320E-18-1.000E+00 2.280E-09 2.910E-09 SKIN(FGR) 6.240E-14 2.897E-10 2.924E-09 1.050E-14-1.000E+00 0.000E+00 0.000E+00 Y-91 GONADS 2.560E-16 1.756E-13 3.546E-12 6.110E-18-1.000E+00 8.200E-12 3.540E-12 BREAST 2.930E-16 1.713E-13 3.459E-12 5.960E-18-1.000E+00 8.920E-12 5.540E-13 LUNGS 2.500E-16 1.526E-13 3.082E-12 5.310E-18-1.000E+00 9.870E-08 2.020E-13 RED MARR 2.410E-16 1.521E-13 3.070E-12 5.290E-18-1.000E+00 3.190E-10 6.590E-12 BONE SUR 4.560E-16 2.903E-13 5.862E-12 1.010E-17-1.000E+00 3.180E-10 6.130E-12 THYROID 2.600E-16 1.564E-13 3.157E-12 5.440E-18-1.000E+00 8.500E-12 1.290E-13 REMAINDER 2.390E-16 1.509E-13 3.047E-12 5.250E-18-1.000E+00 4.200E-09 8.570E-09 EFFECTIVE 2.600E-16 1.650E-13 3.332E-12 5.740E-18-1.000E+00 1.320E-08 2.570E-09 SKIN(FGR) 3.850E-14 1.989E-10 4.016E-09 6.920E-15-1.000E+00 0.000E+00 0.000E+00 Y-92 GONADS 1.270E-14 3.855E-12 4.872E-12 2.650E-16-1.000E+00 2.610E-12 1.960E-11 BREAST 1.440E-14 3.680E-12 4.652E-12 2.530E-16-1.000E+00 1.500E-12 3.550E-12 LUNGS 1.270E-14 3.535E-12 4.468E-12 2.430E-16-1.000E+00 1.240E-09 1.390E-12 RED MARR 1.250E-14 3.608E-12 4.560E-12 2.480E-16-1.000E+00 2.070E-12 4.910E-12 BONE SUR 1.950E-14 5.091E-12 6.435E-12 3.500E-16-1.000E+00 1.510E-12 1.750E-12 THYROID 1.300E-14 3.579E-12 4.523E-12 2.460E-16-1.000E+00 1.050E-12 1.770E-13 REMAINDER 1.220E-14 3.506E-12 4.431E-12 2.410E-16-1.000E+00 2.030E-10 1.700E-09 EFFECTIVE 1.300E-14 3.680E-12 4.652E-12 2.530E-16-1.000E+00 2.110E-10 5.150E-10 SKIN(FGR) 1.140E-13 2.022E-10 2.556E-10 1.390E-14-1.000E+00 0.000E+00 0.000E+00 Y-93 GONADS 4.670E-15 2.108E-12 4.989E-12 9.510E-17-1.000E+00 5.310E-12 2.200E-11 BREAST 5.300E-15 2.026E-12 4.794E-12 9.140E-17-1.000E+00 1.740E-12 3.130E-12 LUNGS 4.680E-15 1.937E-12 4.585E-12 8.740E-17-1.000E+00 2.520E-09 8.670E-13 RED MARR 4.580E-15 1.972E-12 4.669E-12 8.900E-17-1.000E+00 4.040E-12 4.930E-12 BONE SUR 7.580E-15 2.948E-12 6.977E-12 1.330E-16-1.000E+00 3.140E-12 1.730E-12 THYROID 4.790E-15 1.908E-12 4.516E-12 8.610E-17-1.000E+00 9.260E-13 1.260E-13 REMAINDER 4.510E-15 1.919E-12 4.543E-12 8.660E-17-1.000E+00 9.250E-10 4.090E-09 EFFECTIVE 4.800E-15 2.021E-12 4.784E-12 9.120E-17-1.000E+00 5.820E-10 1.230E-09 SKIN(FGR) 8.500E-14 2.726E-10 6.452E-10 1.230E-14-1.000E+00 0.000E+00 0.000E+00 Zr-95 GONADS 3.530E-14 2.182E-11 4.421E-10 7.590E-16-1.000E+00 1.880E-09 8.160E-10 BREAST 4.010E-14 2.084E-11 4.223E-10 7.250E-16-1.000E+00 1.910E-09 1.050E-10 LUNGS 3.510E-14 1.989E-11 4.030E-10 6.920E-16-1.000E+00 2.170E-09 2.340E-11 RED MARR 3.430E-14 2.030E-11 4.112E-10 7.060E-16-1.000E+00 1.300E-08 2.140E-10 BONE SUR 5.620E-14 2.875E-11 5.824E-10 1.000E-15-1.000E+00 1.030E-07 4.860E-10 THYROID 3.610E-14 2.076E-11 4.205E-10 7.220E-16-1.000E+00 1.440E-09 8.270E-12 REMAINDER 3.360E-14 1.963E-11 3.978E-10 6.830E-16-1.000E+00 2.280E-09 2.530E-09 EFFECTIVE 3.600E-14 2.078E-11 4.211E-10 7.230E-16-1.000E+00 6.390E-09 1.020E-09 SKIN(FGR) 4.500E-14 2.561E-11 5.190E-10 8.910E-16-1.000E+00 0.000E+00 0.000E+00 Zr-97 GONADS 4.331E-14 2.179E-11 7.799E-11 9.253E-16-1.000E+00 1.840E-10 6.228E-10 BREAST 4.928E-14 2.083E-11 7.455E-11 8.846E-16-1.000E+00 4.706E-11 8.137E-11 LUNGS 4.322E-14 1.992E-11 7.127E-11 8.456E-16-1.000E+00 4.108E-09 1.770E-11 RED MARR 4.224E-14 2.034E-11 7.279E-11 8.634E-16-1.000E+00 6.376E-11 1.302E-10 BONE SUR 6.897E-14 2.881E-11 1.031E-10 1.224E-15-1.000E+00 3.504E-11 4.558E-11 THYROID 4.443E-14 2.061E-11 7.377E-11 8.7.55E-16-1.000E+00 2.315E-11 2.671E-12 REMAINDER 4.139E-14 1.966E-11 7.035E-11 8.345E-16-1.000E+00 2.041E-09 6.990E-09 EFFECTIVE 4.432E-14 2.078E-11 7.438E-11 8.824E-16-1.000E+00 1.171E-09 2.283E-09 SKIN(FGR) 9.835E-14 2.281E-10 8.148E-10 9.587E-15-1.000E+00 0.000E+00 0.000E+00 Nb-95 GONADS 3.660E-14 2.253E-11 4.435E-10 7.850E-16-1.000E+00 4.320E-10 8.050E-10 BREAST 4.160E-14 2.150E-11 4.231E-10 7.490E-16-1.000E+00 4.070E-10 1.070E-10 LUNGS 3.650E-14 2.055E-11 4.045E-10 7.160E-16-1.000E+00 8.320E-09 2.740E-11 RED MARR 3.560E-14 2.101E-11 4.135E-10 7.320E-16-1.000E+00 4.420E-10 1.990E-10 BONE SUR 5.790E-14 2.957E-11 5.819E-10 1.030E-15-1.000E+00 5.130E-10 2.940E-10 THYROID 3.750E-14 2.144E-11 4.220E-10 7.470E-16-1.000E+00 3.580E-10 1.180E-11 REMAINDER 3.490E-14 2.032E-11 4.000E-10 7.080E-16-1.000E+00 1.070E-09 1.470E-09 EFFECTIVE 3.740E-14 2.147E-11 4.226E-10 7.480E-16-1.000E+00 1.570E-09 6.950E-10 SKIN(FGR) 4.300E-14 2.598E-11 5.112E-10 9.050E-16-1.000E+00 0.000E+00 0.000E+00 Mo-99
