LR-N07-0265, Steam Generator Tube Inspection Report Eighteenth Refueling Outage (1R18)
| ML072970094 | |
| Person / Time | |
|---|---|
| Site: | Salem |
| Issue date: | 10/10/2007 |
| From: | Braun R Public Service Enterprise Group |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| LR-N07-0265 | |
| Download: ML072970094 (50) | |
Text
PSEG Nuclear LLC P.O. Box 236, Hancocks Bridge, NJ 08038-0236 0 PSEG Nuclear L.L. C.
Technical Specification 6.9.1.10 OCT 1 0 2007 LR-N07-0265 U.S, Nuclear Regulatory Commission ATTN: Document Control Desk Washington DC 20555-001 Salem Nuclear Generating Station Unit 1 Facility Operating License No. DPR-70 NRC Docket No. 50-272
SUBJECT:
STEAM GENERATOR TUBE INSPECTION REPORT -
EIGHTEENTH REFUELING OUTAGE (1R18)
PSEG Nuclear, LLC (PSEG) hereby submits its Steam Generator Tube Inspection Report consistent with the requirements of Technical Specification (TS) 6.9.1.10. The report is being submitted within 180 days after the initial entry into HOT SHUTDOWN following completion of the inspection performed in accordance with Technical Specification 6.8.4.i, "Steam Generator (SG) Program." Salem Unit 1 entered HOT SHUTDOWN (Mode 4) on April 16, 2007, following the completion of its eighteenth refueling outage. contains the Steam Generator Tube Inspection Report TS 6.9.1.10. contains the Salem Unit 1 Model F SG Tube Support Arrangement and.
Terminology. contains the Salem Unit 1 - 1 R18 Nondestructive Examination Techniques. contains the 1 R18 Service Induced Indications (AVB Wear).
OCT. 10 2007 Document Control Desk Page 2 LR-N07-0265 Should you have any questions regarding this submittal, please contact Mr. E. Villar at (856) 339-5456.
Sincerely, Robert C. Braun Site Vice President - Salem C
Mr. Samuel Collins, Administrator - Region I U. S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 U. S. Nuclear Regulatory Commission Attn: Mr. S. Bailey, Licensing Project Manager - Salem Mail Stop 08B1 Washington, DC 20555-0001 USNRC Senior Resident Inspector - Salem (X24)
Mr. P. Mulligan, Manager IV Bureau of Nuclear Engineering P.O. Box 415 Trenton, NJ 08625 Document Control Desk LR-N07-0265 PSEG Nuclear LLC Salem Unit 1 STEAM GENERATOR TUBE INSPECTION REPORT TS 6.9.1.10 Introduction In 1998 Salem Unit 1 commenced operating cycle 13 with the newly replaced steam generators (SG) from the canceled Seabrook-2 plant. Salem Unit 1 is a four (4) loop Westinghouse Pressurized Water Reactor (PWR) with Model F SGs that incorporate thermally treated Inconel 600 U-tubes. The tube bundle consists of 5,626 tubes with an outside diameter (OD) of 0.688 inches and a nominal tube wall thickness of 0.040 inches. During SG fabrication, the tubes were hydraulically expanded over the full tubesheet depth and the first ten tube rows were thermally stress relieved after U-bend formation. The seven (7) tube support plates (TSP) are fabricated from 405 stainless steel (SS) and have broached "quatrefoil" tube holes. A flow distribution baffle (FDB) plate, also 405 SS, between the secondary face of the tubesheet and the first tube support plate, provides top-of-tubesheet (TTS) sludge pile control. Tube support within the U-bend region is provided by three V-shaped chrome-plated Inconel 600 antivibration bars (AVB's). provides a general summary of the Salem Unit 1 Model F SG Tube Support Arrangement and Terminology.
Consistent with Technical Specification (TS) 6.9.1.10, this report is being submitted within 180 days after the initial entry into HOT SHUTDOWN following completion of inspection performed in accordance with the Specification 6.8.4.i, "Steam Generator (SG) Program." This report includes:
- a.
The scope of inspections performed on each SG,
- b.
Active degradation mechanisms found,
- c.
Nondestructive examination techniques (NDE) utilized for each degradation mechanism,
- d.
Location, orientation (if linear), and measured sizes (if available) of service induced indications,
- e.
Number of tubes plugged during the inspection outage for each active degradation mechanism,
- f.
Total number and percentage of tubes plugged to date, and
- g.
The results of condition monitoring, including the results of tube pulls and in-situ testing.
- h.
The number of indications detected in the upper 17 inches of the tubesheet thickness along with their location, measured size, orientation, and whether the indication initiated on the primary or secondary side.
- 1.
The operational primary to secondary leakage rate observed in each steam generator during the cycle preceding the inspection and the calculated accident leakage rate for each steam generator from thelower most 4 inches of tubing (the tubesheet is nominally 21.03 inches thick) for the most limiting accident. If the calculated leak rate is less than 2 times the total observed operational leakage rate, the 180 day report should describe how the calculated leak rate is determined.
Page 1 of 5 Document Control Desk LR-N07-0265 SG inspections were performed in accordance with TS 6.8.4.i, "Steam Generator Program", during Salem Unit 1 Outage 1R18 (April 2007). Each reporting requirement of the U1 TS 6.9.1.10 is addressed below (items a through i).
Tech Spec 6.9.1.10.a The scope of inspections performed on each SG are summarized below:
" A full-length bobbin coil inspection was performed on 100% of the in-service tubes in each steam generator.
" Rotating coil (+ Point) on all hydraulic over expansions (OXP) at the hot and cold leg top of tubesheet.
- Rotating coil (+ Point) on 20% of the total Hot Leg (HL) population of OEX (Ž1.5 mils) and BLG
(Ž_18 volts) tubesheet expansion anomalies that are between the TTS to -17" below the TTS. The tubesheet drilling process during manufacture can create minor irregularities in the tubesheet boreholes. When the tube is expanded into the borehole, including into the minor irregularities, the tube wall's variance from a straight normal cylindrical shape is typically referred to as an expansion anomaly. These are classified as an internal tubesheet over expansion (OEX, typically measured in mils) or as a bulge (BLG, typically measured in bobbin probe voltage).
" The following was conservatively performed in approximately 62 tubes from all four SGs as identified from previous efforts supporting resolution of issues stemming from OE 13898:
" Performed rotating coil +Point inspections of>5 volt dents and dings (HL and CL)
" Performed rotating coil +Point inspection of => 2 volt u-bend dents and dings
" Performed a rotating coil +Point inspection of AVB wear that was reported during the bobbin coil inspection
" All previously installed tube plugs, and plugs installed during 1R18, were visually inspected Note that a ding at a support structure (eg: TSP, AVB) is called a Dent (DNT) at Salem Unit 1.
Therefore, the only difference between a Dent and a Ding is the location within the freespan with respect to a support structure.
Tech Spec 6.9.1.10.b Active degradation mechanisms found:
The only active degradation mechanism detected during outage 1R18 was AVB wear. A summary of the AVB wear indications is provided in the table below, and in Attachment 4.
Summary of A VB Wear Indications Detected and Plugged in 1R18 SG 11 SG 12 SG 13 SG 14 Total Detected 356 319 630 344 1649 Removed 55 67 248 77 447 fomn service Returned to 301 252 382 267 1202 service Page 2 of 5 Document Control Desk LR-N07-0265 Tech Spec 6.9.1.10.c Nondestructive examination techniques utilized for each degradation mechanism:
In accordance with Rev. 6 of the EPRI PWR Steam Generator Examination Guidelines (section 6.2.4) a documented review of EPRI Qualified techniques was performed to ensure application of these techniques are pertinent to site-specific SG conditions. See Attachment 3 for examination techniques utilized for each degradation mechanism. The region of tube, to which these techniques are applicable, includes both those that were specifically demonstrated in the industry qualifications and others for which there is no specific demonstration (extended).
Tech Spec 6.9.1.10.d Location, orientation (if linear), and measured sizes (if available) of service induced indications:
The only service induced indications detected during outage 1 RI 8 were due to AVB wear. Attachment 4 provides information for these indications.
Tech Spec 6.9.1.10.e Number of tubes plugged during the inspection outage for each active degradation mechanism:
AVB wear is the primary degradation mechanism for the Salem Ul Model F SGs, and the only active degradation mechanism detected during 1R18. Other than AVB wear, the only other tube plugging was preventative plugging for one tube in SG12 (tube R5-C31) for Permeability Variation (PVN).
Salem IR1 8 Steam Generator Tube Plugging I SG 11 SG 12 SG13 SG14 Total AVB Wear*
I1 15 54 15 95 PVN**
0 1
0 01 Total Tubes Plugged 11 16 54 15 96
- Note that AVB wear indications in all four SGs were conservatively plugged at 33% TW, therefore the largest in-service AVB wear indication is 32%. This is discussed more in response to 6.9.1.10.g.
- Permeability Variation is a condition where the test coil impedance changes due to a change in the tubing material's inherent willingness to conduct magnetic flux lines. Permeability variation signals are not considered to be flaws or degradation. Rather, the signals are considered data quality issues that have additional testing using a magnetically biased rotating coil probe to disposition. The results of this testing did not reveal any flaw like response indicative of degradation in the area of interest. PSEG made the conservative decision to preventively plug this tube. It is PSEG's position that any flaws or degradation in the area where PVN was reported would result in a change in signal response when compared to previous inspection data. Based on look backs performed, there were no observed changes in the signals.
Page 3 of 5 Document Control Desk LR-N07-0265 Tech Spec 6.9.1.10.f Total number and percentage of tubes plugged to date:
Following the completion of outage 1 R18, a total of 96 additional tubes were removed from service from all four-steam generators. This resulted in a total of 224 tubes, or approximately 0.995%, removed from service from all four steam generators. The limiting steam generator is SG 13 with approximately 1.831%
of tubes removed from service. The Table below provides further details.
