BYRON 2014-0051, Annual Radioactive Effluent Release Report
| ML14114A393 | |
| Person / Time | |
|---|---|
| Site: | Byron |
| Issue date: | 04/24/2014 |
| From: | Kearney F Exelon Generation Co |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| BYRON 2014-0051 | |
| Download: ML14114A393 (78) | |
Text
Byron Generating Station 4450 North German Church Rd Exeton Generation www.exeloncorp.com April 24, 2014 LTR:
BYRON 2014-0051 10 CFR 50.36a File 1.10.0101 2.12.1522 United States Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Byron Station, Units 1 and 2 Facility Operating License Nos. NPF-37 and NPF-66 NRC Docket Nos. STN 50-454 and STN 50-455
Subject:
2013 Annual Radioactive Effluent Release Report Enclosed is the Annual Radioactive Effluent Release Report for Byron Station. This report is being submitted in accordance with 10 CFR 50.36 a(2), Technical specifications on effluents from nuclear power reactors, and includes a summary of radiological liquid and gaseous effluents and solid waste released from the site from January 2013 through December 2013.
There were no changes made to the ODCM in 2013.
If you have any questions regarding this information, please contact Steven A. Gackstetter, Regulatory Assurance Manager, at (815) 406-2800.
Respectfully, rA.Kne Site Vice President Byron Nuclear Generating Station FAK/JG/LZIsg
Enclosure:
Annual Radioactive Effluent Release Report cc: Cynthia D. Pederson, Regional Administrator NRC Region III
BYRON NUCLEAR POWER STATION ANNUAL RADIOLOGICAL EFFLUENT RELEASE REPORT (ARERR) 2013 Page 1 of 77
BYRON NUCLEAR POWER STATION UNIT 1/2 DOCKET NUMBER STN-50-454/455 RADIOACTIVE EFFLUENT RELEASE REPORT January 2013
- December 2013 Supplemental Information Regulatory Limits a.
Fission and activation products:
Tech Spec Whole Body 500 mrem/year Skin
=
3000 mrem/year 10CFR5O Gamma
=
5 mrad/quarter; 10 mrad/year Beta
=
10 mrad/quarter; 20 mrad/year b.
Iodine: (summed with particulate, see below) c.
Particulates with half-lives > 8 days:
Tech Spec Organ
=
1500 mrem/year 10CFR5O Organ
=
7.5 mrem/quarter; 15 mrem/year d.
Liquid Effluents:
1 OCFR5O Whole Body
=
1.5 mrem/quarter; 3 mrem/year Organ
=
5 mrem/quarter; 10 mrem/year 2.
Maximum Permissible Concentration a.
Fission and Activation Products: 1 OCFR2O Appendix B Table 2 b.
Iodine: 10CFR2O Appendix B Table 2 c.
Particulates: 10CFR2O Appendix B Table 2 d.
Liquid Effluents: 10 X JOCFR2O Appendix B Table 2 3.
Average Energy: This item is not applicable. The ODCM limits the dose equivalent rates due to the release of noble gases to less than or equal to 500 mrem/year to the total body and less than or equal to 3000 mrem/year to the skin.
4.
Measurements and Approximations of Total Radioactivity a.
Fission and activation products: Prior to release, the isotopic content is determined. Released activity is calculated using volume of release, which is determined by the change in tank level, containment pressure, or containment purge fan flow rates.
b.
Particulate and iodine sampling media for the plant vent stacks are continuously collected and analyzed weekly. Tritium and noble gas analysis for the plant vent stacks are obtained and analyzed weekly.
c.
Liquid effluents: Isotopic analysis is performed on each batch liquid release tank prior to its release. Total release activity is calculated using volume of release. Total tritium activity Page 2 of 77
released is calculated from the highest of a monthly circulating water blowdown composite activity or a sum of the effluent input composite activities.
U.
All positive results (i.e. higher than the lower limit of detection (LLD)) are reported in units of uCi/cc or uCi/mi unless otherwise noted. All LLD values and the associated LLD requirements are listed in Attachment A.
5.
Batch Releases:
a.
Liquid:
1.
Number of batch releases = 70 2.
Total time period for batch releases = 9,132 minutes 3.
Maximum time period for a batch release = 401 minutes 4.
Average time period for a batch release = 130 minutes 5.
Minimum time period for a batch release = 44 minutes 6.
Average Rock River stream flow during periods of release of effluent into a flowing stream = 292 m3/sec, based on information from the U.S. Geological Survey Byron Gauging Station.
b.
Gaseous:
1.
Number of batch releases = 381 2.
Total time period for batch releases = 39,929 minutes 3.
Maximum time period for a batch release = 2,531 minutes 4.
Average time period for batch releases = 105 minutes 5.
Minimum time period for a batch release = 7 minutes 6.
Abnormal Releases:
a.
Liquid
- None b.
GaseousNone 7.
There were no revisions to the Off Site Dose Calculation Manual (ODCM) made in 2013.
8.
Errata The Solid Radioactive Waste for Burial, Estimated Solid Waste Composition tables in previous effluent reports contained errors associated with the categorization of shipments made as combined packages. Each year the station Radwaste Shipper provides the ODCM Specialist with a report that categorizes all radwaste shipments via a standard shipping software program. The ODCM Specialist uses this report to formulate the Estimated Solid Waste Composition table.
It was recently discovered that the report provided to the ODCM Specialist incorrectly placed all shipments classified as combined packages into the Other category instead of splitting the shipment profiles into the appropriate categories (Resins-Filters-Evap Bottoms, DAW, or Irradiated Components). A combined package shipment is a shipment that combines these solid waste types. As a result, in years where combined package shipments were made, the isotopic matrices and volumes reported within the affected categories were inaccurate.
It should be noted the errors did not affect the individual shipment manifests, nor did they affect the classification of shipments, and the total activities and volumes for each year were correct. The errors were reflected only in the Estimated Solid Waste Composition tables of the annual effluent reports. The software program has been in use since the mid 1990s for radioactive shipments, but it is unknown when the ODCM chemists began using the reports. The Estimated Solid Waste Composition table errors will be corrected beginning in 2014.
Page 3 of 77
9.
2013 Radiological Groundwater Protection Program (RGPP) Results Summary:
In 2013, fifteen (15) Radiological Groundwater Protection Program (RGPP) monitoring wells were sampled. The samples were obtained in March, May, August, and November and analyzed for tritium.
In addition, a study of gamma, beta, and alpha radioisotopes was performed in accordance with Nuclear Energy Institute (NEI) 07-07, Groundwater Protection Initiative, for the samples obtained in May. None of the May samples showed concentrations of radionuclides above what is considered background levels. Three wells contained levels of tritium above the lower limit of detection (LLD) of 200 pCiIL. They were: AR-4 (818 pCi/L in March, 523 pCi/L in May, 746 pCi/L in August, 686 pCi/L in November), AR-7 (245 pCi/L in March, 351 pCi/L in May, 306 pCiIL in August, 310 pCiIL in November),
and AR-li (850 pCi/L in March, 933 pCi/L in May, 945 pCiIL in August, 912 pCi/L in November). Wells AR-4 and AR-il are near the Circulating Water Blowdown piping, where historical leakage through vacuum breakers was known to have occurred. Both of these wells are showing a slow but gradual decrease in tritium concentration since being first sampled in 2006. Well AR-7 is located on-site, just west plant structures. Tritium has been measured in this well just above detectable limits on an intermittent basis since the well was first drilled in 2006. The tritium in this well is believed to have originated from precipitation recapture of permitted gaseous releases of tritium from the plant that had entered the well during rainfall events as a result of improperly compacted soil around the well during original installation. The clay-based soil around the well was repacked in 2012. The tritium present in this well is at or below tritium levels that have been measured in rainwater as a result of precipitation recapture from permitted gaseous releases and it is not believed to be the result of new leak(s). Should the water in this aquifer migrate to off-site wells used for drinking, the off-site dose consequence from tritium present in any of these wells is negligible.
Page 4 of 77
SUMMARY
Calculations based on gaseous and liquid effluents and meteorological data indicate that public dose due to radioactive material attributable to Byron Station during the period did not exceed any regulatory or Offsite Dose Calculation Manual (ODCM) limits.
The Total Effective Dose Equivalent (TEDE) due to licensed activities at Byron Station calculated for the maximum exposed individual for the period is 2.60E-01 mrem. The annual limit on TEDE is 100 mrem.
The assessment of radiation doses to the public is performed in accordance with the ODCM.
The results of these analyses confirm that the station is operating in compliance with 10CFR5O Appendix I, 10CFR2O and 40CFR190.
There were no additional operational controls implemented in 2013 that affected radiological effluents.
There were no measurements which exceeded the reporting levels, including any that would not have been attributable to station effluents.
The results of the current radiological environmental monitoring program are approximately the same as those found during the pre-operational studies conducted at Byron Station.
RELEASES Gaseous Effluents to the Atmosrhere A total of 6.62E-O1 curies of fission and activation gases were released with a maximum average quarterly release rate of 3.69E-02 pCi/sec.
A total of 5.05E-06 curies of 1-131 were released during the year with a maximum average quarterly release rate of 4.JOE-07 pCi/sec.
A total of 3.02E-06 curies were released as airborne particulate matter with a maximum average quarterly release rate of 3.84E-07 pCi/sec.
A total of 8.70E+00 curies of other (C-i 4, Br-82) radioisotopes were released with a maximum average quarterly release rate of 2.87E-01 pCi/sec.
A total of 7.15E+01 curies of tritium were released with a maximum average quarterly release rate of 2.60E+O0 pCi/sec.
Gross alpha-emitting radionuclides were below detectable limits.
Liquids Released to Rock River A total of 2.88E+1 0 liters of radioactive liquid wastes containing 1.78E-02 curies of fission and activation products were discharged with a maximum quarterly average concentration of 2.50E-09 pCi/mI.
Page 5 of 77
A total of 1.60E+03 curies of tritium were discharged with a maximum quarterly average concentration of 1.72E-04 uCi/mi.
A total of 3.36E-04 curies of dissolved and entrained gases were discharged with a maximum quarterly average concentration of 5.1SE-11 uCi/mI.
Gross alpha-emitting radionuclides were below detectable limits.
DOSE TO MAN GASEOUS EFFLUENT PATHWAYS Noble Gas - Gamma Dose Rates Offsite Gamma air and whole body dose rates for the period were calculated based on measured release rates, isotopic composition of the noble gases, and average meteorological data. The maximum gamma air dose was 4.43E-05 mrad based on measured effluents and average meteorological data, and 9.20E-06 mrad based on measured effluents and concurrent meteorological data.
Noble Gas - Beta Air and Skin Dose Rates The range of beta particles in air is relatively small (on the order of a few meters or less).
Consequently, plumes of gaseous effluents may be considered semi-infinite for the purpose of calculating the dose from beta radiation incident on the skin. However, the actual dose to sensitive skin tissues is difficult to calculate due to the effect of the beta particle energies, thickness of inert skin, and clothing covering sensitive tissues. For purposes of this report the skin is taken to have a thickness of 7.0 mg/cm2 and an occupancy factor of 1.0 is used. The maximum skin dose was 2.62E-05 mrem based on measured effluents and average meteorological data, and i.13E-05 mrem based on measured effluents and concurrent meteorological data.
The maximum offsite beta air dose for the year based on measured effluents and average meteorological data was 1.18E-05 mrad, and 1.01 E-05 mrad based on measured effluents and concurrent meteorological data.
Radioactive Iodine & Particulate The human thyroid exhibits a significant capacity to concentrate ingested or inhaled iodine.
1-131 released during routine operation of the station may be made available to man resulting in dose to the thyroid. C-14 is also included in this category. C-14 exhibits a capacity to concentrate in bone. C-i 4 is released in gaseous form and is absorbed into vegetation through photosynthesis. The principal pathways of interest for C-i 4 are the consumption of vegetation by humans and milk from which animals have ingested C-i 4 through the consumption of vegetation. With the requirement to begin reporting C-i 4 dose in 2011 and the addition of C-i 4 to plant effluents, human dose in this category is primarily driven by the release of C-14 from the plant.
The hypothetical dose to the maximum exposed individual living near the station via ingestion of milk and vegetation was calculated. The source of milk and vegetation was assumed to be Page 6 of 77
at the nearest site boundary with the cows pastured and vegetation grown from May through October. The maximum organ dose from radioactive iodine and particulate (including C-i 4) to any organ was 7.09E-O1 mrem (child/bone) based on measured effluents and average meteorological data, and 7.81 E-01 mrem (child/bone) based on measured effluents and concurrent meteorological data. The maximum dose from radioactive iodine and particulate (including C-i 4) to the whole body was 1.46E-01 mrem (child) based on measured effluents and average meteorological data, and 1.61 E-01 mrem (child) based on measured effluents and concurrent meteorological data.
Gaseous Total Dose The maximum total dose from gaseous releases to any organ was 7.09E-01 mrem (child/bone) based on measured effluents and average meteorological data, and 7.81 E-01 mrem (child/bone) based on measured effluents and concurrent meteorological data. The maximum total dose from gaseous releases to the whole body was 1.46E-Oi mrem (child) based on measured effluents and average meteorological data, and 1.61 E-O1 mrem (child) based on measured effluents and concurrent meteorological data.
LIQUID EFFLUENT PATHWAYS The principal pathways through the aquatic environment for potential doses to man from liquid waste are ingestion of potable water and eating aquatic foods. Liquid dose was calculated based on the ingestion of potable water and sport fish.
It should be noted, however, there are currently no communities within 10 km downstream of the plant using the Rock River for drinking water. NRC-developed equations are used to calculate the doses to the whole body, bone, liver, thyroid, kidney, lung, lower GI tract, and skin. Specific parameters for use in the equations are given in the Exelon Offsite Dose Calculation Manual (ODCM).
The maximum dose from liquid releases to any organ was 1.53E-01 mrem (adult/gilli). The maximum dose from liquid releases to the whole body was 1.34E-01 mrem (adult).
GASEOUS + LIQUID TOTAL DOSE The maximum total dose to any organ via both gaseous and liquid effluents is 8.40 E-01 mrem (child/bone). The maximum dose to the whole body via both gaseous and liquid effluents is 2.60E-01 mrem (child).
Dose Limits to Members of the Public Byron Station did not exceed any of the dose limits as shown below based on concurrent or historical meteorological data.
The RETS limits on dose or dose commitment to a member of the public due to radioactive materials in liquid effluents from each reactor is 1.5 mrem to the whole body or 5 mrem to any organ during any calendar quarter and 3 mrem to the whole body or 10 mrem to any organ during a calendar year.
The RETS limits on air dose due to noble gases released in gaseous effluents to a member of the public from each reactor is 5 mrad for gamma radiation or 10 mrad for beta radiation Page 7 of 77
during any calendar quarter and 10 mrad for gamma radiation or 20 mrad for beta radiation during a calendar year.
The RETS limits on dose to a member of the public due to radioactive iodine & particulate with half-lives greater than eight days in gaseous effluents released from each reactor is 7.5 mrem to any organ during any calendar quarter and 15 mrem to any organ during a calendar year.
The 1 OCFR2O limit on Total Effective Dose Equivalent to individual members of the public is 100 mrem.
SITE METEOROLOGY Detailed records of the site meteorological measurements taken during each calendar quarter of the year are maintained by the meteorological vendor, retained on site, and are available upon request. The data are presented as cumulative joint frequency distributions of the wind direction for the 250 level and wind speed class by atmospheric stability class determined from the temperature difference between the 250 and 30 levels. Data recovery for all measurements on the meteorological tower was 99.6% during 2013.