DC0004O-122, Revision 0 Page 149 of 155 GONADS 7.130E-15 4.282E-12 4.403E-11 1.550E-16-1.000E+00 9.510E-11 2.180E-10 BREAST 8.130E-15 4.116E-12 4.233E-11 1.490E-16-1.000E+00 2.750E-11 3.430E-11 LUNGS 7.060E-15 3.867E-12 3.977E-11 1.400E-16-1.000E+00 4.290E-09 1.510E-11 RED MARR 6.820E-15 3.923E-12 4.034E-11 1.420E-16-1.000E+00 5.240E-11 8.320E-11 BONE SUR 1.240E-14 6.105E-12 6.278E-11 2.210E-16-1.000E+00 4.130E-11 6.320E-11 THYROID 7.270E-15 4.033E-12 4.147E-11 1.460E-16-1.000E+00 1.520E-11 1.030E-11 REMAINDER 6.740E-15 3.812E-12 3.920E-11 1.380E-16-1.000E+00 1.740E-09 4.280E-09 EFFECTIVE 7.280E-15 4.061E-12 4.176E-11 1.470E-16-1.000E+00 1.070E-09 1.360E-09 SKIN(FGR) 3.140E-14 1.039E-10 1.068E-09 3.760E-15-1.000E+00 0.000E+00 0.000E+00 Tc-99m GONADS 5.750E-15 2.334E-12 3.877E-12 1.240E-16-1.000E+00 2.770E-12 9.750E-12 BREAST 6.650E-15 2.258E-12 3.752E-12 1.200E-16-1.000E+00 2.150E-12 3.570E-12 LUNGS 5.490E-15 2.127E-12 3.533E-12 1.130E-16-1.000E+00 2.280E-11 3.140E-12 RED MARR 4.910E-15 2.070E-12 3.439E-12 1.100E-16-1.000E+00 3.360E-12 6.290E-12 BONE SUR 1.630E-14 5.383E-12 8.942E-12 2.860E-16-1.000E+00 2.620E-12 4.060E-12 THYROID 5.750E-15 2.145E-12 3.564E-12 1.140E-16-1.000E+00 5.010E-11 8.460E-11 REMAINDER 5.150E-15 2.070E-12 3.439E-12 1.100E-16-1.000E+00 1.020E-11 3.340E-11 EFFECTIVE 5.890E-15 2.277E-12 3.783E-12 1.210E-16-1.000E+00 8.800E-12 1.680E-11 SKIN(FGR) 7.140E-15 2.710E-12 4.502E-12 1.440E-16-1.000E+00 0.000E+00 0.000E+00 Ru-103 GONADS 2.191E-14 1.404E-11 2.783E-10 4.892E-16-1.000E+00 3.070E-10 5.720E-10 BREAST 2.512E-14 1.350E-11 2.677E-10 4.705E-16-1.000E+00 3.110E-10 1.200E-10 LUNGS 2.180E-14 1.273E-11 2.522E-10 4.432E-16-1.000E+00 1.561E-08 7.310E-11 RED MARR 2.100E-14 1.287E-11 2.551E-10 4.483E-16-1.000E+00 3.190E-10 1.660E-10 BONE SUR 3.892E-14 1.958E-11 3.882E-10 6.823E-16-1.000E+00 2.370E-10 9.631E-11 THYROID 2.241E-14 1.331E-11 2.639E-10 4.638E-16-1.000E+00 2.570E-10 6.250E-11 REMAINDER 2.080E-14 1.248E-11 2.472E-10 4.346E-16-1.000E+00 1.250E-09 2.110E-09 EFFECTIVE 2.251E-14 1.332E-11 2.641E-10 4.642E-16-1.000E+00 2.421E-09 8.271E-10 SKIN(FGR) 2.774E-14 1.785E-11 3.543E-10 6.229E-16-1.000E+00 0.000E+00 O.000E+00 Ru-105 GONADS 3.720E-14 1.327E-11 1.861E-11 8.070E-16-1.000E+00 1.590E-11 9.670E-11 BREAST 4.240E-14 1.271E-11 1.783E-11 7.730E-16-1.000E+00 6.610E-12 1.590E-11 LUNGS 3.700E-14 1.210E-11 1.697E-11 7.360E-16-1.000E+00 5.730E-10 6.210E-12 RED MARR 3.590E-14 1.230E-11 1.725E-11 7.480E-16-1.000E+00 7.700E-12 2.350E-11 BONE SUR 6.280E-14 1.809E-11 2.537E-11 1.100E-15-1.000E+00 4.620E-12 8.890E-12 THYROID 3.800E-14 1.260E-11 1.766E-11 7.660E-16-1.000E+00 4.150E-12 1.820E-12 REMAINDER 3.540E-14 1.189E-11 1.667E-11 7.230E-16-1.000E+00 1.610E-10 8.540E-10 EFFECTIVE 3.810E-14 1.265E-11 1.773E-11 7.690E-16-1.000E+00 1.230E-10 2.870E-10 SKIN(FGR) 6.730E-14 7.368E-11 1.033E-10 4.480E-15-1.000E+00 0.000E+00 0.000E+00 Ru-106 GONADS 1.010E-14 6.411E-12 1.340E-10 2.230E-16-1.000E+00 1.300E-09 1.640E-09 BREAST 1.160E-14 6.152E-12 1.286E-10 2.140E-16-1.000E+00 1.780E-09 1.440E-09 LUNGS 1.010E-14 5.836E-12 1.220E-10 2.030E-16-1.000E+00 1.040E-06 1.420E-09 RED MARR 9.750E-15 5.893E-12 1.232E-10 2.050E-16-1.000E+00 1.760E-09 1.460E-09 BONE SUR 1.720E-14 8.883E-12 1.856E-10 3.090E-16-1.000E+00 1.610E-09 1.430E-09 THYROID 1.030E-14 6.066E-12 1.268E-10 2.110E-16-1.000E+00 1.720E-09 1.410E-09 REMAINDER 9.630E-15 5.721E-12 1.196E-10 1.990E-16-1.000E+00 1.200E-08 2.110E-08 EFFECTIVE 1.040E-14 6.095E-12 1.274E-10 2.120E-16-1.000E+00 1.290E-07 7.400E-09 SKIN(FGR) 1.090E-13 4.082E-10 8.531E-09 1.420E-14-1.000E+00 0.000E+00 0.000E+00 Rh-105 GONADS 3.640E-15 2.127E-12 1.411E-11 7.980E-17-1.000E+00 2.110E-11 5.800E-11 BREAST 4.160E-15 2.063E-12 1.369E-11 7.740E-17-1.000E+00 5.610E-12 8.970E-12 LUNGS 3.570E-15 1.935E-12 1.284E-11 7.260E-17-1.000E+00 9.580E-10 3.860E-12 RED MARR 3.380E-15 1.946E-12 1.291E-11 7.300E-17-1.000E+00 7.770E-12 1.470E-11 BONE SUR 7.530E-15 3.332E-12 2.210E-11 1.250E-16-1.000E+00 4.460E-12 6.750E-12 THYROID 3.680E-15 1.983E-12 1.316E-11 7.440E-17-1.000E+00 2.880E-12 2.910E-12 REMAINDER 3.390E-15 1.885E-12 1.250E-11 7.070E-17-1.000E+00 4.530E-10 1.270E-09 EFFECTIVE 3.720E-15 2.031E-12 1.347E-11 7.620E-17-1.000E+00 2.580E-10 3.990E-10 SKIN(FGR) 1.070E-14 4.691E-12 3.112E-11 1.760E-16-1.000E+00 0.000E+00 0.000E+00 Sb-127 GONADS 3.260E-14 1.985E-11 2.441E-10 7.100E-16-1.000E+00 2.520E-10 6.140E-10 BREAST 3.720E-14 1.904E-11 2.341E-10 6.810E-16-1.000E+00 9.120E-11 7.600E-11 LUNGS 3.240E-14 1.809E-11 2.224E-10 6.470E-16-1.000E+00 6.940E-09 1.570E-11 RED MARR 3.140E-14 1.834E-11 2.255E-10 6.560E-16-1.000E+00 1.610E-10 1.330E-10
D000040-122, Revision 0 Page 150 of 155 BONE SUR 5.520E-14 2.720E-11 3.345E-10 9.730E-16-1.000E+00 1.340E-10 5.240E-11 THYROID 3.330E-14 1.884E-11 2.317E-10 6.740E-16-1.000E+00 6.150E-11 4.640E-12 REMAINDER 3.090E-14 1.775E-11 2.183E-10 6.350E-16-1.000E+00 2.330E-09 5.870E-09 EFFECTIVE 3.330E-14 1.890E-11 2.324E-10 6.760E-16-1.000E+00 1.630E-09 1.950E-09 SKIN(FGR) 5.580E-14 7.967E-11 9.799E-10 2.850E-15-1.000E+00 0.000E+00 0.000E+00 Sb-129 GONADS 6.970E-14 2.336E-11 3.231E-11 1.440E-15-1.000E+00 2.150E-11 1.510E-10 BREAST 7.910E-14 2.222E-11 3.074E-11 1.370E-15-1.000E+00 1.280E-1112.560E-11 LUNGS 6.980E-14 2.141E-11 2.962E-11 1.320E-15-1.000E+00 8.980E-10 9.390E-12 RED MARR 6.860E-14 2.190E-11 3.029E-11 1.350E-15-1.000E+00 1.700E-11 3.670E-11 BONE SUR 1.070E-13 3.033E-11 4.196E-11 1.870E-15-1.000E+00 1.460E-11 1.340E-11 THYROID 7.160E-14 2.174E-11 3.007E-11 1.340E-15-1.000E+00 9.720E-12 1.470E-12 REMAINDER 6.710E-14 2.125E-11 2.939E-11 1.310E-15-1.000E+00 1.870E-10 1.450E-09 EFFECTIVE 7.140E-14 2.238E-11 3.096E-11 1.380E-15-1.000E+00 1.740E-10 4.840E-10 SKIN(FGR) 1.050E-13 8.273E-11 1.144E-10 5.100E-15-1.000E+00 0.000E+00 0.000E+00 Te-127 GONADS 2.370E-16 1.191E-13 2.661E-13 5.480E-18-1.000E+00 2.020E-12 4.020E-12 BREAST 2.730E-16 1.158E-13 2.588E-13 5.330E-18-1.000E+00 1.880E-12 3.000E-12 