Salem Unit 1 Steam Generator Tube Plugging Status SSG 11 SG 12 SG 13 SG 14 Total Tubes Plugged Prior to 1R18 33 29 49 17 128 Tubes Plugged During 1R18 11 16 54 15 96 Total Tubes Plugged 44 45 103 32 224 Total Percentage 0.782%
0.800%
1.831%
0.569%
0.995%
Tech Spec 6.9.1.10.g The results of condition monitoring, including the results of tube pulls and in-situ testing:
A Condition Monitoring (CM) assessment was performed for the Salem Ul SGs following inspections from outage 1R18 in accordance with TS 6.8.4.i, NEI 97-06, and EPRI Guidelines (including the EPRI Steam Generator Integrity Assessment Guidelines, Revision 2). Consistent with TS 6.8.4.i.a, "Provisions for condition monitoring assessments", "Condition monitoring assessment means an evaluation of the "as found" condition of the tubing with respect to the performance criteria for structural integrity and accident induced leakage. The "as found" condition refers to the condition of the tubing during an SG inspection outage, as determined from the inservice inspection results or by other means, prior to the plugging of tubes. Condition monitoring assessments shall be conducted during each outage during which the SG tubes are inspected or plugged to confirm that the performance criteria are being met" The "as found" condition of the tubing for 1RI 8 is provided in response to TS 6.9.1.10.d.
The Salem Unit 1 Condition Monitoring Limit (CML) for AVB wear is approximately 63% Through-Wall (TW), when using EPRI ETSS technique 96004.1, and as conservatively calculated using guidance consistent with the EPRI Steam Generator Integrity Assessment Guidelines, Revision 2. AVB wear measured less than the CML analytically demonstrates that the structural integrity performance criterion (TS 6.8.4.i.b. 1) is met. Condition Monitoring can be accomplished by analytical methods or in situ pressure testing. All AVB wear indications detected during IR1 8 were found to be well below the NDE analytical CML, except for an indication in SG13 (tube R54-C65 at AV3). The indication in SG 13 R54-C65 was sized at 71%TW with bobbin probe technique 96004.1. Therefore, analytical demonstration of this AVB wear indication could not be accomplished. Because it could not be demonstrated analytically with NDE, it was necessary to perform in-situ pressure testing. In-situ pressure testing was performed on this indication (full length in-situ of this tube), for proof and leak testing in accordance with the EPRI Steam Generator In Situ Pressure Test Guidelines, Revision 2. The results of the pressure test did not provide any leakage at any pressure hold points, up to the three times the normal operating differential Page 4 of 5 Document Control Desk LR-N07-0265 pressure equivalent as provided by the requirements of the EPRI SG In-Situ Pressure Test Guidelines (approximately 4950 psi). Therefore, structural and leakage integrity was confirmed. This tube was plugged and stabilized during IR18.
Of all the AVB wear indications detected during 1R18, the indication in SG13 (tube R54-C65 at AV3) was the only AVB wear indication of this severity. The next two largest AVB wear indications are 53 and 52% TW, with the majority of the AVB wear less than 40% TW. Tube plugging in accordance with the Tech Spec repair criteria (40% TW and greater) provides that 26 tubes require tube plugging for AVB wear. However, the plugging limit for AVB wear was lowered from 40% TW to 33% TW, to support the Operational Assessment and provide margin. Therefore the largest AVB wear returned to service is 32%
TW.
None of the indications detected during the 1 R18 inspection challenged the structural integrity performance criterion; therefore the accident induced leakage performance criterion (TS 6.8.4.i.b.2) is also satisfied. This was also directly demonstrated by the in-situ pressure test performed for the most limiting AVB wear indication detected during 1 R18.
No SG tube pulls were performed during Refueling Outage 18.
Tech Spec 6.9.1.10.h The number of indications detected in the upper 17 inches of the tubesheet thickness along with their location, measured size, orientation, and whether the indication initiated on the primary or secondary side:
There were no indications of degradation detected in the upper 17 inches of the tubesheet thickness during the IR1 8 outage inspections.
Tech Spec 6.9.1.10.i The operational primary to secondary leakage rate observed in each steam generator during the cycle preceding the inspection and the calculated accident leakage rate for each steam generator from the lowermost 4 inches of tubing (the tubesheet is nominally 21.03 inches thick) for the most limiting accident. If the calculated leak rate is less than 2 times the total observed operational leakage rate, the 180-day report should describe how the calculated leak rate is determined:
Salem Unit 1 did not observe any primary to secondary operational leakage at or greater than the detection threshold of approximately one (1) gallon per day over the cycle preceding the inspection in any of the steam generators. Since Salem Unit 1 did not observe any significant measurable SG primary to secondary operational leakage, the calculated accident leakage rate for each steam generator from the lowermost 4 inches of tubing for the most limiting accident would also not be significant. Conservatively assuming that there was a primary to secondary operational leakage at the detection threshold of approximately one (1) gallon per day also provides that the estimated calculated accident leakage would also be negligible. See Reference section 3.4, "Joint Leakage Integrity," in Safety Evaluation by the Office of the Nuclear Reactor Regulation related to Amendment No.279 to Facility Operating License No.
DPR-70, for discussion of calculation methodology.
Page 5 of 5
I-Document Control Desk LR-N07-0265 Salem Unit 1 Model F SG Tube Support Arrangement and Terminology
-AV3 V4 r
A V rat0.n -Br (AVB)
Tube Support Plate (TSP)
Tubei
,:Support.1-64H1 Number j03H 02H Flow Distribution Baffle (FDB) Plate FBC Top of Tubesheet (TTS)
- TSC, Tub6re'ts mc..
Page 1 of 1 Document Control Desk LR-N07-0265 1R18 Nondestructive Examination Techniques Probe EPRI ETSS Damage Technique Applicability Mechanism Bobbin 96001.1 Bobbin Revision 11 Thinning TSP and TTS Bobn 96004.1 Bobbin Revision 10 Wear TSP, AVB, FDB, and PLP 96005.2 Bobbin Revision 9 Pitting Presence of Copper B n 96007.1 Bobbin Revision 11 IGA/ODSCC TSP, Freespan, and <= 5 volt Dents Bobbin 96008.1 Sludge Pile, Freespan, and <= 5 volt Revision 14 Dents 24013.1 ODSCC Bobbin Revision 2
<= 5 Volts Dings <= 5.0 Volts
+/-Point 96910.1
+Point Revision 10 Wear TSP, AVB, FDB, Loose Parts Wear
+/-Po 21998.1
+Point Revision 4 Volumetrics Freespan, TSP, AVB and TTS
+Point 96701.1 Circumferential.
Expansion Transition, Tubesheet, Revision 12 PWSCC Dings, Dents
+Point 20510.1 Circumferential Expansion Transition, Tubesheet, Revision 7 PWSCC Dings, Dents Re o
96703.1 Axial PWSCC Dented and Non-Dented TSP's, Revision 17 Freespan Dings, and within Tubesheet 20511.1 Expansion Transition, Non-Dented
+Point Revision 8 Axial PWSCC TSP's, Dings, and within Tubesheet 21410.1 Circumferential Expansion Transition, Freespan, Revision 6 ODSCC Sludge Pile, within Tubesheet, U-bend 22842.3 Circumferential Dented and Non-Dented TSP's, and
+Point Revision 5 ODSCC Dings 21409.1 TSP, Freespan, Sludge Pile,
+Point Revision 5 Axial ODSCC Expansion Transition and within Tubesheet, and U-bend.