Page $ of 77
SOLID RADIOACTIVE WASTE FOR BURIAL 1ST QUARTER 2013 DISPOSITION OF MATERIAL MODE OF DESTINATION VOLUME (m3)
CURIES*
DATE (DESCRIPTION, CLASS, TYPE AND TRANSPORT PER PER SOLIDIFYING AGENT)
SHIPMENT SHIPMENT RADIOACTIVE MATERIAL, LOW SPECIFIC ACTIVITY 1/25/13 RWS13-001 (LSA-II), 7, UN3321, FISSILE EXCEPTED, CLASS A, Hiffman Transport Beat Creek 4.66E+01 2.86E-03 GENERAL DESIGN PACKAGE (GDP), 20 METAL EXCLUSIVE-USE Oak Ridge, TN DAW (Trash)
BOX(1), NONE RADIOACTIVE MATERIAL, LOW SPECIFIC ACTIVITY 1/25/13 RWS13-002 (LSA-II), 7, UN3321, FISSILE EXCEPTED, CLASS A, Hittman Transport Beat Creek 4.66E+01 2.62E-03 GENERAL DESIGN PACKAGE (GDP), 20 METAL EXCLUSIVE-USE Oak Ridge, TN DAW (Trash)
BOX(1), NONE 2/19/13 RADIOACTIVE MATERIAL, LOW SPECIFIC ACTIVITY RWS13-003 (LSA-II), 7, UN3321, FISSILE EXCEPTED, CLASS A, Hittman Transport EXCLUSIVE-USE Energy Solutions 4.67E+00 5.03E+00 Bead Resin GENERAL DESIGN PACKAGE (GDP), CASK(1), NONE Clive, UT RADIOACTIVE MATERIAL, LOW SPECIFIC ACTIVITY 3/19/13 RWS13-004 (LSA-II), 7, UN3321, FISSILE EXCEPTED, CLASS A, Hiffman Transport Bear Creek 7.16E+01 4.61E-03 GENERAL DESIGN PACKAGE (GDP), 20 METAL EXCLUSIVE-USE Oak Ridge, TN DAW (Trash)
BOX(2), NONE 3/20/13 RADIOACTIVE MATERIAL, EXCEPTED PACKAGE RWS13-005 LIMITED QUANTITY OF MATERIAL, 7, UN2910, Hittman Transport Bear Creek 4.66E+01 1.84E-03 DAW (Trash)
FISSILE EXCEPTED, CLASS A, GENERAL DESIGN Oak Ridge, TN PACKAGE (GDP), 20 METAL BOX(1), NONE RADIOACTIVE MATERIAL, LOW SPECIFIC ACTIVITY 3/19/13 (LSA-II), 7, UN3321, FISSILE EXCEPTED, CLASS A, Hittman Transport RWS13-006 GENERAL DESIGN PACKAGE (GDP), CASK (1),
EXCLUSIVE-USE Bear Creek 6.09E+01 2.94E-02 DAW (Trash)
NONE Oak Ridge, TN Number of Quarterly Totals 6
2.77E+02 5.07E+OO Sh pm ents:
- Calculated using measured ratios CUBIC M CURIES Page 9 of 77
SOLID RADIOACTIVE WASTE FOR BURIAL 2ND QUARTER 2013 DISPOSITION OF MATERIAL VOLUME CURIES*
MODE OF DESTINATION (m3) PER PER DATE (DESCRIPTION, CLASS, TYPE TRANSPORT AND SOLIDIFYING AGENT)
SHIPMENT SHIPMENT 4/02/13 RADIOACTIVE MATERIAL, LOW SPECIFIC Hiltman Transport RWS13-007 ACTIVITY(LSA-II), 7, UN3321, FISSILE EXCLUSIVE-USE Bear Creek 6.44E+01 1.53E-02 DAW (Trash)
EXCEPTED, CLASS A, GENERAL DESIGN Oak Ridge, TN PACKAGE (GDP), 20 METAL BOX (2), NONE RADIOACTIVE MATERIAL, EXCEPTED 4/12/13 PACKAGE LIMITED QUANTITY OF MATERIAL, RWS13-008 7, UN2910, FISSILE EXCEPTED, CLASS A, Hiffman Transport Gallaher Road 1.40E÷01 8.02E-03 Kingston, TN DAW (Trash)
GENERAL DESIGN PACKAGE (GDP), 20 METAL 80X(2), NONE RADIOACTIVE MATERIAL, EXCEPTED 4/17/13 PACKAGE LIMITED QUANTITY OF MATERIAL, RWS13-009 7, UN291 0, FISSILE EXCEPTED, CLASS A, Visionar, Solutions Bear Creek 1.26E+01 2.80E-03 OtherfOil)
GENERAL DESIGN PACKAGE fGDP), 20 Oak Ridge, TN METAL BOX(1), NONE RADIOACTIVE MATERIAL, LOW SPECIFIC 4/17/13 RWS13-010 ACTIVITY fLSA-II), 7, UN3321, FISSILE Hittman Transport Bear Creek 2.28E+01 2.69E+00 EXCEPTED, CLASS A, GENERAL DESIGN EXCLUSIVE-USE Oak Ridge, TN DAW (Trash)
PACKAGE (GDP), 20 METAL BOX (2), NONE RADIOACTIVE MATERIAL, LOW SPECIFIC 4/17/13 RWS13-011 ACTIVITY (LSA-II), 7, UN3321, FISSILE Hiffman Transport Bear Creek 6.98E+01 1.64E-02 EXCEPTED, CLASS A, GENERAL DESIGN EXCLUSIVE-USE Oak Ridge, TN DAW (Trash)
PACKAGE (GDP), 20 METAL BOX (2), NONE RADIOACTIVE MATERIAL, LOW SPECIFIC 4/22/13 RWS13-012 ACTIVITY (LSA-II), 7, UN3321, FISSILE Visionary Solutions Bear Creek 1.26E+01 5.69E-03 EXCEPTED, CLASS A, GENERAL DESIGN EXCLUSIVE-USE OtherfOil)
PACKAGE (GDP), 20 METAL BOX (1), NONE Oak Ridge, TN RADIOACTIVE MATERIAL, EXCEPTED 4/24/13 PACKAGE LIMITED QUANTITY OF MATERIAL, RWS13-013 7, UN2910, FISSILE EXCEPTED, CLASS A, Hiftman Transport Bear Creek 5.62E÷01 3.01 E-03 Oak Ridge, TN DAW (Trash)
GENERAL DESIGN PACKAGE (GOP), 20 METAL BOX(2), NONE
RADIOACTIVE MATERIAL, LOW SPECIFIC 4/27/13 RWS13-014 ACTIVITY (LSA-II), 7, UN3321, FISSILE Hiffman Transport Bear Creek 3.47E÷01 9.94E-02 EXCEPTED, CLASS A, GENERAL DESIGN EXCLUSIVE-USE DAW (Trash)
PACKAGE (GDP), 20 METAL BOX (1), NONE Oak Ridge, TN RADIOACTIVE MATERIAL, LOW SPECIFIC 5/14/13 ACTIVITY (LSA-II), 7, UN3321, FISSILE Hittman Transport RWS13-015 Bear Creek 6.62E+01 3.90E-03 EXCEPTED, CLASS A, GENERAL DESIGN EXCLUSIVE-USE DAW (Trash)
PACKAGE fGDP), 20 METAL BOX (2), NONE Oak Ridge, TN Number of Quarterly Totals 9
3.63E+02 2.84E+OO Shipments:
- Calculated using measured ratios CUBIC M CURIES Page 10 of 77
SOLID RADIOACTIVE WASTE FOR BURIAL 3RD QUARTER 2013 DATE DISPOSITION OF MATERIAL VOLUME (m3)
CURIES* PER MODE OF DESTINATION PER Shipment #
(DESCRIPTION, CLASS, TYPE AND TRANSPORT SHIPMENT Description SOLIDIFYING AGENT)
SHI PMENT RADIOACTIVE MATERIAL, LOW 7/11/13 SPECIFIC ACTIVITY fLSA-II), 7, UN3321, Hittman Transport Bear Creek RWS13-016 7.16E+01 5.35E-03 CLASS A, GENERAL DESIGN PACKAGE EXCLUSIVE-USE Oak Ridge, TN DAW (Trash)
(GDP), 20 METAL BOX (2), NONE RADIOACTIVE MATERIAL, LOW 8/28/13 SPECIFIC ACTIVITY (LSA-II), 7, UN3321, RWS13-017 FISSILE EXCEPTED, CLASS A, GENERAL HiUman Transport Energy Solutions 4.59E+00 7.67E+00 EXCLUSIVE-USE Clive, UT Bead Resin DESIGN PACKAGE (GDP), CASK (1),
NONE RADIOACTIVE MATERIAL, EXCEPTED PACKAGE LIMITED QUANTITY OF 8/29/13 MATERIAL, 7, UN2910, FISSILE Gallaher Road RWS13-018 Hittman Transport 1.52E÷01 6.36E-03 EXCEPTED, CLASS A, GENERAL Kingston, TN DAW (Sludge)
DESIGN PACKAGE (GDP), 20 METAL BOX(6), NONE RADIOACTIVE MATERIAL, EXCEPTED PACKAGE LIMITED QUANTITY OF 8/29/13 MATERIAL, 7, UN2910, FISSILE Gallaher Road RWS13-019 Hittman Transport 1.50E÷01 6.07E-03 EXCEPTED, CLASS A, GENERAL Kingston, TN DAW(Sludge)
DESIGN PACKAGE (GDP), 20 METAL BOX(6), NONE Number of 4
Quarterly Totals Shipments:
1.06E+02 7.69E+00
- Calculated using measured ratios CUBIC M CURIES Page 11 of 77
SOLID RADIOACTIVE WASTE FOR BURIAL 4TH QUARTER 2013 No Shipments DISPOSITION OF MATERIAL VOLUME(m3)
CURIES*
DATE MODE OF DESTINATION PER PER Shipment #
(DESCRIPTION, CLASS, TYPE TRANSPORT AND SOLIDIFYING AGENT)
SHIPMENT SHIPMENT None N/A N/A N/A N/A N/A Number of Quarterly Totals Shipments:
0 0
0
- Calculated using measured ratios CUBIC M CURIES Page 12 of 77
SOLID RADIOACTIVE WASTE FOR BURIAL Estimated Solid Waste Composition 2013 Volume (m3)
Class 0
N/A
% Abund Curies uCi/mi Resins, Filters,_Evap Bottoms 2013 Dry Active Waste 2013 Other Waste Combined Packaqes, Oil, Sea Lands 2013 Volume (m3) 4.592+00 Class A
Nuclide
% Abund Curies uCi/mI H-3 23.347 1.792+00 3.902-01 C-I 4 0.035 2.662-03 5.802-04 Mn-54 1.247 9.572-0 2.082-0 Fe-55 4.349 3.342-0 7.282-0 Co-57 0.19 1.512-0 3.292-0 Co-58 4.02 3.092-0 6.732-0 Co-60 12.07 9.262-0 2.022-01 Ni-59 0.501 3.842-0 8.372-0 Ni-63 52.870 4.066+0 8.852-01 Zn-65 0.15 1.212-0 2.642-0 Sr-90 0.00 6.972-04 1.522-04 Sb-125 0.59 4.592-0 1.002-0 Cs-134 0.08 6.342-0 1.382-0 Cs-137 0.487 3.74E-0 8.152-0 Ce-144 0.009 6.902-04 1.502-04 Pu-238 0.000 3.852-0 8.392-07 Pu-241 0.017 1.292-0 2.812-04 Am-241 0.000 1.742-0 3.792-06 Cm-243 0.000 7.392-0 3.032-06 Volume (m3) 6.892+02 Class A
Nuclide
% Abund Curies uCi/mi H-3 0.360 7.382-04 1.072-0 Cr-51 2.715 5.572-03 8.082-0 Mn-54 2.373 4.872-03 7.072-0 Fe-55 6.884 1.41 2-02 2.052-0 Fe-59 0.256 5.262-04 7.632-07 Co-57 0.237 4.852-04 7.042-07 Co-58 17.627 3.62E-02 5.252-0 Co-60 31.076 6.372-02 9.252-0 Ni-59 0.399 8.192-04 1.192-0 Ni-63 30.570 6.272-02 9.102-0 Zn-65 0.077 1.582-04 2.29E-07 Zr-95 1.735 3.565-03 5.172-06 Nb-94 0.055 1.122-04 1.632-07 Nb-95 2.903 5.952-03 8.642-06 Sn-il 3 0.125 2.562-04 3.722-07 Sb-125 2.395 4.912-03 7.132-06 Cs-137 0.111 2.282-04 3.312-07 Ce-144 0.100 2.042-04 2.962-07 Am-241 0.001 1.712-06 2.482-09 Cm-243 0.000 1.002-06 1.452-09 Irradiated ComDonents 2013
- No Shipments Volume (m3) 5.272+01 Class A
%Abund Curies uCi/ml H-3 28.616 2.212+00 4.192-02 C-14 1.173 9.072-0 1.722-03 Cr-51 0.571 4.422-0 8.392-04 Mn-54 1.260 9.752-0 1.852-03 Fe-55 14.231 1.102+00 2.092-02 Fe-59 0.037 2.832-0 5.376-05 Co-57 0.115 8.912-0 1.692-04 Co-58 10.026 7.762-07 1.472-02 Co-60 12.966 1.002+00 1.902-02 Ni-59 0.136 1.056-0 1.996-04 Ni-63 25.464 1.97E+00 3.742-02 Zn-65 0.091 7.01 E-0 1.332-04 Sr-gO 0.000 2.862-0 5.432-07 Zr-95 0.187 l.45E-0 2.752-04 Nb-94 0.002 1.172-04 2.22E-0 Nb-95 1.857 1.446-01 2.732-0 Tc-99 0.033 2.532-0 4.802-0 Ru-103 0.004 3.402-04 6.452-0 Ru-106 0.0 3.902-0 7.402-0 Ag-hOrn 0.54 4.215-0 7.99E-04 n-113 0.0 1.182-0 2.24E-0 b-124 0.0 1
6.432-0 1.226-0 b-125 1.9 1.522-01 2.882-0 Te-123m 0.0 1
6.126-0 1.162-0 Te-125rn 0.1 1.076-0 2.032-04 Te-132 0.0 0 2.566-07 4.866-09
-129 0.0 0 1.322-0 2.506-08 Cs-134 0.0 1.152-0 2.182-0 Cs-137 0.34 2.696-0 5.106-04 Ce-141 0.001 6.982-0 1.322-0 Ce-144 0.131 1.012+0 1.922+0 Hf-181 0.0 1.512-04 2.875-06 Pu-238 0.000 9.962-0 1.892-07 Pu-239 0.000 8.695-07 1.652-08 Pu-241 0.022 1.742-0 3.30E-05 Am-241 0.000 4.14E-0 7.862-08 Cm-242 0.000 1.372-2.602-08 Cm-243 0.000 4.012-7.615-08 Page 13 of 77
SOLID RADIOACTIVE WASTE FOR BURIAL Estimated Solid Waste Composition 2013 Sum of All Cateaories 2013 Volume (m3) 7.47E÷02 Class A
Nuclide
% Abund Curies uCi/mI H-3 25.656 4.01 E+00 5.37E-03 C-14 0.598 9.34E-02 1.25E-04 Cr-51 0.319 4.97E-02 6.65E-05 Mn-54 7.268 1.98E-01 2.65E-04 Fe-55 9.278 1.45E+00 1.94E-0 Fe-59 0.02 3.35E-03 4.48E-0 Co-57 0.157 2.45E-02 3.28E-0 Co-58 7.176 1.12E+00 1.50E-0 Co-60 12.764 1.99E+00 2.66E-0 Ni-59 0.319 4.98E+00 6.67E-0 Ni-63 38.999 6.09E+00 8.15E-0 Zn-65 0.124 1.93E-02 2.58E-0 Sr-90 0.005 7.26E-04 9.72E-0 Zr-95 0.116 1.80E-02 2.41E-0 b-94 0.00 2.29E-04 3.07E-07 b-95 0.95 i.50E-01 2.01 E-04 c-99 0.01 2.53E-3.39E-0 Ru-i 03 0.00 3.40E-4.55E-07 Ru-i 06 0.02 3.90E-5.22E-0 Aa-llOm 0.27 4.21E-5.64E-0 n-113 0.0 1.44E-1.93E-0 b-i 24 0.0 6.43E-8.61 E-08 b-125 1.2 7 2.03E-2.72E-04 e-123m 0.0 6.12E-8.19E-0 e-125m 0.0 1.07E-1.43E-0 Te-132 0.0 2.56E-07 3.43E-
-129 0.
1.32E-i.77E-Cs-134 0.04 7.49E-i.OOE Cs-i 37 0.41 6.45E-0 8.63E-Ce-i 41 0.00 ft98E-0 9.34E-Ce-144 0.071 1.1OE-0 1.47E-Hf-181 0.001 :1i.04 2.02E-Pu-238 0.000 1.0 1.85E-Pu-239 0.000
.69E-07 i.16E-Pu-241 0.019 3.03E-O 4.06E-Am-241 0.000 2.32E-0 3.11E-Cm-242 0.000 1.37E-0 1.83E-Cm-243 0.000 1.89E-0 2.53E-Page 14 of 77
Process Control Program (PCP) for Radioactive Wastes There were no changes to RW-AA-100, Process Control Program (PCP) for Radioactive Waste, in 2013.
Page 15 of 77
Error Analysis The following is an estimate of the errors associated with effluent monitoring and analysis. The estimate is calculated using the square root of the sum of the squares methodology.
1.
Gaseous Effluents Qme=3.33%
RM=N/A ECe=5%
Stdcse/Sm plcse=5%
qme=N/A Total error = 7.8%
2.
Liquid Effluents Qm e=3.33%
RM=N/A ECe=N/A Stdcse/Smplcse=5%
qme=2.22%
Total error = 6.4%
3.
Waste Resin Qme=1 0.0%
RM=N/A ECe=5%
Stdcse/Smplcse=5%
qme=1.0%
Total error = 12.3%
4.
DAW, Mechanical Filters, and Contaminated Metal Qme=1 0.0%
RM=N/A ECe=N/A Stdcse/Sm plcse=5%
qme=N/A Instrument calibration error = 10%
Total error = 11.2%
Qme = the process quantity measurement error associated with the release point (e.g. flow, level measurements)
RM = error associated with the radiation monitor used in quantifying releases through the release point ECe = error associated with the collection efficiency of the sample media Stdcse = one-sigma counting error associated with the counting instrument of interest Smplcse = one-sigma counting error associated with a sample of a given geometry that is used for the release point of interest qme = sample quantity measurement error associated with the sample of interest Page 16 of 77
Miscellaneous Information A.
As required by Technical Specification 5.6.2, meteorological and environmental impact information is reported in the 2073 Annual Radiological Environmental Operating Report (AREOR) or is retained on file to be provided upon request.
B.
No limits were exceeded during the 2013 reporting period in liquid hold up tanks or waste gas decay tanks as stated in Technical Specification 5.5.12.
C. There were no irradiated fuel shipments during the 2013 reporting period. Independent Spent Fuel Storage Installation (ISFSI) campaign began in 2010 when used fuel was removed from the Spent Fuel Pool (SFP), placed into six (6) casks, each containing 32 fuel bundles, and transferred to an outdoor storage pad. No additional casks were placed on the pad in 2071. In 2012, eight (8) additional casks were placed on the pad for a total of fourteen (14) casks. No additional casks were placed on the pad in 2013. Prior to the ISFSI campaign, additional dosimeters were placed at the site boundary nearest to the storage pad (in between the pad and the nearest resident) in order to measure any potential off site dose from the storage pad. Since the dosimeters were placed, data from the dosimeters, when compared to the existing environmental dosimeters, have shown no statistical difference. As a result, there is currently no offsite dose contribution from the ISFSI facility or any other on-site storage facility, including the Old Steam Generator (OSG) Storage Building, as evidenced by dosimetry data that is indistinguishable from the existing environmental dosimeters.
D. There were no REMP sample results that exceeded any technical specification limits or analytical results investigation levels during the 2013 reporting period. REMP composite surface water samples from point BY-12, Rock River downstream of the plant liquid effluent discharge, detected tritium results of 223 pCi/L in the second quarter, against a lower detection limit of 200 pCi/L. The positive sample result can be attributed to one or more weekly samples being obtained shortly after a permitted liquid discharge, and are not unexpected. The results are well below the TRM reportable limit of 30,000 pCi/L. There are no communities using the Rock River for drinking water within 10 km downstream of the station.
E. There were no elevated releases during the 2013 reporting period. All planned gaseous releases were via vent stacks and are considered to be mixed mode releases.
F.
There were no plant effluent radiation release monitors that exceeded inoperability time limits as stated in Technical Requirements Manual (TRM) TLCO 3.11.a or Technical Specification 5.5.12 during the 2013 reporting period. There was one plant effluent radiation release monitor that exceeded its inoperability time limit as stated in Technical Requirements Manual (TRM) TLCO 3.11.b. 2RE-PROO1, U2 Containment Purge Effluent Rad Monitor, entered the LCO on 3/30/13 09:30 and exited on 4/9/13 14:55. This exceeds the 7-day reporting requirement for this monitor. The monitor entered the LCO due to spiking. During troubleshooting, gas detector HVPS #1 connector was found to be defective. The connector center conductor had broken off and was making intermitting contact, causing the channels to spike. All three (gas, particulate, iodine) high voltage power supplies are fed from the same 26 volt power supply. After the Gas hvps #1 connector was replaced, no more spikes were evident. The amount of time it took to troubleshoot the problem resulted in the monitor exceeding the 7-day reporting requirement.