LUNGS 2.320E-16 1.060E-13 2.370E-13 4.880E-18-1.000E+00 4.270E-10 2.890E-12 RED MARR 2.210E-16 1.058E-13 2.365E-13 4.870E-18-1.000E+00 4.090E-12 6.570E-12 BONE SUR 4.650E-16 1.862E-13 4.162E-13 8.570E-18-1.000E+00 4.090E-12 6.460E-12 THYROID 2.400E-16 1.106E-13 2.472E-13 5.090E-18-1.000E+00 1.840E-12 2.860E-12 REMAINDER 2.210E-16 1.036E-13 2.316E-13 4.770E-18-1.000E+00 1.110E-10 6.130E-10 EFFECTIVE 2.420E-16 1.125E-13 2.515E-13 5.180E-18-1.000E+00 8.600E-11 1.870E-10 SKIN(FGR) 1.140E-14 1.173E-11 2.622E-11 5.400E-16-1.000E+00 0.000E+00 0.000E+00 Te-127m GONADS 1.900E-16 4.689E-13 9.642E-12 1.630E-17-1.000E+00 1.100E-10 1.250E-10 BREAST 2.690E-16 5.150E-13 1.059E-11 1.790E-17-1.000E+00 1.100E-10 9.740E-11 LUNGS 7.620E-17 1.602E-13 3.295E-12 5.570E-18-1.000E+00 3.340E-08 9.620E-11 RED MARR 6.430E-17 1.249E-13 2.567E-12 4.340E-18-1.000E+00 5.360E-09 5.430E-09 BONE SUR 3.940E-16 9.005E-13 1.852E-11 3.130E-17-1.000E+00 2.040E-08 2.070E-08 THYROID 1.500E-16 2.779E-13 5.714E-12 9.660E-18-1.000E+00 9.660E-11 9.430E-11 REMAINDER 8.640E-17 1.999E-13 4.111E-12 6.950E-18-1.000E+00 1.660E-09 2.980E-09 EFFECTIVE 1.470E-16 3.251E-13 6.684E-12 1.130E-17-1.000E+00 5.810E-09 2.230E-09 SKIN(FGR) 8.490E-16 1.496E-12 3.076E-11 5.200E-17-1.000E+00 0.000E+00 0.000E+00 Te-129 GONADS 2.710E-15 3.889E-13 3.922E-13 6.510E-17-1.000E+00 5.050E-13 1.590E-12 BREAST 3.120E-15 3.800E-13 3.832E-13 6.360E-17-1.000E+00 5.390E-13 6.050E-13 LUNGS 2.640E-15 3.298E-13 3.326E-13 5.520E-17-1.000E+00 1.530E-10 4.910E-13 RED MARR 2.540E-15 3.298E-13 3.326E-13 5.520E-17-1.000E+00 6.190E-13 7.640E-13 BONE SUR 4.880E-15 5.753E-13 5.802E-13 9.630E-17-1.000E+00 6.220E-13 5.400E-13 THYROID 2.740E-15 3.525E-13 3.555E-13 5.900E-17-1.000E+00 5.090E-13 3.360E-13 REMAINDER 2.520E-15 3.262E-13 3.289E-13 5.460E-17-1.000E+00 7.280E-12 1.790E-10 EFFECTIVE 2.750E-15 3.590E-13 3.621E-13 6.010E-17-1.000E+00 2.090E-11 5.450E-11 SKIN(FGR) 3.570E-14 3.429E-11 3.458E-11 5.740E-15-1.000E+00 0.000E+00 0.000E+00 Te-129m GONADS 3.321E-15 2.206E-12 4.799E-11 8.561E-17-1.000E+00 1.783E-10 2.420E-10 BREAST 3.838E-15 2.181E-12 4.739E-11 8.454E-17-1.000E+00 1.694E-10 1.664E-10 LUNGS 3.176E-15 1.741E-12 3.815E-11 6.808E-17-1.000E+00 4.040E-08 1.593E-10 RED MARR 3.071E-15 1.729E-12 3.793E-11 6.768E-17-1.000E+00 3.100E-09 3.500E-09 BONE SUR 5.772E-15 3.287E-12 7.147E-11 1.275E-16-1.000E+00 7.050E-09 7.990E-09 THYROID 3.341E-15 1.923E-12 4.201E-11 7.495E-17-1.000E+00 1.563E-10 1.572E-10 REMAINDER 3.048E-15 1.746E-12 3.822E-11 6.819E-17-1.000E+00 3.275E-09 7.196E-09 EFFECTIVE 3.337E-15 1.974E-12 4.308E-11 7.686E-17-1.000E+00 6.484E-09 2.925E-09 SKIN(FGR) 3.811E-14 1.501E-10 3.360E-09 6.001E-15-1.000E+00 0.000E+00 0.000E+00 Te-131m GONADS 7.292E-14 4.020E-11 2.343E-10 1.535E-15-1.000E+00 2.345E-10 7.415E-10 BREAST 8.286E-14 3.853E-11 2.246E-10 1.472E-15-1.000E+00 9.309E-11 1.361E-10 LUNGS 7.265E-14 3.657E-11 2.131E-10 1.397E-15-1.000E+00 2.296E-09 6.335E-11 RED MARR 7.097E-14 3.736E-11 2.178E-10 1.427E-15-1.000E+00 1.417E-10 2.435E-10 BONE SUR 1.174E-13 5.467E-11 3.189E-10 2.090E-15-1.000E+00 2.276E-10 3.248E-10 THYROID 7.471E-14 3.741E-11 2.181E-10 1.429E-15-1.000E+00 3.669E-08 4.383E-08 REMAINDER 6.965E-14 3.626E-11 2.113E-10 1.385E-15-1.000E+00 9.509E-10 3.153E-09 EFFECTIVE 7.463E-14 3.825E-11 2.229E-10 1.461E-15-1.000E+00 1.758E-09 2.514E-09
D000040-122, Revision 0 Page 151 of 155 SKIN(FGR) 1.038E-13 1.033E-10 6.188E-10 4.056E-15-1.000E+00 0.000E+00 0.000E+00 Te-132 GONADS 1.020E-14 6.812E-12 7.706E-11 2.450E-16-1.000E+00 4.150E-10 5.410E-10 BREAST 1.180E-14 6.756E-12 7.643E-11 2.430E-16-1.000E+00 3.630E-10 3.500E-10 LUNGS 9.650E-15 5.727E-12 6.479E-11 2.060E-16-1.000E+00 1.670E-09 3.300E-10 RED MARR 8.950E-15 5.588E-12 6.322E-11 2.010E-16-1.000E+00 4.270E-10 4.440E-10 BONE SUR 2.420E-14 1.273E-11 1.441E-10 4.580E-16-1.000E+00 7.120E-10 8.300E-10 THYROID 1.020E-14 5.978E-12 6.762E-11 2.150E-16-1.000E+00 6.280E-08 5.950E-08 REMAINDER 9.160E-15 5.644E-12 6.385E-11 2.030E-16-1.000E+00 7.890E-10 1.490E-09 EFFECTIVE 1.030E-14 6.339E-12 7.171E-11 2.280E-16-1.000E+00 2.550E-09 2.540E-09 SKIN(FGR) 1.390E-14 8.313E-12 9.405E-11 2.990E-16-1.000E+00 0.000E+00 0.000E+00 1-131 GONADS 1.780E-14 1.119E-11 1.789E-10 3.940E-16-1.000E+00 2.530E-11 4.070E-11 BREAST 2.040E-14 1.082E-11 1.730E-10 3.810E-16-1.000E+00 7.880E-11 1.210E-10 LUNGS 1.760E-14 1.016E-11 1.626E-10 3.580E-16-1.000E+00 6.570E-10 1.020E-10 RED MARR 1.680E-14 1.022E-11 1.635E-10 3.600E-16-1.000E+00 6.260E-11 9.440E-11 BONE SUR 3.450E-14 1.675E-11 2.679E-10 5.900E-16-1.000E+00 5.730E-11 8.720E-11 THYROID 1.810E-14 1.053E-11 1.685E-10 3.710E-16-1.000E+00 2.920E-07 4.760E-07 REMAINDER 1.670E-14 9.908E-12 1.585E-10 3.490E-16-1.000E+00 8.030E-11 1.570E-10 EFFECTIVE 1.820E-14 1.067E-11 1.707E-10 3.760E-16-1.000E+00 8.890E-09 1.440E-08 SKIN(FGR) 2.980E-14 1.825E-11 2.920E-10 6.430E-16-1.000E+00 0.000E+00 0.000E+00 1-132 GONADS 1.090E-13 2.523E-11 2.771E-11 2.320E-15-1.000E+00 9.950E-12 2.330E-11 BREAST 1.240E-13 2.414E-11 2.652E-11 2.220E-15-1.000E+00 1.410E-11 2.520E-11 LUNGS 1.090E-13 2.305E-11 2.532E-11 2.120E-15-1.000E+00 2.710E-10 2.640E-11 RED MARR 1.070E-13 2.360E-11 2.592E-11 2.170E-15-1.000E+00 