22841.3
+Point Revision 5 Axial ODSCC Dented and Non Dented TSP, Dings 96511.1 Axial and
+Point Circumferential U-bend Revision 16 PWC PWSCC 96511.2 Axial&
+Point Circumferential U-bend Revision 16 PWSCC Page 1 of 1 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
ISG -Row C-(ol-11(
,,,T\\
O/
ul~J Inch SG11 22 80 TWD 10 AV1
-0.06 SGll 26 43 TWD 16 AVI
-0.35 SGl1 26 43 TWD 16 AV2 0.08 SG1l 26 91 TWD 17 AVI
-0.11 SG11 26 91 TWD 14 AV6 0.08 SG11 26 91 TWD 8 AV5
-0.1 SGl1 27 33 TWD 15 AV2
-0.08 SGl1 27 44 TWD 16 AV2
-0.15 SG11 27 44 TWD 10 AV5
-0.02 SG11 27 44 TWD 19 AV6 0.19 SGl1 27 78 TWD 12 AV2
-0.04 SGl1 27 79 TWD 10 AV2
-0.15 SG11 27 80 TWD 24 AV2 0.04 SGl1 28 10 TWD 12 AVI 0.23 SGl1 28 114 TWD 16 AV6
-0.08 SGl1 28 114 TWD 21 AVI 0.21 SG11 29 9
TWD 25 AV5
-0.02 SG11 29 9
TWD 16 AV2 0.07 SGl1 29 112 TWD 21 AV2 0.23 SG1l 29 112 TWD 10 AV5
-0.06 SGl1 29 114 TWD 23 AV6
-0.21 SG11 29 114 TWD 16 AVI 0.27 SGl1 30 48 TWD 13 AV2 0.25 SGl1 30 73 TWD 11 AV5
-0.25 SGl1 30 86 TWD 10 AVI 0.44 SGl1 30 86 TWD 14 AV2 0.1 SGl1 32 12 TWD 16 AV4
-0.08 SG11 32 12 TWD 15 AV5 0.13 SG11 32 15 TWD 11 AV2 0.02 SGl1 32 20 TWD 10 AV5
-0.13 SGl1 32 31 TWD 20 AV2
-0.04 SGl1 32 72 TWD 15 AV3
-0.04 SGl1 32 72 TWD 10 AV2 0.15 SGl1 32 72 TWD 14 AV4
-0.04 SGl1 32 72 TWD 15 AVI
-0.04 SG11 32 84 TWD 8 AV4
-0.04 SG11 32 112 TWD 7 AV5 0.51 SGl1 32 112 TWD 7 AV2
-0.32 SGl1 33 107 TWD 5 AV6
-0.02 SG1 34 109 TWD 16 AV2
-0.12 Page 1 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
Ll-"
Row
(,(Ii 11d
'J Suipp Jridih SGl1 34 111 TWD 9 AV2
-0.73 SGl1 34 111 TWD 8 AV6
-0.4 SG11 35 13 TWD 15 AV5
-0.02 SGl1 35 13 TWD 9 AV6
-0.02 SGI1 35 44 TWD 15 AV6 0.02 SG1l 35 44 TWD 24 AV5 0.1 SGll 35 44 TWD 17 AV4 0.06 SG11 35 44 TWD 14 AVI
-0.38 SGI1 36 108 TWD 9 AVI 0.35 SG11 37 48 TWD 10 AV2
-0.15 SGl1 37 65 TWD 10 AV2 0.1 SG11 37 67 TWD 9 AV1 0.33 SG1I 37 68 TWD 21 AV2 0.01 SGl1 37 68 TWD 11 AV4
-0.04 SGl1 37 68 TWD 14 AV5
-0.08 SG11 37 68 TWD 12 AV3
-0.06 SGI1 37 79 TWD 9 AVI 0.18 SG1l 37 79 TWD 11 AV5 0.1 SG11 37 79 TWD 17 AV4 0.17 SGl1 37 79 TWD 16 AV2 0.13 SGl1 38 15 TWD 13 AV2 0.21 SGl1 38 47 TWD 18 AV2
-0.25 SG1l 38 47 TWD 12 AV1 0.11 SGl1 38 47 TWD 32 AV3
-0.34 SG11 38 47 TWD 12 AV4
-0.04 SGl1 38 47 TWD 19 AV5 0.36 SG11 38 49 TWD 17 AV3 0.02 SG11 38 49 TWD 26 AV4 0.03 SG11 38 51 TWD 13 AV2
-0.29 SG11 38 51 TWD 16 AV5 0.15 SGl1 38 51 TWD 18 AV4
-0.15 SGl1 38 56 TWD 26 AV3
-0.49 SG1l 38 56 TWD 35 AV4
-0.08 SG1l 38 56 TWD 35 AV5 0.01 SGl1 38 56 TWD 14 AV2 0.39 SG1l 38 56 TWD 16 AV2
-0.41 SG11 38 56 TWD 21 AV1
-0.23 SG11 38 56 TWD 14 AV6
-0.02 SG11 38 66 TWD 24 AV6 0.1 SG11 38 66 TWD 25 AV5
-0.04 SG11 38 66 TWD 11 AV2 0.01 Page 2 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications AVB Wear)
SG Rowý
('()
111d 0% WT\\\\'upp lnehi SGl1 38 76 TWD 10 AV4 0.1 SG11 38 76 TWD 11 AV2 0.15 SGl1 38 78 TWD 18 AV3
-0.13 SG11 38 78 TWD 19 AV4 0.21 SGl1 38 78 TWD 18 AV6
-0.07 SGl1 38 78 TWD 38 AV5
-0.08 SGl1 38 78 TWD 13 AVI
-0.04 SG11 38 78 TWD 19 AV2 0.17 SG11 38 105 TWD 11 AV4
-0.06 SGl1 38 105 TWD 21 AV2 0.1 SG11 38 105 TWD 23 AV5 0.06 SG11 38 105 TWD 10 AV6 0.1 SG11 38 105 TWD 22 AV3
-0.02 SG11 39 16 TWD 23 AV6
-0.08 SG11 39 16 TWD 45 AV5 0.04 SGl1 39 16 TWD 15 AV4
-0.02 SGl1 39 16 TWD 53 AV2 0.02 SGl1 39 17 TWD 17 AV5 0.02 SG11 39 41 TWD 13 AV2
-0.17 SGl1 39 60 TWD 10 AV4 0.1 SGl1 39 61 TWD 9 AV4 0.27 SG11 39 61 TWD 13 AV5
-0.13 SG11 39 64 TWD 12 AV3 0.04 SG11 39 64 TWD 18 AV4 0.21 SGl1 39 69 TWD 13 AV2 0.13 SGl1 39 72 TWD 15 AV4 0.1 SGl1 39 72 TWD 14 AV2 0.17 SGl1 39 74 TWD 17 AV4
-0.1 SGl1 39 74 TWD 21 AV6 0.29 SG1l 39 74 TWD 26 AV5 0.05 SGl1 39 99 TWD 17 AV5 0.08 SGl1 39 99 TWD 22 AV2
-0.1 SGl1 39 107 TWD 8 AV4 0.31 SGl1 40 18 TWD 20 AV2 0.04 SGl1 40 18 TWD 31 AV3 0.1 SGl1 40 18 TWD 24 AV4 0.04 SGl1 40 18 TWD 34 AV5 0.02 SGl1 40 20 TWD 13 AV3
-0.04 SGl1 40 27 TWD 11 AV4
-0.17 SG1l 40 37 TWD 10 AV2 0.13 SGI1 40 40 TWD 10 AV2
-0.12 Page 3 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
SGlI 40 42 TWD 14 AVI 10.16 SGl1 40 42 TWD 13 AV2 0.1 SG11 40 42 TWD 16 AV4
-0.08 SGl1 40 43 TWD 14 AVI
-0.33 SGl1 40 43 TWD 25 AV4 0.15 SGl1 40 43 TWD 18 AV6 0.15 SGl1 40 43 TWD 30 AV2
-0.12 SG11 40 43 TWD 29 AV3 0.33 SGl1 40 45 TWD 13 AV4 0.02 SGl1 40 45 TWD 15 AV5
-0.04 SG11 40 48 TWD 16 AV2
-0.08 SG11 40 50 TWD 26 AV5
-0.1 SGl1 40 50 TWD 31 AV6 0.1 SGl1 40 50 TWD 21 AV1 0.1 SGl1 40 50 TWD 33 AV2
-0.23 SG11 40 50 TWD 32 AV3
-0.06 SGl1 40 50 TWD 26 AV4
-0.04 SG11 40 58 TWD 15 AV5 0.02 SGl1 40 58 TWD 10 AV4 0.1 SG11 40 58 TWD 14 AV2 0.04 SG1l 40 58 TWD 22 AV6 0.04 SGl1 40 58 TWD 25 AV3 0.02 SG11 40 62 TWD 37 AV2
-0.27 SG11 40 62 TWD 36 AV5 0.1 SG11 40 62 TWD 29 AV4 0.21 SG11 40 62 TWD 11 AV3 0.21 SGl1 40 62 TWD 11 AV3
-0.08 SGl1 40 62 TWD 29 AVI
-0.02 SG11 40 64 TWD 11 AV2
-0.04 SGl1 40 78 TWD 9 AV4
-0.19 SG11 40 78 TWD 12 AV1 0.06 SG11 40 78 TWD 28 AV3
-0.21 SGl1 40 78 TWD 29 AV5 0.31 SG11 40 78 TWD 10 AV6
-0.07 SG11 40 78 TWD 14 AV2
-0.1 SG11 40 79 TWD 17 AV2 0.06 SG11 40 79 TWD 13 AV5 0.19 SGl1 40 79 TWD 7 AV4 0.15 SG1l 40 79 TWD 24 AV3
-0.02 SGl1 40 81 TWD 17 AV4 0.02 SGl1 40 81 TWD 24 AV5
-0.17 Page 4 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
SG Rov col~ Ind
%iWT\\'S~ipp Incti SGl 1 40 81 JTWD 37 AV3 0.04 SG1 40 81 TWD 38 AV2
-0.1 SG1 40 81 TWD 17 AV6
-0.02 SG1 40 84 TWD 16 AV4 0.17 SG11 40 84 TWD 12 AV6 0.1 SG11 40 84 TWD 12 AV5
-0.08 SGl1 40 85 TWD 17 AV2 0.17 SGl1 40 89 TWD 12 AV5
-0.02 SG11 40 89 TWD 19 AV4
-0.04 SG11 40 89 TWD 11 AV3 0.02 SGl1 40 98 TWD 20 AV5
-0.12 SGlI 40 98 TWD 11 AV4 0.21 SGl1 40 104 TWD 27 AV5
-0.02 SG11 40 104 TWD 11 AV3 0.02 SG11 40 104 TWD 24 AV4
-0.02 SGl1 40 104 TWD 7 AV6
-0.02 SG1l 40 105 TWD 14 AV4
-0.04 SG1 40 105 TWD 26 AV6 0.1 SG1l 40 105 TWD 25 AV5 0.12 SG1l 40 105 TWD 8 AV2 0.12 SG11 40 105 TWD 16 AV3 0.02 SG11 40 106 TWD 12 AV5
-0.31 SGl1 40 106 TWD 11 AV6 0.02 SGl1 41 19 TWD 17 AV6 0.02 SGl1 41 53 TWD 28 AV5
-0.04 SG11 41 53 TWD 15 AV6
-0.19 SGI1 41 53 TWD 21 AV3
-0.21 SG11 41 53 TWD 20 AV2
-0.12 SGl1 41 53 TWD 10 AV1 0.21 SG11 41 53 TWD 10 AV4
-0.23 SGl1 41 82 TWD 10 AV4
-0.02 SG11 41 87 TWD 13 AV6
-0.04 SG11 41 90 TWD 13 AV5 0.05 SG11 41 90 TWD 14 AV4 0.08 SG11 41 95 TWD 9 AV5
-0.04 SG11 41 100 TWD 11 AV5
-0.02 SG11 41 100 TWD 11 AV2 0.06 SG11 41 102 TWD 12 AV5 0.08 SGl1 41 102 TWD 11 AV2 0.12 SG11 41 102 TWD 9 AV6