G. There were no unplanned or unmonitored releases of radioactivity from the site to unrestricted areas during the 2013 reporting period.
H. Due to icing conditions near the U.S. Geological Survey Byron Gauging Station for the Rock River, Rock River flow measurements during periods of liquid effluent releases performed on or after December 14, 2013 were obtained from the Rockton flow gauge, located approximately 30 miles upstream of the Byron flow gauge.
Page 17 of 77
Attached are offsite dose calculation reports for January through December of 2013.
The following are the maximum annual calculated cumulative offsite doses resulting from Byron airborne releases in 2013 based on concurrent meteorological data:
Unit 1:
Dose Maximum Value Sector Affected gamma air (1) 7.05 x 106 mrad North-Northwest beta air 5.87 x 106 mrad North-Northwest whole body (3) 8.24 x 102 mrem North-Northwest skin (4) 8.27 x 106 mrem North-Northwest organ (child-bone) 4.02 x 101 mrem North-Northwest Unit 1 Compliance Status 10 CFR 50 Appendix I Yearly Objective
% of Appendix I gamma air 10.0 mrad 0.00 beta air 20.0 mrad 0.02 whole body 5.0 mrem 1.65 skin 15.0 mrem 0.00 organ 15.0 mrem 2.68 Unit 2:
Sector Dose Maximum Value Affected gamma air 2.15 x106 mrad North-Northwest beta air 2) 4.24 x 106 mrad North-Northwest whole body (3) 7.87 x 102 mrem North-Northwest skin (4) 3.06 x 10 mrem North-Northwest organ (5) (chiLd-bone) 3.79 x 10 mrem North-Northwest Unit 2 Compliance Status 10 CFR 50 Appendix I Yearly Objective
% of Appendix I gamma air 10.0 mrad 0.00 beta air 20.0 mrad 0.00 whole body 5.0 mrem 1.57 skin 15.0 mrem 0.00 organ 15.0 mrem 2.52 0)
Gamma Air Dose
- GASPAR II, NUREG-0597 (2)
Beta Air Dose
- GASPAR II, NUREG-0597 Whole Body Dose - GASPAR II, NUREG-0597 (4)
Skin Dose - GASPAR II, NUREG-0597 Inhalation and Food Pathways Dose
- GASPAR II, NUREG-0597 Data recovery: 99.6%
Page 18 of 77
Attachment A, 2013 Radioactive Effluent Release Report 2013 Lower Limits of Detection (LLDs)
Gaseous Required Liquid Required Nuclide LLD fuCilcc)
Gaseous LLD (uCilcc)
Nuclide LLD (uCi/mi)
Liquid LLD (uCi/cc)
H3 4.77E-08 1.OOE-07 H3 l.91E-06 1.OOE-05 Ar41 4.86E-07 Na24 3.27E-08 Cr51 3.98E-12 Cr51 2.58E-07 Mn54 7.24E-13 1.OOE-11 Mn54 4.53E-08 5.OOE-07 Co58 5.26E-13 lODE-li Fe55 5.48E-07 1.OOE-06 Fe59 1.61E-12 1.OOE-1i Co57 2.13E-08 Co60 1.23E-12 1.OOE-1l Co58 4.65E-08 5.OOE-07 Ni63 4.66E-15 Fe59 9.84E-08 5.OOE-07 Zn65 1.38E-12 LODE-il Co60 6.21E-08 5.OOE-07 Br82 6.77E-13 N163 5.63E-07 Kr85m 1.89E-07 Zn65 8.92E-08 5.OOE-07 Kr87 4.56E-07 1.OOE-04 Sr85 3.i7E-08 Kr88 6.26E-07 1.OOE-04 Kr85m 2.53E-05 1.OOE-05 Sr89 3.07E-14 lODE-li Kr87 7.liE-08 i.OOE-05 Sr-90 2.33E-i5 1.OOE-li Kr88 8.23E-08 i.OOE-05 Mo99 2.64E-13 1.OOE-1l Sr89 2.77E-08 5.OOE-08 1131 5.48E-13 i.OOE-12 Sr-gO 7.68E-09 5.OOE-08 Xel3im 6.43E-06 Sr92 6.88E-08 1133 7.83E-13 i.OOE-iO Nb95 3.96E-08 Xei33 3.62E-07 i.OOE-04 Zr95 6.55E-08 Xel 33m 1.65E-06 1.OOE-04 Mo99 2.06E-08 5.OOE-07 Csi34 7.38E-13 l.OOE-ii AgilOm 2.83E-08 1135 4.49E-i2 Sbi22 4.58E-08 Xe135 4.20E-07
.OOE-04 Tei23m 2.35E-08 Cs137 7.78E-i3
.OOE-1 1 Sb124 1.07E-07 Xe138 7.95E-07 1.OOE-04 Sb125 9.35E-08 Ba140 l.77E-12 Te125m 7.1OE-06 La140 9.26E-13 Sbl26 3.55E-08 Cei4l 4.73E-13 i.OOE-il Xel3im i.OOE-06 i.OOE-05 Cei44 2.28E-12 i.OOE-i1 1131 2.92E-08 i.OOE-06 Gross Alpha 4.23E-15 i.OOE-i1 1132 3.82E-08 Tel 32 2.36E-08 1133 4.04E-08 Xe 133 5.55E-08 1.OOE-05 Xei33m 2.06E-07 1.OOE-05 Cs134 4.44E-08 5.OOE-07 Xe135 2.66E-08 1.OOE-05 Csi37 3.78E-08 5.OOE-07 Xe138 2.34E-07 1.OOE-05 Ba140 1.44E-07 Lai4O 4.01 E-08 Cei4i 4.26E-08 5.OOE-07 Ce144 i.77E-07 5.OOE-06 Gross Alpha 7.22E-08 i.OOE-07 Gross Beta 2.63E-07 Page 19 of 77
REPORT FOR 2013 Number of releases Total release time Maximum release time Average release time Minimum release time Note:
Waste Gas Decay EFFLUENT AND WASTE DISPOSAL REPORT SUPPLEMENTAL INFORMATION GASEOUS EFFLUENTS BATCH MODE Unit 1
Units QTR 1
QTR 2
QTR 3
48 61 59 minutes 3.09E+03 4.29E+03 3.68E+03 minutes l.49E+02 3.56E+02 9.OOE+Ol minutes 6.43E+01 7.03E÷01 6.24E+Ol minutes 3.50E+01 7.OOE+00 1.90E+01 Tank releases are included with Unit 1
EFFLUENT AND WASTE DISPOSAL REPORT SUPPLEMENTAL INFORMATION GASEOUS EFFLUENTS BATCH MODE Unit 2
Note:
Liquid releases are divided evenly between units Page 20 of 77 QTR 4
68 6.26E+03
- 1. 20E+03
- 9. 2lE+01
- 2. 60E+Ol data QTR 2
47
- 1. 82E+04 2
. 53E+03 3
. 86E+02
- 1. 80E+Ol QTR 3
29
- 1. 34E+03 7
. OOE+Ol
- 4. 62E+01
- 1. 70E+01 Units QTR 1
36 minutes 1.62E+03 minutes 6.40E+01 minutes 4.50E+Ol minutes 1.90E+01 Units QTR 1
15 YEAR 236
- 1. 73E+04
- 1. 20E+03
- 7. 34E+Ol 7
. OOE+0O YEAR 145
- 2. 26E+04 2
. 53E+03
- 1. 56E+02
- 8. OOE+00 YEAR 70
- 9. l3E+03
- 4. OlE+02
- 1. 30E+02
- 4. 40E+Ol
- 0. OOE+00 REPORT FOR 2013 Number of releases Total release time Maximum release time Average release time Minimum release time REPORT FOR 2013 Number of releases Total release time Maximum release time Average release time Minimum release time Average dilution flow EFFLUENT AND WASTE DISPOSAL REPORT SUPPLEMENTAL INFORMATION LIQUID EFFLUENTS BATCH MODE Unit 1
& Unit 2
QTR 2
24 QTR 4
33
- 1. 49E+03
- 6. 50E+Ol
- 4. 52E+Ol
- 8. OOE+00 QTR 4
13 2.35E+03
- 4. O1E+02
- 1. 8lE+02
- 4. 60E+Ol
- 0. OOE+00 minutes minutes minutes minutes gpm 3
. 07E+03
- 4. OOE÷02 2
. 05E+02
- 8. 40E+Ol 0. OOE+00 QTR 3
18
- 1. l3E+03
- 1. 83E+02 6.29E+Ol 5.20E+Ol
- 0. OOE+00 2
. 58E+03 2
. 75E+02
- 1. 08E+02
- 4. 40E+01
- 0. OOE+00
EFFLUENT AND WASTE DISPOSAL REPORT TABLE 1A GASEOUS EFFLUENTS SUMMATION OF ALL RELEASES Unit 1
REPORT FOR 2013 Units QTR 1
QTR 2
QTR 3
QTR 4
YEAR Fission and Activation Gases
- 1. Total Release Ci 6.05E02 6.45E02 6.28E-02 l.61E-01 3.49E0l 2.
Avg.
Release Rate uCi/sec 7.78E03 8.20E03 7.90E03 2.03E02 l.11E02 Iodine-131 1.
Total Release Ci (1) 6.63E07 l.l2E06 (1) l.78E-06 2.
Avg.
Release Rate uCi/sec (1) 8.43E-08 1.41E-07 (1) 5.65E-08 Particulates Half Life
>=
8 days 1.
Total Release Ci (1) 3.02E06 (1)
(1) 3.02E06 2.
Avg.
Release Rate uCi/sec (1) 3.84E07 (1)
(1) 9.58E08 Others 1.
Total Release Ci l.13E+00 1.llE+00 l.12E+O0 1.l2E+00 4.48E+00 2.
Avg.
Release Rate uCi/sec l.45E0l l.41E0l 1.4lE-Ol l.41E-Ol 1.42E-0l Tn t IUi 1.
Total Release Ci 8.67E+00 6.39E+00 6.87E+00 7.67E+00 2.96E+Ol 2.
Avg. Release Rate uCi/sec l.llE+00 8.l2E01 8.64EOl 9.65EOl 9.38E01 Gross Alpha Radioactivity 1.
Total Release Ci (1)
(1)
(1)
(1)
(1) 2.
Avg.
Release Rate uCi/sec (1)
(1)
(1)
(1)
(1)
(1)
Less than minimum detectable activity which meets the lower limit of detection fLLD) requirements of TRM Section 3.11 Page 21 of 77
EFFLUENT AJJD WASTE DISPOSAL REPORT TABLE 1C
- MIXED MODE RELEASES CONTINUOUS MODE GASEOUS EFFLUENTS Unit 1
REPORT FOR 2013 Fission and Activation Gases XE-133 Ci Totals for Period...
Units QTR 1
QTR 2
QTR 3
QTR 4
YEAR 5.69E02 5.98E02 4.51E02 1.29E0l 2.91E-01 Ci 5.69E02 5.98E02 4.51E02 1.29E01 2.91E01 Tn t ium H-3 Ci Totals for Period...
Ci Gross Alpha Radioactivity No Nuclide Activities Totals for Period...
Ci (1)
Less than minimum detectable activity requirements of TRM Section 3.11 Iodines 1131 Ci 1133 Ci Totals for Period...
Ci Particulates Half Life
>=
8 days CO-58 Ci CO-60 Ci SB-125 Ci Totals for Period...
Ci Others BR-82 Ci C-14 Ci Totals for Period...
Ci (1) 6.63E07 1.12E06 (1) l.78E06 (1) 2.8lE05 1.78E05 (1) 4.59E-05 (1) 2.88E05 l.89E05 (1) 4.77E05 (1) l.90E06 (1)
(1) l.90E06 (1) 8.44E07 (1)
(1) 8.44E07 (1) 2.73E07 (1)
(1) 2.73E-07 (1) 3.02E06 (1)
(1) 3.02E06 (1)
(1)
(1) 1.96E06 l.96E06 l.l3E+00 l.11E+00 1.l2E+00 1.l2E+00 4.48E÷00 l.13E÷00 l.11E÷00 l.12E+00 1.l2E+00 4.48E+00 8.57E+00 6.21E+00 6.73E+00 7.57E÷00 2.9lE+01 8.57E+00 6.21E+00 6.73E+00 7.57E+00 2.9lE+Ol (1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1) which meets the lower limit of detection fLLD)
Page 22 of 77
EFFLUENT AND WASTE DISPOSAL REPORT TABLE 1C GASEOUS EFFLUENTS
- MIXED Unit 1
MODE RELEASES BATCH MODE REPORT FOR 2013 Units QTR 1
QTR 2
QTR 3
QTR 4
YEAR Fission and Activation Gases Particulates Half Life
>=
8 days No Nuclide Activities Totals for Period.
Ci Totals for Period...
Ci Tn t ium H-3 Ci Totals for Period...
Ci (1)
(1)
(1)
(1)
(1)
(1)
(1)
Gross Alpha Radioactivity No Nuclide Activities Totals for Period...
Ci (1)
Less than minimum detectable activity requirements of TEN Section 3.11 (1)
(1)
(1)
(1)
(1) which meets the lower limit of detection fLLD)
- 1. OlE-03 (1)
- 2. 56E03
- 1. 62E05
- 1. 89E05 AR-4l Ci KR-85M Ci XE-l33 Ci XE-133M Ci XE-135 Ci Totals for Period...
Ci lodines
- No Nuclide Activities Totals for Period...
Ci
- 2. 12E03
- 3. 33E06 2.37E03
- 3. 48E05
- 1. 45E04
- 1. 74E02 (1)
- 9. 49E05 (1) 2.38E04
- 3. l3E02 (1) 5
. 40E04
- 1. 06E05 (1)
- 5. 18E02 3.33E06
- 5. 56E03
- 6. 16E05
- 4. 02E04 3.60E03 4.67E03 l.77E02 3.l9E02 5.78E02 (1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
Others
- No Nuclide Activities (1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1) 9.49E02 l.77E01 1.34E01 l.05EOl 5.1EOl 9.49E02 1.77E0l l.34EOl 1.05E-Ol 5.llEOl (1)
(1)
(1)
(1)
(1)
Page 23 of 77
EFFLUENT A1D WASTE DISPOSAL REPORT TABLE 1A GASEOUS EFFLUENTS SUMMATION OF ALL RELEASES Unit 2
REPORT FOR 2013 Units QTR 1
QTR 2
QTR 3
QTR 4
YEAR Fission and Activation Gases 1.
Total Release Ci 6.60E02 6.95E-02 4.52E02 1.32E0l 3.13E0l 2.
AVg.
Release Rate uCi/sec 8.49E03 8.84E-03 5.69E-03 1.66E-02 9.93E-03 Iodine-13 1 1.
Total Release Ci (1) 2.56E06 (1) 7.09E07 3.27E06 2.
Avg.
Release Rate uCi/sec (1) 3.26E07 (1) 8.93E08 1.04E07 Particulates Half Life
>=
8 days
- 1. Total Release Ci (1)
(1)
(1)
(1)
(1) 2.
Avg.
Release Rate uCi/sec (1)
(1)
(1)
(1)
(1)
Others
- 1. Total Release Ci 1.09E+00 8.48E-01 1.l6E+00 1.12E+00 4.22E+00 2.
Avg.
Release Rate uCi/sec l.40E-0l 1.08E-01 1.46E-01 1.41E-01 1.34E-01 Tn tiuin 1.
Total Release Ci 9.60E+00 8.66E+00 l.07E+0l l.30E+Ol 4.l9E+0l 2.
Avg.
Release Rate uCi/sec 1.24E+00 l.1OE+00 l.35E+00 1.63E+00 1.33E÷O0 Gross Alpha Radioactivity 1.
Total Release Ci (1)
(1)
(1)
(1)
(1) 2.
Avg.
Release Rate uCi/sec (1)
(1)
(1)
(1)
(1)
(1)
Less than minimum detectable activity which meets the lower limit of detection fLLD) requirements of TEN Section 3.11 Page 24 of 77
EFFLUENT AND WASTE DISPOSAL REPORT TABLE 1C GASEOUS EFFLUENTS
- MIXED MODE RELEASES CONTINUOUS MODE Unit 2
REPORT FOR 2013 Units QTR 1
QTR 4
YEAR Fission and Activation Gases XE133 Ci 5.69E02 5.98E02 4.51E02 l.29E0l 2.91E0l Totals for Period...
Ci 5.69E02 5.98E02 4.51E-02 l.29E0l 2.91E0l lodines 1131 Ci (1) 2.56E06 (1) 7.09E07 3.27E06 Totals for Period...
Ci (1) 2.56E-06 (1) 7.09E07 3.27E06 Particulates Half Life
>=
8 days No Nuclide Activities (1)
(1)
(1)
(1)
(1)
Totals for Period.
Ci (1)
(1)
(1)
(1)
(1)
Others C14 Ci 1.09E+00 8.48E01 l.16E+00 l.l2E+00 4.22E+00 Totals for Period...
Ci l.09E+00 8.48E0l 1.16E÷00 1.12E+00 4.22E+00 Tn t ium H-3 Ci 9.49E+00 8.14E+00 1.07E÷01 1.29E+01 4.12E+Ol Totals for Period...
Ci 9.49E+00 8.14E+00 1.07E÷0l 1.29E÷01 4.12E+01 Gross Alpha Radioactivity No Nuclide Activities (1)
(1)
(1)
(1)
(1)
Totals for Period...
Ci (1)
(1)
(1)
(1)
(1)
(1)
Less than minimum detectable activity which meets the lower limit of detection (LLD) requirements of TRN Section 3.11 Page 25 of 77
EFFLUENT AND WASTE DISPOSAL REPORT TABLE 1C GASEOUS EFFLUENTS
- MIXED MODE RELEASES BATCH MODE Unit 2
REPORT FOR 2013 Units Fission and Activation Gases AR-41 Ci KR-85M Ci XE-133 Ci XE-133M Ci XE-135 Ci Totals for Period...
Ci lodines
- No Nuclide Activities (1)
Totals for Period...
Ci (1)
Particulates Half Life
>=
8 days
- No Nuclide Activities Totals for Period...
Ci Others No Nuclide Activities Totals for Period...
Ci Gross Alpha Radioactivity
- No Nuclide Activities Totals for Period...
