05000373/LER-2009-001, Regarding Automatic Reactor Scram Due to Failure of Main Power Transformer Surge Arrestor
| ML092020179 | |
| Person / Time | |
|---|---|
| Site: | LaSalle |
| Issue date: | 07/20/2009 |
| From: | Rhoades D Exelon Generation Co, Exelon Nuclear |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| LER 09-001-00 | |
| Download: ML092020179 (5) | |
| Event date: | |
|---|---|
| Report date: | |
| Reporting criterion: | 10 CFR 50.73(a)(2)(iv)(A), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.73(a)(2)(ix)(A) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor 10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat 10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications |
| 3732009001R00 - NRC Website | |
text
Nuclear 10 CFR 50.73 SM Exelon Generation Company, LLC www.exeloncorp.com LaSalle County Station 2601 North 21" Road Marseilles, IL 61341-9757 July 20, 2009 United States Nuclear Regulatory Commission Attention: Document Control Desk Washington, D.C. 20555 LaSalle County Station, Units 1 and 2 Facility Operating License No. NPF 11 and 18 NRC Docket No. 50-373 and 50-374
Subject:
Licensee Event Report In accordance with 10 CFR 50.73 (a)(2)(iv)(A), Exelon Generation Company, (EGC), LLC, is submitting Licensee Event Report Number 09-001-00, Docket No. 050-373.
Should you have any questions concerning this letter, please contact Mr. Terrence W. Simpkin, Regulatory Assurance Manager, at (815) 415-2800.
Respectfully, David P. Rhoades Plant Manager LaSalle County Station
Attachment:
Licensee Event Report cc:
Regional Administrator - NRC Region III NRC Senior Resident Inspector - LaSalle County Station
NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY OMB: NO. 3150-0104 EXPIRES: 08/31/2010 (9-2007)
, the NRC may digits/characters for each block) not conduct or sponsor, and a person is not required to respond to, the information rnllantinn.
- 3. PAGE LaSalle County Station Unit 1 05000373 1
OF 4
- 4. TITLE Automatic Reactor Scram Due to Failure of Main Power Transformer Surge Arrestor
- 5. EVENT DATE
- 6. LER NUMBER
- 7. REPORT DATE
- 8. OTHER FACILITIES INVOLVED FACILITY NAME DOCKET NUMBER MONTH DAY YEAR YEAR SEQUENTIAL NUMBER REV NO NO.
MONTH DAY YEAR LaSalle County Station Unit 2 05000374 FACILITY NAME DOCKET NUMBER 05 21 2009 2009 001 00 1
07 20 2009
- - L
- 9. OPERATING MODE
- 11. THIS REPORT IS SUBMITTED PURSUANT TO THE REQUIREMENTS OF 10 CFR §:
(Check all that apply) q 20.2201(b) q 20.2203(a)(3)(i) q 50.73(a)(2)(i)(C) q 50.73(a)(2)(vii) 1 q 20.2201(d) q 20.2203(a)(3)(ii) q 50.73(a)(2)(ii)(A) q 50.73(a)(2)(viii)(A) q 20.2203(a)(1) q 20.2203(a)(4) q 50.73(a)(2)(ii)(B) q 50.73(a)(2)(vifl)(B) q 20.2203(a)(2)(i) q 50.36(c)(1)(i)(A) q 50.73(a)(2)(iii) q 50.73(a)(2)(ix)(A)
- 10. POWER LEVEL q 20.2203(a)(2)(ii) q 50.36(c)(1)(ii)(A)
Z 50.73(a)(2)(iv)(A) q 50.73(a)(2)(x) q 20.2203(a)(2)(iii) q 50.36(c)(2) q 50.73(a)(2)(v)(A) q 73.71(a)(4) 100 q 20.2203(a)(2)(iv) q 50.46(a)(3)(ii) q 50.73(a)(2)(v)(B) q 73.71(a)(5) q 20.2203(a)(2)(v) q 50.73(a)(2)(i)(A) q 50.73(a)(2)(v)(C) q OTHER q 20.2203(a)(2)(vi) q 50.73(a)(2)(i)(B) q 50.73(a)(2)(v)(D)
Specify in Abstract below or in =
A.
PLANT AND SYSTEM IDENTIFICATION
General E l e c t r i c - Boiling Water Reactor, 3489 Megawatts Thermal Rated Core Power
CONDITION PRIOR TO EVENT
Unit(s): 1 Event Date: 5/21/09 Event Time: 1635 Reactor Mode(s): 1 Power Level(s): 100 Mode(s) Name: Power Operation B.
