ML13038A714

From kanterella
Jump to navigation Jump to search
IR 05000275-12-008 & 05000323-12-008, October 22 to December 20, 2012, Pacific Gas and Electric Company; Diablo Canyon Power Plant, Units 1 and 2; Triennial Fire Protection Team Inspection
ML13038A714
Person / Time
Site: Diablo Canyon  Pacific Gas & Electric icon.png
Issue date: 02/07/2013
From: Geoffrey Miller
NRC/RGN-IV/DRS/EB-2
To: Halpin E
Pacific Gas & Electric Co
References
EA-13-021 IR-12-008
Download: ML13038A714 (42)


See also: IR 05000275/2012008

Text

February 7, 2013

EA-13-021

Mr. Edward D. Halpin

Senior Vice President and

Chief Nuclear Officer

Pacific Gas and Electric Company

Diablo Canyon Power Plant

P.O. Box 56, Mail Code 104/6

Avila Beach, CA 93424

SUBJECT: DIABLO CANYON POWER PLANT, UNITS 1 AND 2 - NRC TRIENNIAL FIRE

INSPECTION REPORT (05000275/2012008; 05000323/2012008) AND EXERCISE

OF ENFORCEMENT DISCRETION

Dear Mr. Halpin:

On November 8, 2012, the U.S. Nuclear Regulatory Commission (NRC) completed an

inspection at the Diablo Canyon Power Plant. The enclosed inspection report documents the

inspection results, which were discussed in a debrief meeting on November 8, 2012, with you

and other members of your staff. Following additional in-office review, an exit meeting was

conducted on December 20, 2012, with you and other members of your staff.

The inspection examined activities conducted under your license as they relate to safety and

compliance with the Commissions rules and regulations and with the conditions of your license.

The team reviewed selected procedures and records, observed activities, and interviewed

personnel.

One NRC-identified finding and one self-revealing finding of very low safety significance (Green)

were identified during this inspection. Both of these findings involved violations of NRC

requirements. Additionally, two findings involving 10 CFR 50.48(b) were identified and were

violations of NRC requirements. The team screened these violations and determined that they

warrant enforcement discretion per NRC Enforcement Policy, Section 9.1, Enforcement

Discretion for Certain Fire Protection Issues (10 CFR 50.48) and Section 11.05(b) of Inspection

Manual Chapter 0305 (EA-13-021).

UNITED STATES

NUCLEAR REGULATORY COMMISSION

RE G IO N I V

1600 EAST LAMAR BLVD

ARLINGTON, TEXAS 76011-4511

E. Halpin

- 2 -

If you contest any findings in this report, you should provide a written response within 30 days of

the date of this inspection report, with the basis for your denial, to the Nuclear Regulatory

Commission, ATTN.: Document Control Desk, Washington, D.C. 20555-0001; with copies to the

Regional Administrator, Region IV; the Director, Office of Enforcement, United States Nuclear

Regulatory Commission, Washington, D.C. 20555-0001; and the NRC Senior Resident

Inspector at the Diablo Canyon Power Plant.

If you disagree with a cross-cutting aspect assignment in this report, you should provide a

response within 30 days of the date of this inspection report, with the basis for your

disagreement, to the Regional Administrator, Region IV, and the NRC Senior Resident

Inspector at Diablo Canyon Power Plant. The information you provide will be considered in

accordance with Inspection Manual Chapter 0305.

In accordance with 10 CFR 2.390 of the NRCs Rules of Practice, a copy of this letter, its

enclosure, and your response (if any) will be available electronically for public inspection in the

NRC Public Document Room or from the Publicly Available Records (PARS) component of the

NRCs document system (ADAMS). ADAMS is accessible from the NRC Website at

http://www.nrc.gov/reading-rm/adams.html (the Public Electronic Reading Room).

Sincerely,

/RA/

Geoffrey B. Miller, Chief

Engineering Branch 2

Division of Reactor Safety

Dockets: 50-275; 50-323

Licenses: DPR-80; DPR-82

Enclosure: Inspection Report No. 05000275/2012008; 05000323/2012008

w/Attachment:

1 - Supplemental Information

Electronic Distribution to Diablo Canyon

E. Halpin

- 3 -

Electronic distribution by RIV:

Regional Administrator (Elmo.Collins@nrc.gov)

Deputy Regional Administrator (Steven.Reynolds@nrc.gov)

DRP Director (Kriss.Kennedy@nrc.gov)

Acting DRP Deputy Director (Michael.Scott@nrc.gov)

Acting DRS Director (Tom.Blount@nrc.gov)

Acting DRS Deputy Director (Jeff.Clark@nrc.gov)

Senior Resident Inspector (Thomas.Hipschman@nrc.gov)

Resident Inspector (Laura.Micewski@nrc.gov)

Branch Chief, DRP/B (Neil.OKeefe@nrc.gov)

Senior Project Engineer, DRP/B (Leonard.Willoughby@nrc.gov)

Project Engineer, DRP/B (David.You@nrc.gov)

DC Administrative Assistant (Madeleine.Arel-Davis@nrc.gov)

Public Affairs Officer (Victor.Dricks@nrc.gov)

Public Affairs Officer (Lara.Uselding@nrc.gov)

Project Manager (Joseph.Sebrosky@nrc.gov)

Branch Chief, DRS/TSB (Ray.Kellar@nrc.gov)

RITS Coordinator (Marisa.Herrera@nrc.gov)

Regional Counsel (Karla.Fuller@nrc.gov)

Technical Support Assistant (Loretta.Williams@nrc.gov)

Congressional Affairs Officer (Jenny.Weil@nrc.gov)

OEMail Resource

Include Mark Salley from RES on distribution

Inspection Reports/MidCycle and EOC Letters to the following:

ROPreports

Only inspection reports to the following:

RIV/ETA: OEDO (John.Cassidy@nrc.gov)

DRS/TSB STA (Dale.Powers@nrc.gov)

R:\\REACTORS\\DC\\DC 2012008 TFP

ADAMS ML13038A714

ADAMS: No Yes

SUNSI Review Complete

Reviewer Initials: GBM

Publicly Available

Non-Sensitive

Non-publicly Available

Sensitive

RIV: EB2\\SRI

RI

RI

RI

J. Mateychick

S. Alferink,

B. Correll

N. Okonkwo

/RA/

/RA/

/RA/

/RA/

2/5/13

2/6/13

2/6/13

2/6/13

SRA

ACES

C:\\DRP\\B

C:

D. Loveless

R. Browder

N. OKeefe

G. Miller

/RA/

/RA/

/RA/

/RA/

2/6/13

2/7/13

2/7/13

2/7/13

OFFICIAL RECORD COPY T=Telephone E=E-mail F=Fax

- 1 -

Enclosure

ENCLOSURE

U.S. NUCLEAR REGULATORY COMMISSION

REGION IV

Dockets:

50-275; 50-323

Licenses:

DPR-80; DPR-82

Report Nos.:

05000275/2012008 and 05000323/2012008

Licensee:

Pacific Gas and Electric Company

Facility:

Diablo Canyon Power Plant, Units 1 and 2

Location:

7 1/2 miles NW of Avila Beach

Avila Beach, California

Dates:

October 22 to December 20, 2012

Team Leader:

J. Mateychick, Senior Reactor Inspector, Engineering Branch 2

Inspectors:

S. Alferink, Reactor Inspector, Engineering Branch 2

B. Correll, Reactor Inspector, Engineering Branch 2

N. Okonkwo, Reactor Inspector, Engineering Branch 2

Approved By:

Geoffrey B. Miller, Branch Chief

Engineering Branch 2

Division of Reactor Safety

- 2 -

Enclosure

SUMMARY OF FINDINGS

IR; 05000275/2012008; 05000323/2012008; October 22 to December 20, 2012; Pacific Gas

and Electric Company; Diablo Canyon Power Plant, Units 1 and 2: Triennial Fire Protection

Team Inspection.

The report covered a two-week triennial fire protection team inspection by specialist inspectors

from Region IV. Two Green findings, which were non-cited violations (NCVs), were identified.

The significance of most findings is indicated by their color (Green, White, Yellow, Red) using

Inspection Manual Chapter 0609, Significance Determination Process, dated June 2, 2012.

Findings for which the significance determination process (SDP) does not apply may be Green

or be assigned a severity level after NRC management review. Cross-cutting aspect are

determined using IMC 0310, Components Within the Cross Cutting Areas dated October 28,

2012. All violations of NRC requirements are dispositioned in accordance with the NRCs

Enforcement Policy dated June 7, 2012. The NRCs program for overseeing the safe operation

of commercial nuclear power reactors is described in NUREG-1649, Reactor Oversight

Process, Revision 4, dated December 2006.

A.

NRC-Identified and Self-Revealing Findings

Cornerstone: Mitigating Systems

Green. The team reviewed a self-revealing non-cited violation of License Conditions

2.C(4) for Unit 1 and 2.C(5) for Unit 2, Fire Protection Program, due to the licensee

inadvertently isolating the firewater yard loop for approximately three days, reducing the

plants fire protection capability without compensatory actions. The licensee entered this

issue in their corrective action program as Notification 50513006.

The failure to maintain the fire water system configuration as required in the approved

fire protection program was a performance deficiency. The performance deficiency was

more than minor because it was associated with the protection against external events

(fire) attribute of the Mitigating Systems Cornerstone and it adversely affected the

cornerstone objective of ensuring the availability, reliability, and capability of systems

that respond to initiating events to prevent undesirable consequences. The performance

deficiency affected the fire protection defense-in depth strategies involving post-fire safe

shutdown systems. The major fire loading in the yard area resulted from the 12 large

transformers. The senior reactor analyst made the bounding assumption that any

transformer fire without suppression would result in an unrecoverable loss of offsite

power. A bounding value was calculated by multiplying the fire ignition frequency by the

conditional core damage probability. This resulted in a change to core damage

frequency of 1.2 x 10-7. Therefore, the subject finding was of very low safety significance

(Green).

This performance deficiency had a cross-cutting aspect in the area of resources

associated with providing complete, accurate and up-to-date design documentation,

procedures, and work packages, and correct labeling of components. Specifically, the

licensee did not provide sufficient details in procedures for operators to successfully align

an infrequently operated valve with no position indication. H.2(c) (Section 1R05.03.b)

- 3 -

Enclosure

Green. The team identified a non-cited violation of License Conditions 2.C(4) for Unit 1

and 2.C(5) for Unit 2, Fire Protection Program, due to the licensees failure to establish

or adequately implement compensatory measures for non-compliances with the

licensees approved fire protection program. These non-compliances were identified

during the licensees ongoing transition to a new fire protection program in compliance

with National Fire Protection Association Standard 805, Performance-Based Standard

for Fire Protection for Light Water Reactor Electric Generating Plants, (NFPA 805). The

licensee entered this issue in their corrective action program as Notifications 50521360

and 50531363.

The failure to establish or maintain appropriate compensatory measures for identified

deficiencies in the approved fire protection program was a performance deficiency. The

performance deficiency was more than minor because it was associated with the

protection against external events (fire) attribute of the Mitigating Systems Cornerstone

and it adversely affected the cornerstone objective of ensuring the availability, reliability,

and capability of systems that respond to initiating events to prevent undesirable

consequences. A senior reactor analyst evaluated the significance of this performance

deficiency.

A fire that results in the loss of switchgear room ventilation would cause a loss of all ac

and dc power if operators did not take action to recover cooling. The analyst determined

that the licensed operators would have at least two clear annunciators indicating that

ventilation had been lost and that room temperatures were increasing. Additionally,

Procedure CP-M10, Fire Protection of Safe Shutdown Equipment, was available to

assist in providing portable fan cooling to the rooms.

