ML082480044

From kanterella
Jump to navigation Jump to search

Response to 2007 Steam Generator Tube Inspection Report Request for Additional Information
ML082480044
Person / Time
Site: Cook  American Electric Power icon.png
Issue date: 08/05/2008
From: Jensen J
Indiana Michigan Power Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
AEP-NRC-2008-9, TAC MD8397
Download: ML082480044 (7)


Text

IID~~

Indiana Michigan Power Company Nuclear Generation Group One Cook Place Bridgman, MI 49106 aep.com AEP-NRC-2008-9 August 5,2008 Docket Nos.:

50-315 50-316 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Mail Stop:O-P17 17 Wash ington,.DC:20555,-0001

,-,Donald C..-Cook Nuclear:Plant, Units 1-.and2..

RESPONSE TO. 2007.STEAM GENERATOR TUBE INSPECTION REPORT REQUEST FOR ADDITIONAL INFORMATION

References:

1.

Letter from Joseph N. Jensen, Indiana Michigan Power Company (I&M),

to U. S. Nuclear Regulatory-: Commission

.(NRC)

Document Control

Desk, "Donald C. Cook Nuclear Plant Units 1 and 2, 2007 Steam Generator Tube Inspection Report," AEP:NRC:8691, dated March 18, 2008 (ML080870429).
2. Letter from Peter S. Tam, NRC, to Michael W. Rencheck, I&M, "D. C. Cook Nuclear Plant, Unit 2 (DCCNP-2) - Request for Additional Information, Regarding Steam Generator Inspection Report for Year 2007 (TAC No. MD8397)," dated July 11, 2008 (ML081790843).

In Reference 1, Indiana Michigan Power Company (I&M),.the licensee for Donald C. Cook Nuclear Plant Unit 1 and Unit 2, provided the Nuclear-Regulatory.'Commission (NRC) the 2007 Steam Generator Tube Inspection Report.

In Reference 2,.theINRC requested additional information regarding -&M's submittal.

attachment to this letter provides.&M's response to the. requestfor addi.tional information.

The This letter: contains no new or revised commitments.

Should you have any questions, please contactMr:* John A. Zwolinski, Regulatory Affairs Manager, at (269) 466-2478.

Sincerely, Jo eph N. Jensen SiteSupport Services Vice President SLA/rdw

Attachment:

Response to 2007 Steam Generator Tube Inspection Report Request for Additional Information A-f 7 k"i21(

U. S. Nuclear Regulatory Commission AEP-NRC-2008-9 Page 2 c:

R. Aben - Department of Labor and Economic Growth T. A. Beltz - NRC Washington DC J. L. Caldwell - NRC Region III K. D. Curry - AEP Ft. Wayne, w/o attachment J. T. King - MPSC, w/o attachment MDEQ -WHMD/RPS, w/o attachment NRC Resident Inspector

Attachment to AEP-NRC-2008-9 STEAM GENERATOR TUBE INSPECTION REPORT REQUEST FOR ADDITIONAL INFORMATION In Reference 1, Indiana Michigan Power Company (I&M), the licensee for Donald C. Cook Nuclear Plant (CNP) Unit 1 and Unit 2, provided the Nuclear Regulatory Commission (NRC) the 2007 Steam Generator Tube Inspection Report.

In Reference 2, the NRC requested additional information regarding I&M's submittal.

I&M's response to the request for additional information is provided below.

NRC Request 1 Indiana Michigan Power Company (I&M) mentioned that at the time of the 2007 inspection, the steam generators (SGs) had operated for 132.6 effective full power months (EFPM). Please clarify this statement by providing the following information: For each refueling outage and SG tube inspection outage since the replacement of the SGs, please provide the cumulative EFPM that the SGs have operated.

I&M Response to Request 1 CNP Unit 2 SG's were replaced prior to the start of fuel cycle 7. The subsequent accumulated EFPM of operation and the associated end of cycle (EOC) SG inspections for the replacement SG's are noted in the following table.

Note: The statement of 132.6 EFPM in the original submittal (Reference 1) stated it did not include the first cycle of operation (13.36 EFPM). Not including the first cycle of operation was intended to allow comparison to the Technical Specification (TS) 5.5.7.d.2 sequential inspection period length of 144 EFPM which is noted within the TS to not begin until after the first inservice inspection of the SG's.

The additional cycle 17 EFPM data in the table pertains to the current ongoing cycle of operation that has been accumulating after the 2007 SG inspection was completed. Therefore, this value was not included in the original submittal.