DESCRIPTION OF EVENT
On May 21, 2009, at 1635 CDT, LaSalle Unit 1 automatically scrammed from 100% power. The scram was due to a generator lockout signal caused by a failure of the surge arrester on the `A' phase of the Unit 1 West Main Power Transformer (1W MPT) (MP)[EL]. Deluge protection of the 1W MPT actuated and no fire resulted from the arc caused by the surge arrester failure.
Following the scram, reactor water level was restored using the Motor Driven Reactor Feed Pump (FW)[SJ], and pressure control was established with the Main Condenser (CD)[SG] via the turbine bypass valves.
The surge arrester failure caused a voltage transient on both LaSalle Units. On Unit 2, the 24B and 25B Low Pressure Feedwater Heaters (HD)[SM] and the 24C Low Pressure Heater Normal Drain tripped, which forced a reduction in reactor power to approximately 85%. The voltage transient also resulted in a number of other non-valid isolation signals, including Reactor Water Cleanup (RT) [CE] and Reactor Building Ventilation (VR)[VA]. The VR system isolated on both Units 1 and 2.
Unit 2 returned to full power on May 22, 2009, at 1100 CDT. Following replacement of the 1W MPT `A' phase surge arrester and verification that the MPT had not been damaged, Unit 1 was restarted on May 23, 2009, and was synchronized to the grid on May 25, 2009. The Unit returned to full power at 1412 CDT on May 27, 2009.
An Emergency Notification System call was made at 1946 CDT on May 21, 2009, in accordance with 10 CFR 50.72(b)(2)(iv)(B) as an event or condition that resulted in actuation of the reactor protection system when the reactor was critical.
C.
CAUSE OF EVENT
A forensic analysis was performed on the failed surge arrester. The analysis determined that the root cause was a manufacturing defect. The glass tape used to hold together the metal oxide blocks inside the arrester was folded and wedged between the metal oxide blocks in two
different areas, which prevented face-to-face contact between the blocks. As a consequence, under normal operating conditions an air gap existed between the blocks, leading to uneven current flow through adjacent blocks. Surges from normal switching operation and lightning strikes in the years following the installation caused punctures near the edge of the affected blocks.
Although all arresters are tested prior to shipping, the defect in this arrester was either not detected by the factory testing or the defective arrester was not discarded upon identification of the defect. It is the opinion of the vendor that this defect should have been identified in production testing. Retrieval of the original Joslyn test reports is no longer possible. The arresters were satisfactorily Doble tested on site prior to installation, but this test was not capable of identifying the defect.
As a result of Doble test results in 2004, the original 1 W MPT 'A' phase surge arrester was replaced, along with the 1 East (1 E) MPT `A' phase surge arrester. The Joslyn Manufacturing Co. (now MacLean Power System) ZSH series (MOV-Metal Oxide Varistor) station class surge arresters were selected to replace the original Westinghouse CPL series silicon carbide gapped surge arresters because they use metal oxide technology, which represented an improved design over the silicon carbide gap type arresters.
These arresters performed without problems until the day of the event. On April 30, 2009, a temperature scan of the Unit 1 transformers was performed and no differential temperatures were noted on either the MOV or silicon carbide arresters. Due to the manufacturer defect, degradation of the arrester would have started with the installation in 2004, but the degradation did not result in significant heat generation due to the low current in the arrester. Therefore, thermography did not identify the defect.
D.
SAFETY ANALYSIS
The safety significance of this event was minimal. All control rods fully inserted and all systems responded as expected to the scram. The Emergency Core Cooling Systems were not challenged. This event did not meet the NEI 99-02 definition of an unplanned scram with complications. There were no safety system functional failures.
E.
CORRECTIVE ACTIONS
Corrective Actions:
The 'A' phase arresters were replaced on both the 1 E and 1W MPT.
The 1E and 1W MPTs were tested to verify that they had not been degraded as a result of the transient.
Corrective Action to Prevent Recurrence:
Procurement requirements will be changed to require that vendor test data be supplied for future station surge arrester purchases. (AT# 923160-15)
F.
PREVIOUS OCCURENCES
LaSalle Station has not previously experienced a failure of a surge arrester.
G.
COMPONENT FAILURE DATA
Joslyn ZSH Metal Oxide Arrester with 264kV RatingPRINTED ON RECYCLED PAPEFI