For a fire to result in an intersystem loss of coolant accident, it would have to cause

a 3-phase hot short on both of two shutdown cooling suction valves. Given that each

valve is on a different electrical train, the analyst determined that the conditional

probabilities of the hot shorts involved would best be modeled as independent.

Accounting for the risk associated with both issues evaluated, the analyst estimated the

change to core damage probability to be 1.5 x 10-7 per unit. Therefore, the performance

deficiency was considered to be of very low safety significance (Green).

This finding did not have a cross-cutting aspect because it was not indicative of the

licensees present performance. (Section 1R05.10.b)

B.

Licensee-Identified Violations

None.

- 4 -

Enclosure

REPORT DETAILS

1.

REACTOR SAFETY

Cornerstones: Initiating Events, Mitigating Systems, and Barrier Integrity

1R05 Fire Protection (71111.05T)

This report presents the results of a triennial fire protection inspection conducted in

accordance with NRC Inspection Procedure 71111.05T, Fire Protection (Triennial), at

the Diablo Canyon Power Plant. The licensee committed to adopt a risk-informed fire

protection program in accordance with National Fire Protection Association

Standard 805 (NFPA 805) on June 24, 2011, as approved by NRC on July 28, 2011,

(ML112010657), but has not yet completed the program transition. The inspection team

evaluated the implementation of the approved fire protection program in selected

risk-significant areas, with an emphasis on the procedures, equipment, fire barriers, and

systems that ensure the post-fire capability to safely shutdown the plant.

Inspection Procedure 71111.05T requires the selection of three to five fire areas for

review. The inspection team used the fire hazards analysis section of the Diablo

Canyon Power Plants Fire-Induced Risk Model to select the following three

risk-significant fire areas in Unit 1 (inspection samples) for review:

Fire Area 3-BB, Containment Penetration Rooms (all elevations)

Fire Area 7A, Cable Spreading Room

Fire Area 5-A-4, 480V Nonvital Switchgear and Hot Shutdown Panel Area

The inspection team evaluated the licensees fire protection program using the

applicable requirements, which included plant Technical Specifications, Operating

License Condition 2.C.(5), NRC safety evaluations, 10 CFR 50.48, and Branch

Technical Position 9.5-1. The team also reviewed related documents that included the

Final Safety Analysis Report (FSAR), Section 9.5; the fire hazards analysis; and the

post-fire safe shutdown analysis.

Specific documents reviewed by the team are listed in the attachment. Three inspection

samples were completed.

.01

Protection of Safe Shutdown Capabilities

a. Inspection Scope

The team reviewed the piping and instrumentation diagrams, safe shutdown equipment

list, safe shutdown design basis documents, and the post-fire safe shutdown analysis to

verify that the licensee properly identified the components and systems necessary to

achieve and maintain safe shutdown conditions for fires in the selected fire areas. The

team observed walkdowns of the procedures used for achieving and maintaining safe

shutdown in the event of a fire to verify that the procedures properly implemented the

safe shutdown analysis provisions.

- 5 -

Enclosure

For each of the selected fire areas, the team reviewed the separation of redundant

safe shutdown cables, equipment, and components located within the same fire area.

The team also reviewed the licensees method for meeting the requirements

of 10 CFR 50.48; Branch Technical Position 9.5-1, Appendix A; and 10 CFR Part 50,

Appendix R,Section III.G. Specifically, the team evaluated whether at least one post-

fire safe shutdown success path remained free of fire damage in the event of a fire. In

addition, the team verified that the licensee met applicable license commitments.

b. Findings

No findings were identified.

.02

Passive Fire Protection

a. Inspection Scope

The team walked down accessible portions of the selected fire areas to observe the

material condition and configuration of the installed fire area boundaries (including walls,

fire doors, and fire dampers) and verify that the electrical raceway fire barriers were

appropriate for the fire hazards in the area. The team compared the installed

configurations to the approved construction details, supporting fire tests, and applicable

license commitments.

The team reviewed installation, repair, and qualification records for a sample of

penetration seals to ensure the fill material possessed an appropriate fire rating and that

the installation met the engineering design. The team also reviewed similar records for

the rated fire wraps to ensure the material possessed an appropriate fire rating and that

the installation met the engineering design.

b. Findings

No findings were identified.

.03

Active Fire Protection

a. Inspection Scope

The team reviewed the design, maintenance, testing, and operation of the fire detection

and suppression systems in the selected fire areas. The team verified the automatic

detection systems and the manual and automatic suppression systems were installed,

tested, and maintained in accordance with the National Fire Protection Association code

of record or approved deviations, and that each suppression system was appropriate for

the hazards in the selected fire areas.

The team performed a walkdown of accessible portions of the detection and suppression

systems in the selected fire areas. The team also performed a walkdown of major

system support equipment in other areas (e.g., fire pumps and carbon dioxide supply

systems) to assess the material condition of these systems and components.

- 6 -

Enclosure

The team reviewed the fire pumps flow and pressure tests to verify that the pumps met

their design requirements. The team also reviewed the carbon dioxide suppression

system functional tests to verify that the system capability met the design requirements.

The team assessed the fire brigade capabilities by reviewing training, qualification, and

drill critique records. The team also reviewed pre-fire plans and smoke removal plans

for the selected fire areas to determine if appropriate information was provided to fire

brigade members and plant operators to identify safe shutdown equipment and

instrumentation, and to facilitate suppression of a fire that could impact post-fire safe

shutdown capability. In addition, the team inspected fire brigade equipment to determine

operational readiness for fire fighting.

b. Findings

Introduction. The team evaluated a self-revealing finding due to the firewater yard loop

being inadvertently isolated for approximately three days. The team determined the

finding to be a Green non-cited violation of the licensees approved fire protection

program as defined in License Conditions 2.C(4) for Unit 1 and 2.C(5) for Unit 2.

Description. The firewater yard loop within the protected area is normally supplied by

the raw water storage reservoirs with the elevation difference maintaining the firewater

yard loop pressure. The firewater yard loop supplies firewater to both the power block

and the intake structure. The power block, including safety related areas, have a backup

supply from fire water storage tank 0-1 via two electric driven fire pumps which activate

on low system pressure. The fire hose stations and two fire sprinklers in the intake

structure are only supplied from the firewater yard loop.

The south firewater loop serving additional site facilities outside of the protected area

has two additional fire pumps with their own fire water storage tank. The south firewater

loop is normally isolated from the firewater yard loop but can be aligned to feed the

firewater yard loop. The licensees Equipment Control Guideline (ECG) 18.1, Fire

Suppression Systems/Fire Suppression Water Systems, Revision 9, requires that if the

raw water gravity feed water supply is inoperable, within 7 days either restore the supply

or align the south loop fire pumps and fire water storage tank to supply the firewater yard

loop.

On September 9, 2012, operators isolated the raw water storage reservoirs from the

firewater yard loop and south firewater loop for planned maintenance work. Operators

also aligned the south firewater loop to supply the firewater yard loop. On

September 12, 2012, operators restored the fire water supply from the raw water storage

reservoirs and isolated the south firewater loop from the firewater yard loop.

On September 15, 2012, operators attempted to add water from the raw water storage

reservoirs to fire water storage tank 0-2 in the south firewater loop system. Flow to the

tank stopped and the firewater yard loop lost pressure, initiating alarms on the fire

computer in the control room. Fire pump 0-2 started on low pressure to supply the fire

suppression systems in the power block from fire water storage tank 0-1 as designed.

Operators aligned the south firewater loop to supply the firewater yard loop and started

fire pump 0-3 to restore pressure in the firewater yard loop. Operators rechecked the

- 7 -

Enclosure

system valve alignment and reopened valve MU-0-268, which pressurized the firewater

yard loop from the raw water storage reservoir.

During the approximately three day period when valve MU-0-268 was inadvertently left

in the closed position, the following fire suppression systems were without a water

supply:

The automatic water spray deluge systems for the main transformers, auxiliary

transformers, and startup transformers for both units

All outdoor fire hydrants in the protected area

The hose stations and two sprinkler heads in the intake structure

Valve MU-0-268 is a buried 12-inch valve which is manually operated with a T handle.

This valve is infrequently operated and has no position indication. The operator

restoring the valve to the open position turned the T handle approximately 20 turns in

the open direction and felt an increase in resistance. The operator interpreted the

resistance as the valve reaching its fully opened position. The second operator verifying

the valve position turned the valve closed a few turns then reopened the valve until the

increased resistance was also felt. The licensees investigation identified that valve

MU-0-268 requires approximately 80 turns to fully open. From the fully closed position,

approximately 20 turns are required before the disc begins to pull out of its seat. The

increased resistance the operators encountered was due to the forces required to pull

the disc out of its seat and was not due to the valve being fully open.

Analysis. The failure to maintain the fire water system configuration as required in the

approved fire protection program was a performance deficiency. The performance

deficiency was more than minor because it was associated with the protection against

external events (fire) attribute of the Mitigating Systems Cornerstone and it adversely

affected the cornerstone objective of ensuring the availability, reliability, and capability of

systems that respond to initiating events to prevent undesirable consequences. The

team evaluated this deficiency using Inspection Manual Chapter 0609, Appendix F, Fire

Protection Significance Determination Process. The performance deficiency affected

the fire protection defense-in depth strategies involving post-fire safe shutdown systems.

However, the Assumptions and Limitations section of Appendix F states, The SDP

approach is intended to support the assessment of known issues only in the context of

an individual fire area. A systematic plant-wide search and assessment effort is beyond

the intended scope of the fire protection SDP. Therefore, a senior reactor analyst

evaluated the significance of this performance deficiency.

The analyst evaluated this finding using the Standardized Plant Analysis Risk Model for

Diablo Canyon, Units 1 & 2, Revision 8.15. The analyst noted that the major fire loading

in the yard area resulted from the 12 large transformers. Using the generic fire ignition

frequency for outdoor transformers (4.2 x 10-3/year) from NRC Inspection Manual

Chapter 0609, Appendix F, Attachment 4, Fire Ignition Source Mapping Information:

Fire Frequency, Counting Instructions, Applicable Fire Severity Characteristics, and

Applicable Manual Fire Suppression Curves, the analyst calculated a fire ignition

frequency for all 12 transformers of 5.0 x 10-2/year. For a 3-day exposure period, the

analyst calculated a fire ignition probability of 4.1 x 10-4.

- 8 -

Enclosure

The analyst made the bounding assumption that any transformer fire without

suppression would result in an unrecoverable loss of offsite power. Using the SPAR

model, the analyst quantified this conditional core damage probability as 2.8 x 10-4. A

bounding value was then calculated by multiplying the fire ignition frequency by the

conditional core damage probability. This resulted in a change of core damage

frequency of 1.2 x 10-7. Therefore, the subject finding was of very low safety significance

(Green).

This performance deficiency had a cross-cutting aspect in the area of resources

associated with providing complete, accurate and up-to-date design documentation,

procedures, and work packages, and correct labeling of components. Specifically, the

licensee did not provide sufficient details in procedures for operators to successfully

align an infrequently operated valve with no position indication. H.2(c)

Enforcement. License Conditions 2.C(4) for Unit 1 and 2.C(5) for Unit 2, Fire Protection

Program, require the licensee to implement and maintain in effect all provisions of the

approved Fire Protection Program as discussed in the Final Safety Analysis Report

Update; in PG&Es December 6, 1984, Appendix R Report; and in the NRC staffs Fire

Protection Evaluation in the Supplements to the Diablo Canyon Safety Evaluation Report

listed for each unit.