1.400E-11 2.460E-11 BONE SUR 1.730E-13 3.327E-11 3.655E-11 3.060E-15-1.000E+00 1.240E-11 2.190E-11 THYROID 1.120E-13 2.381E-11 2.616E-11 2.190E-15-1.000E+00 1.740E-09 3.870E-09 REMAINDER 1.050E-13 2.283E-11 2.509E-11 2.100E-15-1.000E+00 3.780E-11 1.650E-10 EFFECTIVE 1.120E-13 2.403E-11 2.640E-11 2.210E-15-1.000E+00 1.030E-10 1.820E-10 SKIN(FGR) 1.580E-13 8.199E-11 9.007E-11 7.540E-15-1.000E+00 0.000E+00 0.000E+00 1-133 GONADS 2.870E-14 1.585E-11 6.748E-11 6.270E-16-1.000E+00 1.950E-11 3.630E-11 BREAST 3.280E-14 1.519E-11 6.468E-11 6.010E-16-1.000E+00 2.940E-11 4.680E-11 LUNGS 2.860E-14 1.446E-11 6.156E-11 5.720E-16-1.000E+00 8.200E-10 4.530E-11 RED MARR 2.770E-14 1.466E-11 6.242E-11 5.800E-16-1.000E+00 2.720E-11 4.300E-11 BONE SUR 4.870E-14 2.161E-11 9.202E-11 8.550E-16-1.000E+00 2.520E-11 4.070E-11 THYROID 2.930E-14 1.502E-11 6.393E-11 5.940E-16-1.000E+00 4.860E-08 9.100E-08 REMAINDER 2.730E-14 1.418E-11 6.038E-11 5.610E-16-1.000E+00 5.000E-11 1.550E-10 EFFECTIVE 2.940E-14 1.509E-11 6.425E-11 5.970E-16-1.000E+00 1.580E-09 2.800E-09 SKIN(FGR) 5.830E-14 1.150E-10 4.897E-10 4.550E-15-1.000E+00 0.000E+00 0.000E+00 1-134 GONADS 1.270E-13 1.200E-11 1.202E-11 2.640E-15-1.000E+00 4.250E-12 1.100E-11 BREAST 1.440E-13 1.145E-11 1.147E-11 2.520E-15-1.000E+00 6.170E-12 1.170E-11 LUNGS 1.270E-13 1.100E-11 1.102E-11 2.420E-15-1.000E+00 1.430E-10 1.260E-11 RED MARR 1.250E-13 1.127E-11 1.129E-11 2.480E-15-1.000E+00 6.080E-12 1.090E-11 BONE SUR 1.960E-13 1.568E-11 1.571E-11 3.450E-15-1.000E+00 5.310E-12 9.320E-12 THYROID 1.300E-13 1.127E-11 1.129E-11 2.480E-15-1.000E+00 2.880E-10 6.210E-10 REMAINDER 1.220E-13 1.091E-11 1.093E-11 2.400E-15-1.000E+00 2.270E-11 1.340E-10 EFFECTIVE 1.300E-13 1.150E-11 1.152E-11 2.530E-15-1.000E+00 3.550E-11 6.660E-11 SKIN(FGR) 1.870E-13 4.477E-11 4.485E-11 9.850E-15-1.000E+00 0.000E+00 0.000E+00 1-135 GONADS 8.078E-14 3.113E-11 5.489E-11 1.599E-15-1.000E+00 1.700E-11 3.610E-11 BREAST 9.143E-14 2.971E-11 5.240E-11 1.526E-15-1.000E+00 2.340E-11 3.850E-11 LUNGS 8.145E-14 2.886E-11 5.089E-11 1.482E-15-1.000E+00 4.410E-10 3.750E-11 RED MARR 8.054E-14 2.965E-11 5.228E-11 1.523E-15-1.000E+00 2.240E-11 3.650E-11 BONE SUR 1.184E-13 3.983E-11 7.024E-11 2.046E-15-1.000E+00 2.010E-11 3.360E-11 THYROID 8.324E-14 2.852E-11 5.030E-11 1.465E-15-1.000E+00 8.460E-09 1.790E-08 REMAINDER 7.861E-14 2.883E-11 5.084E-11 1.481E-15-1.000E+00 4.700E-11 1.540E=10 EFFECTIVE 8.294E-14 2.989E-11 5.271E-11 1.535E-15-1.000E+00 3.320E-10 6.080E-10 SKIN(FGR) 1.156E-13 9.826E-11 1.733E-10 5.047E-15-1.000E+00 0.000E+00 0.000E+00 Xe-133 GONADS 1.610E-15 1.465E-12 2.052E-11 5.200E-17-1.000E+00 0.000E+00 0.000E+00 BREAST 1.960E-15 1.505E-12 2.107E-11 5.340E-17-1.000E+00 0.000E+00 0.000E+00
D000040-122, Revision 0 Page 152 of 155 LUNGS 1.320E-15 1.045E-12 1.464E-11 3.710E-17-1.000E+00 0.000E+00 0.000E+00 RED MARR 1.070E-15 8.791E-13 1.231E-11 3.120E-17-1.000E+00 0.000E+00 0.000E+00 BONE SUR 5.130E-15 4.254E-12 5.958E-11 1.510E-16-1.000E+00 0.000E+00 0.000E+00 THYROID 1.510E-15 1.181E-12 1.653E-11 4.190E-17-1.000E+00 0.000E+00 0.000E+00 REMAINDER 1.240E-15 1.042E-12 1.460E-11 3.700E-17-1.000E+00 0.000E+00 0.000E+00 EFFECTIVE 1.560E-15 1.299E-12 1.819E-11 4.610E-17-1.000E+00 0.000E+00 0.000E+00 SKIN(FGR) 4.970E-15 1.953E-12 2.734E-11 6.930E-17-1.000E+00 0.000E+00 0.000E+00 Xe-135 GONADS 1.170E-14 5.455E-12 1.194E-11 2.530E-16-1.000E+00 0.000E+00 0.000E+00 BREAST 1.330E-14 5.325E-12 1.166E-11 2.470E-16-1..000E+00 0.000E+00 0.000E+00 LUNGS 1.130E-14 4.959E-12 1.086E-11 2.300E-16-1.000E+00 0.000E+00 0.000E+00 RED MARR 1.070E-14 4.959E-12 1.086E-11 2.300E-16-1.000E+00 0.000E+00 0.000E+00 BONE SUR 2.570E-14 9.120E-12 1.997E-11 4.230E-16-1.000E+00 0.000E+00 0.000E+00 THYROID 1.180E-14 5.023E-12 1.100E-11 2.330E-16-1.000E+00 0.000E+00 0.000E+00 REMAINDER 1.080E-14 4.829E-12 1.058E-11 2.240E-16-1.000E+00 0.000E+00 0.000E+00 EFFECTIVE 1.190E-14 5.217E-12 1.142E-11 2.420E-16-1.000E+00 0.000E+00 0.000E+00 SKIN(FGR) 3.120E-14 4.506E-11 9.867E-11 2.090E-15-1.000E+00 0.000E+00 0.000E+00 Cs-134 GONADS 7.400E-14 4.607E-11 9.646E-10 1.600E-15-1.000E+00 1.300E-08 2.060E-08 BREAST 8.430E-14 4.406E-11 9.224E-10 1.530E-15-1.000E+00 1.080E-08 1.720E-08 LUNGS 7.370E-14 4.204E-11 8.802E-10 1.460E-15-1.000E+00 1.180E-08 1.760E-08 RED MARR 7.190E-14 4.262E-11 8.922E-10 1.480E-15-1.000E+00 1.180E-08 1.870E-08 BONE SUR 1.200E-13 6.105E-11 1.278E-09 2.120E-15-1.000E+00 1.100E-08 1.740E-08 THYROID 7.570E-14 4.377E-11 9.163E-10 1.520E-15-1.000E+00 1.110E-08 1.760E-08 REMAINDER 7.060E-14 4.147E-11 8.681E-10 1.440E-15-1.000E+00 1.390E-08 2.210E-08 EFFECTIVE 7.570E-14 4.377E-11 9.163E-10 1.520E-15-1.000E+00 1.250E-08 1.980E-08 SKIN(FGR) 9.450E-14 6.249E-11 1.308E-09 2.170E-15-1.000E+00 0.000E+00 0.000E+00 Cs-136 GONADS 1.040E-13 6.223E-11 1.102E-09 2.180E-15-1.000E+00 1.880E-09 3.040E-09 BREAST 1.180E-13 5.966E-11 1.056E-09 2.090E-15-1.000E+00 1.670E-09 2.650E-09 LUNGS 1.040E-13 5.710E-11 1.011E-09 2.000E-15-1.000E+00 2.320E-09 2.620E-09 RED MARR 1.010E-13 5.824E-11 1.031E-09 2.040E-15-1.000E+00 1.860E-09 2.950E-09 BONE SUR 1.660E-13 8.422E-11 1.491E-09 2.950E-15-1.000E+00 1.700E-09 2.710E-09 THYROID 1.070E-13 5.852E-11 1.036E-09 