I Cook -Unit 2 Cycle Replacement Accumulated Notes Number SG EFPM SG EFPM 7

13.36 13.36 EOC SG Inspection 8

13.34 26.70 EOC SG Inspection 9

14.65 41.35 EOC SG Inspection 10 14.02 55.37 No EOC SG Inspection 11 15.05 70.42 EOC SG Inspection 12 16.85 87.27 EOC SG Inspection 13 12.50 99.77 No EOC SG.Inspection 14 14.18 113.95 EOC SG Inspection 15 15.83 129.78 No EOC SG Inspection 16 16.18 145.96 EOC Inspection 17 4.54 +

150.50 +

Cycle ongoing - EFPM data thru 3/26/08

Attachment to AEP-NRC-2008-9 Page 2 NRC Request 2 I&M indicated that no abnormal conditions were identified during the inspection of the steam drum area (including the feedring, J-nozzles, and moisture separator units). Please discuss whether any degradation was observed during these inspections.

I&M Response to Reauest 2 An area of minor surface pitting was found on the underside of the primary separator diffuser window (also known as the primary separator intermediate plate assembly) on SG 22. This was not considered abnormal given the service time of this unit and was not indicative of any threat to the functionality or integrity of the separator assembly.

Periodic future inspections will continue to monitor this area in all of the Unit 2 SG's.

NRC Request 3 Please discuss the results of I&M's foreign object search and retrieval efforts. If any loose parts were left in the SG, please discuss whether I&M confirmed that it was acceptable (from a tube integrity standpoint) to leave these loose parts in the steam generator.

I&M ResDonse to Reauest 3 Foreign object search and retrieval (FOSAR) efforts were completed on SG's 21, 22, and 24.

No foreign objects were detected in SG 23. The results of the FOSAR efforts are summarized in the following table and associated discussion:

SG Object Region Detection Eddy.

Disposition Description, Method

Current, Results 21 Metal curl Cold leg Visual No tube Retrieved:

Item A 0.75" long annulus damage in No future action.

<1mm OD or around location 21 Wire strand Hot leg annulus Visual No tube Retrieved:

Item B 0.5" long damage in No future action.

very thin or around location 21 Sludge Hot Leg Top of Eddy Current No tube Not retrieved:

Item C Tubesheet (ECT) damage in Visually confirmed as a sludge rock.

or around Object broke into pieces while R24-25/C13 location attempting retrieval. Left in place. No future action.

21 Sludge Hot Leg Top of ECT No tube Not retrieved:

Item D Tubesheet damage in Visually confirmed as a sludge rock but or around not accessible for retrieval. Reexamine R22-23/C8 location during next scheduled inspection in Fall 2010.

Attachment to AEP-NRC-2008-9 Page 3 SG Object Region Detection Eddy Disposition Description Method Current Results 22 Small wire Hot Leg Top of Visual No tube Not retrieved:

Item E 0.5" long Tubesheet damage in Visually confirmed as a small wire.

0.055" dia.

or around Item was fixed to the tubesheet and R38/C54-55 location dispositioned to be left in place.

Reexamine during next scheduled inspection in Fall 2010.

22 Metal strip Cold Leg Top Historical No tube Not retrieved:

Item F 4" long of Tubesheet FOSAR &

damage in Visually confirmed to not have moved.

0.125" wide ECT indication or around Item is fixed to the tubesheet and was R3/C55-56 location dispositioned to be left in place in the previous inspection. Reexamine during next scheduled inspection in Fall 2010.

22 Sludge Hot Leg Top of ECT No tube Not retrieved:

Item G Tubesheet damage in Visually confirmed as a sludge rock.

or around Reexamine during next scheduled R8/C31 location inspection in Fall 2010.

22 Nothing Hot Leg Top of Historical ECT No tube Nothing found during FOSAR (limited Item H found Tubesheet indication damage in access). Reexamine during next or around scheduled inspection in Fall 2010.

R18/C50 location 22 Sludge Hot Leg Top of ECT No tube Not retrieved:

Item I Tubesheet damage in Visually confirmed as a sludge rock.

or around Reexamine during next scheduled R28/C56-57 location inspection in Fall 2010.

24 Metallic strip Hot Leg Top of Visual No tube Not retrieved:

Item J 1" long Tubesheet damage in Visually confirmed as a small wire.

0.13" wide or around Item was fixed to a sludge deposit and R8/C42-43 location dispositioned to be left in place.

Reexamine during next scheduled inspection in Fall 2010.