Updated Final Safety Analysis Report Appendix 9.5B, DCPP Regulatory Compliance

Summary, Table B-1, Comparison of DCPP to Appendix A of BTP APCSB 9.5-1,

Section C, Quality Assurance Program, Sub-Section 2, Instructions, Procedures, and

Drawings, states Inspections, tests, administrative controls, fire drills, and training that

govern the fire protection program should be prescribed by documented instructions,

procedures, or drawings and should be accomplished in accordance with these

documents. The DCPP Compliance to Commitment states, Procedures govern

inspections, tests, administrative controls, fire drills, and training relating to the FP

Program.

Contrary to the above, from September 12, 2012 to September 15, 2012, the licensee

failed to implement and maintain in effect the provisions of the approved fire protection

program. Specifically, the licensee failed to maintain the required configuration of the

fire water system. The performance deficiency was due to the licensees failure to

provide adequate information to operators concerning the operation of Valve MU-0-268

in Clearance 0C18 D-16-005. Because this finding is of very low safety significance and

has been entered into the corrective action program (Notification 50513006), this

violation is being treated as a non-cited violation, consistent with Section 2.3.2 of the

NRC Enforcement Policy: NCV 05000275/2012008-01, 05000323/2012008-01; Failure

to Maintain Required Firewater System Configuration

.04

Protection From Damage From Fire Suppression Activities

a. Inspection Scope

The team performed plant walkdowns and document reviews to verify that redundant

trains of systems required for hot shutdown, which are located in the same fire area,

would not be subject to damage from fire suppression activities or from the rupture or

inadvertent operation of fire suppression systems. Specifically, the team verified that:

- 9 -

Enclosure

A fire in one of the selected fire areas would not directly, through production of

smoke, heat, or hot gases, cause activation of suppression systems that could

potentially damage all redundant safe shutdown trains.

A fire in one of the selected fire areas or the inadvertent actuation or rupture of a

fire suppression system would not directly cause damage to all redundant trains

(e.g., sprinkler-caused flooding of other than the locally affected train).

Adequate drainage is provided in areas protected by water suppression systems.

b. Findings

No findings were identified.

.05

Alternative Shutdown Capability

a. Inspection Scope

Review of Methodology

The team reviewed the safe shutdown analysis, operating procedures, piping and

instrumentation drawings, electrical drawings, the Final Safety Analysis Report, and

other supporting documents to verify that hot and cold shutdown could be achieved and

maintained from outside the control room for fires that require evacuation of the control

room, with or without offsite power available.

Plant walkdowns were conducted to verify that the plant configuration was consistent

with the description contained in the safe shutdown and fire hazards analyses. The

team focused on ensuring the adequacy of systems selected for reactivity control,

reactor coolant makeup, reactor decay heat removal, process monitoring

instrumentation, and support systems functions.

The team also verified that the systems and components credited for shutdown would

remain free from fire damage. Finally, the team verified that the transfer of control from

the control room to the alternative shutdown location would not be affected by

fire-induced circuit faults (e.g., by the provision of separate fuses and power supplies for

alternative shutdown control circuits).

Review of Operational Implementation

The team verified that licensed and non-licensed operators received training on

alternative shutdown procedures. The team also verified that sufficient personnel to

perform a safe shutdown were trained and available onsite at all times, exclusive of

those assigned as fire brigade members.

The team performed a walkthrough of the post-fire safe shutdown procedure with

licensed and non-licensed operators to determine the adequacy of the procedure. The

team verified that the operators could be reasonably expected to perform specific

actions within the time required to maintain plant parameters within specified limits.

Time critical actions that were verified included restoring electrical power, establishing

- 10 -

Enclosure

control at the remote shutdown and local shutdown panels, establishing reactor coolant

makeup, and establishing decay heat removal.

The team also reviewed the periodic testing of the alternative shutdown transfer

capability and instrumentation and control functions to verify that the tests were

adequate to demonstrate the functionality of the alternative shutdown capability.

b. Findings

.1 Introduction. The team identified a violation of Technical Specification 5.4.1.d for the

failure to implement and maintain adequate written procedures covering fire protection

program implementation. Specifically, the team identified five examples (with a total of

eight fire scenarios) where the licensee failed to maintain an alternative shutdown

procedure that ensured operators could safely shutdown the plant in the event of a

control room or cable spreading room fire. This violation has been screened and

determined to warrant enforcement discretion in accordance with the NRC Enforcement

Policy, Section 9.1, Enforcement Discretion for Certain Fire Protection Issues

(10 CFR 50.48), and Inspection Manual Chapter 0305.

Description. Operations personnel would use Procedure OP AP-8A, Control Room

Inaccessibility - Establishing Hot Standby, Revision 31, to shutdown the reactor at the

hot shutdown panel, dedicated shutdown panel, and other control stations outside of the

control room in the event a fire required evacuation of the control room. This alternative

shutdown procedure was developed based on the results of the safe shutdown and

thermal hydraulic analyses contained in the following calculations:

M-680, 10 CFR 50 Appendix R Safe Shutdown Equipment, Revision 18-01

M-928, 10 CFR 50 Appendix R Safe Shutdown Analysis, Revision 18-02

M-944, 10 CFR 50 Appendix R Alternate Shutdown Methodology - Time and

Manpower Study/Safe Shutdown System Considerations, Revision 7

STA-251, RETRAN Evaluation of Appendix R Scenarios with RSGs, Revision 0

The alternative shutdown procedure provided methods to maintain several post-fire safe

shutdown functions, including maintaining reactor coolant inventory, controlling decay

heat removal, and providing electrical power, from outside the control room. The

procedure directed operators to maintain reactor coolant inventory by isolating letdown

and maintaining the pressurizer level and pressure within prescribed limits using the

emergency core cooling system charging pumps. The procedure directed operators to

control decay heat removal by using the motor-driven auxiliary feedwater pumps to inject

water into the steam generators. The procedure directed operators to provide electrical

power by ensuring the emergency diesel generators started and energized the 4kV

and 480V busses.

The team performed a timed walkdown of the alternative shutdown procedure. Based

on the timed walkdown results, the team identified five examples (with a total of eight fire

scenarios) where the licensee failed to maintain an alternative shutdown procedure that

ensured operators could safely shutdown the plant in the event of a control room or

cable spreading room fire. These examples included scenarios where the licensee

failed to ensure charging pumps remained available to maintain reactor coolant

- 11 -

Enclosure

inventory, steam generators remained available to remove decay heat, 480V equipment

remained available to shutdown the plant, and the pressurizer level remained within the

indicating region (both high and low). For each example, the licensee implemented

corrective actions to revise their procedures and establish compensatory fire patrols, as

appropriate.

Example 1: Potential Loss of the Emergency Core Cooling System Charging Pumps

The first example involved a control room or cable spreading room fire with the spurious

closure of one of the volume control tank outlet valves (LCV-112B or LCV-112C)

combined with a loss of offsite power. In this scenario, the expected plant response to

the loss of offsite power causes both emergency core cooling system charging pumps to

start, and the spurious closure of one of the volume control tank outlet valves results in

the loss of both pumps.

Westinghouse examined this scenario and provided an evaluation in Letter PGE-92-621,

Diablo Canyon Appendix R Charging Pump Evaluation, dated July 14, 1992. Their

evaluation stated that severe pump damage and failure could occur within

approximately 30 seconds after a loss of suction, but most likely would not occur for an

additional one or two minutes. Based on this evaluation, the team concluded that

operators need to stop all running charging pumps within 2.5 minutes of the loss of

suction for the charging pumps to maintain reactor coolant inventory.

The team determined that operators could mitigate this scenario by opening the refueling

water storage tank outlet valves or stopping the pumps prior to pump damage. The

alternative shutdown procedure provided steps for operators to transfer the suction for

the charging pumps from the volume control tank to the refueling water storage tank.

Based on the timed walkdown, the team determined that operators would begin opening

the refueling water storage tank outlet valves 5.5 minutes after the reactor trip and

complete this action within 3 minutes. Since this time exceeded 2.5 minutes, the team

concluded that the alternative shutdown procedure was inadequate to ensure that the

charging pumps remained available to maintain reactor coolant inventory under all

alternative shutdown fire scenarios.

The team noted that the licensee had a third charging pump which received power from

an emergency diesel generator, but would not automatically start on a loss of offsite

power. The team reviewed the alternative shutdown procedure and determined that the

procedure did not provide operators with instructions on using the third charging pump in

the event the other two pumps were damaged.

Example 2: Potential Overfilling of the Steam Generators

The second example involved a control room or cable spreading room fire where fire

damage prevents the feedwater isolation on a reactor trip and low Tavg signal, resulting in

the turbine-driven main feedwater pumps continuing to inject feedwater into the steam

generators and a loss of decay heat removal and overcooling.

- 12 -

Enclosure

The licensee performed a preliminary analysis of this scenario and concluded that

operators had approximately 3 minutes to stop the main feedwater injection prior to

overfilling the steam generators.

The team determined that operators could mitigate this scenario by closing the main

feedwater isolation valves or the main steam isolation valves. The alternative shutdown

procedure provided steps for operators to close the main steam isolation valves from the

control room prior to evacuation; however, the team determined that the approved fire

protection program did not credit this action. The team noted that the alternative

shutdown procedure provided steps for operators to close the main steam isolation

valves outside the control room, but did not provide steps for operators to close the main

feedwater isolation valves. As noted in the next violation, (1R05.05.b.2), the safe

shutdown analysis determined that operator actions were required to isolate main

feedwater, but this requirement was not carried forward to the alternative shutdown

procedure.

Based on the timed walkdown, the team determined that operators would begin closing

the main steam isolation valves approximately 11 minutes after the reactor trip and

complete this action within 15 minutes. Since this time exceeded 3 minutes, the team

concluded that the alternative shutdown procedure was inadequate to ensure that the

steam generators remained available to remove decay heat under all alternative

shutdown fire scenarios.

Example 3: Potential Loss of 480V Safe Shutdown Equipment

The third example involved a control room or cable spreading room fire where fire

damage causes the 480V feeder breakers (52HF10, 52GH10, and 52HH10) to open,

resulting in a loss of the following 480V safe shutdown equipment:

E-103

Auxiliary Salt Water Pump 1-1 Room HVAC

ED11

Vital Battery Charger

PP0-2

Fuel Oil Transfer Pump 0-2

E-101

Auxiliary Salt Water Pump 1-2 Room HVAC

HTR1-2

Pressurizer Heater Group 1-2

ED12

Vital Battery Charger

LCV-85

Day Tank 1-1 Level

LCV-86

Day Tank 1-2 Level

LCV-87

Day Tank 1-3 Level

PP0-1

Fuel Oil Transfer Pump 0-1

HTR1-3

Pressurizer Heater Group 1-3

ED132

Vital Battery Charger

LCV-88

Day Tank 1-1 Level

LCV-89

Day Tank 1-2 Level

LCV-90

Day Tank 1-3 Level

The team determined that none of the affected equipment was required immediately,

and operators could mitigate this scenario by ensuring the breakers were closed after

placing the respective transfer switches to Local. The team reviewed the alternative

- 13 -

Enclosure

shutdown procedure and determined that the procedure did not provide operators with

instructions on ensuring the 480V feeder breakers were closed. As noted in the next

violation, (1R05.05.b.2), the safe shutdown analysis determined that operator actions

were required to ensure the 480V feeder breakers were closed, but this requirement was

not carried forward to the alternative shutdown procedure.