2.050E-15-1.000E+00 1.730E-09 2.740E-09 REMAINDER 9.950E-14 5.652E-11 1.001E-09 1.980E-15-1.000E+00 2.190E-09 3.520E-09 EFFECTIVE 1.060E-13 5.966E-11 1.056E-09 2.090E-15-1.000E+00 1.980E-09 3.040E-09 SKIN(FGR) 1.250E-13 7.251E-11 1.284E-09 2.540E-15-1.000E+00 0.000E+00 0.000E+00 Cs-137 GONADS 2.669E-14 1.669E-11 3.530E-10 5.840E-16-1.000E+00 8.760E-09 1.390E-08 BREAST 3.047E-14 1.596E-11 3.376E-10 5.585E-16-1.000E+00 7.840E-09 1.240E-08 LUNGS 2.649E-14 1.517E-11 3.209E-10 5.309E-16-1.000E+00 8.820E-09 1.270E-08 RED MARR 2.583E-14 1.542E-11 3.260E-10 5.3.94E-16-1.000E+00 8.300E-09 1.320E-08 BONE SUR 4.382E-14 2.238E-11 4.734E-10 7.832E-16-1.000E+00 7.940E-09 1.260E-08 THYROID 2.725E-14 1.588E-11 3.358E-10 5.556E-16-1.000E+00 7.930E-09 1.260E-08 REMAINDER 2.536E-14 1.490E-11 3.152E-10 5.215E-16-1.000E+00 9.120E-09 1.450E-08 EFFECTIVE 2.725E-14 1.585E-11 3.353E-10 5.546E-16-1.000E+00 8.630E-09 1.350E-08 SKIN(FGR) 4.392E-14 5.253E-11 1.110E-09 1.836E-15-1.000E+00 0.000E+00 0.000E+00 Ba-139 GONADS 2.130E-15 3.368E-13 3.429E-13 4.790E-17-1.000E+00 2.560E-12 1.560E-12 BREAST 2.450E-15 3.297E-13 3.357E-13 4.690E-17-1.000E+00 2.460E-12 5.170E-13 LUNGS 2.030E-15 3.002E-13 3.057E-13 4.270E-17-1.000E+00 2.530E-10 3.890E-13 RED MARR 1.870E-15 2.932E-13 2.985E-13 4.170E-17-1.000E+00 3.410E-12 8.590E-13 BONE SUR 5.290E-15 6.841E-13 6.965E-13 9.730E-17-1.000E+00 2.490E-12 4.380E-13 THYROID 2.130E-15 3.044E-13 3.100E-13 4.330E-17-1.000E+00 2.400E-12 2.660E-13 REMAINDER 1.920E-15 2.932E-13 2.985E-13 4.170E-17-1.000E+00 4.820E-11 3.570E-10 EFFECTIVE 2.170E-15 3.227E-13 3.286E-13 4.590E-17-1.000E+00 4.640E-11 1.080E-10 SKIN(FGR) 6.160E-14 7.241E-11 7.373E-11 1.030E-14-1.000E+00 0.000E+00 0.000E+00 Ba-140 GONADS 8.410E-15 5.451E-12 9.607E-11 1.910E-16-1.000E+00 4.300E-10 9.960E-10 BREAST 9.640E-15 5.280E-12 9.305E-11 1.850E-16-1.000E+00 2.870E-10 1.590E-10 LUNGS 8.270E-15 4.852E-12 8.550E-11 1.700E-16-1.000E+00 1.660E-09 6.630E-11 RED MARR 7.930E-15 4.880E-12 8.601E-11 1.710E-16-1.000E+00 1.290E-09 4.390E-10 BONE SUR 1.550E-14 8.020E-12 1.413E-10 2.810E-16-1.000E+00 2.410E-09 5.530E-10 THYROID 8.530E-15 5.109E-12 9.003E-11 1.790E-16-1.000E+00 2.560E-10 5.250E-11
D00004O-122, Revision 0 Page 153 of 155 REMAINDER 7.890E-15 4.766E-12 8.399E-11 1.670E-16-1.000E+00 1.410E-09 7.370E-09 EFFECTIVE 8.580E-15 5.137E-12 9.053E-11 1.800E-16-1.000E+00 1.010E-09 2.560E-09 SKIN(FGR) 2.520E-14 5.565E-11 9.808E-10 1.950E-15-1.000E+00 0.000E+00 0.000E+00 La-140 GONADS 1.140E-13 6.027E-11 4.425E-10 2.240E-15-1.000E+00 4.540E-10 1.340E-09 BREAST 1.290E-13 5.758E-11 4.228E-10 2.140E-15-1.000E+00 1.450E-10 1.800E-10 LUNGS 1.150E-13 5.596E-11 4.109E-10 2.080E-15-1.000E+00 4.210E-09 4.010E-11 RED MARR 1.140E-13 5.731E-11 4.208E-10 2.130E-15-1.000E+00 2.140E-10 2.810E-10 BONE SUR 1.690E-13 7.776E-11 5.709E-10 2.890E-15-1.000E+00 1.410E-10 9.770E-11 THYROID 1.180E-13 5.462E-11 4.010E-10 2.030E-15-1.000E+00 6.870E-11 6.400E-12 REMAINDER 1.110E-13 5.569E-11 4.089E-10 2.070E-15-1.000E+00 2.120E-09 6.260E-09 EFFECTIVE 1.170E-13 5.812E-11 4.267E-10 2.160E-15-1.000E+00 1.310E-09 2.280E-09 SKIN(FGR) 1.660E-13 2.217E-10 1.628E-09 8.240E-15-1.000E+00 0.000E+00 0.000E+00 La-141 GONADS 2.330E-15 7.315E-13 9.675E-13 4.740E-17-1.000E+00 1.010E-11 3.770E-12 BREAST 2.640E-15 7.007E-13 9.267E-13 4.540E-17-1.000E+00 9.840E-12 7.070E-13 LUNGS 2.340E-15 6.713E-13 8.879E-13 4.350E-17-1.000E+00 6.460E-10 2.720E-13 RED MARR 2.310E-15 6.852E-13 9.063E-13 4.440E-17-1.000E+00 2.930E-11 1.070E-12 BONE SUR 3.490E-15 9.923E-13 1.312E-12 6.430E-17-1.000E+00 1.200E-10 6.060E-13 THYROID 2.390E-15 6.590E-13 8.716E-13 4.270E-17-1.000E+00 9.400E-12 5.290E-14 REMAINDER 2.260E-15 6.682E-13 8.838E-13 4.330E-17-1.000E+00 2.280E-10 1.240E-09 EFFECTIVE 2.390E-15 7.007E-13 9.267E-13 4.540E-17-1.000E+00 1.570E-10 3.740E-10 SKIN(FGR) 6.580E-14 1.667E-10 2.204E-10 1.080E-14-1.000E+00 0.000E+00 0.000E+00 La-142 GONADS 1.400E-13 1.978E-11 2.034E-11 2.540E-15-1.000E+00 1.660E-11 6.990E-11 BREAST 1.570E-13 1.885E-11 1.938E-11 2.420E-15-1.000E+00 1.130E-11 1.540E-11 LUNGS 1.420E-13 1.846E-11 1.898E-11 2.370E-15-1.000E+00 3.010E-10 8.400E-12 RED MARR 1.420E-13 1.900E-11 1.954E-11 2.440E-15-1.000E+00 1.360E-11 1.930E-11 BONE SUR 1.950E-13 2.484E-11 2.554E-11 3.190E-15-1.000E+00 1.110E-11 7.400E-12 THYROID 1.450E-13 1.768E-11 1.818E-11 2.270E-15-1.000E+00 8.740E-12 1.160E-12 REMAINDER 1.380E-13 1.853E-11 1.906E-11 2.380E-15-1.000E+00 8.070E-11 5.200E-10 EFFECTIVE 1.440E-13 1.916E-11 1.970E-11 2.460E-15-1.000E+00 6.840E-11 1.790E-10 SKIN(FGR) 2.160E-13 9.111E-11 9.368E-11 1.170E-14-1.000E+00 0.000E+00 0.000E+00 Ce-141 GONADS 3.380E-15 2.213E-12 4.332E-11 7.710E-17-1.000E+00 5.540E-11 1.080E-10 BREAST 3.930E-15 2.170E-12 4.247E-11 7.560E-17-1.000E+00 4.460E-11 1.110E-11 LUNGS 3.170E-15 1.951E-12 3.820E-11 6.800E-17-1.000E+00 1.670E-08 1.430E-12 RED MARR 2.830E-15 1.860E-12 3.641E-11 6.480E-17-1.000E+00 8.960E-11 3.390E-11 BONE SUR 9.410E-15 5.166E-12 1.011E-10 1.800E-16-1.000E+00 2.540E-10 2.300E-11 THYROID 3.350E-15 2.003E-12 3.922E-11 6.980E-17-1.000E+00 2.550E-11 1.800E-13 REMAINDER 2.980E-15 1.894E-12 3.708E-11 6.600E-17-1.000E+00 1.260E-09 2.500E-09 EFFECTIVE.