-0.02 SGl1 41 102 TWD 10 AVI -0.08 Page 5 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
SGl1 41 103 TWD 8 AV4
-0.06 SG11 41 103 TWD 8 AV2 0.12 SGl1 41 103 TWD 14 AVI 0.17 SG1l 41 103 TWD 18 AV5
-0.02 SGl1 41 105 TWD 11 AV6
-0.33 SG11 42 19 TWD 34 AV6 0.02 SG11 42 20 TWD 30 AV4 0.02 SG11 42 20 TWD 29 AV3 0.08 SG11 42 20 TWD 30 AV2 0.02 SG1l 42 20 TWD 13 AV1 0.02 SGl1 42 20 TWD 30 AV5 0.02 SGl1 42 33 TWD 23 AV2 0.04 SG11 42 33 TWD 17 AV3
-0.06 SG11 42 50 TWD 10 AV5
-0.02 SGl1 42 78 TWD 10 AV5 0.23 SGll 42 95 TWD 10 AV3 0.02 SGl1 42 95 TWD 11 AV4
-0.02 SGl1 42 97 TWD 10 AV1 0.06 SGl1 42 97 TWD 9 AV3
-0.06 SGl1 42 104 TWD 10 AV6
-0.33 SGl1 42 104 TWD 7 AV6 0.02 SG11 43 20 TWD 21 AV5 0.08 SG11 43 22 TWD 20 AV4 0.02 SG11 43 25 TWD 23 AV4 0.08 SGl1 43 25 TWD 11 AV3 0.02 SG11 43 25 TWD 28 AV5 0.04 SGI1 43 38 TWD 27 AV2
-0.02 SGl1 43 38 TWD 31 AV3 0.08 SG11 43 38 TWD 18 AVI 0.11 SG11 43 41 TWD 34 AV6 0.02 SGl1 43 41 TWD 30 AV5
-0.02 SGl1 43 41 TWD 36 AV4
-0.04 SGl1 43 41 TWD 20 AVI 0.19 SG11 43 41 TWD 20 AV2
-0.19 SGl1 43 41 TWD 30 AV3 0.04 SGl1 43 43 TWD 23 AV3
-0.21 SGl1 43 43 TWD 27 AV5 0.02 SG11 43 43 TWD 27 AV2 0.06 SG11 43 44 TWD 13 AV6 0.17 SG11 43 44 TWD 23 AV5 0.13 SGl1 43 44 TWD 14 AV4
-0.02 Page 6 of 41 Document Control Desk LR-N07-0265 iR18 Service Induced Indications (AVB Wear)
[SGC J
hd~ %\\fls upp ~Ici SG11 43 44 TWD 19 AV3
-0.02 SG11 43 44 TWD 27 AV2
-0.34 SGl1 43 44 TWD 14 AVI
-0.57 SGl1 43 46 TWD 16 AV4 0.04 SG11 43 46 TWD 23 AV6 0.25 SG11 43 49 TWD 12 AV6
-0.02 SG11 43 49 TWD 14 AV3
-0.02 SGl1 43 49 TWD 24 AV4
-0.13 SG11 43 52 TWD 16 AV3 0.04 SGl1 43 75 ITWD 10 AV3
-0.1 SGl1 43 75 TWD 17 AVI
-0.17 SGl1 43 79 TWD 14 AV5 0.08 SGl1 43 79 TWD 13 AV6 0.1 SG11 43 83 TWD 24 AV4
-0.19 SG1l 43 100 TWD 10 AVI 0.12 SG1l 43 100 TWD 18 AV2
-0.02 SG1l 43 100 TWD 21 AV3 0.06 SG1l 44 22 TWD 14 AV4
-0.06 SG11 44 22 TWD 28 AV5 0.02 SG11 44 23 TWD 11 AV5
-0.06 SG11 44 23 TWD 24 AV4
-0.08 SGl1 44 23 TWD 31 AV2
-0.1 SGl1 44 23 TWD 15 AV3
-0.1 SGl1 44 41 TWD 19 AV4
-0.06 SGl1 44 41 TWD 11 AVI 0.08 SG11 44 45 TWD 13 AV3
-0.13 SG11 44 58 TWD 22 AV4 0.08 SG11 44 59 TWD 18 AV3
-0.12 SG1l 44 59 TWD 15 AV4
-0.06 SGl1 44 59 TWD 15 AV2 0.04 SGl1 44 59 TWD 12 AV1 0.14 SGl1 44 60 TWD 16 AV3 0.01 SGl1 44 60 TWD 26 AV4 0.01 SGl1 44 60 TWD 7 AV2 0.06 SGl1 44 68 TWD 21 AV6
-0.08 SGl1 44 68 TWD 16 AV4 -0.1 SGl1 44 68 TWD 15 AV5
-0.08 SGl1 44 68 TWD 14 AV3
-0.06 SG11 44 71 TWD 11 AV6 0.13 SG11 44 71 TWD 12 AV4
-0.02 SG11 44 73 TWD 33 AV3 0.27 Page 7 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear) wSG lol In3Td 29T AV6 0.04li SGl1 44 73 TWD 29 AV6 0.04 SGl1 44 73 TWD 22 AV4 0.27 SG1 1 44 73 TWD 22 AV5 0.33 SG11 44 73 TWD 15 AV5
-0.12 SGl1 44 74 TWD 29 AV3 0.21 SG11 44 74 TWD 15 AV5
-0.15 SGl1 44 74 TWD 16 AV4 0.21 SG11 44 74 TWD 13 AV6
-0.02 SGl1 44 88 TWD 10 AV4 0.02 SG11 44 100 TWD 32 AV5 0.06 SG11 44 102 TWD 8 AV6
-0.27 SG11 44 102 TWD 8 AV5 0.1 SGl1 45 23 TWD 12 AV2 0.31 SG11 45 26 TWD 14 AV3 0.08 SGl1 45 26 TWD 11 AV2
-0.04 SG1l 45 83 TWD 12 AV5
-0.17 SG11 45 100 TWD 9 AV6 0.02 SG11 47 99 TWD 12 AV3
-0.02 SG11 48 26 TWD 12 AV6
-0.25 SG11 48 26 TWD 16 AV5
-0.04 SG11 48 47 TWD 16 AV5 0.06 SGl1 48 97 TWD 11 AV3
-0.04 SGl1 48 97 TWD 10 AV4 0.12 SGl1 49 27 TWD 13 AVI
-0.13 SG1l 49 29 TWD 10 AV4
-0.04 SGl1 49 29 TWD 23 AV5 0.04 SG1l 49 36 TWD 11 AV4
-0.06 SGl1 49 36 TWD 14 AV2
-0.11 SGl1 49 39 TWD 21 AV2 0.04 SGl1 49 39 TWD 13 AV4 0.03 SG11 49 43 TWD 18 AV4 0.15 SG11 49 85 ITWD 10 AV2 0.08 SG11 49 85 TWD 11 AV6 0.02 SG1l 49 85 TWD 27 AV5 0.04 SG1l 49 85 TWD 20 AV3 0.23 SG11 49 85 TWD 28 AV4 0.27 SG11 49 93 TWD 14 AV4 0.1 SGl1 49 93 TWD 26 AV3 0.02 SGl1 49 93 TWD 17 AV2
-0.02 SG1l 49 93 TWD 39 AV5 0.02 SGl1 49 93 TWD 12 AV6 0.02 Page 8 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
SG RowGo
~111(
%"TNVSup~p hich SG1l 49 94 TWD I1 AV6
-0.02 SGl1 49 96 TWD 11 AV6
-0.08 SGl1 50 28 TWD 17 AV4 0.04 SG11 50 28 TWD 21 AV5
-0.1 SG1l 50 28 TWD 13 AV3
-0.15 SG11 50 65 TWD 12 AV2 0.21 SGl1 50 93 TWD 12 AV6
-0.1 SGl1 50 94 TWD 11 AV5
-0.12 SGl1 52 89 TWD 10 AV4
-0.02 SGl1 52 91 TWD 11 AV2 0.25 SGl1 54 39 TWD 14 AV6 0.08 SGl1 54 65 TWD 13 AV4 0.15 SGl1 54 86 TWD 13 AV3 0.12 SG11 54 88 TWD 10 AV3 0.17 SG11 55 82 TWD 10 AV2 0.15 SGl1 55 83 TWD 12 AV5 0.02 SGll 55 83 TWD 12 AV2 0.02 SGl1 55 84 TWD 12 AV6
-0.04 SGl1 55 84 TWD 11 AV5 0.02 SG11 57 70 TWD 12 AVI
-0.1 SGl1 57 77 TWD 14 AV2 0.15 SG11 57 77 TWD 12 AV6
-0.04 SGl1 57 79 TWD 10 AV2 0.09 SGl1 58 61 TWD 11 AV6 0.2 SGl1 58 62 TWD 13 AV.6 0.23 SG11 58 62 TWD 15 AV1
-0.12 SGl1 58 65 TWD 13 AV1
-0.38 SGl1 59 56 TWD 15 AV6 0.44 SGl1 59 58 TWD 12 AV6 0.22 SG12 21 118 TWD 10 AV6 0.15 SG12 21 118 TWD 13 AV1 0.57 SG12 23 89 TWD 10 AV2
-0.04 SG12 23 89 TWD 19 AV6
-0.02 SG12 23 91 TWD 15 AVI
-0.3 SG12 25 116 TWD 11 AVI 0.21 SG12 26 38 TWD 16 AV6
-0.04 SG12 26 74 TWD 11 AV5 0.41 SG12 26 74 TWD 22 AV2
-0.08 SG12 26 83 TWD 15 AV2 0.12 SG12 26 95 TWD 11 AV5 0.23 SG12 26 95 TWD 10 AV2
-0.02 Page 9 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
SG12 26 103 TWD 12 AV2
-0.15 SG12 27 8
TWD 13 AV6
-0.25 SG12 27 8
TWD 24 AV6 0.06 SG12 27 8
TWD 24 AVI 0.08 SG12 27 8
TWD 26 AV1
-0.44 SG12 27 112 TWD 21 AV2 0.09 SG12 27 115 TWD 26 AV6
-0.3 SG12 27 115 TWD 14 AV1 0.45 SG12 28 109 TWD 7 AV5 0.19 SG12 29 13 TWD 16 AV6
-0.44 SG12 29 39 TWD 21 AV5 0.04 SG12 29 39 TWD 22 AV2 0.01 SG12 29 41 TWD 11 AVI 0.1 SG12 29 41 TWD 12 AV2
-0.06 SG12 29 41 TWD 13 AV6
-0.13 SG12 29 41 TWD 11 AV5
-0.08 SG12 29 54 TWD 20 AV5
-0.02 SG12 29 54 TWD 12 AV2
-0.08 SG12 29 54 TWD 17 AV1 0.54 SG12 29 54 TWD 12 AV6 0.06 SG12 29 77 TWD 12 AV2
-0.09 SG12 29 86 TWD 14 AV2 0.04 SG12 29 89 TWD 10 AV2
-0.04 SG12 29 90 TWD 13 AV2 0.14 SG12 29 107 TWD 13 AV2 0.08 SG12 29 108 TWD 21 AV5 0.06 SG12 29 109 TWD 19 AV2 0.04 SG12 29 112 TWD 15 AV5 0.11 SG12 30 12 TWD 11 AV2
-0.17 SG12 30 13 TWD 18 AV2 0.02 SG12 30 104 TWD 13 AV5 0.08 SG12 30 111 TWD 13 AV6 0.02 SG12 30 111 TWD 13 AV3 0.29 SG12 31 16 TWD 8 AV2
-0.14 SG12 31 113 TWD 8 AV2
-0.31 SG12 31 113 TWD 8 AV5 0.53 SG12 32 109 TWD 20 AV4 0.04 SG12 32 110 TWD 9 AV2
-0.06 SG12 32 111 TWD 11 AV1 0.19 SG12 32 111 TWD 22 AV2 0.08 SG12 32 111 TWD 18 AV5 0.08 Page 10 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear).