Example 4: Potential Overfilling of the Pressurizer

The fourth example involved three fire scenarios that could result in overfilling the

pressurizer. Two of these scenarios could also result in voiding in the core due to rapid

depressurization of the reactor coolant system.

The first scenario involved a control room or cable spreading room fire with a spurious

safety injection signal. The second scenario involved a control room or cable spreading

room fire with the spurious actuation of a pressurizer power-operated relief valve,

resulting in a rapid depressurization of the reactor coolant system and subsequent safety

injection signal within approximately one minute. The third scenario involved a control

room or cable spreading room fire with the spurious opening of a pressurizer auxiliary

spray valve (8145 or 8148), resulting in a slightly slower depressurization of the reactor

coolant system and subsequent safety injection signal within a maximum of four minutes

(depending of the number of charging pumps running). In all three scenarios, the safety

injection signal results in the two emergency core cooling system charging pumps

starting and injecting water into the reactor coolant system through the charging injection

valves (8801A, 8801B, 8803A, and 8803B).

The licensee examined the spurious actuation of the safety injection system in the Final

Safety Analysis Report Section 15.2.15. The licensees analysis assumed the safety

injection signal occurred at 100 percent power, the emergency core cooling system

actuated, letdown isolated, and offsite power was lost. The licensee concluded that

operators had 8.5 minutes to control charging prior to the pressurizer reaching a water

solid condition.

The team determined this time limit was not conservative for all three scenarios. First,

the time limit was based on reaching a water solid condition in the pressurizer, not

maintaining the level within the indicating region, as required by the approved fire

protection program. Second, the analysis was based on an injection from the charging

pumps. In the second and third scenarios, the depressurization of the reactor coolant

system could lower the pressure quickly enough that the safety injection pumps would

also be able to inject water into the reactor coolant system, thereby reducing the amount

of time available prior to exceeding the indicating region of the pressurizer or reaching a

water solid condition in the pressurizer.

The team determined that operators could mitigate all three scenarios by controlling

charging at the hot shutdown panel. The alternative shutdown procedure provided steps

for operators to control charging and maintain the pressurizer level between 22 percent

and 70 percent, and it provided steps to stop the charging pumps if level could not be

maintained. Based on the timed walkdown, the team determined that operators would

reach this step nearly 30 minutes after the reactor trip. Since this time exceeded the

amount of time allowed for all three scenarios (even though this limit was not

- 14 -

Enclosure

conservative), the team concluded that the alternative shutdown procedure was

inadequate to ensure the pressurizer level remained within the indicating region and the

pressurizer did not overfill under all alternative shutdown fire scenarios.

Example 5: Potential Draining of the Pressurizer

The fifth example involved two fire scenarios that could result in draining of the

pressurizer and the potential to develop a bubble outside of the pressurizer. The first

scenario involved a control room or cable spreading room fire with the spurious opening

of a 10 percent atmospheric dump valve.

The licensee examined this scenario in Calculation STA-251 and concluded that

operators had approximately 4.5 minutes to close the atmospheric dump valve prior to

the pressurizer reaching 0 percent indicated level. The team noted that this number was

not conservative since it assumed that the reactor coolant pumps remained running and

main feedwater was isolated shortly after the reactor trip, adding heat to the reactor

coolant system and lengthening the plant cooldown.

The team determined that operators could mitigate this scenario by closing the

atmospheric dump valves. The alternative shutdown procedure provided steps for

operators to close the atmospheric dump valves. Based on the timed walkdown, the

team determined that operators would begin closing the atmospheric dump valves

approximately 20 minutes after the reactor trip and complete this action within 15

additional minutes. Since this time exceeded 4.5 minutes, the team concluded that the

alternative shutdown procedure was inadequate to ensure that the pressurizer remained

within the indicating region and a bubble did not develop outside of the pressurizer under

all alternative shutdown fire scenarios.

The second scenario involved a control room or cable spreading room fire with the

spurious opening of a steam dump valve combined with a loss of offsite power.

The licensee examined this scenario in Calculation STA-251 and concluded that

operators had less than 24.5 minutes to close the main steam isolation valves prior to

the pressurizer reaching 0 percent indicated level.

The team determined that operators could mitigate this scenario by closing the main

steam isolation valves. The alternative shutdown procedure provided steps for

operators to close the main steam isolation valves. Based on the timed walkdown, the

team determined that operators would begin closing the main steam isolation valves

within 11 minutes and complete this action within 15 additional minutes. Since this time

exceeded 24.5 minutes, the team concluded that the alternative shutdown procedure

was inadequate to ensure that the pressurizer remained within the indicating region and

a bubble did not develop outside of the pressurizer under all alternative shutdown

scenarios.

Analysis. The failure to maintain adequate written procedures covering fire protection

program implementation was a performance deficiency. The performance deficiency

was more than minor because it was associated with the protection against external

events (fire) attribute of the Mitigating Systems cornerstone and it adversely affected the

- 15 -

Enclosure

cornerstone objective of ensuring the availability, reliability, and capability of systems

that respond to initiating events to prevent undesirable consequences.

A senior reactor analyst performed a hand calculation to bound the risk significance of

this finding. The senior reactor analyst determined that the change in core damage

frequency was less than 1E-4, so the finding was not of high safety significance (Red).

Therefore, this finding qualified for enforcement discretion using Section 9.1 of the

Enforcement Policy, Enforcement Discretion for Certain Fire Protection Issues

(10 CFR 50.48).

This finding did not have a cross-cutting aspect because it qualified for enforcement

discretion.

Enforcement. Technical Specification 5.4.1.d states that written procedures shall be

established, implemented, and maintained covering fire protection program

implementation. Contrary to this requirement, prior to November 8, 2012, the licensee

failed to establish, implement, and maintain adequate written procedures covering fire

protection program implementation. Specifically, the team identified five examples

involving the potential loss of the emergency core cooling system charging pumps,

overfilling of the steam generators, loss of 480V safe shutdown equipment, overfilling of

the pressurizer, and draining of the pressurizer where the licensee failed to maintain an

alternative shutdown procedure that ensured operators could safely shutdown the plant

in the event of a control room or cable spreading room fire.

Because the licensee committed to adopting National Fire Protection Association

Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor

Electric Generating Plants, and committed to changing their fire protection program

license basis to comply with 10 CFR 50.48(c) by submitting a license amendment

request to the NRC, this violation was eligible for enforcement discretion as described in

Section 9.1 of the Enforcement Policy, Enforcement Discretion for Certain Fire

Protection Issues (10 CFR 50.48). Under this Enforcement Policy, the NRC will

normally not take enforcement action for a violation of 10 CFR 50.48(b) (or the

requirements in a fire protection license condition) involving a problem in an area such

as engineering, design, implementing procedures, or installation if the violation is

documented in an inspection report and meets all of the following criteria:

The licensee identified the violation as a result of a voluntary initiative to adopt

the risk-informed, performance-based fire protection program under

10 CFR 50.48(c), or, if the NRC identified the violation, the NRC found it likely

that the licensee would have identified the violation in light of the defined scope,

thoroughness, and schedule of its transition to 10 CFR 50.48(c).

The licensee corrected the violation or will correct the violation after completing

its transition to 10 CFR 50.48(c). Also, the licensee took immediate corrective

action or compensatory measures or both within a reasonable time

commensurate with the risk significance of the issue following identification; this

action should involve expanding the initiative, as necessary, to identify other

issues caused by similar root causes.

Routine licensee efforts, such as normal surveillance or quality assurance

activities, were not likely to have previously identified the violation.

- 16 -

Enclosure

The violation was not willful.

The violation is not associated with a finding of high safety significance.

Specifically, the team determined that the licensee: (1) would have identified the

violation in light of the defined scope, thoroughness, and schedule of its transition

to 10 CFR 50.48(c) because the licensee was performing new analyses and developing

a new alternative shutdown procedure for the transition to NFPA-805; (2) the licensee

will correct the violation after completing its transition to 10 CFR 50.48(c) and took

immediate corrective action or compensatory measures or both within a reasonable time

commensurate with the risk significance of the issue following identification; (3) routine

licensee efforts (such as normal surveillance or quality assurance activities) were not

likely to have previously identified the violation; (4) the violation was not willful; and

(5) the team determined that this violation was not of high safety significance (Red).

The licensee entered these issues into their corrective action program as Notification

50522666 and implemented appropriate compensatory measures. Since all the criteria

for enforcement discretion were met, the NRC is exercising enforcement discretion for

this issue. (EA-13-021)

.2 Introduction. The team identified a violation of License Condition 2.C(5) for the failure to

implement and maintain in effect all provisions of the approved fire protection program.

Specifically, the team identified four examples where the licensee failed to maintain the

fire protection program design basis documents (e.g., fire hazards analysis, safe

shutdown analysis, and thermal hydraulic analysis) and the alternative shutdown

procedure to adequately implement the approved fire protection program. This violation

has been screened and determined to warrant enforcement discretion in accordance

with the NRC Enforcement Policy, Section 9.1, Enforcement Discretion for Certain Fire

Protection Issues (10 CFR 50.48), and Inspection Manual Chapter 0305.

Description. Operations personnel used Procedure OP AP-8A, Control Room

Inaccessibility - Establishing Hot Standby, Revision 31, to shutdown the reactor at the

hot shutdown panel, dedicated shutdown panel, and other control stations outside of the

control room in the event a fire required evacuation of the control room. This alternative

shutdown procedure was developed based on the results of the safe shutdown and

thermal hydraulic analyses contained in the following calculations:

M-680, 10 CFR 50 Appendix R Safe Shutdown Equipment, Revision 18-01

M-928, 10 CFR 50 Appendix R Safe Shutdown Analysis, Revision 18-02

M-944, 10 CFR 50 Appendix R Alternate Shutdown Methodology - Time and

Manpower Study/Safe Shutdown System Considerations, Revision 7

STA-251, RETRAN Evaluation of Appendix R Scenarios with RSGs, Revision 0

The team reviewed the alternative shutdown procedure, safe shutdown equipment list

(Calculation M-680), safe shutdown analysis (Calculation M-928), time and manpower

study (Calculation M-944), thermal hydraulic analysis (Calculation STA-251), and the fire

hazards analysis. During this review, the team identified four examples of errors and

inconsistencies between these documents. Some of these errors led to examples of the

inadequate alternative shutdown procedure described above in Section 1R05.05.b.1.

- 17 -

Enclosure

Example 1: Errors Associated with the 10 percent Atmospheric Dump Valves

The first example involved a discrepancy between the safe shutdown analysis and the

time and manpower study. The safe shutdown analysis noted that a fire in the cable

spreading room could spuriously open the 10 percent atmospheric dump valves and

prevent operation from the hot shutdown panel. The time and manpower study,

however, stated that the spurious opening of a 10 percent atmospheric dump valve

would not occur due to a fire in the control room or cable spreading room. This study

also stated that this scenario was not a credible scenario. As a result, the licensee failed

to provide a time limit for operators to close the atmospheric dump valves.

The team disagreed with the licensees position that the scenario was not credible for an

alternative shutdown scenario. The team noted that supplemental guidance, specific for

alternative shutdown scenarios, was promulgated in Generic Letter 86-10,

Question 5.3.10. In this question, the staff noted that the safe shutdown capability

should not be adversely affected by any one spurious actuation or signal resulting from a

fire in any plant area. The team noted that the spurious opening of a 10 percent

atmospheric dump valve is considered a single spurious actuation and was required to

be considered.

Example 2: Errors Associated with the Alternative Shutdown Procedure

The second example involved a discrepancy between the safe shutdown analysis and

the alternative shutdown procedure. The safe shutdown analysis included requirements

for operators to close the 480V feeder breakers as well as isolate the main feedwater

system by closing the main feedwater isolation valves and their bypasses.

