ML090440528

From kanterella
Jump to navigation Jump to search
Emergency Response Data System Data Point Library Changes
ML090440528
Person / Time
Site: Kewaunee Dominion icon.png
Issue date: 02/13/2009
From: Funderburk C
Dominion Energy Kewaunee, Dominion Resources Services
To:
Document Control Desk, Office of Nuclear Security and Incident Response
References
09-080
Download: ML090440528 (12)


Text

Dominion Resources Services, Inc.

"110l1llominion Boulevard, Glen Allen, VA.','1 lid,

\\\\d, Address: www.dom.com February 13, 2009 U. S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, DC 20555 Serial No.

KPS/UC/NW:

Docket No.

License No.09-080 RO 50-305 DPR-43 DOMINION ENERGY KEWAUNEE, INC.

KEWAUNEE POWER STATION EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY CHANGES Pursuant to 10 CFR 50, Appendix E, Dominion Energy Kewaunee, Inc. (DEK) hereby submits copies of changes to seven Kewaunee Power Station (KPS)

Emergency Response Data System (EROS) data point library tables.

The EROS data point library is maintained in KPS procedure EPMP 9.5, "Control of EROS Hardware and Software."

Changes to seven of the data point library tables have recently been made.

10 CFR 50, Appendix E, Section VI.3 requires that any hardware and software changes that affect the transmitted data points identified in the EROS data point library must be submitted to the NRC within 30 days after the changes are completed.

Therefore, a copy of each of the seven revised EROS data point library tables are provided as an attachment to this letter, as required 10 CFR 50, Appendix E, Section V1.3. provides a summary of the changes to the KPS EROS data point library tables. provides an up to date copy of each of the EROS data point tables which have been changed.

The data point information is provided in a format consistent with guidance specified in NUREG-1394, "Emergency Response Data System Implementation" Revision 1.

Each change has been annotated with a vertical line in the margin adjacent to the change.

If you have questions or require additional information, please feel free to contact Mr. Craig Sly at (804)-273-2784.

Very truly yours, Chris Funderburk - Director Nuclear Licensing &Operations Support Dominion Resources Services, Inc.

For Dominion Energy Kewaunee

Serial No 09-080 ERDS Data Point Changes Page 2 of 2 Attachments:

1. Summary of Kewaunee ERDS Data Point Library Changes 2.

Kewaunee Revised ERDS Data Point Library Tables Commitments made by this letter: None cc:

Regional Administrator, Region III U. S. Nuclear Regulatory Commission 2443 Warrenville Road Suite 210 Lisle, IL 60532-4352 Mr. P. S. Tam Sr. Project Manager U.S. Nuclear Regulatory Commission One White Flint North, Mail Stop 08-H4A 11555 Rockville Pike Rockville, MD 20852-2738 NRC Senior Resident Inspector Kewaunee Power Station

ATTACHMENT 1 EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY CHANGES

SUMMARY

OF KEWAUNEE EROS DATA POINT LIBRARY CHANGES KEWAUNEE POWER STATION DOMINION ENERGY KEWAUNEE, INC.

Serial No.09-080 Page 1 of 1

SUMMARY

OF KEWAUNEE EROS DATA POINT LIBRARY CHANGES TABLE NUMBER CHANGE DESCRIPTION Table 7 - Reactor Coolant Flow Loop A Updated the DATE to 1/23/09.

Updated the UNIQUE SYS DESC:

Table 8 - Reactor Coolant Flow Loop S Updated the DATE to 1/23/09.

Updated the UNIQUE SYS DESC:

Table 23 - Primary System Charging Updated the DATE to 1/28/09.

Flow Updated the UNIQUE SYS DESC:

Table 29 - Radioactivity of Released Updated the DATE to 1/14/09.

Gasses Updated the UNIQUE SYS DESC:

Table 30 - Radioactivity of Released Updated the DATE to 1/14/09.

Liquids Updated the ALARMITRIP SET PT:

Table 31 - Condenser Air Ejector Updated the DATE to 1/14/09.

Radioactivity Updated the ALARMITRP SET PT:

Updated the UNIQUE SYS DESC:

Table 36 - Steam Generator Slowdown Updated the DATE to 1/14/09..