SG 4 OwN
(,)
11k
(!oT%'
YW:
)
iThj SG12 132 112 TWD 10 AV5
ý0.43 SG12 33 108 TWD 19 AV3 0.1 SG12 33 108 TWD 18 AV5 0.15 SG12 35 110 TWD 10 AV6 0.12 SG12 36 15 TWD 18 AV4 0.04 SG12 36 15 TWD 12 AV3 0.04 SG12 36 15 TWD 7 AV6
-0.06 SG12 36 110 TWD 14 AV3 0.02 SG12 38 15 TWD 9 AV3
-0.5 SG12 38 70 TWD 10 AV3 0.17 SG12 38 70 TWD 13 AV4 0.13 SG12 38 104 TWD 17 AV2 0.02 SG12 38 105 TWD 10 AV6
-0.01 SG12 38 105 TWD 23 AV2 0.07 SG12 38 105 TWD 17 AVI 0.1 SG12 38 105 TWD 34 AV3 0.1 SG12 38 107 TWD 24 AV2 0.02 SG12 38 107 TWD 25 AV3 0.02 SG12 39 48 TWD 14 AV6
-0.05 SG12 39 54 TWD 24 AV6 0.06 SG12 39 55 TWD 12 AV5
-0.02 SG12 39 58 TWD 23 AV4
-0.04 SG12 39 58 TWD 10 AV5 0.19 SG12 39 58 TWD 13 AV2
-0.15 SG12 39 58 TWD 34 AV3 0.02 SG12 39 63 TWD 20 AV4
-0.08 SG12 39 63 TWID 18 AV5
-.0.06 SG12 39 63 TWD 32 AV2 0.19 SG12 39 63 TWID 23 AV3 0.02 SG12 39 65 TWD 13 AV2 0.08 SG12 39 65 TWD 15 AV4 0.04 SG12 39 65 TWD 26 AV3 0.02 SG12 39 72 TWD 15 AV5
-0.08 SG12 39 72 TWD 12 AV3
-0.04 SG12 39 73 TWD 17 AV5 0.42 SG12 39 73 TWD 15 AVI
-0.06 SG12 39 73 TWD 21 AV3
-0.15 SG12 39 73 TWD 8 AV4
-0.08 SG12 39 73 TWD 19 AV6
-0.03 SG12 39 96 TWID 10 AV2
-0.04 SG12 39 100 TWD 10 AV5 0.1 Page 11 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
SG12 40 24 TWD 18 AV4 0.06 SG12 40 24 TWD 20 AV5 0.02 SG12 40 24 TWD 15 AV2 0.02 SG12 40 27 TWD 7 AV5 0.04 SG12 40 30 TWD 9 AV2 0.01 SG12 40 45 TWD 36 AV5 0.08 SG12 40 45 TWD 18 AV4 0.21 SG12 40 45 TWD 24 AV3 0.15 SG12 40 45 TWD 44 AV6 0.1 SG12 40 45 TWD 18 AV2
-0.33 SG12 40 47 TWD 33 AV3 0.02 SG12 40 47 TWD 36 AV4
-0.01 SG12 40 47 TWD 32 AV2 0.02 SG12 40 47 TWD 10 AVI 0.02 SG12 40 47 TWD 31 AV5 0.02 SG12 40 62 TWD 12 AV1
-0.08 SG12 40 62 TWD 34 AV3 0.1 SG12 40 62 TWD 28 AV4 0.27 SG12 40 62 TWD 13 AV5 0.17 SG12 40 69 TWD 10 AV2
-0.04 SG12 40 78 TWD 13 AV4 0.06 SG12 40 80 TWD 10 AV5 0.08 SG12 40 80 TWD 24 AV2 0.02 SG12 40 80 TWD 28 AV3 0.15 SG12 40 80 TWD 22 AV4 0.13 SG12 40 80 TWD 10 AV6 0.25 SG12 40 82 TWD 12 AVI
-0.1 SG12 40 82 TWD 13 AV4 0.21 SG12 40 82 TWD 19 AV5 0.08 SG12 40 82 TWD 28 AV3
-0.02 SG12 40 83 TWD 32 AV5 0.01 SG12 40 83 TWD 23 AV6 0.23 SG12 40 83 TWD 12 AV1
-0.02 SG12 40 83 TWD 23 AV2 0.1 SG12 40 83 TWD 23 AV4 0.1 SG12 40 83 TWD 30 AV3 0.02 SG12 40 84 TWD 11 AV4
-0.04 SG12 40 87 TWD 18 AV3 0.02 SG12 40 87 TWD 8 AV1 0.08 SG12 40 87 TWD 22 AV5 0.02 SG12 40 87 TWD 20 AV2 0.09 Page 12 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
FG jRow
-Co hind >tý,W -SLpp lu1ci SG12 40 87 TWD 17 AV4
-0.02 SG12 40 88 TWD 27 AV1 0.02 SG12 40 88 TWD 21 AV5
-0.02 SG12 40 88 TWD 13 AV4 0.21 SG12 40 88 TWD 28 AV3 0.08 SG12 40 88 TWD 18 AV2
-0.17 SG12 40 91 TWD 37 AV5
-0.04 SG12 40 91 TWD 38 AV4 0.1 SG12 40 91 TWD 21 AV1 0.02 SG12 40 91 TWD 36 AV2 0.13 SG12 40 91 TWD 27 AV6 0.08 SG12 40 91 TWD 33 AV3 0.08 SG12 40 94 TWD 20 AV3 0.17 SG12 40 94 TWD 18 AV5
-0.04 SG12 40 94 TWD 21 AV2 0.06 SG12 40 94 TWD 11 AV4
-0.02 SG12 40 95 TWD 24 AV5 0.1 SG12 40 95 TWD 17 AV3 0.06 SG12 40 95 TWD 25 AV2 0.13 SG12 40 95 TWD 14 AV1
-0.19 SG12 40 96 TWD 18 AV2 0.04 SG12 40 100 TWD 28 AV3
-0.04 SG12 40 100 TWD 14 AVI 0.1 SG12 40 100 TWD 31 AV2
-0.17 SG12 40 100 TWD 31 AV5 0.13 SG12 40 106 TWD 10 AV1 0.02 SG12 40 106 TWD 35 AV3
-0.15 SG12 40 106 TWD 40 AV5 0.04 SG12 40 106 TWD 39 AV4
-0.02 SG12 41 29 TWD 9 AV4
-0.02 SG12 41 29 TWD 12 AV5
-0.13 SG12 41 29 TWD 9 AV3 0.19 SG12 41 56 TWD 10 AV2
-0.17 SG12 41 56 TWD 16 AV3
-0.15 SG12 41 82 TWD 9 AV3
-0.06 SG12 41 82 TWD 10 AV2 0.17 SG12 41 82 TWD 11 AVI
-0.17 SG12 41 83 TWD 8 AV2 0.06 SG12 41 85 TWD 11 AV4 0.19 SG12 41 85 TWD 21 AV3 0.15 SG12 41 87 TWD 29 AV4
-0.06 Page 13 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
SG1 Row 87 T1d 16TWSpp Inch.