As discussed above in Section 1R05.05.b.1, the team determined that these actions

were not carried forward from the safe shutdown analysis into the alternative shutdown

procedure. Further, the team noted that the requirement to close the 480V feeder

breakers was described in the fire hazards analysis, but the licensee failed to carry

forward the requirement to isolate the main feedwater system from the safe shutdown

analysis to the fire hazards analysis.

Example 3: Errors Associated with Reactor Coolant Pump Seal Cooling

The third example involved a discrepancy between the fire hazards analysis, safe

shutdown equipment list, safe shutdown analysis, and the alternative shutdown

procedure. The fire hazards analysis stated that Valves 8384A and 8384B would be

used to isolate seal injection and component cooling water to the thermal barrier heat

exchanger. This requirement was reflected in the logic diagrams contained in the safe

shutdown equipment list. The team determined that the licensee modified the safe

shutdown analysis and the alternative shutdown procedure at some point to use

Valves 8382A and 8382B instead, but failed to update the fire hazards analysis and the

safe shutdown equipment list logic diagrams.

- 18 -

Enclosure

Example 4: Errors Associated with the Thermal Hydraulic Analysis

The fourth example involved errors associated with the thermal hydraulic analysis. The

time and manpower study was used to determine the amount of time available for

operators to perform specific manual actions. This study provided a set of assumptions

to be used when calculating the time limits. These assumptions included the

consideration of any single spurious actuation, the potential loss of automatic function

(signals, logic, etc.), and the potential for a loss of offsite power. These assumptions

were consistent with the regulatory guidance.

The team determined that the thermal hydraulic analysis did not properly implement the

assumptions contained in the time and manpower study. Specifically, the team

determined that the licensees RETRAN calculations included assumptions that the

turbine tripped, main feedwater isolated, and letdown isolated.

The team noted that the incorrect assumptions in the thermal hydraulic analyses led to

errors in the safe shutdown analysis. First, the assumption that the turbine tripped

provided additional time for the operators to perform their actions and led to the turbine

trip not being included as a required manual action. This, in turn, led to a lack of

dedicated 8-hour emergency lighting for the operators to perform a manual turbine trip.

The results of the thermal hydraulic analysis indicated that the spurious opening of a

single steam dump valve coincident with a loss of offsite power would result in the

pressurizer reaching 0 percent indicated level within 24.5 minutes. However, the time

and manpower study stated that the spurious opening of a steam dump valve was not a

credible scenario. As a result, the licensee failed to provide a time limit for operators to

close the main steam isolation valves. Instead, the licensee assumed that operators

would perform this task within 30 minutes. The team disagreed with the licensees

position that the scenario was not credible for an alternative shutdown scenario as

discussed in Example 1 of this violation.

Analysis. The failure to maintain the fire protection program design basis documents

(e.g., fire hazards analysis, safe shutdown analysis, and thermal hydraulic analysis) and

the alternative shutdown procedure to adequately implement the approved fire protection

program was a performance deficiency. The performance deficiency was more than

minor because it was associated with the protection against external events (fire)

attribute of the Mitigating Systems cornerstone and it adversely affected the cornerstone

objective of ensuring the availability, reliability, and capability of systems that respond to

initiating events to prevent undesirable consequences.

A senior reactor analyst performed a hand calculation to bound the risk significance of

this finding. The senior reactor analyst determined that the change in core damage

frequency was less than 1E-4, so the finding was not of high safety significance (Red).

Therefore, this finding qualified for enforcement discretion using Section 9.1 of the

Enforcement Policy, Enforcement Discretion for Certain Fire Protection Issues

(10 CFR 50.48).

This finding did not have a cross-cutting aspect because it qualified for enforcement

discretion.

- 19 -

Enclosure

Enforcement. License Condition 2.C.(5) requires, in part, that the licensee shall

implement and maintain in effect all provisions of the approved fire protection program

as discussed in the Final Safety Analysis Report Update and the staffs fire protection

evaluation contained in Supplements 8, 9, 13, 23, and 27 of the Safety Evaluation

Report. Supplement 13 of the Safety Evaluation Report stated that the licensee met the

requirements of 10 CFR Part 50, Appendix R, Sections III.G, III.J, and III.O. Since the

licensee was required to meet the requirements of 10 CFR Part 50, Appendix R,

Section III.G, they were also required to meet the requirements of 10 CFR Part 50,

Appendix R,Section III.L.

The licensee demonstrated compliance with Sections III.G and III.L of 10 CFR Part 50,

Appendix R through the fire hazards analysis and Calculations M-680, M-928, M-944,

and STA-251. The results of these calculations were used to develop the alternative

shutdown procedure, OP AP-8A, Control Room Inaccessibility - Establishing Hot

Standby, Revision 31. Contrary to the above, prior to November 8, 2012, the licensee

failed to implement and maintain in effect all provisions of the approved fire protection

program. Specifically, the licensee failed to maintain the fire hazards analysis and

Calculations M-680, M-928, M-944, and STA-251 such that the licensee met the

requirements of 10 CFR Part 50, Appendix R, Sections III.G and III.L.

The licensee entered these issues into their corrective action program as Notification

50522745 and implemented appropriate compensatory measures. Because the

licensee committed to adopting National Fire Protection Association Standard 805, the

team evaluated this issue using the process described above in Section 1R05.05.b.1.

Since all the criteria for enforcement discretion were met, the NRC is exercising

enforcement discretion for this issue. (EA-13-021)

.06

Circuit Analysis

a. Inspection Scope

The team reviewed the post-fire safe shutdown analysis to verify that the licensee

identified the circuits that may impact the ability to achieve and maintain safe shutdown.

The team verified, on a sample basis, that the licensee properly identified the cables for

equipment required to achieve and maintain hot shutdown conditions in the event of a

fire in the selected fire areas. The team verified that these cables were either

adequately protected from the potentially adverse effects of fire damage or were

analyzed to show that fire induced circuit faults (e.g., hot shorts, open circuits, and

shorts to ground) would not prevent safe shutdown. The team reviewed the circuits

associated with the following components:

RP086, RP086A and 456

Pressurizer Power-Operated Relief Valves

RP093, RP093A and 474

Pressurizer Power-Operated Relief Valves

RP100, RP100A and 455C

Pressurizer Power Operated Relief Valves

F40P00 and 8000A

Pressurizer Power-Operated Relief Block Valves

G46P00 and 8000B

Pressurizer Power Operated Relief Block Valves

H33P00 and 8000C

Pressurizer Power Operated Relief Block Valves

G44P00 and G68P00

Auxiliary Feedwater Pumps Motor Operated Valves

- 20 -

Enclosure

G69P00 and G70P00

Auxiliary Feedwater Pumps Motor Operated Valves

For this sample, the team reviewed electrical elementary and block diagrams and

identified power, control, and instrument cables necessary to support their operation. In

addition, the team reviewed cable routing information to verify that fire protection

features were in place as needed to satisfy the separation requirements specified in the

fire protection license basis. The team also reviewed circuit coordination studies for the

safety-related 4160 volt emergency bus.

b. Findings

No findings were identified.

.07

Communications

a. Inspection Scope

The team inspected the contents of designated emergency storage lockers and

reviewed the alternative shutdown procedure to verify that portable radio

communications and fixed emergency communications systems were available,

operable, and adequate for the performance of designated activities. The team verified

the capability of the communication systems to support the operators in the conduct and

coordination of their required actions. The team also verified that the design and

location of communications equipment such as repeaters and transmitters would not

cause a loss of communications during a fire. The team discussed system design,

testing, and maintenance, and conducted a communication system visual inspection with

the system engineer.

b. Findings

No findings were identified.

.08

Emergency Lighting

a. Inspection Scope

The team reviewed the portion of the emergency lighting system required for alternative

shutdown to verify that it was adequate to support the performance of manual actions

required to achieve and maintain hot shutdown conditions, and to illuminate access and

egress routes to the areas where manual actions would be required. The team

evaluated the locations and positioning of the emergency lights during an in-plant

walkthrough of the alternative shutdown procedure.

The licensee received NRC approval in Supplement 23 to the Safety Evaluation Report

to credit use of the emergency AC and emergency DC lighting systems, in conjunction

with the 8-hour self-contained battery light units described in Appendix R, section III.J.

The team verified that the licensee installed emergency lights with an 8-hour capacity, or

had credited appropriate emergency AC or emergency DC powered lights to meet the

requirements of Appendix R, section III.J. The team verified that the licensee

- 21 -

Enclosure

maintained the emergency light batteries in accordance with industry standards, and

tested and performed maintenance in accordance with plant procedures and industry

practices. The team verified through a sample of maintenance records that emergency

AC lights, emergency DC lights, and battery operated lights were repaired within a 7 day

self-imposed commitment. The team verified through in-plant inspections and

engineering calculation reviews that required access and egress routes, and manual

actions of safe shutdown components were properly illuminated with emergency lighting

fixtures.

b. Findings

No findings were identified.

.09

Cold Shutdown Repairs

a. Inspection Scope

The team verified that the licensee identified repairs needed to reach and maintain cold

shutdown and had dedicated repair procedures, equipment, and materials to accomplish

these repairs. Using these procedures, the team evaluated whether these components

could be repaired in time to bring the plant to cold shutdown within the time frames

specified in their design and licensing bases. The team verified that the repair

equipment, components, tools, and materials needed for the repairs were available and

accessible on site.

b. Findings

No findings were identified.

.10

Compensatory Measures

a. Inspection Scope

The team verified that compensatory measures were implemented for out-of-service,

degraded, or inoperable fire protection and post-fire safe shutdown equipment, systems,

or features (e.g., detection and suppression systems and equipment; passive fire

barriers; or pumps, valves, or electrical devices providing safe shutdown functions). The

team also verified that the short-term compensatory measures compensated for the

degraded function or feature until appropriate corrective action could be taken and that

the licensee was effective in returning the equipment to service in a reasonable period of

time.

b. Findings

Introduction. The team identified a Green non-cited violation of License

Conditions 2.C(4) for Unit 1 and 2.C(5) for Unit 2, Fire Protection Program, due to the

licensees failure to establish or adequately implement compensatory measures for non-

compliances with the licensees approved fire protection program. These non-

compliances were identified during the licensees ongoing transition to a new fire

- 22 -

Enclosure

protection program in compliance with National Fire Protection Association

Standard 805, Performance-Based Standard for Fire Protection for Light Water Reactor

Electric Generating Plants, (NFPA 805).

Description. The licensee is transitioning to a new fire protection program in compliance

with NFPA 805 as allowed by 10 CFR 50.48(c). Corrective actions for non-compliances

with the licensees current approved fire protection program identified during the

licensees transition process may be deferred until implementation of the new NFPA 805

fire protection program. To ensure that adequate safety is maintained, the licensee must

establish compensatory measures within a reasonable time commensurate with the risk

significance of the issue following identification. Appropriate compensatory measures

could be those specified in the plants Equipment Control Guidelines for fire protection or

alternate compensatory measures developed for the specific issue.

The team requested the licensee provide a list of non-compliances identified during the

ongoing transition process and the compensatory measures established. Issues were

identified where compensatory measures either had not been established or the

implementation of the compensatory measures was inadequate. The licensee reported

the current unanalyzed condition to the NRC in an event notification (Event

Number 48395). The non-compliances identified by the NFPA transition process

included errors in the post-fire safe shutdown analysis and inadequate implementing

procedures including operator guidance on dealing with the potential effects of fire

damage and multiple spurious operations scenarios not addressed in the approved fire

protection program. Should a fire have occurred in an area with missing or inadequate

compensatory measures, operators might not have had adequate procedural guidance

to deal with the effects of fire damage and their ability to achieve safe shutdown could

have been challenged.