Radiation Level Updated the ALARMITRIP SET PT:

ATTACHMENT 2 EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY CHANGES KEWAUNEE REVISED ERDS DATA POINT LIBRARY TABLES KEWAUNEE POWER STATION DOMINION ENERGY KEWAUNEE, INC.

REACTOR COOLANT FLOW LOOP A KEWAUNEE POWER STATION ITEM FIELD KPS ERDS DATA LENGTH DATE:

(8) 01/23/09 REACTOR UNIT:

(3)

KWI DATA FEEDER:

(10)

N/A NRC ERDS PARAM:

(12)

CORE FLOW POINTID:

(12)

F8007G PLANT SPEC PT DESC:

(40)

RCLA AVERAGE FLOW (LOOP A)

GENERIC/COND DESC:

(32)

REACTOR COOLANT FLOW LOOP A ANALOGIDIGITAL:

(1)

A (A, D)

ENGR UNITS/DIG ST:

(12)

PCT ENGR UNITS CONYERS:

(40)

N/A MIN INSTR RANGE:

(10) 0 MAX INSTR RANGE:

(10) 110 ZERO PTREF:

(6)

N/A REF PT NOTES:

(40)

N/A PROC OR SENS:

(1)

P (P, S)

NUMBER OF SENSORS:

(3) 3 HOW PROCESSED:

(40)

AVERAGE SENSOR LOCATIONS:

(40)

CONTAINMENT ALARM/TRIP SET PT:

(40) 90% REACTOR TRIP NI DET PWR SUPPLY (15)

N/A CUTOFF PWR LVL:

NI DET PWR SUPPLY (15)

N/A TURN ON PWR LVL:

INSTR FAIL MODE:

(30)

LOW TEMP COMP FOR DP (3)

N (Y, N, N/A)

XMTRS:

LEVEL REF LEG:

(3)

N/A (DRY, WET)

UNIQUE SYS DESC:

(600)

INSTRUMENTS:

AVERAGE OF AT LEAST TWO OF FT-41 L FT-412. FT-413 ACTUAL STEADY STATE 100% FLOW CHANGES SLIGHTLY EACH FUEL CYCLE BASED ON CORE AND SG CONFIGURATION. POST-REFUELING POWER ESCALAnON TESTING VERIFIES THAT TOTAL FLOW IS ;:: THE TS MINIMUM OF 178.000 GPM AVERAGE (MINIMUM 89,000 GPM AVERAGE/LOOP) AND;:: THE LIMIT SPECIFIED IN THE COLR.

Table 7 EPMP-09.05 Rev. 3 Date: FEB 5 2009 REFERENCE USE Page 11 of 48

REACTOR COOLANT FLOW LOOP B KEWAUNEE POWER STATION ITEM FIELD KPS ERDS DATA LENGTH DATE:

(8) 01/23/09 REACTOR UNIT:

(3 )

KWI DATA FEEDER:

(10)

N/A NRC ERDS PARAM:

(12)

CORE FLOW POINT ID:

(12)

F8008G PLANT SPEC PT DESC:

(40)

RCLB AVERAGE FLOW (LOOP B)

GENERIC/COND DESC:

(32)

REACTOR COOLANT FLOW LOOP B ANALOG/DIGITAL:

(1)

A (A, D)

ENGR UNITS/DIG ST:

(12)

PCT ENGR UNITS CONYERS:

(40)

N/A MIN INSTR RANGE:

(10) 0 MAX INSTR RANGE:

(10) 110 ZERO PTREF:

(6)

N/A REF PT NOTES:

(40)

N/A PROC OR SENS:

(I)

P (P, S)

NUMBER OF SENSORS:

(3) 3 HOW PROCESSED:

(40)

AVERAGE SENSOR LOCATIONS:

(40)

CONTAINMENT ALARMITRIP SET PT:

(40) 90% REACTOR TRIP NI DET PWR SUPPLY (15)

N/A CUTOFF PWR LVL:

NI DET PWR SUPPLY (15)

N/A TURN ON PWR LVL:

INSTR FAIL MODE:

(30)