As noted in the above table, several items could not be retrieved from the secondary side of the SG and were left in place. All of the above items were documented and dispositioned under CNP's Corrective Action Program (Action Request 819443) and in the U2C17 Steam Generator Condition Monitoring and Operational Assessment Evaluation (Areva Doc. # 51-9063150-000) to ensure that tube integrity would be maintained.

Sludqe rocks: Identified as being incapable of causing tube damage and were acceptable to be left in the SG.

Items E, F, & J:

Evaluated following industry guidance and determined to not impact tube integrity.

o Item E: Identified during the 2007 inspection by FOSAR. It was not touching any tubes and was not identified by ECT. Retrieval attempts were unsuccessful and the object could not be moved by either FOSAR equipment or the 1500 pounds per square inch (psi) sludge lancing operation. Expanded ECT of the tube and the surrounding area (12 tubes) confirmed no degradation was present.

Attachment to AEP-NRC-2008-9 Page 4 Evaluations determined that no tube damage is expected from this object and that integrity will be maintained. This area will be reexamined during the next scheduled inspection to validate that there has been no change in the current conditions.

Item F: Identified during its 2004 inspection and dispositioned to be left in place.

FOSAR efforts in 2007 confirmed that the object was in the same location.

Expanded ECT of the tube and the surrounding area (36 tubes) confirmed no degradation was taking place.

Evaluations determined no tube damage is expected from this object and tube integrity will be maintained. This area will be reexamined during the next scheduled inspection to validate that there has been no change in the current conditions.

o Item J: Identified during the 2007 inspection by FOSAR. The metal object was anchored to sludge deposits.

It was not touching any tubes and was not identified by ECT. Retrieval attempts were unsuccessful and the object could not be moved by either FOSAR equipment or the 1500 psi sludge lancing operation.

Evaluations determined that it is likely to remain in its present location.

Expanded ECT of the tube and the surrounding area (12 tubes) confirmed no degradation was present. Evaluations determined no tube damage is expected from this object and tube integrity will be maintained.

This area will be reexamined during the next scheduled inspection to validate that there has been no change in the current conditions.

NRC Request 4 Please confirm that the condition monitoring limit for wear at the tube support plate is 41-percent through-wall (which would indicate that such indications may need to be plugged at through-wall depths much less than the technical specification repair criteria).

I&M Response to Request 4 Tube support indication condition monitoring limits for Unit 2 2007 inspection is 41 percent (%),

as stated in CNP's Unit 2 Steam Generator Condition Monitoring and Operational Assessment.

The limit for support plate wear is very conservative as a result of using a bounding primary-to-secondary pressure differential value in the condition monitoring calculation. Instead of using the standard industry methodology of three times normal operating pressure differential (3 x 1430 pounds per square inch absolute (psia)), the support plate indications were evaluated against a condition monitoring limit based upon three times design pressure differential (3 x 1600 psi).

In addition, the extents of the indications were assumed to be equal to the thickness of the support plate for ease of calculation.

Had an indication-specific extent measurement been used, additional conservatism would have been removed and the condition monitoring limit would have been increased. Based upon the available margin between the maximum indication size and the calculated condition monitoring limit, further calculation refinement was not warranted.

Attachment to AEP-NRC-2008-9 Page 5 The above calculation resulted in a conservative condition monitoring limit. CNP acknowledges this methodology increases the potential for tube repair at lower levels. However, due to the small indication size, stable indication growth rate, and the general lack of indications to date, no low-level through-wall repairs have been required in order to maintain our desired inspection interval.

NRC Request 5 I&M indicated that no active degradation (as defined by the Electric Power Research Institute) was identified during the 2007 inspections. In addition, I&M indicated that the "indications of interest were limited to seven support plate wear indications." Please discuss whether any degradation/flaws (other than the seven support plate wear indications) were observed.

I&M Response to Request 5 No additional degradation or flaws were observed during this inspection.

References

1. Letter from Joseph N. Jensen, I&M, to U. S. NRC Document Control Desk, "Donald C. Cook Nuclear Plant Units 1 and 2, 2007 Steam Generator Tube Inspection Report,"

AEP:NRC:8691, dated March 18, 2008 (ML080870429).

2. Letter from Peter S. Tam, NRC, to Michael W. Rencheck, I&M, "D. C. Cook Nuclear Plant; Unit 2 (DCCNP-2) -

Request for Additional Information, Regarding -Steam Generator-.

Inspection ýReport for Year 2007 (TAC No. MD8397)", dated July 11, 2008 (ML081!790843)..