In September 2008, the NFPA 805 transition project identified four fire areas in Unit 1

and five fire areas in Unit 2 where circuits for redundant HVAC fans for electrical rooms

could be damaged. No compensatory measures were established. This issue was

identified during the licensees preparation for the current inspection and hourly fire

patrol was established as a compensatory measure in accordance with Equipment

Control Guideline 18.7 on October 8, 2012. The licensees current fire protection

program identified the potential loss of normal ventilation to these rooms for other fire

locations and has both procedures and equipment available to use portable fans to

provide cooling to assure the continued operation of the required electrical equipment.

In January 2008, the NFPA 805 transition project identified two fire areas in each unit

containing both power cables to motor-operated valves 8701 and 8702 for the respective

unit. Valves 8701 and 8702 are in series in the piping between the reactor coolant

system and the residual heat removal system. During normal operation, these valves

isolate the low pressure piping from the coolant system, operating at high pressure.

Since these are high/low pressure interface valves the potential for 3-phase hot shorts

causing spurious operation of the valves must be considered in the fire safe shutdown

analysis. Administrative controls maintain the breakers for each valve open during

normal operation which prevents the possibility of fire damage to control circuits causing

a valve to spuriously open. An open breaker does not address potential spurious

- 23 -

Enclosure

operation due to a 3-phase hot short on a power cable between the breaker and the

valve motor.

Analysis. The failure to establish or maintain appropriate compensatory measures for

identified deficiencies in the approved fire protection program was a performance

deficiency. The performance deficiency was more than minor because it was associated

with the protection against external events (fire) attribute of the Mitigating Systems

Cornerstone and it adversely affected the cornerstone objective of ensuring the

availability, reliability, and capability of systems that respond to initiating events to

prevent undesirable consequences. The performance deficiency affected the fire

protection defense-in depth strategies involving post-fire safe shutdown systems. The

team evaluated this deficiency using Inspection Manual Chapter 0609, Appendix F, Fire

Protection Significance Determination Process. However, the Assumptions and

Limitations section of Appendix F states, The SDP approach is intended to support the

assessment of known issues only in the context of an individual fire area. A systematic

plant-wide search and assessment effort is beyond the intended scope of the fire

protection SDP. Therefore, a senior reactor analyst evaluated the significance of this

performance deficiency.

Failure to Compensate for Ventilation System Failure

A fire in Fire Areas 3BB-100, 3BB-115, 5A1, 5A3, 3CC-100, 3CC-115, 5B1, 5B3,

and 6B5 containing cables associated with the redundant 480 V switchgear, dc panels,

and battery chargers could result in loss of ventilation systems for the affected rooms

which could require non-proceduralized use of portable fans to maintain adequate

cooling of the electrical equipment necessary to perform the Appendix R safe shutdown

function.

A fire that results in the loss of switchgear room ventilation would cause a loss of all ac

and dc power if operators did not take action to recover cooling. The analyst determined

that the licensed operators would have at least two clear annunciators indicating that

ventilation had been lost and that room temperatures were increasing. Additionally,

Procedure CP-M10, Fire Protection of Safe Shutdown Equipment, was available to

assist in providing portable fan cooling to the rooms. Using the SPAR-H method, the

analyst approximated the failure of operators to provide portable cooling to the ac

switchgear and dc equipment as 6.0 x 10-3. This approximation compares well with the

licensees human error probability of 3.2 x 10-3.

The analyst determined that the fire ignition frequency for all affected areas in Unit 1 (the

higher of the two units) was 5.9 x 10-3/year. Additionally, the analyst applied a hot short

probability of 0.015 for all areas to account for the requirement that the fire cause the

failure of 2 trains. The total bounding risk was then calculated to be 1.0 x 10-7/year

without compensation.

Failure to Administratively Control High/Low Pressure Interface Valves

The licensee determined that a high consequence interfacing system loss of coolant

accident could occur from the spurious opening of residual heat removal system hot leg

suction valves 8701 and 8702.

- 24 -

Enclosure

For a fire to result in an intersystem loss of coolant accident, it would have to cause

a 3-phase hot short on both of two shutdown cooling suction valves. Given that each

valve is on a different electrical train, the analyst determined that the conditional

probabilities of the hot shorts involved would best be modeled as independent. Using

the methods in NUREG 6850, the licensee calculated conditional probabilities for

a 3-phase proper-polarity hot short on ungrounded ac systems using thermoplastic

cables. The bounding high value was 2.25 x 10-4 per occurrence. Therefore, the

conditional probability of two independent hot shorts causing both valves to open would

be 5.1 x 10-8.

Evaluating the core damage probability would likely be much lower because this

probability would be multiplied by the frequency of the fire scenarios and the conditional

core damage probability of the event.

Summary

Accounting for the risk associated with all issues evaluated, the analyst estimated the

change in core damage frequency to be 1.5 x 10-7 per unit. Therefore, the performance

deficiency was considered to be of very low safety significance (Green).

This finding did not have a cross-cutting aspect because it is not indicative of the

licensees present performance.

Enforcement. License Conditions 2.C(4) for Unit 1 and 2.C(5) for Unit 2, Fire Protection

Program, require the licensee to implement and maintain in effect all provisions of the

approved Fire Protection Program as discussed in the Final Safety Analysis Report

Update; in PG&Es December 6, 1984, Appendix R Report; and in the NRC staffs Fire

Protection Evaluation in the Supplements to the Diablo Canyon Safety Evaluation Report

listed for each unit.

Updated Final Safety Analysis Report Appendix 9.5B, DCPP Regulatory Compliance

Summary, Table B-1, Comparison of DCPP to Appendix A of BTP APCSB 9.5-1,

Section C, Quality Assurance Program, Sub-Section 8, Corrective Action, states:

Measures should be established to assure that conditions adverse to fire

protection, such as failures, malfunctions, deficiencies, deviations, defective

components, uncontrolled combustible material, and nonconformance are

promptly identified, reported, and corrected.

The DCPP Compliance to Commitment states, Policies governing corrective measures

relative to fire protection failures, malfunctions, deficiencies, deviations, defective

components, uncontrolled combustible material, and nonconformances are addressed in

administrative procedures.

Contrary to the above, from 2008 through November 8, 2012, the licensee failed to

implement and maintain in effect all provisions of the approved fire protection program.

Specifically, the licensee failed to establish and maintain timely and adequate

compensatory measures for deficiencies identified in the current fire protection program.

- 25 -

Enclosure

Because this finding is of very low safety significance and has been entered into the

corrective action program (Notifications 50521360 and 50521363), this violation is being

treated as a non-cited violation, consistent with Section 2.3.2 of the NRC Enforcement

Policy: NCV 05000275/2012008-02, 05000323/2012008-02; Inadequate Compensatory

Measures for Fire Protection Program Deficiencies.

.11

B.5.b Inspection Activities

a. Inspection Scope

The team reviewed the licensees implementation of guidance and strategies intended to

maintain or restore core, containment, and spent fuel pool cooling capabilities under the

circumstances associated with loss of large areas of the plant due to explosions or fire

as required by Section B.5.b of the Interim Compensatory Measures Order, EA-02-026,

dated February 25, 2002 and 10 CFR 50.54(hh)(2).

The team reviewed licensees strategies to verify that they continued to maintain and

implement procedures, maintain and test equipment necessary to properly implement

the strategies, and ensure station personnel are knowledgeable and capable of

implementing the procedures. The team performed a visual inspection of portable

equipment used to implement the strategy to ensure the availability and material

readiness of the equipment, including the adequacy of the fire engines used to

implement the strategies. The team also verified the availability of on-site fuel trucks

required to refuel the fire engine. The team performed a sample inspection of the B.5.b

equipment storage locker and visually inspected a penetration used to implement the

mitigation strategy. The strategy and procedure selected for this inspection sample was

Containment Flooding with Portable Pump; EDMG EDG-10, Containment Flooding with

Portable Pump, Revision 0.

b. Findings

No findings were identified.

4.

OTHER ACTIVITIES [OA]

4OA2 Identification and Resolution of Problems

Corrective Actions for Fire Protection Deficiencies

a. Inspection Scope

The team selected a sample of notifications associated with the licensee's fire protection

program to verify that the licensee had an appropriate threshold for identifying

deficiencies. In addition the team reviewed the corrective actions proposed and

implemented to verify that they were effective in correcting identified deficiencies. The

team also evaluated the quality of recent engineering evaluations through a review of

notifications, calculations, and other documents during the inspection.

- 26 -

Enclosure

b. Findings

An example of a problem with establishing and maintaining timely and adequate

compensatory measures for deficiencies identified in the current fire protection program

through the corrective action program is discussed in Section 1R05.10(b).

4OA6 Meetings, Including Exit

Exit Meeting Summary

The team presented the inspection results to Mr. E. Halpin, Senior Vice President and

Chief Nuclear Officer, and other members of the licensee staff at an debrief meeting

on November 8, 2012. The licensee acknowledged the findings presented.

Following additional in-office review and determination of the safety significance of the

findings, an exit meeting was conducted on December 20, 2012, with Mr. E. Halpin,

Senior Vice President and Chief Nuclear Officer, and other members of the licensee

staff.

The team asked the licensee whether any of the material examined during the inspection

should be considered proprietary. No proprietary information was identified.

4OA7 Licensee-Identified Violations

None.

ATTACHMENT: SUPPLEMENTAL INFORMATION

- 1 -

Attachment

SUPPLEMENTAL INFORMATION

KEY POINTS OF CONTACT

Licensee Personnel

B. Allan, Site Vice President

A. Arsene, Engineer, Fire Protection

S. Baker, Manager, Design Engineering

T. Baldwin, Manager, Regulatory Services

R. Baradaran, Supervisor, Probabilistic Risk Assessment

A. Bates, Director, Engineering Services

P. Bemis, Strategic Projects

A. Chitwood, Operations Shift Manager

J. Cook, Engineer, Electrical Design

K. Cormany, Engineer, ICE

T. Cuddy, Senior Manager, Communications

F. DePeralta, Consultant

R. Dyer, Engineer, Project Engineering

S. Ellis, Fire Training Coordinator

J. Fields, Auditor, Quality Verification

J. Fledderman, Director, Strategic Projects

L. Fusco, Engineer, NFPA 805

P. Gerfen, Manager, Operations

W.Giffrow, Supervisor, Operations Services

J. Gregerson, Technical Manager, NFPA 805

E. Halpin, Senior Vice President and Chief Nuclear Officer

D. Hampshire, Supervisor, Fire Protection Engineering

C. Harbor, Director, Compliance and Risk

C. Harrison, Engineer

B. Hinds, Manager, Operations Planning

J. Hinds, Director, Quality Verification

K. Hiwrichsen, Programs Supervisor, Radiological Protection

L. Hopsm, Assistant Director, Maintenance Services

T. Jaurez, Engineer, Balance of Plant Systems

K. Johnston, Manager, Operations Performance

R. Justice, Fire Chief

T. King, Director, Work Management

S. Kirvsen, Manager, Security

W. Landreth, Engineer, Regulatory Services

G. Lautt, Supervisor, Quality Verification

R. Leatham, Electrical Engineer

J. MacIntyre, Director, Maintenance Services

M. McCoy, Engineer, Regulatory Services

C. Murry, Director, Safety

J. Nimick, Director, Operations Services

L. Padovan, Supervisor, Regulatory Services

T. Poindexter, Consultant

- 2 -

Attachment

M. Richardson, Senior Engineer, Regulatory Services

S. Queen, Engineer, Electrical Design Engineering

L. Radle, Engineer, Contractor

J. Schmidf, Auditor, Quality Verification

M. Sheppard, Engineer, Probabilistic Risk Assessment

P.Soenen, Supervisor, Regulatory Services

T. Stanton, Engineer, NFPA 805

M. Stephens, Auditor, Quality Verification

J. Summy, Senior Director, Engineering and Technical Services

L. Walter, Station Director

J. Welsch, Senior Station Director

D. Wilcox, Licensing Basis Verification Project

M. Winsor, Manager, Project Engineering

B. Wong, Contractor

M. Wright, Manager, Mechanical Systems

T. Wright, Auditor, Quality Verification

NRC personnel

L. Micewski, Resident Inspector

L. Willoughby, Senior Project Engineer

LIST OF ITEMS OPENED, CLOSED, AND DISCUSSED

Opened

None

Opened and Closed 05000275/2012008-01

05000323/2012008-01

NCV

Failure to Maintain Required Firewater System

Configuration (Section 1R05.03.b)05000275/2012008-02

05000323/2012008-02

NCV

Inadequate Compensatory Measures for Fire

Protection Program Deficiencies (Section 1R05.10.b)