3.430E-15 2.118E-12 4.146E-11 7.380E-17-1.000E+00 2.420E-09 7.830E-10 SKIN(FGR) 1.020E-14 3.788E-12 7.416E-11 1.320E-16-1.000E+00 0.000E+00 0.000E+00 Ce-143 GONADS 1.280E-14 7.900E-12 4.958E-11 2.980E-16-1.000E+00 7.530E-11 2.120E-10 BREAST 1.470E-14 7.688E-12 4.825E-11 2.900E-16-1.000E+00 1.660E-11 2.320E-11 LUNGS 1.230E-14 6.893E-12 4.325E-11 2.600E-16-1.000E+00 3.880E-09 3.820E-12 RED MARR 1.170E-14 6.787E-12 4.259E-11 2.560E-16-1.000E+00 2.960E-11 5.070E-11 BONE SUR 2.520E-14 1.323E-11 8.302E-11 4.990E-16-1.000E+00 1.640E-11 1.610E-11 THYROID 1.280E-14 7.211E-12 4.525E-11 2.720E-16-1.000E+00 6.230E-12 4.350E-13 REMAINDER 1.170E-14 6.734E-12 4.226E-11 2.540E-16-1.000E+00 1.420E-09 3.890E-09 EFFECTIVE 1.290E-14 7.396E-12 4.642E-11 2.790E-16-1.000E+00 9'.160E-10 1.230E-09 SKIN(FGR) 3.960E-14 1.058E-10 6.638E-10 3.990E-15-1.000E+00 0.000E+00 0.000E+00 Ce-144 GONADS 2.725E-15 6.328E-13 1.319E-11 6.088E-17-1.000E+00 2.390E-10 6.987E-11 BREAST 3.129E-15 6.274E-13 1.307E-11 5.922E-17-1.000E+00 3.480E-10 1.223E-11 LUNGS 2.639E-15 5.228E-13 1.089E-11 5.362E-17-1.000E+00 7.911E-07 6.551E-12 RED MARR 2.507E-15 4.755E-13 9.907E-12 5.247E-17-1.000E+00 2.880E-09 8.923E-11 BONE SUR 5.441E-15 1.646E-12 3.429E-11 1.127E-16-1.000E+00 4.720E-09 1.280E-10 THYROID 2.753E-15 5.529E-13 1.152E-11 5.418E-17-1.000E+00 2.920E-10 5.154E-12 REMAINDER 2.534E-15 5.086E-13 1.060E-11 5.283E-17-1.000E+00 1.910E-08 1.890E-08 EFFECTIVE 2.773E-15 5.909E-13 1.231E-11 5.766E-17-1.000E+00 1.010E-07 5.711E-09 SKIN(FGR) 8.574E-14 7.648E-13 1.594E-11 1.250E-14-1.000E+00 0.000E+00 0.000E+00 Pr-143
D000040-122, Revision 0 Page 154 of 155 GONADS 2.130E-17 2.264E-14 4.032E-13 7.930E-19-1.000E+00 4.370E-18 8.990E-18 BREAST 2.550E-17 2.330E-14 4.149E-13 8.160E-19-1.000E+00 2.220E-18 1.090E-18 LUNGS 1.860E-17 1.642E-14 2.923E-13 5.750E-19-1.000E+00 1.330E-08 1.910E-19 RED MARR 1.620E-17 1.493E-14 2.659E-13 5.230E-19-1.000E+00 1.480E-11 1.030E-12 BONE SUR 5.930E-17 5.454E-14 9.711E-13 1.910E-18-1.000E+00 1.490E-11 1.030E-12 THYROID 2.050E-17 1.802E-14 3.208E-13 6.310E-19-1.000E+00 1.680E-18 2.660E-20 REMAINDER 1.760E-17 1.642E-14 2.923E-13 5.750E-19-1.000E+00 1.970E-09 4.220E-09 EFFECTIVE 2.100E-17 2.002E-14 3.564E-13 7.010E-19-1.000E+00 2.190E-09 1.270E-09 SKIN(FGR) 1.760E-14 5.711E-11 1.017E-09 2.000E-15-1.000E+00 0.000E+00 0.000E+00 Nd-147 GONADS 6.130E-15 4.218E-12 7.235E-11 1.480E-16-1.000E+00 8.410E-11 1.790E-10 BREAST 7.120E-15 4.132E-12 7.088E-11 1.450E-16-1.000E+00 3.450E-11 1.870E-11 LUNGS.
5.820E-15 3.648E-12 6.257E-11 1.280E-16-1.000E+00 1.060E-08 2.440E-12 RED MARR 5.400E-15 3.505E-12 6.013E-11 1.230E-16-1.000E+00 9.190E-11 5.050E-11 BONE SUR 1.320E-14 8.265E-12 1.418E-10 2.900E-16-1.000E+00 3.260E-10 2.220E-11 THYROID 6.120E-15 3.876E-12 6.648E-11 1.360E-16-1.000E+00 1.820E-11 2.640E-13 REMAINDER 5.530E-15 3.562E-12 6.111E-11 1.250E-16-1.000E+00 1.760E-09 3.760E-09 EFFECTIVE 6.190E-15 3.961E-12 6.795E-11 1.390E-16-1.000E+00 1.850E-09 1.180E-09 SKIN(FGR) 1.950E-14 3.135E-11 5.377E-10 1.100E-15-1.000E+00 0.000E+00 0.000E+00 Np-239 GONADS 7.530E-15 4.691E-12 4.380E-11 1.710E-16-1.000E+00 7.450E-11 1.620E-10 BREAST 8.730E-15 4.636E-12 4.329E-11 1.690E-16-1.000E+00 1.630E-11 1.720E-11 LUNGS 7.180E-15 4.115E-12 3.842E-11 1.500E-16-1.000E+00 2.360E-09 2.400E-12 RED MARR 6.500E-15 4.005E-12 3.740E-11 1.460E-16-1.000E+00 2.080E-10 4.660E-11 BONE SUR 2.000E-14 1.001E-11 9.349E-11 3.650E-16-1.000E+00 2.030E-09 3.590E-11 THYROID 7.520E-15 4.197E-12 3.919E-11 1.530E-16-1.000E+00 7.620E-12 2.070E-13 REMAINDER 6.760E-15 4.005E-12 3.740E-11 1.460E-16-1.000E+00 9.590E-10 2.770E-09 EFFECTIVE 7.690E-15 4.471E-12 4.175E-11 1.630E-16-1.000E+00 6.780E-10 8.820E-10 SKIN(FGR) 1.600E-14 7.215E-12 6.737E-11 2.630E-16-1.000E+00 0.000E+00 0.000E+00 Pu-238 GONADS 6.560E-18 4.291E-14 9.011E-13 1.490E-18-1.000E+00 1.040E-05 2.330E-09 BREAST 1.270E-17 5.558E-14 1.167E-12 1.930E-18-1.000E+00 4.400E-10 1.800E-13 LUNGS 1.060E-18 2.267E-15 4.759E-14 7.870E-20-1.000E+00 3.200E-04 8.640E-14 RED MARR 1.680E-18 5.587E-15 1.173E-13 1.940E-19-1.000E+00 5.800E-05 1.270E-08 BONE SUR 9.300E-18 3.514E-14 7.378E-13 1.220E-18-1.000E+00 7.250E-04 1.580E-07 THYROID 4.010E-18 9.792E-15 2.056E-13 3.400E-19-1.000E+00 3.860E-10 7.990E-14 REMAINDER 1.990E-18 9.216E-15 1.935E-13 3.200E-19-1.000E+00 2.740E-05 2.180E-08 EFFECTIVE 4.880E-18 2.413E-14 5.068E-13 8.380E-19-1.000E+00 7.790E-05 1.340E-08 SKIN(FGR) 4.090E-17 2.776E-13 5.830E-12 9.640E-18-1.000E+00 0.000E+00 0.000E+00 Pu-239 GONADS 4.840E-18 1.768E-14 3.713E-13 6.140E-19-1.000E+00 1.200E-05 2.640E-09 BREAST 7.550E-18 2.238E-14 4.699E-13 7.770E-19-1.000E+00 3.990E-10 1.210E-13 LUNGS 2.650E-18 2.267E-15 4.760E-14 7.870E-20-1.000E+00 3.230E-04 7.890E-14 RED MARR 2.670E-18 3.456E-15 7.258E-14 1.200E-19-1.000E+00 6.570E-05 1.410E-08 BONE SUR 9.470E-18 1.673E-14 3.514E-13 5.810E-19-1.000E+00 8.210E-04 1.760E-07 THYROID 3.880E-18 5.126E-15 1.077E-13 1.780E-19-1.000E+00 3.750E-10 7.500E-14 REMAINDER 2.860E-18 4.838E-15 1.016E-13 1.680E-19-1.000E+00 3.020E-05 2.120E-08 EFFECTIVE 4.240E-18 1.057E-14 2.220E-13 3.670E-19-1.000E+00 8.330E-05 1.400E-08 SKIN(FGR) 