SG12 41 87 TWD 16 AV6 0.33 SG12 41 87 TWD 8 AV6
-0.17 SG12 41 87 TWD 17 AV3 0.08 SG12 41 87 TWD 30 AV5 0.02 SG12 41 90 TWD 8 AV4 0.02 SG12 41 90 TWD 10 AV3 0.02 SG12 41 90 TWD 21 AV2 0.08 SG12 41 90 TWD 14 AVI 0.4 SG12 41 90 TWD 15 AV5 0.06 SG12 41 92 TWD 33 AV2
-0.31 SG12 41 92 TWD 25 AV3
-0.02 SG12 41 92 TWD 27 AV4 0.19 SG12 41 92 TWD 23 AV5 0.17 SG12 41 93 TWD 7 AV2 0.13 SG12 41 93 TWvD 15 AV4 0.1 SG12 41 94 TWD 12 AV5
-0.03 SG12 41 95 TWD 10 AV6 0.19 SG12 41 97 TWD 20 AV4 0.08 SG12 41 97 TWD 15 AV6 0.17 SG12 41 97 TWD 10 AV5
-0.1 SG12 41 97 TWD 17 AV3
-0.06 SG12 41 97 TWD 12 AV2 0.08 SG12 41 98 TWD 26 AV2 0.05 SG12 41 98 TWD 10 AV4
-0.06 SG12 41 98 TWD 15 AV5 0.04 SG12 41 98 TWD 21 AV6
-0.02 SG12 41 100 TWD 18 AV3 0.02 SG12 41 100 TWD 22 AV2
-0.42 SG12 41 100 TWD 17 AV1
-0.04 SG12 41 100 TWD 11 AV6 0.19 SG12 41 101 TWD 30 AV6 0.1 SG12 41 101 TWD 27 AV5 0.23 SG12 41 101 TWD 28 AV2 0.02 SG12 41 101 TWD 17 AV1 0.04 SG12 41 102 TWD 21 AV5 0.04 SG12 41 102 TWD 9 AV4
-0.02 SG12 41 102 TWD 8 AV6 0.06 SG12 42 24 TWD 11 AV1 0.24 SG12 42 46 TWD 27 AV5
-0.27 SG12 42 47 TWD 21 AV5 0.01 SG12 42 47 TWD 14 AV2 0.06 Page 14 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
ISG1 Ro Co4 7
id TWD W Sup2 A
0ich SG12 42 47 TWD 28 AV4 0.01 SG12 42 47 TWD 31 AV3 0.02 SG12 42 47 TWD 31 AV6 0.39 SG12 42 47 TWD 11 AVI 0.17 SG12 42 51 TWD 12 AV6 0.1 SG12 42 55 TWD 35 AV5 0.02 SG12 42 55 TWD 18 AV4 0.08 SG12 42 55 TWD 28 AV2
-0.35 SG12 42 55 TWD 26 AV3 0.1 SG12 42 62 TWD 12 AV2 0.06 SG12 42 62 TWD 35 AV3
-0.13 SG12 42 62 TWD 19 AV5 0.1 SG12 42 62 TWD 19 AV6 0.17 SG12 42 62 TWD 36 AV4
-0.04 SG12 42 64 TWD 10 AV6 0.04 SG12 42 64 TWD 33 AV3 0.08 SG12 42 64 TWD 18 AVI 0.04 SG12 42 64 TWD 41 AV5
-0.06 SG12 42 64 TWD 29 AV2 0.02 SG12 42 64 TWD 28 AV4
-0.25 SG12 42 100 TWD 13 AV2 0.17 SG12 42 104 TWD 9 AV6
-0.02 SG12 43 27 TWD 19 AV2
-0.27 SG12 43 40 TWD 25 AV3 0.02 SG12 43 40 TWD 26 AV2 0.06 SG12 43 44 TWD 31 AV4
-0.08 SG12 43 44 TWD 28 AV5 0.04 SG12 43 44 TWD 29 AV3 0.41 SG12 43 44 TWD 18 AV6
-0.04 SG12 43 44 TWD 38 AV2
-0.12 SG12 43 45 TWD 30 AV4
-0.1 SG12 43 45 TWD 11 AV3
-0.29 SG12 43 45 TWD 20 AV5 0.21 SG12 43 97 TWD 11 AV2 0.1 SG12 44 26 TWD 11 AV6
-0.1 SG12 45 100 TWD 8 AV2 0.08 SG12 45 100 TWD 10 AV4
-0.04 SG12 45 101 TWD 34 AV5 0.06 SG12 45 101 TWD 38 AV6 0.04 SG12 45 101 TWD 42 AV4 0.06 SG12 45 101 TWD 34 AV3 0.06 Page 15 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
SG1 46 91 co D
1AV 5 0.08 SG12 46 91 TWD 11 AV5
-0.08 SG12 46 91 TWD 14 AV4
-0.08 SG12 46 94 TWD 10 AV6
-0.04 SG12 46 94 TWD 31 AV5 0.17 SG12 46 97 TWD 24 AV5 0.08 SG12 46 99 TWD 38 AV5
-0.06 SG12 46 99 TWD 13 AV2
-0.06 SG12 46 99 TWD 29 AV6 0.06 SG12 47 24 TWD 13 AV6 0.06 SG12 47 24 TWD 8 AVI 0.08 SG12 47 87 TWD 9 AV6 0.19 SG12 47 95 TWD 15 AV4 0.06 SG12 47 95 TWD 12 AV3 0.08 SG12 47 95 TWD 10 AV5 0.02 SG12 47 98 TWD 16 AV5 0.1 SG12 47 98 TWD 15 AV6 0.08 SG12 48 26 TWD 11 AV6
-0.02 SG12 48 79 TWD 8 AV3 0.15 SG12 48 79 TWD 15 AV2 0.04 SG12 48 83 TWD 14 AV2
-0.02 SG12 48 86 TWD 13 AV2
-0.04 SG12 49 35 TWD 9 AV3
-0.12 SG12 49 60 TWD 11 AV2
-0.1 SG12 49 95 TWvD 13 AV6
-0.02 SG12 49 95 TWD 9 AV4
-0.04 SG12 49 95 TWD 14 AV5 0.08 SG12 49 96 TWD 25 AV5
-0.02 SG12 49 96 TWD 10 AV4
-0.04 SG12 50 67 TWD 24 AV4 0.1 SG12 50 67 TWD 31 AV2 0.02 SG12 50 67 TWD 17 AVI
-0.08 SG12 50 67 TWD 31 AV3 0.06 SG12 50 93 TWD 10 AV6
-0.1 SG12 50 95 TWD 9 AVI 0.17 SG12 51 67 TWD 13 AV2 0.08 SG12 51 82 TWD 12 AV1
-0.08 SG12 51 91 TWD 37 AV3
-0.25 SG12 51 91 TWD 16 AV5 0.08 SG12 51 91 TWD 28 AV4 0.06 SG12 51 91 TWD 13 AV2 0.03 SG12 52 80 TWD 12 AVI
-'0.1 Page 16 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
SG 12 co 1d 5
8TW SupT 4
017nc SG12 52 80 TWD 24 AV2 0.17 SG12 52 80 TWD 9 AV3 0.13 SG12 52 89 TWD 13 AV5
-0.02 SG12 52 90 TWD 9 AV2 0.12 SG12 52 91 TWD 10 AV1 0.25 SG12 53 33 TWD 8 AV3 0.12 SG12 53 34 TWD 13 AV6 0.02 SG12 53 90 TWD 9 AV5
-0.02 SG12 53 90 TWD 8 AVI
-0.02 SG12 54 35 TWD 15 AV6
-0.14 SG12 54 88 TWD 12 AVI 0.11 SG12 56 41 TWD 10 AV6
-0.08 SG12 56 77 TWD 16 AV4
-0.15 SG12 57 44 TWD 13 AV6
-0.1 SG12 57 44 TWD 12 AV4
-0.1 SG12 57 79 TWD 12 AVI 0.06 SG12 58 52 TWD 15 AV6 0.32 SG12 58 58 TWD 12 AV6 0.39 SG12 58 72 TWD 11 AV6 0.51 SG12 59 59 TWD 18 AV6 0.16 SG13 12 2
TWD 13 AV6
-0.43 SG13 12 121 TWD 14 AV1 0.25 SG13 13 78 TWD 10 AV6
-0.2 SG13 19 53 TWD 14 AV1 0.01 SG13 19 78 TWD 12 AVI 0.1 SG13 19 80 TWD 17 AV6
-0.04 SG13 20 81 TWD 11 AV2 0.19 SG13 21 118 TWD 10 AV1 0.33 SG13 21 118 TWD 10 AV6 0.04 SG13 22 5
TWD 23 AV6
-0.33 SG13 23 116 TWD 15 AV1 0.23 SG13 23 117 TWD 21 AVI 0.48 SG13 24 6
TWD 17 AVI
-0.31 SG13 24 7
TWD 21 AV6
-0.18 SG13 24 7
TWD 16 AVI 0.21 SG13 24 8
TWD 13 AVI
-0.23 SG13 24 53 TWD 15 AV2 0.12 SG13 25 7
TWD 21 AV1
-0.21 SG13 25 7
TWD 25 AV6 0.13 SG13 25 31 TWD 18 AV2
-0.27 SG13 25 36 TWD 11 AV5
-0.08 Page 17 of 41
(~4 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
SG13 25 36 TWD 15 AV2 0.06 SG13 25 38 TWD 22 AV2 0.17 SG13 25 115 TWD 16 AV6
-0.17 SG13 26 43 TWD 20 AVI 0.02 SG13 26 43 TWD 16 AV6 0.17 SG13 26 43 TWD 19 AV2 0.02 SG13 26 43 TWD 18 AV5 0.02 SG13 26 80 TWD 14 AV2 0.15 SG13 26 80 TWD 11 AV5 0.15 SG13 26 115 TWD 13 AVI 0.04 SG13 26 115 TWD 11 AV6
-0.1 SG13 26 116 TWD 12 AV6
-0.04 SG13 27 10 TWD 10 AVI 0.04 SG13 27 10 TWD 13 AV5 0.02 SG13 27 11 TWD 14 AV2 0.02 SG13 27 11 TWD 12 AV6
-0.17 SG13 27 12 TWD 12 AV6
-0.08 SG13 27 115 TWD 35 AV1 0.38 SG13 27 115 TWD 22 AV6
-0.19 SG13 27 115 TWD 26 AV6 0.21 SG13 28 52 TWD 14 AV2 0.4 SG13 28 108 TWD 12 AV2 0.08 SG13 28 108 TWD 16 AVI 0.1 SG13 28 109 TWD 12 AVI
-0.13 SG13 30 11 TWD 16 AV6 0.12 SG13 30 46 TWD 20 AV2 0.12 SG13 30 47 TWD 11 AV1
-0.26 SG13 30 47 TWD 13 AV5 0.02 SG13 30 47 TWD 16 AV2