Closed

None

- 3 -

Attachment

LIST OF DOCUMENTS REVIEWED

CABLE ROUTING DATA

Component

Component

Component

Component

Component

RP086A

RP093A

RP100A

F40P00

G46P00

H33P00

ABAN025

H23P00A

H37P00A

H65P01

G44P00

G68P00

G69P00

G70P00

RP086

RP093

RP100

PCV45

PCV455C

PCV474

PORV 8000A

PORV 8000B

PORV 8000C

CALCULATIONS

Number

Title

Revision

M-680

High/Low Pressure Interface Component

14

M-680

10 CFR 50 Appendix R Safe Shutdown Equipment

17

M-680

10 CFR 50 Appendix R Safe Shutdown Equipment

18-01

M-912

HVAC Interactions for Safe Shutdown, Room Heat-up

Due to Loss of HVAC

5

M-928

10 CFR 50 Appendix R Safe Shutdown Analysis

17

M-928

10 CFR 50 Appendix R Safe Shutdown Analysis

18-01

M-928

10 CFR 50 Appendix R Safe Shutdown Analysis

18-02

M-944

10 CFR 50 Appendix R Alternate Shutdown

Methodology - Time and Manpower Study/Safe

Shutdown System Considerations

7

M-997, Appendix

2.16

Qualification of Penetration Seal Typical F-1L, A Three

A Hour Rated Six Inch Silicone Foam Seal

10

M-997, Appendix

2.25

Qualification of Penetration Seal Typical FP-5, A Three

A Hour Rated Low Density Silicone Elastomer (LDSE)

Seal

12

M-997, Appendix 2.3

Qualification of Penetration Seal Typical F-3, A Three A

Hour Rated Silicone Foam Sea Without Permanent

Ceramic Damming

10

N-089

Fire Protection Study for Pressurizer PORV Stuck

Open

July 29,

1993

STA-207

RETRAN Evaluation of Appendix R Operator Action

Times

1

STA-251

RETRAN Evaluation of Appendix R Scenarios with

RSGs

0

- 4 -

Attachment

134-DC

Circuit Analysis-Electrical Appendix R Analysis

26

335-DC

Emergency Lighting and Communications

8

CONDITION REPORTS

A0642680

A0646729

A0724491

A0627424

A0635344

A0620761

A0646729

50035114

50408579

50409764

500032962

50513006

50514313

50512140

50512128

50511911

50511896

50511882

50511736

50511729

50510511

5059635

50509560

50507834

50507529

50506331

5050594

50358360

50350593

50340288

50340108

50513995

50474308

50286358

50038548

50515422

50515872

505209828*

502022298*

50521043*

50520533*

50520532*

50520531*

50520530*

50520521*

50520512*

50520493*

50520487*

50520485*

50520371*

50520370*

50520333*

50520332*

50520331*

50520330*

50520299*

50520283*

50520282*

50520149*

50520513*

50520144*

50520096*

50520095*

50520092*

50519958*

50519957*

50519857*

50516460*

50516347*

50507988*

50507455*

50507350*

50507230*

50503976*

50520148*

50518956*

50519957*

50519958*

50520092*

50520144*

50520148*

50520299*

50520330*

50520331*

50520332*

50520333*

50520929*

50520962*

50521394*

50522131*

50522141*

50522145*

50522149*

50522161*

50518721*

50520530*

50520531*

50520532*

50520533*

50521470*

50521471*

50520341*

50522103*

50520531*

50520980*

50520202*

50522666*

50522072*

50522445*

50522478*

50522191*

50522479*

50522273*

50522745*

50521601*

  • Issued as a result of inspection activities.