Ci (1)
Less than minimum detectable activity requirements of TEN Section 3.11 QTR 1
QTR 2
QTR 3
QTR 4
YEAR 4.82E-03 1.09E03 (1) 3.33E06 4.22E03 8.43E03 l.62E05 3.49E05 l.88E05 1.45E04 (1)
(1)
- 9. 51E05 (1)
(1) 1
. 48E03 (1)
- 1. 46E03
- 1. 06105 (1) 9.08E-03 9.70E03 9.5lE05 2.95E03
- 7. 39E03
- 3. 33E06 1.42102 6
. l7E05 1.64104 2.18E02 (1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
Tritium H-3 Ci Totals for Period...
Ci
- 1. l4E0l
- 1. l4EOl
- 5. l7EOl
- 5. 17E-0l 3.33102 3
. 33E02 4.76E02
- 4. 76E02 (1)
(1)
(1)
(1)
(1)
(1)
(1)
(1) 7
. 12EOl 7
. l2E0l (1)
(1) which meets the lower limit of detection (LLD)
Page 26 of 77
EFFLUENT AND WASTE DISPOSAL REPORT TABLE 2A LIQUID EFFLUENTS SUMMATION OF ALL RELEASES Unit 1
REPORT FOR 2013 Units QTR 1
QTR 2
QTR 3
QTR 4 YEAR Fission and Activation Products 1.
Total Release Ci 1.73E03 4.12E03 l.69E03 l.38E03 8.92E03 2.
Avg. Diluted Coiic.
uCi/mi 5.O1ElO l.25E-09 4.24ElO 3.71E10 6.17El0 Tn t ium 1.
Total Release Ci 2.96E+02 2.23E+02 6.36E+0l 2.16E+02 7.99E+02 2.
Avg. Diluted Conc.
uCi/ml 8.58E05 6.77E05 l.60E-05 5.80E05 5.53E05 Dissolved and Entrained Gases 1.
Total Release Ci 8.26E-05 8.53E05 (1)
(1) 1.68E04 2.
Avg.
Diluted Conc.
uCi/ml 2.39Ell 2.59E1l (1)
(1) l.l6E11 Gross Alpha Radioactivity 1.
Total Release Ci (1)
(1)
(1)
(1)
(1)
Volume of liquid waste liters 3.45E+09 3.29E+09 3.98E+09 3.73E+09 l.44E÷lO (1)
Less than minimum detectable activity which meets the lower limit of detection (LLD) requirements of TRM Section 3.11 Page 27 of 77
EFFLUENT AND WASTE DISPOSAL REPORT TABLE 2A
- Release Tank LIQUID EFFLUENTS SUMWTION BY RELEASE POINT Unit 1
REPORT FOR 2013 Units QTR 1
QTR 2
QTR 3
QTR 4
YEAR Fission and Activation Products 1.
Total Release Ci l.73E03 4.12E03 l.69E03 l.38E03 8.92E03 2.
Avg. Diluted Conc. uCi/mi 2.73E06 4.09E06 2.22E06 2.48E06 3.02E06 Tritium 1.
Total Release Ci 2.60E÷02 l.72E+02 5.64E+0l l.79E+02 6.68E+02 2.
Avg. Diluted Conc.
uCi/ml 4.lOE-0l l.70E-01 7.43E-02 3.22E-01 2.26E-0l Dissolved and Entrained Gases 1.
Total Release Ci 8.26E05 8.53E05 (1)
(1) 1.68E04 2.
Avg. Diluted Conc.
uCi/ml l.30E07 8.45E-08 (1)
(1) 5.68E-08 Gross Alpha Radioactivity 1.
Total Release Ci (1)
(1)
(1)
(1)
(1)
Volume of liquid waste liters 6.34E+05 1.O1E+06 7.59E+05 5.56E+05 2.96E+06 (1)
Less than minimum detectable activity which meets the lower limit of detection fLLD) requirements of TEN Section 3.11 Page 28 of 77
EFFLUENT AND WASTE DISPOSAL REPORT TABLE 2A
- Circulating Water Blowdown LIQUID EFFLUENTS SUIIITION BY RELEASE POINT Unit 1
REPORT FOR 2013 Units QTR 1
QTR 2
QTR 3
QTR 4
YEAR Fission and Activation Products 1.
Total Release Ci (1)
(1)
(1)
(1)
(1) 2.
Avg.
Diluted Conc.
uCi/mi (1)
(1)
(1)
(1)
(1)
Tn t ium 1.
Total Release Ci 3.62E+0l 5.12E+Ol 7.20E+00 3.68E+0l l.31E+02 2.
Avg. Diluted Conc.
uCi/ml 1.05E05 1.56E05 l.8lE-06 9.87E06 9.lOE06 Dissolved and Entrained Gases 1.
Total Release Ci (1)
(1)
(1)
(1)
(1) 2.
Avg.
Diluted Conc.
uCi/ml (1)
(1)
(1)
(1)
(1)
Gross Alpha Radioactivity 1.
Total Release Ci (1)
(1)
(1)
(1)
(1)
Volume of liquid waste liters 3.45E+09 3.29E+09 3.97E+09 3.73E+09 l.44E+lO (1)
Less than minimum detectable activity which meets the lower limit of detection (LLD) requirements of TRN Section 3.11 Page 29 of 77
EFFLUENT AND WASTE DISPOSAL REPORT TABLE 23 LIQUID EFFLUENTS CONTINUOUS MODE Unit 1
REPORT FOR 2013 Units QTR 1
QTR 2
QTR 3
QTR 4
YEAR Fission and Activation Products No Nuclide Activities Ci (1)
(1)
(1)
(1)
(1)
Totals for Period...
Ci (1)
(1)
(1)
(1)
(1)
Tn tium H3 Ci 3.62E+0l 5.12E+Ol 7.20E+00 3.68E+0l l.3lE+02 Totals for Period...
Ci 3.62E+Ol 5.12E+Ol 7.20E+00 3.68E+01 l.3lE+02 Dissolved and Entrained Gases No Nuclide Activities Ci (1)
(1)
(1)
(1)
(1)
Totals for Period...
Ci (1)
(1)
(1)
(1)
(1)
Gross Alpha Radioactivity No Nuclide Activities Ci (1)
(1)
(1)
(1)
(1)
Totals for Period...
Ci (1)
(1)
(1)
(1)
(1)
(1)
Less than minimum detectable activity which meets the lower limit of detection (LLD) requirements of TEN Section 3.11 Page 30 of 77
EFFLUENT AND WASTE DISPOSAL REPORT TABLE 23 LIQUID EFFLUENTS BATCH MODE Unit 1
REPORT FOR 2013 Units QTR 1
QTR 2
QTR3 QTR4 YEAR Totals for Period...
Ci Tn t ium 1.73E03 4.12E03 1.69E03 1.38E03 8.92E03 H-3 Ci Totals for Period...
Ci 2.60E÷02 l.72E+02 5.64E+Ol l.79E+02 6.68E+02 2.60E+02 l.72E+02 5.64E+0l l.79E+02 6.68E+02 Dissolved and Entrained Gases XE-133 Ci XE-l35 Ci 8.26E05 8.30E05 (1)
(1) 2.27E06 (1)
(1) l.66E04 (1) 2.27E06 Totals for Period...
Ci 8.26E05 8.53E05 (1)
(1) l.68E04 Gross Alpha Radioactivity No Nuclide Activities Ci (1)
Totals for Period...
Ci (1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
Less than minimum detectable activity which meets the lower limit of detection (LLD) requirements of TEN Section 3.11 Fission and Activation Products AG11OM Ci (1) 3.58E06 (1)
(1) 3.58E06 CO57 Ci 4.32E06 (1) 2.30E06 5.76E06 l.24E05 CO58 Ci 6.91E04 l.73E03 l.06E-03 5.65E04 4.05E03 CO-60 Ci 2.3lE04 2.84E04 2.40E04 1.75E04 9.30E04 CR5l Ci (1) l.1OE04 (1)
(1) l.1OE04 FE59 Ci (1) 2.74E04 7.09E06 (1) 2.81E04 MN54 Ci 9.69E06 1.26E05 (1) 7.81E06 3.O1E05 NI63 Ci 7.92E04 l.02E03 3.28E04 6.29E04 2.77E03 SB125 Ci (1) l.53E05 4.87E-05 (1) 6.40E05 S3126 Ci (1) 9.75E07 (1)
(1) 9.75E07 TEl23M Ci (1) 9.27E06 (1)
(1) 9.27E06 TE125M Ci (1) 6.65E04 (1)
(1) 6.65E04 Page 31 of 77
EFFLUENT AND WASTE DISPOSAL REPORT TABLE 2A LIQUID EFFLUENTS SUMMATION OF ALL RELEASES Unit 2
REPORT FOR 2013 Units QTR 1
QTR 2
QTR 3
QTR 4
YEAR Fission and Activation Products 1.
Total Release Ci l.73E03 4.12E-03 l.69E03 l.38E-03 8.92E03 2.
Avg.
Diluted Conc.
uCi/mi 5.O1E-1O 1.25E-09 4.24E10 3.71E-l0 6.17El0 Tn t ium 1.
Total Release Ci 2.96E+02 2.23E+02 6.36E+0l 2.16E+02 7.99E+02 2.
Avg. Diluted Conc. uCi/mi 8.58E05 6.77E05 l.60E05 5.80E05 5.53E05 Dissolved and Entrained Gases 1.
Total Release Ci 8.26E05 8.53E05 (1)
(1) 1.68E04 2.
Avg. Diluted Conc. uCi/ml 2.39E-l1 2.59E-ll (1)
(1) 1.16Ell Gross Alpha Radioactivity 1.
Total Release Ci (1)
(1)
(1)
(1)
(1)
Volume of liquid waste liters 3.45E+09 3.29E+09 3.98E+09 3.73E+09 l.44E+l0 (1)
Less than minimum detectable activity which meets the lower limit of detection (LLD) requirements of TEN Section 3.11 Page 32 of 77
EFFLUENT AND WASTE DISPOSAL REPORT TABLE 2A
- Release Tank LIQUID EFFLUENTS SUMMATION BY RELEASE POINT Unit 2
REPORT FOR 2013 Units QTR 1
QTR 2
QTR 3
QTR 4
YEAR Fission and Activation Products 1.
Total Release Ci 1.73E03 4.l2E-03 1.69E-03 l.38E03 8.92E03 2.
Avg.
Diluted Conc.
uCi/mi 2.73E06 4.09E06 2.22E-06 2.48E06 3.02E06 Tn t ium 1.
Total Release Ci 2.60E+02 l.72E+02 5.64E÷0l l.79E÷02 6.68E+02 2.
Avg.
Diluted Conc.
uCi/ml 4.1OE01 l.70E-01 7.43E-02 3.22E-0l 2.26E0l Dissolved and Entrained Gases 1.
Total Release Ci 8.26E05 8.53E05 (1)
(1) 1.68E04 2.
Avg. Diluted Conc.
uCi/ml 1.30E07 8.45E08 (1)
(1) 5.68E08 Gross Alpha Radioactivity
- 1. Total Release Ci (1)
(1)
(1)
(1)
(1)
Volume of liquid waste liters 6.34E+05 1.O1E+06 7.59E+05 5.56E+05 2.96E+06 (1)
Less than minimum detectable activity which meets the lower limit of detection fLLD) requirements of TRM Section 3.11 Page 33 of 77
EFFLUENT AND WASTE DISPOSAL REPORT TABLE 2A
- Circulating Water Blowdown LIQUID EFFLUENTS SUMMATION BY RELEASE POINT Unit 2
REPORT FOR 2013 Units QTR 1
QTR 2
QTR 3
QTR 4
YEAR Fission and Activation Products 1.
Total Release Ci (1)
(1)
(1)
(1)
(1) 2.
Avg. Diluted Conc.
uCi/mi (1)
(1)
(1)
(1)
(1)
Tn t ium 1.
Total Release Ci 3.62E+Ol 5.l2E+Ol 7.20E+00 3.68E+Ol l.3lE+02 2.
Avg. Diluted Conc.
uCi/mi l.05E-05 l.56E-05 l.8lE-06 9.87E-06 9.1OE-06 Dissolved and Entrained Gases 1.
Total Release Ci (1)
(1)
(1)
(1)
(1) 2.
Avg. Diluted Conc. uCi/ml (1)
(1)
(1)
(1)
(1)
Gross Alpha Radioactivity
- 1. Total Release Ci (1)
(1)
(1)
(1)
(1)
Volume of liquid waste liters 3.45E+09 3.29E+09 3.97E+09 3.73E+09 l.44E+lO (1)
Less than minimum detectable activity which meets the lower limit of detection (LLD) requirements of TRM Section 3.11 Page 34 of 77
EFFLUENT AND WASTE DISPOSAL REPORT TABLE 23 LIQUID EFFLUENTS CONTINUOUS MODE Unit 2
REPORT FOR 2013 Units QTR 1
QTR 2
QTR 3
QTR 4
YEAR Fission and Activation Products No Nuclide Activities Ci (1)
(1)
(1)
(1)
(1)
Totals for Period..
Ci (1)
(1)
(1)
(1)
(1)
Tn t ium H3 Ci 3.62E+Ol 5.l2E+0l 7.20E+00 3.68E+0l l.31E+02 Totals for Period...
Ci 3.62E+0l 5.12E+01 7.20E+0Q 3.68E+0l l.31E+02 Dissolved and Entrained Gases No Nuclide Activities Ci (1)
(1)
(1)
(1)
(1)
Totals for Period...
Ci (1)
(1)
(1)
(1)
(1)
Gross Alpha Radioactivity No Nuclide Activities Ci (1)
(1)
(1)
(1)
(1)
Totals for Period.
Ci (1)
(1)
(1)
(1)
(1)
(1)
Less than minimum detectable activity which meets the lower limit of detection (LLD) requirements of TRM Section 3.11 Page 35 of 77
EFFLUENT AND WASTE DISPOSAL REPORT TABLE 23 LIQUID EFFLUENTS BATCH MODE Unit 2
REPORT FOR 2013 Units QTR 1
QTR 2
QTR3 QTR4 YEAR Totals for Period...
Ci Tn t ium l.73E03 4.12E03 l.69E03 l.38E03 8.92E03 3-3 Ci Totals for Period...
Ci Dissolved and Entrained Gases XE-l33 Ci XE-l35 Ci 8.26E05 8.30E05 (1)
(1) 2.27E06 (1)
Totals for Period...
Ci 8.26E05 8.53E05 (1)
(1) 1.68E04 Gross Alpha Radioactivity No Nuclide Activities Ci (1)
Totals for Period...
Ci (1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
Less than minimum detectable activity which meets the lower limit of detection fLLD) requirements of TEN Section 3.11 Fission and Activation Products AGllOM Ci (1) 3.58E06 (1)
(1) 3.58E06 CO57 Ci 4.32E06 (1) 2.30E06 5.76E06 l.24E05 CO-58 Ci 6.91E04 l.73E-03 l.06E03 5.65E04 4.05E03 CO-60 Ci 2.3lE04 2.84E04 2.40E04 l.75E04 9.30E04 CR5l Ci (1) l.1OE04 (1)
(1) l.lOE04 FE59 Ci (1) 2.74E04 7.09E06 (1) 2.81E04 MN54 Ci 9.69E06 l.26E05 (1) 7.8lE06 3.O1E05 NI63 Ci 7.92E04 l.02E03 3.28E04 6.29E04 2.77E03 SB125 Ci (1) l.53E05 4.87E05 (1) 6.40E-05 S3l26 Ci (1) 9.75E07 (1)
(1) 9.75E07 TEl23M Ci (1) 9.27E06 (1)
(1) 9.27E06 TE125M Ci (1) 6.65E04 (1)
(1) 6.65E04 2.60E+02 l.72E+02 5.64E+Ol l.79E+02 6.68E+02 2.60E+02 l.72E÷02 5.64E+Ol l.79E+02 6.68E+02 (1)
(1)
- 1. 66E04 2.27E06 Page 36 of 77
4OCFR19O URANIUM FUEL CYCLE DOSE REPORT LIQUID DOSE
SUMMARY
Unit 1
2 Report for:
2013 Unit Range
- From:
1 To:
2 Liquid Receptor PERIOD DOSE BY ORGAN AND AGE GROUP (mrem)
QUARTER 1
Agegrp Bone Liver Thyroid Kidney Lung GI-ILI Skin TB ADULT 2.03E02 3.97E02 3.82E02 3.82E02 3.82E02 4.06E02 TEEN 2.1OE02 3.03E02 2.87E02 2.87E02 2.87E02 3.03E02 CHILD 2.77E02 3.35E02 3.19E02 3.20E02 3.19E02 3.25E02 INFANT l.55E04 1.42E02 1.42E02 l.42E02 1.42E02 1.42E02
= = = SITE DO SE LIMIT ANALYSIS
= = = = = = = = = = = = = = = = = = = = = = = = = = =
QUARTER 1
= = = = = = = = =
Age Dose Limit Max
% of Quartr
- Limit Group Organ (mrem) fmrem)
Limit Qtr 1
- Admin.
Any Organ ADULT GILLI 4.06E-02 3.75E÷00 1.08E+00 Qtr 1
- Admin.
Total Body ADULT TBODY 3.91E-02 l.13E÷00 3.48E+00 Qtr 1
- T.Spc.
Any Organ ADULT GILLI Critical Pathway:
Fresh Water Fish Sport (FFSP)
Major Contributors (0% or greater to total)
Nuclide Percentage H3 9.42E÷01
- 2. 63E01 2
. 54E+00
- 2. 26E÷00
- 7. 23E01 Qtr 1
- T.Spc.