LOW TEMP COMP FOR DP (3)

N (Y, N, N/A)

XMTRS:

LEVEL REF LEG:

(3)

N/A (DRY, WET)

UNIQUE SYS DESC:

(600)

INSTRUMENTS:

AVERAGE OF AT LEAST TWO OF FT-414, FT-415, FT-416 ACTUAL STEADY STATE 100% FLOW CHANGES SLIGHTLY EACH FUEL CYCLE BASED ON CORE AND SG CONFIGURATION. POST-REFUELING POWER ESCALATION TESTING VERIFIES THAT TOTAL FLOW IS ~ THE TS MINIMUM OF 178,000 GPM AVERAGE (MINIMUM 89,000 GPM AVERAGE/LOOP) AND> THE LIMIT SPECIFIED IN THE COLR.

Table 8 EPMP-09.05 Rev. 3 Date: FEB 5 2009 REFERENCE USE Page 12 of 48

PRIMARY SYSTEM CHARGING FLOW KEWAUNEE POWER STATION ITEM FIELD KPS ERDS DATA LENGTH DATE:

(8) 01128/09 REACTOR UNIT:

(3)

KWI DATA FEEDER:

(10)

N/A NRC ERDS PARAM:

(12)

RCS CHGIMU POINT 10:

(12)

FOl28G PLANT SPEC PT DESC:

(40)

CHG PUMP DISCH HDR FLOW GENERIC/COND DESC:

(32)

PRIMARY SYSTEM CHARGING FLOW ANALOGIDIGITAL:

(I)

A (A, D)

ENGR UNITS/DIG ST:

(12)

GPM ENGR UNITS CONYERS:

(40)

N/A MIN INSTR RANGE:

(10) 0 MAX INSTR RANGE:

(10) 110 ZERO PT REF:

(6)

N/A REF PT NOTES:

(40)

N/A PROC OR SENS:

(I)

S (P, S)

NUMBER OF SENSORS:

(3 )

I HOW PROCESSED:

(40)

N/A SENSOR LOCATIONS:

(40)

ON 2" DIAM. HEADER AT PUMPS' DISCHARGE ALARMITRIP SET PT:

(40)

N/A NI DET PWR SUPPLY (IS)

N/A CUTOFF PWR LVL:

NI DET PWR SUPPLY

(\\5)

N/A TURN ON PWR LVL:

INSTR FAIL MODE:

(30)

LOW TEMP COMP FOR DP (3)

N (Y, N, N/A)

XMTRS:

LEVEL REF LEG:

(3)

N/A (DRY, WET)

UNIQUE SYS DESC:

(600)

INSTRUMENT FT-128. THREE CHARGING PUMPS. EACH PUMP HAS A DESING FLOWRATE OF 60.5 GPM (MAX.)

AND DISCHARGE PRESSURE OF 3000 PSIG. PUMPS lA, IB AND IC - AC INDUCTION MOTOR. NORMAL CHARGING FLOW IS 30-40 GPM.

Table 23 EPMP-09.05 Rev. 3 Date: FEB 5 2009 REFERENCE USE Page 27 of 48

RADIOACTIVITY OF RELEASED GASSES KEWAUNEE POWER STATION ITEM FIELD KPS ERDS DATA LENGTH DATE:

(8) 01/14/09 REACTOR UNIT:

(3 )

KWI DATA FEEDER:

(10)

N/A NRC ERDS PARAM:

(12)

EFFGAS RAD POINT ID:

(12)

GOOl4G PLANT SPEC PT DESC:

(40)

AUX BLDG VENT MONITOR GENERIC/COND DESC:

(32)

RADIOACTIVITY OF RELEASED GASSES ANALOGIDIGITAL:

(1)

A (A, D)

ENGR UNITS/DIG ST:

(12)

CPM ENGR UNITS CONVERS:

(40)

N/A MIN INSTR RANGE:

(10) 1.0 E+ I MAX INSTR RANGE:

(10) 1.0 E+7 ZERO PTREF:

(6)

N/A REF PT NOTES:

(40)

N/A PROC OR SENS:

(1 )

S (P, S)

NUMBER OF SENSORS:

(3)

I HOW PROCESSED:

(40)

N/A SENSOR LOCATIONS:

(40)

AUX BLDG VENT STACK ALARM/TRIP SET PT:

(40) 8.0E+4 CPM NI DET PWR SUPPLY (15)

N/A CUTOFF PWR LVL:

NI DET PWR SUPPLY (15)

N/A TURN ON PWR LVL:

INSTR FAIL MODE:

(30)

LOW TEMP COMP FOR DP (3)

N/A (Y, N, N/A)

XMTRS:

LEVEL REF LEG:

(3)

N/A (DRY, WET)

UNIQUE SYS DESC:

(600)

RAD MONITOR R-I4, AUX BLDG VENT MONITOR B, CONSISTS OF A BETA SENSITIVE PLASTIC SCINTILLATION DETECTOR. R-14 PROVIDES AUTOMATIC INITIATION OF THE FOLLOWING ESF FUNCTION: ISOLATE NORMAL VENT EXHAUST AND START AUXILIARY BUILDING ZONE SV (SPECIAL VENTILATION).

Table 29 EPMP-09.05 Rev. 3 Date: FEB 5 2009 REFERENCE USE Page 33 of 48

RADIOACTIVITY OF RELEASED LIQUIDS KEWAUNEE POWER STATION ITEM FIELD KPS ERDS DATA LENGTH DATE:

(8) 01/14/09 REACTOR UNIT:

(3)

KWI DATA FEEDER:

(10)

N/A NRC EROS PARAM:

(12)

EFFLIQRAD POINT ID:

(12)

GOOl8G PLANT SPEC PT DESC:

(40)

WASTE DISP LIQ EFFLUENT GENERIC/COND DESC:

(32)

RADIOACT. OF RELEASED LIQUIDS ANALOG/DIGITAL:

(I)

A (A, D)

ENGR UNITS/DIG ST:

(12)

CPM ENGR UNITS CONVERS:

(40)

N/A MIN INSTR RANGE:

(10) 1.0 E+ I MAX INSTR RANGE:

(10) 1.0 E+7 ZERO PTREF:

(6)

N/A REF PT NOTES:

(40)

N/A PROC OR SENS:

(I)

S (P, S)

NUMBER OF SENSORS:

(3)

I HOW PROCESSED:

(40)

N/A SENSOR LOCATIONS:

(40)

DISCHARGE OF WASTE CONDENSATE PUMPS ALARMITRIP SET PT:

(40) 5.0 E+5 CPM NI DET PWR SUPPLY (15)

N/A CUTOFF PWR LVL:

NI DET PWR SUPPLY (15)

N/A TURN ON PWR LVL:

INSTR FAIL MODE:

(30)

LOW TEMP COMP FOR DP (3)

N/A (Y, N, N/A)

XMTRS:

LEVEL REF LEG:

(3)

N/A (DRY, WET)

UNIQUE SYS DESC:

(600)

RAD MONITOR R-18, WASTE DISPOSAL SYSTEM LIQUID EFFLUENT MONITOR - CONSISTS OF ANAl SCINT.

COUNTER AND SAMPLE VOLUME CHAMBER ASSEMBLE. INITIATES AUTOMATIC CLOSURE OF VALVE WD-19 TO PREVENT FURTHER RELEASE.

Table 30 EPMP-09.05 Rev. 3 Date: FEB 5 2009 REFERENCE USE Page 34 of 48

CONDENSER AIR EJECTOR RADIOACTIVITY KEWAUNEE POWER STATION ITEM FIELD KPS ERDS DATA LENGTH DATE:

(8) 01/14/09 REACTOR UNIT:

(3)

KWI DATA FEEDER:

(10)

NIA NRC ERDS PARAM:

(12)

CONDAlE RAD POINT ID:

(12)

GOOl5G PLANT SPEC PT DESC:

(40)

CDSR AIR EJECTOR EXHAUST GENERICICOND DESC:

(32)

CONDENSER AIR EJECTOR RADIOACT.