1.860E-17 1.057E-13 2.220E-12 3.670E-18-1.000E+00 0.000E+00 0.000E+00 Pu-240 GONADS 6.360E-18 4.118E-14 8.649E-13 1.430E-18-1.000E+00 1.200E-05 2.640E-09 BREAST 1.230E-17 5.328E-14 1.119E-12 1.850E-18-1.000E+00 4.330E-10 1.730E-13 LUNGS 1.090E-18 2.249E-15 4.723E-14 7.810E-20-1.000E+00 3.230E-04 8.220E-14 RED MARR 1.650E-18 5.386E-15 1.131E-13 1.870E-19-1.000E+00 6.570E-05 1.410E-08 BONE SUR 9.260E-18 3.398E-14 7.137E-13 1.180E-18-1.000E+00 8.210E-04 1.760E-07 THYROID 3.920E-18 9.446E-15 1.984E-13 3.280E-19-1.000E+00 3.760E-10 7.510E-14 REMAINDER 1.960E-18 8.870E-15 1.863E-13 3.080E-19-1.000E+00 3.020E-05 2.130E-08 EFFECTIVE 4.750E-18 2.313E-14 4.857E-13 8.030E-19-1.000E+00 8.330E-05 1.400E-08 SKIN(FGR) 3.920E-17 2.644E-13 5.552E-12 9.180E-18-1.000E+00 0.000E+00 0.000E+00 Pu-241 GONADS 7.190E-20 6.653E-17 1.396E-15 2.310E-21-1.000E+00 2.760E-07 5.660E-11 BREAST 8.670E-20 7.229E-17 1.517E-15 2.510E-21-1.000E+00 2.140E-11 2.790E-15 LUNGS 6.480E-20 4.090E-17 8.584E-16 1.420E-21-1.000E+00 3.180E-06 4.480E-15 RED MARR 5.630E-20 4.003E-17 8.403E-16 1.390E-21-1.000E+00 1.430E-06 2.780E-10
D000040-122, Revision 0 Page 155 of 155 BONE SUR 2.190E-19 1.385E-16 2.908E-15 4.810E-21-1.000E+00 1.780E-05 3.480E-09 THYROID 6.980E-20 4.522E-17 9.491E-16 1.570E-21-1.000E+00 9.150E-12 1.010E-15 REMAINDER 6.090E-20 4.291E-17 9.007E-16 1.490E-21-1.000E+00 6.020E-07 1.850E-10 EFFECTIVE 7.250E-20 5.558E-17 1.167E-15 1.930E-21-1.000E+00 1.340E-06 2.070E-10 SKIN(FGR) 1.170E-19 2.033E-16 4.268E-15 7.060E-21-1.000E+00 0.000E+00 0.000E+00 Am-241 GONADS 8.580E-16 9.360E-13 1.966E-11 3.250E-17-1.000E+00 3.250E-05 2.700E-07 BREAST 1.070E-15 1.014E-12 2.129E-11 3.520E-17-1.000E+00 2.670E-09 2.620E-11 LUNGS 6.740E-16 5.789E-13 1.216E-11 2.010E-17-1.000E+00 1.840E-05 3.360E-11 RED MARR 5.210E-16 4.838E-13 1.016E-11 1.680E-17-1.000E+00 1.740E-04 1.450E-06 BONE SUR 2.870E-15 2.678E-12 5.625E-11 9.300E-17-1.000E+00 2.170E-03 1.810E-05 THYROID 7.830E-16 6.365E-13 1.337E-11 2.210E-17-1.000E+00 1.600E-09 1.320E-11 REMAINDER 6.340E-16 5.933E-13 1.246E-11 2.060E-17-1.000E+00 7.820E-05 6.660E-07 EFFECTIVE 8.180E-16 7.920E-13 1.663E-11 2.750E-17-1.000E+00 1.200E-04 9.840E-07 SKIN(FGR) 1.280E-15 2.396E-12 5.032E-11 8.320E-17-1.000E+00 0.000E+00 0.000E+00 Cm-242 GONADS 7.830E-18 4.893E-14 1.013E-12 1.700E-18-1.000E+00 5.700E-07 5.200E-09 BREAST 1.480E-17 6.159E-14 1.275E-12 2.140E-18-1.000E+00 9.440E-10 8.950E-12 LUNGS 1.130E-18 3.022E-15 6.257E-14 1.050E-19-1.000E+00 1.550E-05 8.840E-12 RED MARR 1.890E-18 6.562E-15 1.359E-13 2.280E-19-1.000E+00 3.900E-06 3.570E-08 BONE SUR 1.060E-17 4.231E-14 8.759E-13 1.470E-18-1.000E+00 4.870E-05 4.460E-07.
THYROID 4.910E-18 1.261E-14 2.610E-13 4.380E-19-1.000E+00 9.410E-10 8.820E-12 REMAINDER 2.270E-18 1.079E-14 2.235E-13 3.750E-19-1.000E+00 2.450E-06 4.020E-08 EFFECTIVE 5.690E-18 2.751E-14 5.697E-13 9.560E-19-1.000E+00 4.670E-06 3.100E-08 SKIN(FGR) 4.290E-17 2.700E-13 5.589E-12 9.380E-18-1.000E+00 0.000E+00 0.000E+00 Cm-244 GONADS 6.900E-18 4.522E-14 9.492E-13 1.570E-18-1.000E+00 1.590E-05 1.330E-07 BREAST 1.330E-17 5.702E-14 1.197E-12 1.980E-18-1.000E+00 1.040E-09 8.820E-12 LUNGS 7.080E-19 2.592E-15 5.441E-14 9.000E-20-1.000E+00 1.930E-05 8.810E-12 RED MARR 1.460E-18 5.875E-15 1.233E-13 2.040E-19-1.000E+00 9.380E-05 7.820E-07 BONE SUR 8.820E-18 3.859E-14 8.101E-13 1.340E-18-1.000E+00 1.170E-03 9.770E-06 THYROID 4.190E-18 1.146E-14 2.406E-13 3.980E-19-1.000E+00 1.010E-09 8.440E-12 REMAINDER 1.810E-18 9.821E-15 2.062E-13 3.410E-19-1.000E+00 4.780E-05 4.150E-07 EFFECTIVE 4.910E-18 2.529E-14 5.308E-13 8.780E-19-1.000E+00 6.700E-05 5.450E-07 SKIN(FGR) 3.910E-17 2.506E-13 5.260E-12 8.700E-18-1.000E+00 0.000E+00 0.000E+00
TECHNICAL WORK RECORD Originator:
Michael Waselu Date:
07/30/2012 System:
N/A Project Title Verification of DC00040-122, RO ECR 50786 Page 1
of 3
1.0 Purpose
This TWR is developed to document the verification of D000040-122, "Loss of Coolant Accident -TSC."
2.0
Reference:
Calculation DC00040-122, "Loss of Coolant Accident - TSC.
3.0 Discussion
The verification of the calculation is to assure that the calculation has been completed IAW ES-412. The verification is performed IAW ES-110. ES-110, Attachment Ill is included as Attachment 1 to this TWR.
The verification included check of input, mathematical manipulations, computer code input/output and results. The RADTRAD computer code was utilized in the analysis. RADTRAD is a validated and verified code for nuclear use IAW WorleyParsons QA procedures. There are no assumptions in the calculation requiring future confirmation..
4.0 Comments
Technical comments resulted from the review.
1.
None Editorial comments:
1.
Add FSAR Section 15.4.1 to Affected Documents 2.
Add VC Summer Calculation DC00040-097, R1, "Loss of Coolant Accident - AST to References.
3.
Add EAB and LPZ doses to Summary of Results to compare to results in DC00040-097.
4.
Miscellaneous small typographical changes provided to originator incorporated.
5.
Successfully incorporated David McCreary comments.
5.0 Results
The verifier comments have been resolved and the results of the calculation are acceptable for use.