Total Body ADULT TBODY Critical Pathway:
Fresh Water Fish Sport (FFSP)
Major Contributors f 0% or greater to total)
Nuclide Percentage H-3 MM 54 CO-58 CO-60 NI63
- 0. OOE+00
- 0. OOE+00 0
. OOE+00
- 0. OOE+00
- 3. 91E02 2.96E02
- 3. 31E02
- 1. 42E02 MM-54 CO-58 CO-60 NI63 4.06E02 5.OOE+00 8.11EOl 3.91E02 l.50E+00 2.61E+00 9.77E+01 1.70E02
- 2. 92EOl
- 2. 75EOl
- 1. 74E+00 Page 37 of 77
4OCFR19O URANIUM FUEL CYCLE DOSE REPORT LIQUID DOSE StThTh4ARY Unit 1
2 Report for:
2013 Unit Range
- From:
1 To:
2 Liquid Receptor PERIOD DOSE BY ORGAN AND AGE GROUP (mrem)
==
QUARTER 2
Agegrp Bone Liver Thyroid Kidney Lung GI-LLI Skin TB ADULT 3.50E02 3.58E-02 324E02 3.91E02 3.21E02 4.66E02 0.OOE+00 3.40E02 TEEN 3.64E02 2.80E02 2.45E-02 2.39E02 2.42E02 3.50E02 0.OOE+00 2.62E02 CHILD 478E02 3.06E02 2.74E-02 2.67E02 2.69E02 3.1OE02 0.OOE+00 2.94E02 INFANT 2.61E04 1.19E02 1.1SE-02 1.18E02 1.1BE02 1.19E02 0.OOE÷00 1.19E02
= = = SITE DOSE LIMIT ANALYS IS
= = = = = = = = = = = = = = = = = = = = = = = = = = =
QUARTER 2
= = = ====
Age Dose Limit Max
% of Quartr
- Limit Group Organ (mrem)
(mrem)
Limit Qtr 2
- Admin.
Any Organ CHILD BONE 4.78E-02 3.75E÷00 1.28E÷00 Qtr 2
- Admin.
Total Body ADULT TBODY 3.40E-02 1.13E+00 3.03E+00 Qtr 2
- T.Spc.
Any Organ CHILD BONE 4.78E-02 5.OOE+00 9.57E-01 Critical Pathway:
Fresh Water Fish Sport (FFSP)
Major Contributors (0% or greater to total)
Nuclide Percentage FE59 7.74E01 NI63 9.41E+01 AGibM 1.OOE05 TE125M 5.17E÷00 Qtr 2
- T.Spc. Total Body ADULT TBODY 3.40E-02 1.50E+00 2.27E+00 Critical Pathway:
Fresh Water Fish Sport (FFSP)
Major Contributors f 0% or greater to total)
Nuclide Percentage H-3 9.37E+Ol CR51 4.26E04 MN54 3.21E02 FE59 7.8lE01 CO58 1.06E+00 CO-60 4.9lE-Ol NI63 3.25E+00 AGibM 6.07E06 TE125M 6.96E0l Page 38 of 77
4OCFR19O URANIUM FUEL CYCLE DOSE REPORT LIQUID DOSE
SUMMARY
Unit 1
2 Report for:
2013 Unit Range
- From:
1 To:
2 Liquid Receptor PERIOD DOSE BY ORGAN AND AGE GROUP (mrem)
==
QUARTER 3
Agegrp Bone Liver Thyroid Kidney Lung GI-LLI Skin TB ADULT 2.04E02 2.18E02 2.O1E02 2.O1E02 2.O1E02 2.66E-02 0.OOE+00 2.14E02 TEEN 2.11E02 1.69E02 1.50E02 1.50E02 1.51E02 1.96E02 0.OOE+00 1.65E02 CHILD 2.78E02 1.85E02 1.68E02 1.68E02 1.68E02 1.83E02 0.OOE+00 1.85E02 INFANT 1.56E04 7.44E03 7.43E03 7.43E03 7.43E03 7.44E03 0.OOE+00 7.44E03
=
SITE DOSE LIMIT ANALYSIS
= = = = = = = = = = = = = = = = = = = = = = = = = = =
QUARTER 3
= = = = = = = = =
Age Dose Limit Max
% of Quartr
- Limit Group Organ (mrem)
(mrem)
Limit Qtr 3
- Admin.
Any Organ CHILD BONE 2.78E-02 3.75E+00 7.41E-01 Qtr 3
- Admin.
Total Body ADULT TBODY 2.14E-02 1.l3E+00 1.91E+00 Qtr 3
- T.Spc.
Any Organ CHILD BONE 2.78E-02 5.OOE+00 5.56E-01 Critical Pathway:
Fresh Water Fish Sport (FFSP)
Major Contributors (0% or greater to total)
Nuclide Percentage FE59 6.63E02 NI63 9.99E+Ol Qtr 3
- T.Spc.
Total Body ADULT TBODY 2.14E-02 1.50E+00 l.43E+00 Critical Pathway:
Fresh Water Fish Sport (FFSP)
Major Contributors (0% or greater to total)
Nuclide Percentage H3 9.35E+Ol FE59 6.17E02 CO58 l.98E+00 CO60 l.26E+00 NI63 3.l8E+00 Page 39 of 77
4OCFR19O URANIUM FUEL CYCLE DOSE REPORT LIQUID DOSE
SUMMARY
Unit 1
2 Report for:
2013 Unit Range
- From:
1 To:
2 Liquid Receptor PERIOD DOSE BY ORGAN AND AGE GROUP fmrem)
==
QUARTER 4
=
Agegrp Bone Liver Thyroid Kidney Lung GI-LLI Skin TB ADULT 2.03E02 3.48E02 3.33E-02 3.33E02 3.33E02 3.56E02 TEEN 2.1E-02 2.66E02 2.50E02 2.50E02 2.50E02 2.66E02 CHILD 2.78E02 2.94E02 2.78E02 2.78E02 2.78E02 2.84E02 INFANT 1.55E04 1.24E02 1.23E02 1.23E02 1.23E02 1.23E02 SITE DOSE LIMIT ANALYSIS
=========================== QUARTER 4
Age Dose Limit Group Organ (mrem) fmrem)
Quartr
- Limit Qtr 4
- Admin.
Any Organ ADULT Qtr 4
- Admin. Total Body ADULT GILLI 3.56E02 3.75E+00 TBODY 3.42E-02 1.13E+00 Max
% of Limit
- 9. 50E01 3
. 04E+00 Qtr 4
- T.Spc.
Any Organ ADULT GILLI Critical Pathway: Fresh Water Fish Sport (FFSP)
Major Contributors (0% or greater to total)
Nuclide Percentage Qtr 4
- T.Spc. Total Body ADULT TBODY Critical Pathway:
Fresh Water Fish Sport fFFSP)
Major Contributors (0% or greater to total)
Nuclide Percentage H3 9.73E+0l NN54 1.98E02 CO58 3.44E01 CO60 3.02EOl NI63 1.99E+00 3.42E02 l.50E+00 2.28E+00
- 0. OOE+00
- 0. OOE+00
- 0. OOE+00
- 0. OOE+00 3
. 42E02 2. 59E02
- 2. 90E02
- 3. 05E0l 2. 99E+00
- 2. 47E+00 8.25EOl Page 40 of 77
4OCFR19O URANIUM FUEL CYCLE DOSE REPORT LIQUID DOSE
SUMMARY
Unit 1
2 Report for:
2013 Unit Range
- From:
1 To:
2 Liquid Receptor PERIOD DOSE BY ORGAN AND AGE GROUP (mrem)
ANNUAL 2013 Agegrp Bone Liver Thyroid Kidney Lung GI-LLI Skin ADULT TEEN CHILD INFANT
- 0. OOE+00
- 0. OOE+00
- 0. OOE+00
- 0. OOE+00 TB
- 1. 34E01
- 1. 02E01
- 1. 14E01
- 4. 79E02
= = = SITE DOSE LIMIT ANALYSIS
= = = = = = = ===== = = = = = = = = = = = = =
ANNUAL 2013
=
= = =
Age Dose Group Organ (mrem)
Limit Max
% of (mrem)
Limit 2013
- Adntin.
Any Organ 2013
- Admin.
Total Body ADULT GILLI ADULT TBODY i.53E0l 7.50E÷00 2.05E+00 i.34E0l 2.25E+00 5.96E÷00 Nuclide H-3 CR-51 MN 54 FE-59 CO-S 8 CO-60 NI-63 AG-li OM TE-l25M H-3 CR-51 MN54 FE-59 CO-S 8 CO-60 NI63 AG-il OM TE-i2SM Percentage
- 8. 4iE+Oi
- 2. 47E02 2
. 84E01
- 1. 6iE+00
- 5. 18E+00 3
. 17E+00 8.79EOi
- 9. 64E04 4.79E+00
- 9. 62E+0l
- 1. l3E04
- 2. 03E02
- 2. l2E0l
- 6. 55E0l
- 4. 25EOl 2
. 33E+00
- 1. 61E06
- 1. 84E-Oi 9.53E02 i.38EOl 9.89E02 i.06EOl 1.30E0i l.17EOi 7.21E04 4.79E02 l.29E0i 1.36EOl i.29E0l l.53EOi 9.73E02 9.68E02 9.70E02 i.i5E0i i.09E01 1.08EOi i.08E0l l.1SE0i 4.78E02 4.78E02 4.78E02 4.78E02 Annual
- Limit 2013
- T.Spc.
Any Organ ADULT GILLI Critical Pathway: Fresh Water Fish Sport (FFSP)
Major Contributors (0% or greater to total) i.53EOl l.OOE+0l l.53E+00 i.34EOl 3.OOE+00 4.47E+00 2013
- T.Spc.
Total Body ADULT TBODY Critical Pathway:
Fresh Water Fish Sport (FFSP)
Major Contributors (0% or greater to total)
Nuclide Percentage Page 41 of 77
4OCFR19O URANIUM FUEL CYCLE DOSE REPORT GASEOUS DOSE
SUMMARY
Unit 1
2 Report for:
2013 Unit Range
- From:
1 To:
2
= = = I & P DOSE LIMIT ANALYSIS
= = = = = = = = = = = = = = = = = = = = = = = = = = = =
QUARTER 1
= = = = = = = = =
Age Dose Limit Max
% of Quartr
- Limit Group Organ (mrem)
(mrem)
Limit Qtr 1
- Admin.
Any Organ CHILD BONE 1.81E-01 5.63E+00 3.22E+00 Qtr 1
- Admin.
Total Body CHILD TBODY 3.72E-02 5.25E+00 7.09E-0l Qtr 1
- T.Spc.
Any Organ CHILD BONE 1.81E-0l 7.50E+00 2.41E÷00 Receptor:
5 Composite Crit. Receptor IP Distance:
800 (meters)
Compass Point:
SSE Critical Pathway: Vegetation Major Contributors f 0% or greater to total)
Nuclide Percentage H3 0.OOE+O0 Cl4 l.OOE+02 Qtr 1
- T.Spc. Total Body CHILD TBODY 3.72E-02 7.50E+00 4.96E-0l Receptor:
5 Composite Crit. Receptor
- IP Distance:
800 (meters)
Compass Point:
SSE Critical Pathway: Vegetation Major Contributors (0% or greater to total)
Nuclide Percentage H3 2.77E+00 C14 9.72E+Ol Page 42 of 77
4OCFR19O URANIUM FUEL CYCLE DOSE REPORT GASEOUS DOSE
SUMMARY
Unit 1
2 Report for:
2013 Unit Range From:
1 To:
2
=
NG DO SE LIMIT ANALYSIS
= = = = = = = = = = = ==== = = = = = = = = = = = =
QUARTER 1
= = = = = = = = =
Dose Limit Max
% of Quartr
- Limit (mrad)
(mrad)
Limit Qtr 1
Admin.
Gamma 5.62E06 3.75E+00 1.50E04 Qtr 1
- Admin.
Beta 2.08E-06 7.50E+00 2.77E-05 Qtr 1
- T.Spc.
Gamma 5.62E-06 5.OOE+00 1.12E-04 Receptor:
4 Composite Crit.
Receptor NG Distance:
800 (meters)
Compass Point:
SSE Nuclide Percentage AR-41 5.60E+01 XE135 7.47E02 XE133M 1.09E02 XE133 4.40E+01 Qtr 1
- T.Spc.
Beta 2.08E-06 1.OOE+01 2.08E-05 Receptor:
4 Composite Crit.
Receptor NG Distance:
800 (meters)
Compass Point:SSE Nuclide Percentage AR41 1.31E+01 XE135 6.36E02 XE133M 3.28E02 XE133 8.68E+01 Page 43 of 77
4OCFR19O URANIUM FUEL CYCLE DOSE REPORT GASEOUS DOSE
SUMMARY
Unit 1
2 Report for:
2013 Unit Range From:
1 To:
2
= = = I &P DOSE LIMIT ANALYSIS
= = = = = = = = = = = = = = = = = = = = = = = = = = = =
QUARTER 2
= = = = = = = = =
Age Dose Limit Max
% of Quartr
- Limit Group Organ (mrem)
(mrem)
Limit Qtr 2
- Admin.
Any Organ CHILD BONE 1.60E-01 5.63E+00 2.84E+00 Qtr 2
- Ad.min.
Total Body CHILD TBODY 3.28E-02 5.25E+00 6.24E-0l Qtr 2
- T.Spc.
Any Organ CHILD BONE 1.60E-01 7.50E+00 2.13E+00 Receptor:
5 Composite Crit. Receptor
- I?
Distance:
800 (meters)
Compass Point:
SSE Critical Pathway: Vegetation Major Contributors (0% or greater to total)
Nuclide Percentage H3 0.OOE+00 C14 1.OOE+02 CO58 5.40E05 CO60 1.55E03 1131 3.58E04 1133 5.28E05 Qtr 2
- T.Spc. Total Body CHILD TBODY 3.28E-02 7.50E+00 4.37E-01 Receptor:
5 Composite Crit. Receptor IP Distance:
800 (meters)
Compass Point:
SSE Critical Pathway: Vegetation Major Contributors (0% or greater to total)
Nuclide Percentage H3 2.59E+00 C14 9.74E+01 CO-58 4.61E-04 CO60 7.97E03 1131 l.OOE03 1133 1.34E04 Page 44 of 77
Report for:
2013 Unit Range From:
1 4OCFR19O URANIUM FUEL CYCLE DOSE REPORT GASEOUS DOSE
SUMMARY
To:
2 Unit 1
2
=
NG DO SE L IMIT ANALYSIS
= = = = = = = = = = = = = = = = = = = = = = = = = = = = =
Dose Quartr
- Limit (mrad)
Qtr 2
- Admin.
Gamma 4.44E-06 Qtr 2
- Admin.
Beta 2.12E-06 Qtr 2
- T.Spc.
Gamma Receptor:
4 Composite Crit.
Receptor NG Distance:
800 (meters)
Compass Point:
SSE Nuclide Percentage 3
. 90E+01
- 1. 07E02
- 7. 27E-01
- 2. 98E02 6
. 02E+01 Qtr 2
Receptor:
Distance:
Nuclide AR 41 KR-85M XE-13 5 XE-13 3M XE-13 3
- 7. 1OE+00
- 8. 84E03
- 4. 80E01
- 6. 95E02 9.23E+01 QUARTER 2
= = = = = = = = =
Limit Max
% of (mrad)
Limit 3.75E÷00 1.18E04 7.50E+00 2.82E05 AR-41 KR-85M XE-13 5 XE-13 3M XE -133 4.44E06 5.OOE÷00 8.88E05 T.Spc.
Beta 2.12E06 1.OOE+01 2.12E-05 4
Composite Crit.
Receptor NG 800 (meters)
Compass Point:
SSE Percentage Page 45 of 77
4OCFR19O URANIUM FUEL CYCLE DOSE REPORT GASEOUS DOSE SUIYUIARY Unit 1
2 Report for:
2013 Unit Range From:
1 To:
2
= = = I &P DOSE LIMIT ANALYSIS
= = = = = = = = = = = = = = = = = = = = = = = = =
QUARTER 3
= = = = = = = = =
Age Dose Limit Max
% of Quartr
- Limit Group Organ (mrem)
(mrem)
Limit Qtr 3
- Admin.
Any Organ CHILD BONE l.86E-01 5.63E÷00 3.31E+00 Qtr 3
Adirtin.
Total Body CHILD TBODY 3.82E-02 5.25E+00 7.28E-01 Qtr 3
- T.Spc.
Any Organ CHILD BONE 1.86E-0l 7.50E+00 2.48E+00 Receptor:
5 Composite Crit.
Receptor
- I?
Distance:
800 (meters)
Compass Point:
SSE Critical Pathway: Vegetation Major Contributors (0% or greater to total)
Nuclide Percentage H3 0.OOE+00 C14 l.OOE+02 1131 l.06E04 1133 2.86E05 Qtr 3
- T.Spc.
Total Body CHILD TBODY 3.82E-02 7.50E+00 5.lOE-Ol Receptor:
5 Composite Crit.
Receptor
- IP Distance:
800 (meters)
Compass Point:
SSE Critical Pathway: Vegetation Major Contributors (0% or greater to total)
Nuclide Percentage H3 2.60E+00 C14 9.74E+01 1131 2.99E04 1133 7.23E05 Page 46 of 77
4OCFR19O URANIUM FUEL CYCLE DOSE REPORT GASEOUS DOSE
SUMMARY
Unit 1
2 Report for:
2013 Unit Range From:
1 To:
2
=
NG DO SE LIMIT ANALYSIS
= = = = = = = = = = = = = = = = = = = = = = = = = = = = =
QUARTER 3
= = = = = = = = =
Dose Limit Max
% of Quartr
- Limit (mrad)
(mrad)
Limit Qtr 3
- Admin.
Gamma 1.13E05 3.75E+OO 3.01E04 Qtr 3
- Admin.
Beta 2.18E-06 7.50E+00 2.90E-05 Qtr 3
- T.Spc.
Gamma 1.13E-05 5.OOE+00 2.26E-04 Receptor:
4 Composite Crit.
Receptor NO Distance:
800 (meters)
Compass Point:
SSE Nuclide Percentage AR41 8.34E+01 XE135 2.35E01 XE133 1.64E+01 Qtr 3
- T.Spc.
Beta 2.18E-06 1.OOE+01 2.18E-05 Receptor:
4 Composite Crit.
Receptor NG Distance:
800 (meters)
Compass Point:
SSE Nuclide Percentage AR-41 3.74E+01 XE135 3.84E01 XE133 6.22E+01 Page 47 of 77
4OCFR19O URANIUM FUEL CYCLE DOSE REPORT GASEOUS DOSE
SUMMARY
Unit 1
2 Report for:
2013 Unit Range From:
1 To:
2
= = = I &P DO SE LIMIT ANALYSIS
= = = = = = = = = = = = = = = = = = = = = = = = = = = =
QUARTER 4
= = = = = = = = =
Age Dose Limit Max
% of Quartr
- Limit Group Organ fmrem)
(mrem)
Limit Qtr 4
- Admin.
Any Organ CHILD BONE 1.83E-01 5.63E+00 3.25E+00 Qtr 4
- Admin.
Total Body CHILD TBODY 3.77E-02 5.25E+00 7.17E-Ol Qtr 4
- T.Spc.