ANALOGIDIGITAL:

(1)

A (A, D)

ENGR UNITSIDIG ST:

(12)

CPM ENGR UNITS CONVERS:

(40)

NIA MIN INSTR RANGE:

(10) 1.0 E+1 MAX INSTR RANGE:

(10) 1.0 E+7 ZERO PT REF:

(6)

NIA REF PT NOTES:

(40)

N/A PROC OR SENS:

(I)

S (I', S)

NUMBER OF SENSORS:

(3) 1 HOW PROCESSED:

(40)

NIA SENSOR LOCATIONS:

(40)

IN CONDENSER AIR EJECTOR EXHAUST HEADER ALARM/TRIP SET PT:

(40) 4.0 E+6 CPM NI DET PWR SUPPLY (15)

NIA CUTOFF PWR LVL:

NI DET PWR SUPPLY (IS)

NIA TURN ON PWR LVL:

INSTR FAIL MODE:

(30)

LOW TEMP COMP FOR DP (3)

N/A (Y, N, N/A)

XMTRS:

LEVEL REF LEG:

(3)

NIA (DRY, WET)

UNIQUE SYS DESC:

(600)

RAD MONITOR R-15, CONDENSER AIR EJECTOR GAS MONITOR --CONTAINS A GAMMA SENSITIVE SCINITILLATION DETECTOR. PROVIDES THE FOLLOWING AUTOMATIC ESF ACTUATION: ISOLATE SIG BLOWDOWN AND SHIFT CONDENSER AIR EJECTOR DISCHARGE TO EXHAUST VIA AUX BLDG VENT.

Table 31 EPMP-09.05 Rev. 3 Date: FEB 5 2009 REFERENCE USE Page 35 of 48

STEAM GENERATOR BLOWDOWN RADIATION LEVEL KEWAUNEE POWER STATION ITEM FIELD KPS ERDS DATA LENGTH DATE:

(8) 01114/09 REACTOR UNIT:

(3)

KWI DATA FEEDER:

(10)

NIA NRC ERDS PARAM:

(12)

SGBDRAD POINT ID:

(12)

GOOl9G PLANT SPEC PT DESC:

(40)

STEAM GENERATOR BLOWDOWN GENERIC/COND DESC:

(32)

STM GEN BLOWDOWN RAD LEVEL ANALOGIDIGITAL:

(I)

A (A, D)

ENGR UNITS/DIG ST:

(12)

CPM ENGR UNITS CONVERS:

(40)

N/A MIN INSTR RANGE:

(10) 1.0 E+I MAX INSTR RANGE:

(10) 1.0 E+7 ZERO PTREF:

(6)

N/A REF PT NOTES:

(40)

N/A PROC OR SENS:

(I)

S (P, S)

NUMBER OF SENSORS:

(3)

I HOW PROCESSED:

(40)

N/A SENSOR LOCATIONS:

(40)

DOWNSTREAM OF S/G BLOWDOWN HTEXCH'S ALARM/TRIP SET PT:

(40) 2.5 E+4CPM NI DET PWR SUPPLY (IS)

N/A CUTOFF PWR LVL:

NI DET PWR SUPPLY (IS)

N/A TURN ON PWR LVL:

INSTR FAIL MODE:

(30)

LOW TEMP COMP FOR DP (3)

N/A (Y, N, N/A)

XMTRS:

LEVEL REF LEG:

(3)

N/A (DRY, WET)

UNIQUE SYS DESC:

(600)

STEAM GENERATOR BLOWDOWN SYSTEM LIQUID SAMPLE MONITOR R NAI SCINT. DETECTOR PROVIDES THE FOLLOWING AUTOMATIC ESF FUNCTION: ISOLATE S/G BLOWDOWN AND SHIFT CONDENSER AIR EJECTOR DISCHARGE TO EXHAUST VIA THE AUX BLDG VENT STACK. FOLLOWING S/G BLOWDOWN ISOLATION, MANUAL VALVE MANIPULATION ALLOWS MANUAL SAMPLING IN SAMPLE ROOM. THIS RAD MONITOR IS COMMON FOR BOTH TRAIN A AND TRAIN B OF S/G BLOWDOWN.

Table 36 EPMP-09.0S Rev. 3 Date: FEB 5 2009 REFERENCE USE Page 40 of 48