- 5 -

Attachment

DRAWINGS

Number

Title

Revision

437507, Sheet 1

Schematic Diagram Auxiliary Feed water Motor

Operated Valves

24

437811, Sheet 1

Schematic Diagram of Connections 480 Volt Motor

Control Center IH Units 1R, 2R, & 3R

23

437798

Schematic Diagram of Connections 480 Volt Motor

Control Center IF Units 1R, 2R, & 3R

21

437543, Sheet 1

Single line meter and relay Diagram 480 Volt System

Bus Section H

49

437916, Sheet 1

Single line meter and relay Diagram 480 Volt System

Bus Section 1F

46

437587

Electrical Schematic diagram Reactor Coolant Motor

Operated Valves

20

437916, Sheet 1

Electrical Single line meter and relay Diagram 480 Volt

System Bus Section 1F

46

437542, Sheet 1

Electrical Single line meter and relay Diagram 480 Volt

System Bus Section 1G

53

437895, Sheet 1

Electrical Single line Diagram Main Control Board 1VB1

and 1BV2 Fuse Panel

49

437519, Sheet 1

Electrical Single line Diagram 12/4.16KV system

24

437526

Electrical System Phasing Diagram

13

437529, Sheet 1

Electrical Single line Meter & Relay Diagram

Generation Excitation Main and Auxiliary Transformers

41

437533, Sheet 1

Electrical Single line Diagram Single line meter & Relay

Diagram 4160 Volt System

40

437531, Sheet 1

Single line Meter & Relay Diagram 12KV System

27

437532, Sheet 1

Single line Meter & Relay Diagram 4160 Volt System

28

050003, Sheet 1

Description of Electrical Schematic Diagrams, Symbol,

Circuit designations and Related Notes for Diagram of

Connections

7

050003, Sheet 2

Description of Electrical Schematic Diagrams, Symbol,

Circuit designations and Related Notes for Diagram of

Connections

6

050003, Sheet 3

Description of Electrical Schematic Diagrams, Symbol,

Circuit designations and Related Notes for Diagram of

Connections

6

050003, Sheet 4

Description of Electrical Schematic Diagrams, Symbol,

Circuit designations and Related Notes for Diagram of

Connections

6

050003, Sheet 5

Description of Electrical Schematic Diagrams, Symbol,

Circuit designations and Related Notes for Diagram of

Connections

6

- 6 -

Attachment

050003, Sheet 6

Description of Electrical Schematic Diagrams, Symbol,

Circuit designations and Related Notes for Diagram of

Connections

6

050003, Sheet 7

Description of Electrical Schematic Diagrams, Symbol,

Circuit designations and Related Notes for Diagram of

Connections

6

050003, Sheet 8

Description of Electrical Schematic Diagrams, Symbol,

Circuit designations and Related Notes for Diagram of

Connections

6

050003, Sheet 9

Description of Electrical Schematic Diagrams, Symbol,

Circuit designations and Related Notes for Diagram of

Connections

6

050003, Sheet 10

Description of Electrical Schematic Diagrams, Symbol,

Circuit designations and Related Notes for Diagram of

Connections

7

050003, Sheet 11

Description of Electrical Schematic Diagrams, Symbol,

Circuit designations and Related Notes for Diagram of

Connections

7

050003, Sheet 12

Description of Electrical Schematic Diagrams, Symbol,

Circuit designations and Related Notes for Diagram of

Connections

7

102001

Instrument Schematic Legend Systems

18

102030, Sheet 3

Instrument Schematic Legend Systems

21

102030, Sh 3A

Instrument Schematic Legend Systems

29

102030, Sheet 3B

Instrument Schematic Legend Systems

16

102030, Sheet 4

Instrument Schematic Legend Systems

26

102030, Sheet 5

Instrument Schematic Legend Systems

26

445650

Separation & Color Code Instrument & Control

Engineered Safety Features

7

445651

Separation & Color Code Instrument & Control

Engineered Safety Features

10

102008, Sheet 4

Chemical & Volume Control System

114

102008, Sheet 4D

Chemical & Volume Control System

128

102931, Sheet 6B

Radiation Instrument System

72

102036, Sheet 7F

Multivariable Instrument Systems

107

109807, Sheet 31

Functional Loop Diagram

19

109807, Sheet 72

Functional Loop Diagram

20

109807, Sheet 85

Functional Loop Diagram

9

- 7 -

Attachment

109807, Sheet 92

Functional Loop Diagram

19

109807, Sheet 4a

Functional Loop Diagram

2

109807, Sheet 23

Functional Loop Diagram

25

109807, Sheet 5a

Functional Loop Diagram

1

109807, Sheet 21

Functional Loop Diagram

25

109807, Sheet 71

Functional Loop Diagram

19

109807, Sheet 73

Functional Loop Diagram

21

109807, Sheet 74

Functional Loop Diagram

13

109807, Sheet 75

Functional Loop Diagram

19

109807, Sheet 89

Functional Loop Diagram

19

102008, Sheet 4

Chemical Volume Control System

114

102008, Sheet 4D

Chemical Volume Control System

128

109808, Sheet 3

Functional Loop Diagram

2

102032, Sheet 26

Flow Instrument Systems

152

102032, Sheet 26J

Flow Instrument Systems

112

102036, Sheet 7

Multivariable Instrument Systems

98

102036, Sheet 7B

Multivariable Instrument Systems

98

102036, Sheet 7H

Multivariable Instrument Systems

98

102036, Sheet 7I

Multivariable Instrument Systems

98

102034, Sheet 7C

Multivariable Instrument Systems

2

102035, Sheet 6F

Multivariable Instrument Systems

94

102034, Sheet 7D

Multivariable Instrument Systems

1

102035, Sheet 6E

Multivariable Instrument Systems

94

102036, Sheet 7A

Multivariable Instrument Systems

98

102036, Sheet 7B

Multivariable Instrument Systems

98

437579, Sheet 1

Electrical Schematic diagram 4KV Diesel Generator

Control No. 11 & 12

42

437580, Sheet 1

Electrical Schematic diagram 4KV Diesel Generator

Control No. 11 & 12 Valves

39

- 8 -

Attachment

437587

Electrical Schematic Diagram Reactor Coolant Motor

Operated Valves

20

437683, Sheet 1

Electrical Schematic Diagram Chemical & Volume

Control System

23

437682, Sheet 1

Electrical Schematic Diagram Chemical & Volume

Control System

23

441312, Sheet 1

Schematic Diagram, Charging Pumps No 21 & 22

26

050016, Sheet 1

Raceway and Wire Color separation Charts

7

050016, Sheet 2

Raceway and Wire Color separation Charts

7

050016, Sheet 3

Raceway and Wire Color separation Charts

7

437533, Sheet 1

Single Line Diagram Single line meter and Relay

Diagram 4160 Volt System

40

437738, Sheet 1

Electrical Wiring Diagram 4160 Volt Switchgear Bus

Sect. G Cell 5 to 9

8

448580

Electrical Diagram of Connections 4160 Volt Switchgear

Bus Sect. G Cell 6

15

437594, Sheet 1

Electrical Schematic diagram Auxiliary Salt Water Pump

30

57601

Cable Tray & Conduit Layout Below elevation 115-0

Area H

46

57606

Cable Tray & Conduit Layout Section E-E and F - F

Area H

32

437595, Sheet 1

Electrical Schematic diagram Charging Pumps No 11 &

12

33

437513

Diagram of Connection, Hot Shutdown Control Panel

24

437667, Sheet 1

Electrical Schematic Diagram 4KV Diesel Generator

Control No. 13,

45

4007993, Sheet 1

Diagram of Connections Diesel Generator 11 DC

Control Power Transfer switch

2

4007994, Sheet 1

Diagram of Connections Diesel Generator 12 DC

Control Power Transfer switch

2

4007995, Sheet 1

Diagram of Connections Diesel Generator 13 DC

Control Power Transfer switch

2

102007, Sheet 6

Piping Schematic Diagram Reactor Coolant System

68

102008, Sheet 4D

Piping Schematic Diagram, Chemical and Volume

Control

128

102008, Sheet 4

Piping Schematic Diagram, Chemical and Volume

Control

114

102017, Sheet 1

Piping Schematic Salt Water System

89

102017, Sheet 3B

Piping Schematic Diagram, Salt Water System

128

106725, Sheet 26

Compressed Air System

172

- 9 -

Attachment

111906, Sheet 17

Fire Protection Auxiliary Building Elevation 85

7

111906, Sheet 19

Fire Protection Auxiliary Building Elevation 100

4

111906, Sheet 21

Fire Protection Auxiliary Building Elevation 115*

5

111906, Sheet 25

Fire Protection Auxiliary Building Elevations 128, 154

and 164

3

693299, Sheet 8

Mechanical Fire Protection North Auxiliary Building

Elevation 100 Area GE/GW Penetration Area

8

693299, Sheet 9

Mechanical Fire Protection North Auxiliary Building

Elevation 115 Area GE/GW Penetration Area

3

ENGINEERING INFORMATION RECORDS

Number

Title

Revision

TE-PG&E-113-R001

Multiple Spurious Operation Report dated Nov. 3, 2010

0

MODIFICATIONS

Number

Title

Revision

DCP A-049070

Thermo-Lag Removal/Install 3M Fireproofing

0

PROCEDURES

Number

Title

Revision

AR PK01-08

Annunciator Response CCW Header C

19

AR PK05-01

Annunciator Response RCP Number 11

33

AR PK05-04

Annunciator Response RCP Number 14

31

AWP E-002

10 CFR 50 Appendix R Safe Shutdown Analysis

1A

AWP E-009

Combustible Design Control

1

CP M-6

Fire

33A

CP M-10

Fire Protection of Safe Shutdown Equipment - Unit 1

24

CP M-10

Fire Protection of Safe Shutdown Equipment - Unit 1

25

CP M-10

Fire Protection of Safe Shutdown Equipment - Unit 1

26

CP M-10

Fire Protection of Safe Shutdown Equipment - Unit 2

25

CP M-10

Fire Protection of Safe Shutdown Equipment - Unit 2

26

- 10 -

Attachment

CP M-10

Fire Protection of Safe Shutdown Equipment - Unit 2

27

DCM No. T-18

Electrical System Protection

13

DCM No. T-19

Electrical Separation and Isolation

11

DCM No. T-22

Electrical Cable and Raceway

10D

EDMG EDG-6

Makeup to Condensate Storage Tank

1

EDMG EDG-7

Manually Depressurize the SGs to Minimize RCS

Inventory Loss

1

EDMG EDG-9

Use of Fire Engine to Supply Water to Steam

Generators

0

EDMG EDG-10

Containment Flooding with Portable Pump

0

EDMG EDG-14

EDMG Equipment Annual Inventory

2

MP E-50.30B

Electrical Maintenance Procedure Maintenance Agastat

Type ETR Timing Relay maintenance

19

MP E-50.34

Electrical Maintenance Procedure Maintenance

Strutter-Dunn Ground Sensor Relay Maintenance

11

MP E-50.55

Electrical Maintenance Procedure Maintenance Basler

Type BE1-50/51 Over current Relay Maintenance

14

MP E-57.10B

Electrical Maintenance Procedure Maintenance Generic

115VAC and 480 VAC Motor Preventive Maintenance

16

MP E-57.11A

Preparation for Working on Potentially Energized Load

Centers and Transformers

14

MP E-57.11B

Protective Grounding

30

MP E-60.10

Electrical Maintenance Procedure Maintenance Generic

Relay Functional Test

16

MP E-63.3C

Electrical Maintenance Procedure Maintenance of 4

and 12 KV Switchgear

24

MP E-67.5A

Testing and Maintenance of Battery Operated Lights

Inside Power Block

32

OM8

Fire Protection Program

3

OM8.ID1

Fire Loss Prevention

23

OM8.ID2

Fire System Impairment

17

OM8.ID4

Control of Flammable and Combustible Materials

19

OM8.ID5

Fire Protection Program Administration

0

OP AP-8A

Control Room Inaccessibility - Establishing Hot

Standby

31 & 32

OP AP-8B

Control Room Inaccessibility - Establishing Hot

Standby to Cold Shutdown

23

OP AP-28

Reactor Coolant Pump Malfunction

12

- 11 -

Attachment

OP AP-31

Rapid Containment Entry

5

OP B-1A:III

CVCS - Establishing a Hydrogen Blanket on the VCT

14

OP B-1A:X

CVCS - VCT Degassing

31

OP C-2:II

Main Steam and Steam Dump Systems - Local

Operation of Steam Dumps

11

STP I-29

Emergency Signals and Communication Systems

Functional Test

41

STP I-34A

Fire Detection System Detector Functional Panel A

24

STP I-34C

Fire Detection System Supervisory Functional

11

STP I-34H

Fire Detection System RTD Calibration Check

3

STP M-5

Surveillance Test of the Fuel Handling Building

Ventilation System

30

STP M-13A

Manual and Auto Transfer of 4KV Vital Buses Off-Site

Power Source

13

STP M-13F

4KV Bus F Non-SI Auto Transfer Test

47

STP M-16Q3FG

Functional Testing of Buses F and G Auto transfer to

Startup Power

2

STP M-17C3

Check of the Emergency AC Lighting System

17A

STP M-31A

Continuity Testing of Remote Shutdown Control

Transferfr Switches (4KV Pumps)

1

STP M-39B

Routine Surveillance Test of Cable Spreading Room

Carbon Dioxide Fire System Operation

27

STP M-51

Routine Surveillance Test of Containment Fan Cooler

31

STP M-67A

Fire Valve Inspection

49

STP M-70D

Inspection of Fire Barriers, Rated Enclosures, Credited

Cable Tray Fire Stops, and Equipment Hatches

13

STP M-71

Firewater System Flow Test

9

STP M-74

Auto Start of ASW Pumps on Low pressure

8

STP P-FPP-A01

Fire Pump 0-1 Performance Test

3

STP P-FPP-A02

Fire Pump 0-2 Performance Test

5

STP P-FPP-B01

Fire Pump 0-1 Routine Surveillance

12

STP P-FPP-B02

Fire Pump 0-2 Routine Surveillance

12

STY V-2Y

Surveillance Test Procedure, Regenerative Heat

Exchanger Letdown Inlet and Letdown Outlet Orifice

Isolation Valves

19

- 12 -

Attachment

VENDOR DOCUMENTS

Number

Title

Revision

RPE E-6653

Vendor Manual - Eaton Cutler Hammer Industrial

Related AC/DC Toggle Switch

2

663336

Vendor Diagram-Westinghouse Motor Control Center IF

IG & IH Control Center Drawings

8

01914963-WD-04

Nuclear Logistics Inc, Wiring Diagram for 18 NEME

Size 3 FVNR Cubicle 52-1F-05

2

01914963-WD-05

Nuclear Logistics Inc, Wiring Diagram for 36 NEME

Size 4 FVNR Cubicle 52-1F-66

2

01914963-WD-06

Nuclear Logistics Inc, Wiring Diagram for 18 NEME

Size 2 two SPD cubicle 52-1F-50

2

01914963-WD-07

Nuclear Logistics Inc, Wiring Diagram for 12 NEME

Size 3 FVNR Cubicle 52-1F-38

2

01914963-WD-08

Nuclear Logistics Inc, Wiring Diagram for 12 NEME

Size 2 FVNR Cubicle 52-1F-39

2

WORK ORDERS

64031002

64019502

64066957

64080891

64051343

64020120

64087588

64039494

64021407

64079883

64079086

64083409

R0232602

6009159

C0130254

R0192538

64009147

64008771

64082180

64006554

MISCELLANEOUS DOCUMENTS

Number

Title

Revision

ANSUL Technical

Bulletin Number 54

Shelf Life of ANSULITE AFFF Concentrates and Their

Premixed Solutions

N/A

A-8

Systems Training Guide, Remote/Hot Shutdown Panels

8

E-6

Systems Training Guide, Salt Water System

14

ECG 18.1

Equipment Control Guideline - Fire Suppression

Systems/Fire Suppression Water Systems

9

ECG 18.2

Equipment Control Guideline - Fire Hose Stations

9

ECG 18.3

Equipment Control Guideline - Fire Detection

Instrumentation

10

ECG 18.4

Equipment Control Guideline - Spray and/or Sprinkler

Systems

6

ECG 18.5

Equipment Control Guideline - CO2 System

9

- 13 -

Attachment

ECG 18.7

Equipment Control Guideline - Fire Rated Assemblies

9

FHARE 110

Separation of Redundant ASW Pump and Exhaust Fan

Circuits in the Intake Structure

1

FHARE 150

Administrative Control Requirements for Fire Rated

Assemblies

1

FHARE 152

Evaluation of Fire Dampers in 480V Switchgear and

Battery Rooms

0

FSAR Section 9.5.1

Fire Protection System

20

IN 92-18

Information Notice "Potential For Loss of Remote

Shutdown Capability During a Control Room Fire,"

February

28, 1992

Letter PGE-92-621

Diablo Canyon Appendix R Charging Pump Evaluation

July 14,

1992

Memo

Appendix R Transient Analysis for Stuck Open

Pressurizer PORV

August 11,

1993

NFPA Standard 805

Performance-Based Standard for Fire Protection for

Light Water Reactor Electric Generating Plants

2001

Edition

Operations Crew

Watch Bill

October 15 - 21, 2012

39

Operations Crew

Watch Bill

October 22 - 28, 2012

33

SSER 23

Supplement 23 of Safety Evaluation Report

June 1984

TE-PG&E-113-R001

Multiple Spurious Operations Report

0

T35110

Appendix R Operability of Emergency Lights

0C18 D-16-005

Clearance - Equipment ID: 0-16-M-TK-RWOR1A, Raw

Water Storage Reservoir West 0-1A

September

9, 2012

13698

Maintenance Item 13698 ASP2 Test and Calibrate

Motor

N/A

67997

Set Route Data Raceway Report for Raceway K6958-

61

19

N/A

Diablo Canyon Nuclear Power Plant 450 MHz System

Coverage Report

October 5,

2004

N/A

Time Critical Operator Action Documentation

39