-0.06 SG13 31 32 TWD 11 AV2
-0.21 SG13 31 32 TWD 22 AV5
-0.12 SG13 31 55 TWD 13 AV2 0.04 SG13 31 61 TWD 10 AV5 0.1 SG13 32 14 TWD 13 AV6 0.1 SG13 32 15 TWD 26 AV2
-0.02 SG13 32 16 TWD 24 AV2 0.02 SG13 32 16 TWD 10 AV5 0.02 SG13 32 19 TWD 12 AV2
-0.16 SG13 32 48 TWD 18 AV2
-0.08 SG13 32 80 TWD 12 AV3 0.13 SG13 32 101 TWD 10 AV5 0.13 Page 18 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
SG ?Ro~v(Io 61fi d%
W
(ý'YVSup Inch SG13 32 108 TWD 13 AV5 0.13 SG13 32 110 TWD 17 AV6
-0.06 SG13 32 110 TWD 38 AV5
-0.02 SG13 32 111 TWD 11 AVI 0.12 SG13 32 111 TWD 20 AV6
-0.02 SG13 32 111 TWD 34 AV5 0.04 SG13 32 111 TWD 21 AV3
-0.04 SG13 33 15 TWD 14 AV4
-0.15 SG13 33 15 TWD 12 AV2
-0.08 SG13 34 48 TWD 10 AV6
-0.17 SG13 34 48 TWD 31 AV4
-0.15 SG13 34 48 TWD 12 AV3 0.02 SG13 34 48 TWD 16 AV5 0.02 SG13 34 48 TWD 24 AVI 0.17 SG13 34 48 TWD 16 AV2 0.08 SG13 34 111 TWD 16 AV5 0.25 SG13 34 111 TWD 10 AV2 0.02 SG13 34 111 TWD 16 AVI
-0.04 SG13 34 111 TWD 11 AV6
-0.06 SG13 35 81 TWD 11 AV4
-0.02 SG13 36 14 TWD 12 AV6
-0.2 SG13 36 15 TWD 14 AVI 0.02 SG13 36 43 TWD 13 AV4 0.1 SG13 36 43 TWD 15 AV2
-0.15 SG13 36 43 TWD 14 AV5 0.12 SG13 36 50 TWD 12 AV3 0.02 SG13 36 80 TWD 17 AV5 0.19 SG13 36 80 TWD 20 AV4
-0.02 SG13 36 80 TWD 32 AV3
-0.04 SG13 36 87 TWD 10 AV1 0.06 SG13 36 87 TWD 22 AV6
-0.02 SG13 36 87 TWD 10 AV4 0.02 SG13 36 87 TWD 18 AV3
-0.02 SG13 36 87 TWD 22 AV2 0.02 SG13 36 88 TWD 27 AV4 0.08 SG13 36 88 TWD 15 AVI 0.13 SG13 36 88 TWD 15 AV2 0.13 SG13 36 88 TWD 21 AV6
-0.02 SG13 36 88 TWD 16 AV3
-0.01 SG13 36 88 TWD 19 AV5 0.08 SG13 36 89 TWD 17 AV2 0.08 Page 19 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
S(G Row#- col In
",YW SLIpp1 111_1 SG13 36 89 TWD 11 AV3 0.11 SG13 36 89 TWD 19 AV4
-0.02 SG13 36 89 TWD 14 AV5 0.04 SG13 36 97 TWD 16 AV2 0.08 SG13 36 97 TWD 11 AVI 0.04 SG13 36 97 TWD 21 AV3 0.08 SG13 36 97 TWD 15 AV5 0.02 SG13 36 109 TWD 12 AV2
-0.1 SG13 36 109 TWD 10 AVI 0.37 SG13 36 109 TWD 10 AV6 0.17 SG13 36 109 TWD 13 AVI 0.08 SG13 36 109 TWD 12 AV2 0.1 SG13 36 110 TWD 16 AV6 0.06 SG13 37 58 TWD 11 AV4 0.02 SG13 37 58 TWD 26 AV2 0.02 SG13 37 58 TWD 20 AV6 0.06 SG13 37 58 TWD 33 AV3
-0.02 SG13 37 58 TWD 20 AV5
-0.1 SG13 37 60 TWD 14 AV4 0.04 SG13 37 100 TWD 17 AV2
-0.01 SG13 37 100 TWD 24 AV5 0.02 SG13 37 100 TWD 35 AV3 0.02 SG13 38 15 TWD 13 AV6
-0.55 SG13 38 19 TWD 33 AV4
-0.04 SG13 38 19 TWD 10 AV2
-0.04 SG13 38 19 TWD 20 AV3 0.04 SG13 38 19 TWD 30 AV5 0.16 SG13 38 26 TWD 13 AV3
-0.02 SG13 38 26 TWD 13 AV2 0.04 SG13 38 28 TWD 12 AV2 0.08 SG13 38 28 TWD 20 AV3
-0.02 SG13 38 28 TWD 13 AV6
-0.08 SG13 38 28 TWD 12 AV4 0.08 SG13 38 39 TWD 22 AV3 0.02 SG13 38 39 TWD 17 AV4
-0.15 SG13 38 39 TWD 15 AV4 0.29 SG13 38 39 TWD 36 AV5 0.08 SG13 38 39 TWD 14 AV6 0.1 SG13 38 39 TWD 19 AV2 0.06 SG13 38 53 TWD 22 AV5 0.3 SG13 38 53 TWD 15 AV1 0.02 Page 20 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
Si
<RoW (o
Ind
')%,T\\
WSupp:J)
IThK SG13 38 53 TWD 26 AV2
-0.19 SG13 38 53 TWD 13 AV3
-0.04 SG13 38 53 TWD 14 AV4
-0.02 SG13 38 58 TWD 14 AV6 0.02 SG13 38 58 TWD 20 AV5
-0.1 SG13 38 60 TWD 24 AV5 0.04 SG13 38 60 TWD 15 AV6
-0.14 SG13 38 60 TWD 35 AV4
-0.06 SG13 38 60 TWD 36 AV3
-0.14 SG13 38 60 TWD 40 AV2 0.04 SG13 38 63 TWD 9 AV2
-0.23 SG13 38 63 TWD 11 AV5
-0.04 SG13 38 66 TWD 24 AV3 0.19 SG13 38 66 TWD 14 AV1 0.04 SG13 38 66 TWD 35 AV5 0.15 SG13 38 66 TWD 13 AV2
-0.04 SG13 38 66 TWD 36 AV4 0.1 SG13 38 67 TWD 14 AV3
-0.17 SG13 38 67 TWD 11 AV6 0.02 SG13 38 68 TWD 19 AV6
-0.06 SG13 38 68 TWD 13 AV2 0.1 SG13 38 68 TWD 27 AV4
-0.01 SG13 38 68 TWD 21 AV3 0.08 SG13 38 68 TWD 39 AV5
-0.17 SG13 38 69 TWD 16 AV2 0.02 SG13 38 70 TWD 11 AV1 0.04 SG13 38 70 TWD 21 AV5
-0.14 SG13 38 70 TWD 33 AV4
-0.37 SG13 38 70 TWD 17 AV3
-0.1 SG13 38 72 TWD 32 AV4 0.25 SG13 38 72 TWD 11 AV5 0.15 SG13 38 72 TWD 28 AV3 0.15 SG13 38 72 TWD 30 AV2 0.1 SG13 38 73 TWD 9 AV3
-0.35 SG13 38 73 TWD 11 AV2
-0.02 SG13 38 81 TWD 16 AV6 0.04 SG13 38 81 TWD 16 AV5
-0.02 SG13 38 82 TWD 15 AV3 0.17 SG13 38 83 TWD 11 AV2 0.06 SG13 38 83 TWD 16 AV4
-0.02 SG13 38 83 TWD 23 AV5 0.19 Page 21 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
SG Row
(()
111' (J~fT W S
Inp1ch SG13 38 83 TWD 27 AV3
-0.04 SG13 38 85 TWD 18 AV4 0.08 SG13 38 85 TWD 10 AVI 0.04 SG13 38 85 TWD 16 AV3
-0.02 SG13 38 86 TWD 35 AV4 0.04 SG13 38 86 TWD 34 AV5
-0.04 SG13 38 86 TWD 29 AV3
-0.01 SG13 38 86 TWD 20 AVI 0.23 SG13 38 86 TWD 30 AV2 0.1 SG13 38 86 TWD 14 AV6 0.35 SG13 38 86 TWD 26 AV6
-0.15 SG13 38 88 TWD 11 AV4 0.04 SG13 38 88 TWD 21 AV3 0.06 SG13 38 88 TWD 10 AV2 0.02 SG13 38 91 TWD 18 AV2 0.08 SG13 38 91 TWD 27 AV5
-0.06 SG13 38 91 TWD 17 AV6 0.02 SG13 38 91 TWD 13 AV4 0.04 SG13 38 91 TWD 14 AV3 0.08 SG13 38 92 TWD 15 AV4 0.04 SG13 38 92 TWD 13 AV2 0.21 SG13 38 92 TWD 21 AV5 0.12 SG13 38 93 TWD 40 AV5 0.08 SG13 38 93 TWD 14 AV6
-0.08 SG13 38 93 TWD 21 AV2
-0.12 SG13 38 93 TWD 13 AVI 0.02 SG13 38 93 TWD 23 AV4
-0.02 SG13 38 94 TWD 17 AV4 0.08 SG13 38 94 TWD 16 AV6
-0.1 SG13 38 94 TWD 33 AV3 0.15 SG13 38 94 TWD 27 AV2 0.13 SG13 38 94 TWD 17 AV5 0.06 SG13 38 98 TWD 24 AV3
-0.02 SG13 38 98 TWD 20 AV6 0.04 SG13 38 98 TWD 22 AV2 0.14 SG13 38 101 TWD 15 AV5 0.23 SG13 38 101 TWD 9 AV3
-0.06 SG13 38 106 TWD 37 AV6 0.06 SG13 38 106 TWD 40 AV5 0.02 SG13 38 106 TWD 39 AV4 0.06 SG13 38 106 TWD 47 AV2 0.04 Page 22 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
SG; Row
(,()
11d<
IWS-Upp -Inch-SG13 38 106 TWD 28 AV3 0.06 SG13 39 16 TWD 13 AV6
-0.61 SG13 39 16 TWD 9 AVI 0.02 SG13 39 20 TWD 16 AV5
-0.04 SG13 39 22 TWD 15 AV5 0.1 SG13 39 22 TWD 15 AV4
-0.02 SG13 39 22 TWD 13 AV3 0.06 SG13 39 22 TWD 16 AV2
-0.04 SG13 39 23 TWD 11 AV5
-0.2 SG13 39 33 TWD 26 AV3
-0.02 SG13 39
- 33.