Any Organ CHILD BONE l.83E-Ol 7.50E+00 2.43E+00 Receptor:
5 Composite Crit.
Receptor
- I?
Distance:
800 (meters)
Compass Point:
SSE Critical Pathway: Vegetation Major Contributors (0% or greater to total)
Nuclide Percentage H3 0.OOE+00 C14 1.OOE+02 1131 6.88E05 Qtr 4
- T.Spc.
Total Body CHILD TBODY 3.77E-02 7.50E+00 5.02E-01 Receptor:
5 Composite Crit. Receptor IP Distance:
800 (meters)
Compass Point:
SSE Critical Pathway: Vegetation Major Contributors (0% or greater to total)
Nuclide Percentage H3 3.09E+00 C14 9.69E+01 1131 l.92E04 Page 48 of 77
4OCFR19O URANIUM FUEL CYCLE DOSE REPORT GASEOUS DOSE
SUMMARY
Unit 1
2 Report for:
2013 Unit Range From:
1 To:
2
=
NG DO SE LIMIT ANALYSIS
= = = = = = = = = = = = = = = = = = = = = = = = = = = = =
QUARTER 4
= = = = = = = = =
Dose Limit Max
% of Quartr
- Limit (mrad)
(mrad)
Limit Qtr 4
- Admin.
Gamma 2.30E-05 3.75E+00 6.13E-04 Qtr 4
- Admin.
Beta 5.43E-06 7.50E+00 7.23E-05 Qtr 4
- T.Spc.
Gamma 2.30E05 5.OOE+00 4.60E-04 Receptor:
4 Composite Crit.
Receptor NG Distance:
800 (meters)
Compass Point:
SSE Nuclide Percentage AR41 7.68E+01 XE133M 1.75E03 XE133 2.32E+01 Qtr 4
- T.Spc.
Beta 5.43E-06 1.OOE+01 5.43E-05 Receptor:
4 Composite Crit.
Receptor NG Distance:
800 (meters)
Compass Point:
SSE Nuclide Percentage AR41 2.82E+01 XE133M 8.26E03 XE133 7.18E+01 Page 49 of 77
4OCFR19O URANIUM FUEL CYCLE DOSE REPORT GASEOUS DOSE
SUMMARY
Unit 1
2 Report for:
2013 Unit Range
- From:
1 To:
2
=
I&P DOSE LIMIT ANALYSIS
= = = = = = = = = = = = = = = = = = = = = = = = = = = =
ANNUAL 2013
= = = = = = =
Age Dose Limit Max
% of Annual
- Limit Group Organ (mrem)
(mrem)
Limit 2013
- Admin.
Any Organ CHILD BONE 7.09E-01 1.13E+01 6.31E+00 2013
- Admin. Total Body CHILD TBODY l.46E-Ol 1.05E+Ol l.39E+00 2013
- T.Spc.
Any Organ CHILD BONE 7.09E-01 1.50E+0l 4.73E+00 Receptor:
5 Composite Crit.
Receptor
- IP Distance:
800 (meters)
Compass Point:
SSE Critical Pathway: Vegetation Major Contributors (0% or greater to total)
Nuclide Percentage H3 0.OOE+00 C-14 1.OOE+02 CO58 l.22E05 CO60 3.48E04 1131 l.26E04 1133 1.94E05 2013
- T.Spc. Total Body CHILD TBODY l.46E-01 l.50E+01 9.73E-0l Receptor:
5 Composite Crit.
Receptor
- IP Distance:
800 (meters)
Compass Point:
SSE Critical Pathway: Vegetation Major Contributors f 0% or greater to total)
Nuclide Percentage H3 2.77E+00 Cl4 9.72E÷Ol CO58 1.03E-04 CO60 l.79E03 1131 3.54E04 1133 4.90E05 Page 50 of 77
4OCFR19O URANIUM FUEL CYCLE DOSE REPORT GASEOUS DOSE
SUMMARY
Unit 1
2 Report for:
2013 Unit Range From:
1 To:
2
=
NG DOSE LIMIT ANALYSIS
= = = = = = = = = = = = = = = = = = = = = = = = = = = = =
ANNUAL 2013
= = = = = = =
Dose Limit Max
% of Annual
- Limit (mrad)
(mrad)
Limit 2013 Admin.
Gamma 4.43E-05 7.50E+00 5.91E04 2013 Admin.
Beta 1.18E-05 1.50E+01 7.86E05 2013
- T.Spc.
Gamma 4.43E05 1.OOE+01 4.43E04 Receptor:
4 Composite Crit.
Receptor NG Distance:
800 (meters)
Compass Point:
SSE Nuclide Percentage AR41 7.21E+01 KR85M 1.07E03 XE135 1.42E01 XEl33M 5.28E03 XE133 2.78E+01 2013
- T.Spc.
Beta l.18E-05 2.OOE+01 5.90E-05 Receptor:
4 Composite Crit.
Receptor NG Distance:
800 (meters)
Compass Point:
SSE Nuclide Percentage AR41 2.35E+0l KR85M l.58E03 XE135 l.68E0l XE-133M 2.21E02 XE133 7.63E+Ol Page 51 of 77
4OCFR19O URANIUM FUEL CYCLE DOSE REPORT Unit 1
2 Report for:
2013 Unit Range
- From:
1 To:
2
=
MAXIMUM DO SE ANALYSIS
= = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
AJSJNUAL 2013
= = = = = = =
Age Dose Dose Type Group Organ (mrem)
Any Organ CHILD BONE 8.40E-01 Liquid Receptor:
0 Liquid Receptor Gaseous Receptor:
5 Composite Crit. Receptor IP Distance:
800 (meters)
Compass Point:
SSE Liquid Dose:
1.30E-01
% of Total:
1.55E+01 Critical Pathway:
Fresh Water Fish
- Sport (FFSP)
Major Contributors (0% or greater to total)
Nuclide Percentage H3 0.OOE+00 CR5l 0.OOE+00 M[\\I54 0.OOE+00 FE59 3.04E0l CO58 0.OOE+00 CO60 0.OOE+00 NI63 9.77E+Ol AG11OM 3.82E06 TE125M 1.98E+00 Gaseous Dose:
7.09E-01
% of Total:
8.45E+0l Critical Pathway:
Vegetation (VEG)
Major Contributors (0% or greater to total)
Nuclide Percentage H3 0.OOE+00 C14 1.OOE+02 CO58 1.22E05 CO60 3.48E04 1131 1.26E04 1133 l.94E05
=
MAXIMUM DO SE ANALYSIS
= = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
ANISJUAL 2013
= = = = = = =
Age Dose Dose Type Group Organ (mrem)
Total Body CHILD TBODY 2.60E-0l Liquid Receptor:
0 Liquid Receptor Gaseous Receptor:
5 Composite Crit. Receptor IP Distance:
800 (meters)
Compass Point:
SSE Page 52 of 77
40CFR190 URANIUM FUEL CYCLE DOSE REPORT Liquid Dose:
l.14E-01
% of Total:
4.40E+01 Critical Pathway:
Fresh Water Fish
- Sport (FFSP)
Major Contributors (0% or greater to total)
Nuclide Percentage H3 9.42E+Ol CR51 1.45E-04 54 2.55E02 FE59 2.79E-0l CO58 8.39E0l CO60 5.45EOl NI-63 3.78E+00 AGibM 2.35E06 TE125M 3.OOEOl Gaseous Dose:
1.46E-0l
% of Total:
5.61E+0l Critical Pathway:
Vegetation (VEG)
Major Contributors (0% or greater to total)
Nuclide Percentage H3 2.77E+00 Cl4 9.72E+Ol CO58 l.03E04 CO60 l.79E03 1131 3.54E04 1133 4.90E05 Page 53 of 77
GASEOUS RELEASE AND DOSE
SUMMARY
REPORT BY UNIT (Composite Critical Receptor
- Limited Analysis)
Release ID 1
All Gas Release Types Period Start Date....:
01/01/2013 00:00 Period End Date 01/01/2014 00:00 Period Duration (mm):
5.256E+05 Coefficient Type
- Historical Unit 1
=
RELEASE DATA
= = = ==== = = = = = = = = = = === = === = === = = = ==== === = = = = = = = = = = = = = = = = = = === ==
Total Release Duration (minutes) 5.470E+05 Total Release Volume (cf) 6.784E+10 Average Release Flowrate (cfm) l.240E÷05 Average Period Flowrate (cfm) l.29lE+05
== = NUCLIDE DATA
=== = = = = = === = = = = ===== ======== = = = ==== === = = = = = === === === = =
=
uC i
- 5. 18E+04 3
. 33E÷00
- 6. l7E+Ol 2
. 96E+05
- 4. 02E+02 Average uCi / cc
- 2. 70Ell
- 1. 73El5 3
. 21E14
- 1. 54El0 2
. 09E13 EC Ratio 2.70E03
- 1. 73E08
- 5. 35E08
- 3. 09E04
- 2. 99E-06 3.49E+05 l.82ElO 3.OlE03 Nuclide AR-41 KR-85M XE-13 3M XE-133 XE-135 F&AG 1-131 1133 Iodine BR-82 C-l4 Other H-3 H-3 SB-l25 CO-58 CO-60 P> = 8 Total EC
- 1. OOE08
- 1. OOE07
- 6. OOE07 5. OOE07
- 7. OOE08 2
. OOElO
- 1. OOE09
- 5. OOE09 3
. OOE09
- 1. OOE07 7
. OOEl0
- 1. OOE09
- 5. OOEl1 1.78E+00 9.28E16 4.64E06 4.59E+Ol 2.39E14 2.39E-05 4.77E+01 2.48E-14 2.85E05 l.96E+00 l.02E15 2.04E07 4.48E+06 2.33E09 7.78EOl 4.48E+06 2.33E09 7.78E01 2.96E+07 l.54E08 l.54E0l 2.96E÷07 l.54E08 1.54EOl 2.73EOl l.42El6 2.03E07 1.90E+00 9.91E16 9.9lE07 8.44EOl 4.39E16 8.79E-06 3.02E+00 l.57E15 9.98E06 3.44E+07 1.79E08 9.35EOl Page 54 of 77
GASEOUS RELEASE AND DOSE
SUMMARY
REPORT BY UNIT (Composite Critical Receptor
- Limited Analysis)
Release ID 1
All Gas Release Types Period Start Date 01/01/2013 00:00 Period End Date 01/01/2014 00:00 Period Duration (mm):
5.256E+05 Coefficient Type
- Historical Unit 1
=
MAXIMUM I &P DO SE FOR PERIOD
= = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
Limit Organ Age Dose Limit Limit Percent Type Type Group Organ (mrem)
Period (mrem) of Limit Admin Any Organ CHILD BONE 3.65E-01 31-day 2.25E-Ol 1.62E+02 Quarter 5.63E+00 6.50E+00 Annual l.13E+0l 3.25E+00 T.Spec Any Organ CHILD BONE 3.65E-0l 31-day 3.OOE-01 1.22E+02 Quarter 7.50E+00 4.87E+00 Annual 1.50E+01 2.44E+00 Receptor 5
Composite Crit.
Receptor
- IP Distance (meters) 800 Compass Point SSE Critical Pathway 2
Vegetation (VEG)
Major Contributors 0.0
% or greater to total Nuclide Percentage H3 0.OOE+00 C14 1.OOE+02 CO58 2.36E05 CO60 6.75E04 1131 8.64E05 1133 3.77E05 Page 55 of 77
GASEOUS RELEASE AND DOSE
SUMMARY
REPORT BY UNIT (Composite Critical Receptor
- Limited Analysis)
Release ID Period Start Date....:
Period End Date Period Duration (mm)
Coefficient Type 1
All Gas Release Types 01/01/2013 00:00 01/01/2014 00:00 5.256E+05 Historical TB Unit 1
=
PERIOD ORGAN DOSE BY AGE GROUP AND PATHWAY (mrem)
============
Age/Path Bone Liver Thyroid Kidney Lung GI-Lli Skin AGPD 2.57E06 2.57E06 2.57E06 2.57E06 2.57E06 2.57E06 0.OOE+00 2.57E06 AINHL l.l6E-03 5.21E04 5.23E04 5.2lE04 5.2lE04 5.21E04 0.OOE+0O 5.21E04 AVEG 5.73E02 l.20E02 l.20E02 l.20E02 1.20E02 1.20E02 0.OOE+00 l.20E02 ACMEAT 2.13E02 4.34E03 4.34E03 4.34E03 4.34E03 4.34E03 0.OOE+00 4.34E03 ACMILK 2.32E02 4.83E03 4.86E03 4.83E03 4.83E03 4.83E03 0.OOE÷00 4.83E03 TGPD 2.57E06 2.57E06 2.57E06 2.57E06 2.57E06 2.57E06 0.OOE÷00 2.57E06 TINHL l.66E03 6.l7E04 6.19E04 6.17E04 6.17E04 6.17E04 0.OOE÷00 6.l7E04 TVEG 9.27E02 l.92E02 l.92E02 l.92E02 1.92E02 1.92E02 0.OOE+00 1.92E02 TCMEAT l.80E02 3.64E03 3.64E03 3.64E03 3.64E03 3.64E03 0.OOE+00 3.64E03 TCMILK 4.28E02 8.8lE03 8.86E03 8.81E03 8.81E03 8.81E03 0.OOE+00 S.81E03 CGPD 2.57E06 2.57E06 2.57E06 2.57E06 2.57E06 2.57E06 0.OOE+00 2.57E06 CINHL 2.30E03 7.OOE04 7.03E04 7.OOE04 7.OOE04 7.OOE04 0.OOE+00 7.OOE04 CVEG 2.24EOl 4.58E02 4.58E02 4.58E02 4.58E02 4.58E02 0.OOE+00 4.58E02 CCMEAT 3.38E02 6.83E03 6.83E03 6.83E03 6.83E03 6.83E03 0.OOE+00 6.83E03 CCMILK l.05E-01 2.14E02 2.15E02 2.l4E02 2.14E02 2.14E02 0.OOE+00 2.l4E02 IGPD 2.57E-06 2.57E06 2.57E06 2.57E06 2.57E06 2.57E06 0.OOE+00 2.57E06 IINHL l.69E03 4.95E04 4.98E04 4.95E04 4.95E04 4.95E04 0.OOE+00 4.95E04 ICMILK 2.07E01 4.46E02 4.49E02 4.46E02 4.46E02 4.46E02 0.OOE+00 4.46E02 TOTALS ADULT l.03E01 2.17E02 2.17E02 2.l7E02 2.17E02 2.l7E02 0.OOE+00 2.17E02 TEEN l.55E01 3.23E02 3.24E02 3.23E02 3.23E02 3.23E02 0.OOE÷00 3.23E02 CHILD 3.65EOl 7.47E02 7.49E02 7.47E02 7.47E-02 7.47E02 0.OOE+00 7.47E02 INFANT 2.08EOl 4.5lE02 4.54E02 4.51E02 4.5lE02 4.51E02 0.OOE+00 4.51E02
= = = AGE GROUP /
= = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
Abbreviation Age Group Pathway AGPD ADULT Ground Plane Deposition (GPD)
AINHI ADULT Inhalation (INHL)
AVEG ADULT Vegetation (VEG)
ACMEAT ADULT Grs/Cow/Meat (CMEAT)
ACMILK ADULT Grs/Cow/Milk (CMILK)
TGPD TEEN Ground Plane Deposition (GPD)
TINHL TEEN Inhalation (INHL)
TVEG TEEN Vegetation (lEG)
TCMEAT TEEN Grs/Cow/Meat (CMEAT)
TCMILK TEEN Grs/Cow/Milk fCMILK)
CGPD CHILD Ground Plane Deposition (GPD)
CINHL CHILD Inhalation fINHL)
Page 56 of 77
GASEOUS RELEASE AND DOSE StThIt4ARY REPORT BY UNIT (Composite Critical Receptor
- Limited Analysis)
Release ID 1
All Gas Release Types Period Start Date....:
01/01/2013 00:00 Period End Date 01/01/2014 00:00 Period Duration (mm):
5.256E+05 Coefficient Type Historical Unit 1
=
AGE GROUP /
PATHWAY DESCRIPTIONS
= === = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
Abbreviation Age Group Pathway CVEG CHILD Vegetation (VEG)
CCMEAT CHILD Grs/Cow/Meat (CMEAT)
CCMILK CHILD Grs/Cow/Milk (CMILK)
IGPD INFANT Ground Plane Deposition (GPD)
IINHL INFANT Inhalation (INHL)
ICMILK INFANT Grs/Cow/Milk (CMILK)
Page 57 of 77
GASEOUS RELEASE AND DOSE
SUMMARY
REPORT BY UNIT (Composite Critical Receptor
- Limited Analysis)
Release ID Period Start Date....:
Period End Date Period Duration (mm):
Coefficient Type Unit 1
All Gas Release Types 01/01/2013 00:00 01/01/2014 00:00
- 5. 256E+05 Historical
=
MAXIMUN NO DO SE FOR PERIOD
= = = = = = = = = = = = = = = = = = = = = = = = ==== = = = = = = = = = =
= =
=
T.Spec Beta Receptor 4
Distance (meters) 0.0 Compass Point 0.0 Major Contributors 0.0 Nuclide Percentage Limit Dose Limit Limit Percent Type Dose Type (mrad)
Period (mrad) of Limit Admin Ganuna 3.41E-05 31day 1.50E01 2.27E02 Quarter 3.75E+00 9.09E-04 Annual 7.50E+00 4.54E04 Admin Beta 6.88E-06 31-day 3.OOE-0l 2.29E03 Quarter 7.SOE+00 9.l7E05 Annual 1.50E+0l 4.58E-05 T.Spec Gamma 3.41E-05 31-day 2.OOE-01 1.70E-02 Quarter 5.OOE+00 6.82E-04 Annual l.OOE+01 3.4lE-04 Receptor 4
Composite Crit. Receptor NO Distance (meters) 800 Compass Point SSE Major Contributors 0.0
% or greater to total Nuclide Percentage AR41 8.20E+Ol KR-85M 6.97E-04 XE133M 3.43E03 XE-133 l.78E+Ol XE-135 l.3lE-0l 6.88E-06 31day 4.OOEOl 1.72E03 Quarter 1.OOE+Ol 6.88E-05 Annual 2.OOE+Ol 3.44E05 Composite Crit. Receptor NO
% or greater to total AR-41 KR-8 SM XE-13 3M XE-13 3 3
. 52E+Ol l.36E03
- 1. 89E-02
- 6. 45E+01 Page 58 of 77
GASEOUS RELEASE AND DOSE
SUMMARY
REPORT BY UNIT (Composite Critical Receptor
- Limited Analysis)
Release ID 1
All Gas Release Types Period Start Date 01/01/2013 00:00 Period End Date 01/01/2014 00:00 Period Duration (mm) :
5.256E+05 Coefficient Type
- Historical Unit 1
Major Contributors 0.0
% or greater to total Nuclide Percentage XE135 2.05E01 Page 59 of 77
GASEOUS RELEASE AND DOSE StJMI4ARY REPORT BY UNIT (Composite Critical Receptor
- Limited Analysis)
Release ID 1
All Gas Release Types Period Start Date....:
01/01/2013 00:00 Period End Date 01/01/2014 00:00 Period Duration (mm) 5.256E+05 Coefficient Type
- Historical Unit 2
RELEASE DATA
=====================================================
Total Release Duration (minutes) 5.588E+05 Total Release Volume (cf) 7.211E+l0 Average Release Flowrate (cfm) 1.291E÷05 Average Period Flowrate (cfm) l.372E+05
=
NUCL IDE DATA
= === = = === ===== ===== = = = = = === ===== ====== = = ====== === = = = = = = === = ==
Average EC Nuclide uCi uCi/cc Ratio EC AR4l 7.39E+03 3.62E-12 3.62E04 1.OOE08 KR85M 3.33E÷00 l.63E15 1.63E08 1.OOE07 XE133M 6.17E÷0l 3.02El4 5.03E08 6.OOE07 XE133 3.05E+05 1.49ElO 2.99E04 5.OOE07 XE-135 l.64E+02 8.02E14 l.15E06 7.OOE08 F&AG 3.l3E+05 1.53E-lO 6.62E04 1131 3.27E+00 1.60E1S 8.O1E06 2.OOE10 Iodine 3.27E+00 1.60E-15 8.O1E06 Cl4 4.22E+06 2.07E09 6.89E01 3.OOE09 Other 4.22E÷06 2.07E09 6.89E01 H3 4.l9E+07 2.05E08 2.05E01 1.OOE07 H3 4.l9E+07 2.05E08 2.05E01 Total 4.65E+07 2.28E08 8.95E0l Page 60 of 77
GASEOUS RELEASE AND DOSE
SUMMARY
REPORT BY UNIT (Composite Critical Receptor
- Limited Analysis)
Release ID 1
All Gas Release Types Period Start Date....:
01/01/2013 00:00 Period End Date 01/01/2014 00:00 Period Duration (mm) 5.256E+05 Coefficient Type Historical Unit 2
=
MAX IMUM I & P DOSE FOR PERIOD
= = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
Limit Organ Age Dose Limit Limit Percent Type Type Group Organ (mrem)
Period (mrem) of Limit Admin Any Organ CHILD BONE 3.44E-01 31-day 2.25E-Ol 1.53E+02 Quarter 5.63E+00 6.12E+00 Annual l.13E÷0l 3.06E+00 T.Spec Any Organ CHILD BONE 3.44E-Ol 31-day 3.OOE-0l 1.15E÷02 Quarter 7.50E+00 4.59E+00 Annual 1.50E+0l 2.29E+00 Receptor 5
Composite Crit.
