Low, David From:
David Lew Sent:
Sunday, April 19, 2009 11:57 AM To:
Subject:
RE: UPDATE: OC Tritium Issue 4419 Thanks Marc. What does hydrostop involve?
From: Marc Ferdas Sent: Sunday, April 19, 2009 11:52 AM To: Peter Wilson; John White; Ronald Bellamy; Ronald Nimitz Cc: David Lew; Darrell Roberts; Marc Ferdas; James Clifford
Subject:
UPDATE: OC Tritium Issue 4/19 UPDATE As of April 19 @ 11 am Based on Guided Wave testing, OC is focusing on the 6" condensate transfer system to hotwell makeup system pipe. This portion of the piping also supports makeup to the IC by sending condensate transfer to the turbine building and then reactor building. OC also continues to pursue the CST as a possible source and are determining actions to further explore if needed.
See below for latest status of activities by department.
ENGINEERING
- Developing a TMod to jumper around the 6" condensate transfer pipe and not interupt service flow to hotwell or Isolation Condensers (credited makeup source)
OC would then pressure test portion of piping that would be isolated to determine if the source of the leak.
TMod package expected to be completed on Tuesday.
OPERATIONS (b)(5)
- Expected completion Monday.
CHEMISTRY Results of sample from "leaking" coduit in ESW vault shows 1.2M pCi/L.
Working w/ State of NJ to get permits to install 2 new wells near CST.