TECHNICAL WORK RECORD Engineer Michael Waselus Date 07/30/2012 System:
NA Project Title Verification of DC00040-122, RO ECR 50786 Page 2
of 3
ES-110 ATTACHMENT III PAGE 1 OF 2 REVISION 2 VERIFICATION RECORD: CALCULATION Calculation #
DC00040-122 Revision 0 The following questions, as a minimum should be answered for calculation verification.
Yes N/A
q
q
q Have inputs, including codes, standards, regulations, requirements, procedures, data and engineering methodology been correctly selected and applied?
Has the calculation been developed in accordance with applicable station procedures (e.g., ES-412).
Is the plant design basis/criteria maintained?
Have assumptions been identified, especially those requiring later confirmation?
Have references been properly identified and complete?
Have the calculation, results, tables and figures been reviewed with regard to numerical accuracy, units and consistency?
Has the calculation been developed/revised in a clear and understandable manner as to not require recourse to the originator?
Is the output reasonable compared to the input?
Do the diagrams, or models depicted represent the physical situation correctly and incorporate necessary features for a correct analysis?
Has the calculation cover page been completed in an accurate manner?
Are the sign conventions used in figures and equations consistent?
Is consistent nomenclature used throughout the calculation (e.g., figures, tables)?
Are symbols used on figures and in the text defined?
Are concurrent in-process revisions been addressed and coordinated with this revision?
Has the Calculation Index been updated?
Additional considerations (see attached TWR)?
TECHNICAL WORK RECORD Engineer Michael Waselus Date 07/30/2012 System:
NA Project Title Verification of DC00040-122, RO ECR 50786 Page 3
of 3
ES-110 ATTACHMENT III PAGE 2 OF 2 REVISION 2 VERIFICATION RECORD: CALCULATION Calculation #
D000040-122 Revision 0 CALCULATIONS UTILIZING COMPUTER PROGRAMS:
El z
q Has the program been appropriately defined, including the version?
Is the basic methodology used by the program appropriate for the calculation?
Has the appropriate computer program been used?
Has the calculation been performed within the known limits of the program?
Has the computer program been verified and validated in accordance with SAP-1040? Validated by WorleyParsons.
Has the program been defined, controlled, and benchmarked so that the results reported are traceable to a particular version of the program and a particular set of input data?
Have limits for the program been defined, as appropriate?
Comments have been included and resolved.
Is the Validation Data set for the application complete, and provide repeatable results?
M. M. Waselus/
Verifier's Printed Name Verifier's Signature 07/30/2012 Date
ES-0110 ATTACHMENT XVI PAGE 1 OF/Zq REVISION 2 SIM//1z REVIEW CONSIDERATIONS: OWNER'S ACCEPTANCE REVIEW ECR/Document Number: D000040-079, D000040-118 Through -123 Project
Title:
Review of New NOB TSC Dose Calculations The following questions should be considered, as a minimum, during the performance of an Owner's Acceptance Review of vendor developed engineering documents.
Yes N/A
q 1-1 Is the technical information/design complete, consistent, and correct for the activity under review?
Were inputs, including codes, standards, and regulatory requirements correctly selected and applied?
Are assumptions necessary to perform the design activity adequately described and reasonable? Where necessary, are the assumptions identified for subsequent re-verification when the detailed design activities are completed?
Is the document/package developed in a clear and understandable manner?
Is the plant design basis/criteria maintained?
Are references properly identified and complete?
Were design considerations from EC-01, Attachment I and II adequately add ressed/incorporated?
q Were technical, design, program or procedure requirements adequately addressed/incorporated?
Have applicable construction and operating experiences been considered?
q Were designs developed in accordance with good engineering practices and established ES guidance documents?
q Z Have impacted documents, databases (EC-02) and equipment changes been identified?
q Is the document/package developed in accordance with applicable station procedures (e.g., SAP-133, ES-453, ES-455)?
q Is the document/package developed in a clear and understandable manner as to not require recourse to the Originator?
D
ES-0110 ATTACHMENT XVI PAGE 2 OF,`( o ;
REVISION 2 It Yes N/A Does the design meet interfacing organizations operational/maintenance requirements?
Is technical information adequate to perform the task?
Is the acceptance criteria adequate for the activity under review?
Is the post modification testing adequate to confirm the design?
Has the 10CFR50.59 Review Process been completed, if required?
For work performed in accordance with VC Summer Nuclear Station Procedures, the procedure forms must be signed by the originator and if not qualified must be co-signed by a qualified person. Check the qualifications of the contractor personnel signing the procedure forms.
Yes No Are contractor personnel signing the VCSNS procedure forms qualified under a vendor qualification program or the VCSNS Nuclear Training Manual for those procedures?
If not have the VCSNS forms been co-signed by a person qualified to the applicable procedure?
Technical Reviews
q Are all technical reviews complete and all comments resolved to the satisfaction of the commenter?
TECHNICAL REVIEW: Check all blocks that apply q Principal Piping Engineer q
Principal Engr Analysis Engineer q
Principal I&C Engineer q
Principal Mechanical Engineer q
Principal Civil Engineer q
Principal PSA Engineer q
Principal Nuclear Fuels Engineer q
Principal Digital Engineer q
Principal Electrical Engineer q
Principal EQ Engineer q
Principal Fire Protection Engineer NAnalysis Engineer Dave McCreary q
q Dave McCreary Reviewer's Printed Name Reviewer's SigrTature qi, 2 a;-
Date D
Es-aria afi xv1*
Detailed Owners Acceptance Review Notes P./` 3 of V There are three general comments in all of the dose calculations that should beit addressed:
1)
The initiation of the HVAC "Emergency Mode" would only be manually. There are statements in the calculations of SI signal initiation. These should be removed to avoid confusion with the Unit 1 Control Room Habitability Envelope and it's automatic Emergency Mode initiation on an SI signal.
ement< egardS ng i signals will be`remove 2)
The 1000 cfm allotted for TSC "inleakage" isn't applicable in these scenarios since it is very conservatively assumed that.none of the air flowing through the TSC is filtered or recirculated. Therefore, 13,000 cfm of unfiltered outside air is flowing into the TSC and out of the TSC. The discussions should be cleaned up to state that the 13,000 cfm assumed conservatively bounds the expected design flow rate value of 12,000 cfm, and that the doses calculated due to assuming no filtration throughout the accident is very conservative since the TSC filtration capability and isolation times are currently unknown.
SPON c-Tm assume i.00c Agree as noted r The text will be revised to state '"The 13,000.
conservatively bounds the expected design; flow rate value of the doses are conservative y..calculate.:d assuming no.credit for filtration throughout the;accident refer not to state that the, TSC filtration capability and n
s an curre tly unknown. There is a.,'P&ID showing filter assume5d an operator action such as 30 minutes if we f isolation times are could actually ad chosen 3)
Suggest not listing procedure revision levels in the verification TVVR's. ES-412 and
-110 have been updated.
- reed, RESPONSI below'.. `
leleferevis^on levels:
ua^ commer y
`a fee to Main Steam Line Break, DC00040-118, Rev. 0:
c.ommen o
c s note c
rre tion 1.
Follows same format and methodology as in MSLB dose calculation D000040-099 for CR/EAB/LPZ.
2.
Table of Contents needs to be updated for page number corrections.
3.
Section 5.3 should be revised for the general comments above.
Er -cWO XV1 Locked Rotor, D000040-119, Rev. 0:
j 4.
Follows same format and methodology as in LR dose calculation D000040-100 for CR/EAB/LPZ.
Sections 2.16 and 5.10 should be revised for the general comments above.
5.
References 4.11 and 4.14 are the same. Per DI-5.10, Ref. 4.11 should be same reference as used in D000040-118 Ref. 18.
6.
Reference 4.17 is up to Rev 3... Affects DI-5.9 (10gpm value is now 30gpm), but calc uses the correct mass rate so no change in results.
Fuel Handling Accident, D000040-120, Rev. 0:
7.
Follows same format and methodology as in Fuel Handling dose calculation D000040-102 for CR/EAB/LPZ.
8.
Sections 2.15 and 5.12 should be revised for the general comments above.
SGTR, D000040-121, Rev. 0:
9.
Follows same format and methodology as in SGTR dose calculation D000040-098 for CR/EAB/LPZ.
10.
Section 5.3 should be revised for the general comments above.
LOCH, D000040-122, Rev. 0:
11.
Follows same format and methodology as in LOCA dose calculation D000040-097 for CR/EAB/LPZ.
12.
Section 5.7 should be revised for the general comments above.
CREA, D000040-123, Rev. 0:
13.
Follows same format and methodology as in CREA dose calculation D000040-101 for CR/EAB/LPZ.
14.
References 4.11 and 4.12 are the same. Per DI-5.10, Ref. 4.11 should be same reference as used in D000040-118 Ref. 18.
15.
Section 5.10 should be revised for the general comments above./
G^r^^1 /f? 7SJ s'bi ' Z 411 y
s
^.