Receptor IP Distance (meters) 800 Compass Point SSE Critical Pathway 2
Vegetation (VEG)
Major Contributors 0.0
% or greater to total Nuclide Percentage H3 0.OOE+00 C14 1.OOE+02 1131 l.68E04 Page 61 of 77
AGPD AINHL AVEG ACMEAT ACMILK TGPD TINHL TVEG TCMEAT TCMILK CGPD CINHL GASEOUS RELEASE AND DOSE SUNMARY REPORT BY UNIT (Composite Critical Receptor
- Limited Analysis)
ADULT ADULT ADULT ADULT ADULT TEEN TEEN TEEN TEEN TEEN CHILD CHILD Liver Thyroid Kidney Lung Release ID 1
All Gas Release Types Period Start Date....:
01/01/2013 00:00 Period End Date 01/01/2014 00:00 Period Duration (miii) :
5.256E+05 Coefficient Type
- Historical Unit 2
=
PERIOD ORGAN DOSE BY AGE GROUP AND PATHWAY (mrem)
Age/Path Bone GI-Lli Skin TB AGPD 6.71E09 6.71E09 6.7lE09 6.71E09 6.71E09 6.7lE09 0.OOE+00 6.7lE09 AINHL l.lOE03 6.35E04 6.35E04 6.35E04 6.35E04 6.35E04 0.OOE+00 6.35E04 AVEG 5.40E02 l.15E02 1.l6E02 l.l5E02 l.l5E02 1.15E02 0.OOE+00 1.l5E02 ACMEAT 2.OOE02 4.12E03 4.l2E03 4.l2E03 4.12E03 4.12E03 0.OOE÷00 4.12E03 ACMILK 2.19E02 4.63E03 4.68E03 4.63E03 4.63E03 4.63E03 0.OOE+00 4.63E03 TGPD 6.7lE09 6.71E09 6.7lE09 6.71E09 6.71E09 6.71E09 0.OOE÷00 6.71E09 TINHL l.57E03 7.27E04 7.27E04 7.27E04 7.27E04 7.27E04 0.OOE÷00 7.27E04 TVEG 8.73E02 l.84E02 l.84E02 1.84E02 1.84E02 1.84E02 0.OOE+00 1.84E02 TCMEAT l.69E02 3.45E03 3.45E03 3.45E03 3.45E03 3.45E03 0.OOE+00 3.45E03 TCMILK 4.03E02 8.4lE03 8.49E03 8.41E03 8.4lE03 8.41E03 0.OOE+00 8.41E03 CGPD 6.7lE09 6.7lE09 6.7lE09 6.71E-09 6.71E09 6.71E09 0.OOE+00 6.7lE09 CINHL 2.l6E03 7.88E04 7.89E04 7.88E04 7.88E04 7.88E04 0.OOE+00 7.88E04 CVEG 2.11E0l 4.36E02 4.36E02 4.36E02 4.36E02 4.36E02 0.OOE+00 4.36E02 CCMEAT 3.18E02 6.46E-03 6.46E03 6.46E03 6.46E03 6.46E03 0.OOE+00 6.46E03 CCMILK 9.93E02 2.03E02 2.05E02 2.03E02 2.03E02 2.03E02 0.OOE+00 2.03E02 IGPD 6.7lE09 6.71E09 6.7lE09 6.71E09 6.7lE09 6.71E09 0.OOE+00 6.71E09 IINHL 1.60E03 5.40E04 5.4lE04 5.40E04 5.40E04 5.40E04 0.OOE÷00 5.40E04 ICMILK 1.94E01 4.23E02 4.27E02 4.23E02 4.23E02 4.23E02 0.OOE+00 4.23E02 TOTALS ADULT 9.70E02 2.09E02 2.1OE02 2.09E02 2.09E02 2.09E02 0.OOE+00 2.09E02 TEEN l.46E01 3.lOE02 3.11E02 3.1OE02 3.1OE02 3.OE02 0.OOE+00 3.1OE02 CHILD 3.44E0l 7.12E02 7.14E02 7.l2E02 7.12E02 7.12E02 0.OOE+00 7.12E02 INFANT 1.96E01 4.28E02 4.32E02 4.28E02 4.28E02 4.28E02 0.OOE+00 4.28E02
=
AGE GROUP /
PATHWAY DESCRI PTI ONS
= = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
Abbreviation Age Group Pathway Ground Plane Deposition Inhalation (INHL)
Vegetation (VEG)
Grs/Cow/Meat (CMEAT)
Grs/Cow/Milk (CMILK)
Ground Plane Deposition Inhalation (INHL)
Vegetation (VEG)
Grs/Cow/Meat (CMEAT)
Grs/Cow/Milk (CMILK)
Ground Plane Deposition Inhalation (INHL)
(GPD)
(GPD)
(GPO)
Page 62 of 77
GASEOUS RELEASE AND DOSE
SUMMARY
REPORT BY UNIT (Composite Critical Receptor
- Limited Analysis)
Release ID 1
All Gas Release Types Period Start Date....:
01/01/2013 00:00 Period End Date 01/01/2014 00:00 Period Duration (mm) 5.256E+05 Coefficient Type Historical Unit 2
=
AGE GROUP /
PATHWAY DESCRIPTIONS
= = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
Abbreviation Age Group Pathway CVEG CHILD Vegetation (VEG)
CCMEAT CHILD Grs/Cow/Meat (CMEAT)
CCMILK CHILD Grs/Cow/Milk (CMILK)
IGPD INFANT Ground Plane Deposition (GPD)
IINHL INFANT Inhalation (INHL)
ICMILK INFANT Grs/Cow/Milk (CMILK)
Page 63 of 77
GASEOUS RELEASE AND DOSE
SUMMARY
REPORT BY UNIT (Composite Critical Receptor
- Limited Analysis)
Release ID Period Start Date..
Period End Date Period Duration (mm)
Coefficient Type Unit 2
1 All Gas Release Types 01/01/2013 00:00 01/01/2014 00:00 5.256E+05 Historical Receptor 4
Distance (meters) 800 Compass Point SSE Major Contributors 0.0 Nuclide Percentage AR41 3.89E+01 KR85M 2.32E03 XE133M l.14E02 XE133 6.09E+01 XE135 1.78EOl T.Spec Beta Receptor Distance (meters)
Compass Point Major Contributors Nuclide Percentage AR41 7.03E+00 KR85M 1.90E03 XE133M 2.64E02 XE133 9.28E÷01 Dose (mrad)
- 1. 03E05 Limit (mrad)
- 1. SOE01 3
. 75E+00
- 7. 50E+00
- 3. OOE0l 7
. 50E+00
- 1. SOE+01
- 2. OOE01
- 5. OOE÷00
- 1. OOE+01
- 4. OOE01
- 1. OOE+Ol 2
. OOE+01 Percent of Limit
- 6. 84E03
- 2. 74E-04 1.37E04
- 1. 64E03
- 6. 56E05 3.2 SEOS 5
. 13E03
- 2. OSE-04
- 1. 03EO4
- 1. 23E03
- 4. 92E0S 2.46E05
=
MAX IMUM NG DOSE FOR PERIOD
=== = = = = = = = = = = = = = = = =
= = = = = = = = ======= = = = = = = = = =
Limit Limit Type Dose Type Period Admin Gamma 31-day Quarter Annual Admin Beta 4.92E-06 31-day Quarter Annual T.Spec Gamma 1.03E-0S 31-day Quarter Annual Composite Crit.
Receptor NG
% or greater to total 4.92E06 31-day Quarter Annual Composite Crit.
Receptor NG
% or greater to total 0.0 0.0 0.0 Page 64 of 77
GASEOUS RELEASE AND DOSE
SUMMARY
REPORT BY UNIT (Composite Critical Receptor
- Limited Analysis)
Release ID 1
All Gas Release Types Period Start Date....:
01/01/2013 00:00 Period End Date 01/01/2014 00:00 Period Duration (mm):
5.256E÷05 Coefficient Type
- Historical Unit 2
Major Contributors 0.0
% or greater to total Nuclide Percentage XE135 1.17EOl Page 65 of 77
LIQUID RELEASE AND DOSE
SUMMARY
REPORT (PERIOD BASIS BY UNIT)
Release ID 1
All Liquid Releases Period Start Date 01/01/2013 00:00 Period End Date 01/01/2014 00:00 Period Duration (mins) :
5.256E+05 Unit 1
=
RELEASE DATA
= ==== = = = ==== = = = = = = === === = === = = = = === ==== = = = = = = = = ===== = = = = = = = =
Total Release Duration (minutes) 5.347E÷05 Total Undiluted Volume Released (gallons)
NA Average Undiluted Flowrate (gpm)
NA Total Dilution Volume (gallons)
NA Average Dilution Flowrate (gpm)
NA
=
NUCLIDE DATA
= = = = = = = = = === === = = ===== = = = = = = = = = = === ==== = = = = = =
= = === =
Nuclide uCi CO57 l.24E+01 SB125 6.40E+0l TE123M 9.27E+00 55126 9.75E01 CR51 l.1OE+02 MN54 3.O1E+0l FE59 2.8lE+02 CO58 4.05E+03 CO60 9.30E÷02 AG11OM 3.58E+00 TE125M 6.65E+02 Gamma 6.15E+03 XE133 1.66E+02 XE135 2.27E+00 D&EG 1.68E+02 53 7.99E+08 NI63 2.77E+03 Beta 7.99E+08 Total 7.99E+08 Page 66 of 77
ADULT 4.77E02 6.88E02 6.47E02 TEEN 4.95E02 5.29E02 4.87E02 CHILD 6.51E-02 5.83E02 5.43E02 INFANT 3.61E-04 2.39E02 2.39E02 TOTALS 6.82E02 6.46E02 7.67E02 O.OOE+0O 6.70E02 4.84E02 4.85E02 5.73E02 O.OOE+0O 5.1OE02 5.39E02 5.40E02 5.73E02 O.OOE+O0 5.72E02 2.39E02 2.39E02 2.39E02 0.OOE+00 2.39E02
=
AGE GROUP /
PATHWAY DESCRIPTIONS
= = = = = = = = = = = = = = =
= = = = = = = = = = = = = = = = = = = = = = =
Abbreviat +/- on APWtr AFWFSp TPWtr TFWFSp CPWtr CFWFSp IPWtr Age Group ADULT ADULT TEEN TEEN CHILD CHILD INFANT Pathway Potable Water (PWtr)
Fresh Water Fish
- Sport (FFSP)
Potable Water (PWtr)
Fresh Water Fish
- Sport (FFSP)
Potable Water (PWtr)
Fresh Water Fish
- Sport (FFSP)
Potable Water (PWtr)
LIQUID RELEASE AND DOSE
SUMMARY
REPORT (PERIOD BASIS BY UNIT)
Release ID 1
All Liquid Releases Period Start Date 01/01/2013 00:00 Period End Date 01/01/2014 00:00 Period Duration (mins):
5.256E+05 Unit 1
Receptor 0
Liquid Receptor
=
PERMIT ORGAN DOSE BY AGE GROUP AND PATHWAY (mrem)
Age/Path Bone Liver Thyroid Kidney Lung GI-Lli Skin TB APWtr l.63E04 l.80E02 l.80E-02 l.80E-02 l.80E02 l.81E02 0.OOE+00 l.80E02 AFWFSp 4.75E02 5.08E02 4.67E02 5.02E02 4.66E02 5.86E02 0.OOE+00 4.90E02 TPWtr l.55E04 1.27E02 l.27E02 l.27E02 1.27E02 l.27E02 0.OOE+00 l.27E02 TFWFSp 4.93E02 4.02E02 3.60E02 3.57E02 3.58E02 4.46E02 0.OOE+00 3.84E02 CPWtr 4.70E-04 2.44E02 2.44E02 2.44E-02 2.44E02 2.44E02 0.OOE+0O 2.44E02 CFWFSp 6.46E-02 3.39E02 2.99E-02 2.96E-02 2.97E02 3.29E02 0.OOE+00 3.28E02 IPWtr 3.61E04 2.39E02 2.39E02 2.39E02 2.39E02 2.39E02 0.OOE+00 2.39E02 Page 67 of 77
LIQUID RELEASE AND DOSE
SUMMARY
REPORT (PERIOD BASIS BY UNIT)
Release ID 1
All Liquid Releases Period Start Date 01/01/2013 00:00 Period End Date 01/01/2014 00:00 Period Duration (mins) 5.256E+05 Unit 1
Receptor 0
Liquid Receptor PERMIT ORGAN DOSE BY AGE GROUP AND NUCLIDE (mrem)
Agegroup Bone Liver Thyroid Kidney Lung GI-Lli Skin TB ADUlT H3 0.OOE+00 6.45E02 6.45E02 6.45E02 6.45E02 6.45E02 0.OOE÷00 6.45E02 CR51 0.OOE÷00 0.OOE+00 4.SlE08 l.66E08 1.OOE07 1.90E05 0.OOE+00 7.55E08 MN54 0.OOE+00 7.12E05 0.00E+00 2.l2E05 0.OOE+00 2.18E04 0.OOE÷00 1.36E05 FE59 1.58E-04 3.7lE04 0.OOE+00 0.OOE+00 l.04E04 l.24E03 0.OOE+00 l.42E04 CO58 0.OOE+00 l.96E04 0.OOE+00 0.OOE+00 0.OOE+00 3.97E03 0.OOE÷00 4.39E04 CO60 0.OOE+00 l.29E04 0.OOE+00 0.OOE+00 0.OOE+00 2.43E03 0.OOE+00 2.85E04 NI63 4.66E02 3.23E03 0.OOE÷00 0.OOE+00 0.OOE+00 6.74E04 0.OOE÷00 1.56E03 AGliOM 1.96E-09 1.8lE09 0.OOE÷00 3.56E09 0.OOE+00 7.40E07 0.OOE+00 1.08E09 TE125M 9.2lE04 3.34E04 2.77E04 3.75E03 0.OOE+00 3.68E03 0.OOE+00 1.23E04 TEEN H-3 0.OOE+00 4.84E02 4.84E02 4.84E02 4.84E02 4.84E02 0.OOE+00 4.84E02 CR5l 0.OOE+00 0.OOE+00 4.32E08 1.70E08 l.11E07 1.31E05 0.OOE+00 7.78E08 MM54 0.OOE+00 7.OOE05 0.OOE+00 2.09E05 0.OOE÷00 1.44E04 0.OOE+00 1.39E05 FE59 1.63E04 3.79E04 0.OOE÷00 0.OOE+00 1.20E04 8.97E04 0.OOE+00 1.46E04 CO58 0.OOE+00 l.95E04 0.OOE÷00 0.OOE+00 0.OOE+00 2.68E03 0.OOE+00 4.49E04 CO60 0.OOE+00 1.29E04 0.OOE+00 0.OOE+00 0.OOE+00 1.68E03 0.OOE+00 2.9lE04 NI63 4.83E02 3.4lE03 0.OOE+00 0.OOE+00 0.OOE+00 5.43E04 0.OOE+00 l.64E03 AGibM l.89E09 l.79E09 0.OOE÷00 3.4lE09 0.OOE÷00 5.03E07 0.OOE+00 1.09E09 TE125M 1.OOE03 3.61E04 2.80E04 0.OOE+00 0.OOE÷00 2.96E03 0.OOE+00 1.34E04 CHILD H-3 0.OOE+00 5.39E02 5.39E02 5.39E02 5.39E02 5.39E02 0.OOE+00 5.39E02 CR5l 0.OOE÷00 0.OOE+00 4.6lE08 l.26E08 8.42E08 4.41E06 0.OOE+00 8.3lE08 NN54 0.OOE+00 5.48E05 0.OOE+00 i.54E05 0.OOE+00 4.60E05 0.OOE+00 1.46E05 FE59 1.98E04 3.20E04 0.OOE÷00 0.OOE+00 9.28E05 3.33E04 0.OOE+00 1.59E04 CO58 0.OOE÷00 1.57E04 0.OOE+00 0.OOE+00 0.OOE+00 9.l4E04 0.OOE+00 4.80E04 CO60 0.OOE+00 1.06E04 0.OOE+00 0.OOE÷00 0.OOE+00 5.86E04 0.OOE+00 3.12E04 NI63 6.36E02 3.40E03 0.OOE+00 0.OOE+00 0.OOE+00 2.29E04 0.OOE+00 2.l6E03 AGibM 2.49E09 i.68E09 0.OOE+00 3.13E09 0.OOE+00 2.OOE07 0.OOE+00 1.34E09 TE125M l.29E-03 3.49E04 3.62E04 0.OOE+00 0.OOE+00 1.24E03 0.OOE+00 l.72E04 INFANT H-3 0.OOE+00 2.39E02 2.39E02 2.39E02 2.39E02 2.39E02 0.OOE+00 2.39E02 CR51 0.OOE+00 0.OOE+00 2.05E10 4.47Ell 3.98E10 9.14E09 0.OOE+00 3.14ElO MN54 0.OOE+00 1.22E07 0.OOE+00 2.70E08 0.OOE+00 4.47E08 0.OOE+00 2.76E08 FE59 1.75E06 3.06E06 0.OOE÷00 0.OOE+00 9.05E07 l.46E06 0.OOE+00 1.21E06 CO58 0.OOE+00 2.95E06 0.OOE+00 0.OOE+00 0.OOE+00 7.36E06 0.OOE+00 7.37E06 CO60 0.OOE+00 2.04E06 0.OOE+00 0.OOE+00 0.OOE+00 4.85E06 0.OOE+00 4.8iE06 Page 6$ of 77
LIQUID RELEASE AND DOSE
SUMMARY
REPORT (PERIOD BASIS BY UNIT)
Release ID 1
All Liquid Releases Period Start Date 01/01/2013 00:00 Period End Date 2
01/01/2014 00:00 Period Duration (mins) :
5.256E÷05 PERMIT ORGAN DOSE BY AGE GROUP AND NUCLIDE (mrem)
=============
Agegroup Bone Liver Thyroid Kidney Lung GI-Lli Skin TB NI63 3.56E04 2.20E05 0.00E+00 0.00E+00 0.OOE+00 l.09E06 0.OOE+00 l.23E05 AGliON 7.24El0 5.28E10 0.OOE+00 7.56El0 0.OOE+00 2.74E08 0.OOE+00 3.50E10 TE125M 3.14E06 l.05E06 1.06E06 0.OOE+00 0.OOE+00 l.50E06 0.OOE+00 4.25E07 Page 69 of 77
LIQUID RELEASE AND DOSE
SUMMARY
REPORT (PERIOD BASIS BY UNIT)
Release ID 1
All Liquid Releases Period Start Date 01/01/2013 00:00 Period End Date 01/01/2014 00:00 Period Duration (mins) :
5.256E+05 Unit 1
Receptor 0
Liquid Receptor Limit Period 31-day Quarter Annual ADULT TBODY 6.70E-02 31-day Quarter Annual T.Spec Any Organ ADULT GILLI 7.67E-02 31-day Quarter Annual H-3 CR-51 MN54 FE-59 CO-58 CO-60 NI 63 AG-li OM TE-125M
- 8. 4lE+Ol 2
. 47E02 2
. 84EOl
- 1. 6lE+00
- 5. 18E+00 3
. 17E+00
- 8. 79E0l
- 9. 64E-04
- 4. 79E+00 Critical Pathway 1
Fresh Water Fish
- Sport (FFSP)
Major Contributors 0.0
% or greater to total Nuclide Percentage H3 9.62E+Ol
- 1. 13E04 2
. 03E02 2. 12E0l Percent of Limit
- 5. 11E+0l 2
. 05E+00
- 1. 02E+00
- 1. 49E÷02 5
. 96E+00
- 2. 98E+00 3
. 83E+0l
- 1. 53E+00 7
. 67E0l Limit Type Adinin Organ Type Any Organ
=
MAXIMUM DO SE FOR PERIOD
= = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
= = = = = = = = = = = = = =
Age Group ADULT Organ GILLI Dose mrem)
- 7. 67E-02 Admin Tot Body Critical Pathway 1
Fresh Water Fish
- Sport (FFSP)
Major Contributors 0.0
% or greater to total Nuclide Percentage Limit (mrem)
- 1. 50E0l 3
. 75E+00 7
. 50E+00
- 4. 50E02
- 1. 13E÷00 2.25E+00
- 2. OOEOl
- 5. OOE+00
- 1. OOE+Ol
- 6. OOE02
- 1. 50E+00 3
. OOE÷00 T.Spec Tot Body ADULT TBODY 6.70E-02 31-day Quarter Annual CR-51 MM-54 FE-59
- 1. 12E+02 4.47E+00 2.23E+00 Page 70 of 77
LIQUID RELEASE AND DOSE
SUMMARY
REPORT (PERIOD BASIS BY UNIT)
Release ID 1
All Liquid Releases Period Start Date 01/01/2013 00:00 Period End Date 01/01/2014 00:00 Period Duration (mins) :
5.256E+05 Major Contributors 0.0
% or greater to total Nuclide Percentage CO-58 6.55E01 CO-60 4.25E01 NI63 2.33E+00 AG11OM l.61E06 TE-125M 1.84E-01 Page 71 of 77
LIQUID RELEASE AND DOSE SUARY REPORT (PERIOD BASIS BY UNIT)
Release ID 1
All Liquid Releases Period Start Date 01/01/2013 00:00 Period End Date 01/01/2014 00:00 Period Duration (mins):
5.256E+05 Unit 2
=
RELEASE DATA
=== === = = = = = = = = = === = = = = = = = === = = = = =
== = =
= = =
= = ===
Total Release Duration (minutes) 5.347E+05 Total Undiluted Volume Released (gallons)
NA Average Undiluted Flowrate (gpm)
NA Total Dilution Volume (gallons)
NA Average Dilution Flowrate (gpm)
NA
=
NUCLIDE DATA
= = = = = = = = ==== = = = === = === = = ========== = = === === = === = ===== = === = ====
Nuclide uCi CO57 l.24E+0l SB125 6.40E+0l TE123M 9.27E+00 SBl26 9.75EOl CR-51 l.1OE÷02
?ThT54 3.OlE+Ol FE59 2.81E+02 CO58 4.05E÷03 CO60 9.30E+02 AG-11OM 3.58E+00 TEl25M 6.65E÷02 Gamma 6.l5E+03 XE133 l.66E+02 XE135 2.27E+00 D&EG l.68E+02 H3 7.99E+08 NI63 2.77E÷03 Beta 7.99E+0S Total 7.99E+08 Page 72 of 77
ADULT 4.77E02 6.88E02 6.47E02 TEEN 4.95E02 5.29E02 4.87E02 CHILD 6.51E02 5.83E-02 5.43E02 INFANT 3.61E04 2.39E02 2.39E02 TOTALS 6.82E02 6.46E02 7.67E02 0.OOE+0O 6.70E02 4.84E02 4.85E02 5.73E02 0.OOE+OO 5.1OE02 5.39E02 5.40E02 5.73E02 O.OOE+OO 5.72E02 2.39E02 2.39E02 2.39E02 0.00E+00 2.39E02
=
AGE GROUP /
PATHWAY DESCRIPTIONS
= = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
Abbreviation APWtr AFWFSp TPWtr TFWFSp CPWtr CFWfSp IPWtr Age Group ADULT ADULT TEEN TEEN CHILD CHILD INFANT Pathway Potable Water (PWtr)
Fresh Water Fish
- Sport (FFSP)
Potable Water (PWtr)
Fresh Water Fish
- Sport (FFSP)
Potable Water (PWtr)
Fresh Water Fish
- Sport (FFSP)
Potable Water (PWtr)
LIQUID RELEASE AND DOSE SUMIARY REPORT (PERIOD BASIS BY UNIT)
Release ID 1
All Liquid Releases Period Start Date 01/01/2013 00:00 Period End Date 01/01/2014 00:00 Period Duration (mins) 5.256E+05 Unit 2
Receptor 0
Liquid Receptor PERMIT ORGAN DOSE BY AGE GROUP AND PATHWAY (mrem)
Age/Path Bone Liver Thyroid Kidney Lung GI-Lli Skin TB APWtr 1.63E04 1.80E02 l.80E-02 l.80E-02 1.80E02 1.81E02 0.OOE÷00 1.80E02 AFWFSp 4.75E02 5.08E02 4.67E02 5.02E02 4.66E02 5.86E02 0.OOE+00 4.90E02 TPWtr 1.55E04 l.27E-02 l.27E02 l.27E02 l.27E02 l.27E02 0.OOE÷00 l.27E02 TFWFSp 4.93E02 4.02E02 3.60E02 3.57E02 3.58E02 4.46E02 0.OOE+00 3.84E02 CPWtr 4.70E04 2.44E02 2.44E02 2.44E-02 2.44E02 2.44E02 0.OOE+00 2.44E02 CFWFSp 6.46E02 3.39E02 2.99E02 2.96E-02 2.97E02 3.29E02 0.OOE+00 3.28E02 IPWtr 3.61E04 2.39E02 2.39E02 2.39E-02 2.39E02 2.39E02 0.OOE+00 2.39E02 Page 73 of 77
LIQUID RELEASE AND DOSE
SUMMARY
REPORT (PERIOD BASIS BY UNIT)
Release ID 1
All Liquid Releases Period Start Date 01/01/2013 00:00 Period End Date 01/01/2014 00:00 Period Duration (mins) :
5.256E+05 Unit 2
Receptor 0
Liquid Receptor PERMIT ORGAN DOSE BY AGE GROUP AND NUCLIDE (mrem)
Agegroup Bone Liver Thyroid Kidney Lung GI-Lli Skin TB ADULT H3 0.OOE+00 6.45E02 6.45E02 6.45E02 6.45E02 6.45E02 0.OOE+00 6.45E02 CRSi 0.OOE+00 0.OOE+00 4.51E08 1.66E08 1.OOE07 1.90E05 0.OOE+00 7.55108 MN-54 0.OOE+00 7.12E-05 0.OOE+00 2.12E05 0.OOE+00 2.18E04 0.OOE÷00 1.36E05 FE59 l.58E04 3.71E04 0.OOE+00 0.OOE+00 i.04E04 l.24E03 0.OOE+00 1.42E04 CO58 0.OOE+00 l.96E04 0.OOE+00 0.OOE+00 0.OOE÷00 3.97E03 0.OOE+00 4.39E04 CO60 0.OOE+00 1.29E04 0.OOE+00 0.OOE+00 0.OOE+00 2.43E03 0.OOE+00 2.85E04 NI63 4.66E02 3.23E03 0.OOE+00 0.OOE+00 0.OOE+00 6.74E04 0.OOE+00 l.56E03 AGliOM 1.96E09 l.81E09 0.OOE+00 3.56E09 0.OOE+00 7.40E07 0.OOE+00 l.08E09 TE125M 9.21E04 3.34E04 2.77E04 3.75E03 0.OOE+00 3.68E03 0.OOE+00 i.23E04 TEEN H3 0.OOE+00 4.84E02 4.84E02 4.84E02 4.84E02 4.84E02 0.OOE+00 4.84E02 CR51 0.OOE+00 0.OOE+00 4.32E08 l.70E08 1.liE07 l.3iE05 0.OOE+00 7.78E08 MN54 0.OOE+00 7.OOE05 0.OOE+00 2.09E05 0.OOE+00 l.44E04 0.OOE+00 1.39E05 FE59 i.63E04 3.79E04 0.OOE÷00 0.OOE÷00 i.20E04 8.97E04 0.OOE÷00 i.46E04 CO58 0.OOE+00 i.95E04 0.OOE+00 0.OOE÷00 0.OOE+00 2.68E03 0.OOE+00 4.49E04 CO60 0.OOE+00 i.29E04 0.OOE+00 0.OOE÷00 0.OOE+00 l.68E03 0.OOE+00 2.91E04 NI63 4.83E02 3.41E03 0.OOE+00 0.OOE÷00 0.OOE+00 5.43E04 0.OOE+00 l.64E03 AG11OM l.89E09 1.79109 0.OOE+00 3.41E09 0.OOE+00 5.03107 0.OOE+00 1.09E09 TE125M i.OOE03 3.61E04 2.80E04 0.OOE÷O0 0.OOE+00 2.96E03 0.OOE+00 l.34E04 CHILD H3 0.OOE+00 5.39E02 5.39E02 5.39E02 5.39E02 5.39E02 0.OOE+00 5.39E02 CR5i 0.OOE+00 0.OOE+00 4.6lE08 i.26E08 8.42E08 4.41E06 0.OOE+00 8.3iE08 Lfl\\T54 0.OOE÷00 5.48E05 0.OOE+00 1.54E05 0.OOE+00 4.60E05 0.OOE+00 i.46E05 FE59 1.98E04 3.20E04 0.OOE+00 0.001+00 9.28E05 3.33E04 0.OOE+00 1.59104 CO58 0.OOE+00 1.57E04 0.OOE+00 0.001+00 0.OOE+00 9.14E04 0.OOE+00 4.80E04 CO60 0.OOE+00 1.06E04 0.001+00 0.OOE+00 0.OOE+00 5.86E04 0.OOE÷00 3.12E04 NI63 6.36E02 3.40E03 0.OOE+00 0.OOE+00 0.001+00 2.29E04 0.OOE+00 2.16E03 AGibM 2.49E09 l.68E09 0.OOE+00 3.l3E09 0.OOE+00 2.00107 0.OOE÷00 i.34E09 TEl25M l.29E03 3.49104 3.62E04 0.OOE+00 0.OOE+00 l.24E03 0.OOE+00 i.72E04 INFANT H3 0.OOE+00 2.39E02 2.39E02 2.39E02 2.39E02 2.39E02 0.OOE+00 2.39E02 CR5l 0.OOE÷00 0.OOE+00 2.05EiO 4.47E1l 3.98Eb0 9.i4E09 0.OOE+00 3.14Eb0 MN54 0.001+00 i.22E07 0.OOE+00 2.70E08 0.OOE+00 4.47E08 0.001+00 2.76E08 FE59 l.75E06 3.06E06 0.OOE+00 0.001+00 9.05107 l.46E06 0.OOE+00 i.2iE06 CO58 0.OOE+00 2.95E06 0.OOE+00 0.OOE÷00 0.001+00 7.36E06 0.OOE+00 7.37E06 CO60 0.OOE+00 2.04E06 0.OOE÷00 0.OOE+00 0.OOE+00 4.85E06 0.OOE+00 4.8lE06 Page 74 of 77
LIQUID RELEASE AND DOSE
SUMMARY
REPORT (PERIOD BASIS BY UNIT)
PERMIT ORGAN DOSE BY AGE GROUP AND NUCLIDE fmrem)
Agegroup Bone Liver Thyroid Kidney Lung NI63 3.56E04 2.20E05 O.OOE+OO O.OOE÷OO O.OOE+OO AG11OM 7.24E1O 5.28ElO O.OOE+OO 7.56E1O O.OOE+OO TE-125M 3.14E06 1.05E06 1.06E-06 O.OOE+OO O.OOE+OO GI-Lli Skin TB 1.09E06 O.OOE+OO l.23E05 2.74E08 O.OOE+OO 3.50ElO l.50E06 O.OOE+OO 4.25E07 Release ID Period Start Date Period End Date Period Duration (mins) 1 All Liquid Releases 01/01/2013 00:00 01/01/2014 00:00
- 5. 256E+05 Page 75 of 77
LIQUID RELEASE AND DOSE
SUMMARY
REPORT (PERIOD BASIS BY UNIT)
Release ID 1
All Liquid Releases Period Start Date 01/01/2013 00:00 Period End Date 01/01/2014 00:00 Period Duration (mins):
5.256E+05 Unit 2
Receptor 0
Liquid Receptor
=
MAXIMUM DOSE FOR PERIOD
= = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
Limit Organ Age Dose Limit Limit Percent Type Type Group Organ (mrem)
Period (mrem) of Limit Adinin Any Organ ADULT GILLI 7.67E-02 31-day l.50E-Ol 5.llE+01 Quarter 3.75E+00 2.05E+00 Annual 7.50E+00 l.02E+00 Adinin Tot Body ADULT TBODY 6.70E-02 31-day 4.50E-02 1.49E+02 Quarter 1.l3E+00 5.96E+00 Annual 2.25E+00 2.98E+00 T.Spec Any Organ ADULT GILLI 7.67E-02 31-day 2.OOE-Ol 3.83E+01 Quarter 5.OOE+00 1.53E+00 Annual 1.OOE+01 7.67E-01 Critical Pathway 1
Fresh Water Fish
- Sport (FFSP)
Major Contributors 0.0
% or greater to total Nuclide Percentage H-3 8.41E+Ol CR51 2.47E02 MLJ54 2.84E01 FE59 1.61E+00 CO58 5.18E+00 CO60 3.17E+00 NI63 8.79E01 AG-11OM 9.64E04 TE125M 4.79E+00 T.Spec Tot Body ADULT TBODY 6.70E-02 31-day 6.OOE-02 1.12E+02 Quarter 1.50E+00 4.47E+00 Annual 3.OOE+00 2.23E+00 Critical Pathway 1
Fresh Water Fish
- Sport (FFSP)
Major Contributors 0.0
% or greater to total Nuclide Percentage H3 9.62E÷0l CR51 1.13E04 NN54 2.03E02 FE59 2.12EOl Page 76 of 77
LIQUID RELEASE AND DOSE
SUMMARY
REPORT (PERIOD BASIS BY UNIT)
Release ID 1
All Liquid Releases Period Start Date 01/01/2013 00:00 Period End Date 01/01/2014 00:00 Period Duration (mins):
5.256E+05 Major Contributors 0.0
% or greater to total Nuclide Percentage CO58 6.55EOl CO60 4.25E01 NI63 2.33E+00 AG-ibM l.61E-06 TE-125M l.84E01 Page 77 of 77