TWD 27 AV4 0.08 SG13 39 33 TWD 29 AV2
-0.02 SG13 39 33 TWD 35 AV5 0.04 SG13 39 35 TWD 27 AV5 0.25 SG13 39 35 TWD 11 AV2
-0.19 SG13 39 35 TWD 18 AV3 0.08 SG13 39 38 TWD 20 AV2 0.06 SG13 39 38 TWD 28 AV3
-0.29 SG13 39 38 TWD 25 AV5
-0.1 SG13 39 38 TWD 17 AV6
-0.12 SG13 39 46 TWD 14 AV2
-0.1 SG13 39 47 TWD 22 AV6 0.36 SG13 39 47 TWD 34 AV2
-0.04 SG13 39 47 TWD 28 AV4 0.17 SG13 39 47 TWD 27 AV3
-0.08 SG13 39 47 TWD 37 AV5 0.08 SG13 39 51 TWD 12 AVI 0.14 SG13 39 51 TWD 32 AV6
-0.08 SG13 39 51 TWD 24 AV4
-0.08 SG13 39 51 TWD 18 AV5 0.16 SG13 39 51 TWD 33 AV2 0.14 SG13 39 51 TWD 30 AV3
-0.02 SG13 39 53 TWD 12 AV4
-0.06 SG13 39 53 TWD 15 AV3
-0.12 SG13 39 54 TWD 21 AV4 0.08 SG13 39 54 TWD 11 AV6 0.23 SG13 39 54 TWD 27 AV3 0.02 SG13 39 58 TWD 35 AV4
-0.02 SG13 39 58 TWD 35 AV5 0.01 SG13 39 58 TWD 16 AV6
-0.17 SG13 39 58 TWD 40 AV3
-0.08 Page 23 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear
___RowCol
>nd
" ' N Supp 11C1 SG13 39 58 TWD 32 AV2
-0.04 SG13 39 58 TWD 34 AV1
-0.12 SG13 39 64 TWD 12 AV2
-0.21 SG13 39 65 TWD 32 AV2
-0.08 SG13 39 65 TWD 15 AV3 0.19 SG13 39 65 TWD 18 AV1 0.17 SG13 39 65 TWD 16 AV5
-0.08 SG13 39 65 TWD 10 AV3
-0.02 SG13 39 65 TWD 16 AV4
-0.02 SG13 39 66 TWD 28 AV6 0.15 SG13 39 66 TWD 11 AVI
-0.02 SG13 39 66 TWD 38 AV2 0.06 SG13 39 66 TWD 22 AV5 0.06 SG13 39 66 TWD 35 AV3 0.15 SG13 39 66 TWD 27 AV4
-0.04 SG13 39 70 TWD 40 AV5 0.1 SG13 39 70 TWD 40 AV4 0.14 SG13 39 70 TWD 32 AV3 0.17 SG13 39 70 TWD 29 AV2
-0.12 SG13 39 76 TWD 25 AV6
-0.04 SG13 39 76 TWD 13 AV1
-0.02 SG13 39 76 TWD 29 AV3 0.15 SG13 39 76 TWD 14 AV5 0.1 SG13 39 76 TWD 39 AV2
-0.02 SG13 39 76 TWD 21 AV4 0.29 SG13 39 80 TWD 13 AV6 0.04 SG13 39 80 TWD 23 AV2
-0.04 SG13 39 87 TWD 11 AV5 0.23 SG13 39 87 TWD 11 AV6 0.12 SG13 40 19 TWD 17 AV3
-0.02 SG13 40 57 TWD 10 AV2
-0.15 SG13 40 62 TWD 11 AVI 0.08 SG13 40 62 TWD 25 AV2
-0.02 SG13 40 62 TWD 30 AV3 0.06 SG13 40 62 TWD 36 AV4
-0.04 SG13 40 62 TWD 42 AV5
-0.02 SG13 40 82 TWD 26 AV5
-0.02 SGI3 40 82 TWD 16 AVI 0.1 SG13 40 82 TWD 39 AV3 0.39 SG13 40 82 TWD 40 AV2 0.35 SG13 40 82 TWD 27 AV6
-0.14 Page 24 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
Fs G Row C'oR
-111(i T
SuppfJ 111C1 SG13 40 82 TWD 35 AV4 0.06 SG13 40 100 TWD 14 AV5
-0.02 SG13 41 20 TWD 11 AV5
-0.06 SG13 41 20 TWD 34 AV4 0.02 SG13 41 20 TWD 15 AV3 0.06 SG13 41 20 TWD 12 AV6
-0.08 SG13 41 31 TWD 28 AV4
-0.12 SG13 41 31 TWD 23 AV5
-0.06 SG13 41 33 TWD 14 AV6 0.04 SG13 41 33 TWD 12 AV4 0.08 SG13 41 33 TWD 10 AV2
-0.08 SG13 41 33 TWD 12 AV5 0.04 SG13 41 33 TWD 16 AV3 0.04 SG13 41 66 TWD 10 AV4 0.08 SG13 41 79 TWD 16 AV2
-0.04 SG13 41 85 TWD 36 AV3
-0.02 SG13 41 85 TWD 15 AV4 0.02 SG13 41 85 TWD 36 AV5
-0.02 SG13 41 85 TWD 20 AV6
-0.15 SG13 41 85 TWD 34 AV2 0.06 SG13 41 92 TWD 12 AV2
-0.02 SG13 41 92 TWD 35 AV3 0.02 SG13 41 92 TWD 25 AV4 0.02 SG13 41 96 TWD 14 AV2
-0.06 SG13 41 96 TWD 25 AV3 0.1 SG13 41 104 TWD 20 AV3
-0.02 SG13 41 104 TWD 29 AV2 0.02 SG13 41 104 TWD 12 AVI 0.02 SG13 41 104 TWD 14 AV6 0.06 SG13 41 104 TWD 37 AV5 0.08 SG13 41 104 TWD 20 AV4 0.14 SG13 41 105 TWD 11 AV2 0.12 SG13 42 19 TWD 15 AV4
-0.06 SG13 42 19 TWD I11 AV3 0.04 SG13 42 19 TWD 13 AVI 0.08 SG13 42 33 TWD 10 AVI 0.06 SG13 42 33 TWD 21 AV2
-0.04 SG13 42 33 TWD 33 AV3 0.06 SG13 42 33 TWD 36 AV4 0.22 SG13 42 38 TWD 27 AV4
-0.04 SG13 42 38 TWD 22 AV3
-0.27 Page 25 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
SG1 Row 8o 0
I2Ch SG13 42 38 TWD 13 AV2 0.02 SG13 42 38 TWD 16 AV5 0.04 SG13 42 38 TWD 15 AV6
-0.06 SG13 42 41 TWD 11 AVI
-0.19 SG13 42 41 TWD 16 AV3
-0.1 SG13 42 41 TWD 30 AV4
-0.08 SG13 42 41 TWD 35 AV6 0.08 SG13 42 41 TWD 24 AV2 0.04 SG13 42 41 TWD 39 AV5 0.1 SG13 42 42 TWD 15 AV6 0.02 SG13 42 42 TWD 11 AVI
-0.22 SG13 42 42 TWD 35 AV2
-0.12 SG13 42 42 TWD 35 AV5 0.02 SG13 42 42 TWD 39 AV3
-0.02 SG13 42 42 TWD 39 AV4
-0.1 SG13 42 46 TWD 7 AV2 0.04 SG13 42 53 TWD 10 AVI
-0.08 SG13 42 53 TWD 13 AV4
-0.08 SG13 42 100 TWD 13 AV6
-0.06 SG13 42 104 TWD 14 AV2
-0.02 SG13 42 104 TWD 11I AVI 0.33 SG13 43 23 TWD 11 AV3 0.06 SG13 43 57 TWD 11 AV4
-0.14 SG13 43 62 TWD 10 AV6
-0.15 SG13 43 62 TWD 21 AV5
-0.12 SG13 43 64 TWD 12 AV5
-0.15 SG13 43 64 TWD 13 AV3 0.08 SG13 43 64 TWD 29 AV4 0.21 SG13 43 66 TWD 10 AV6 0.1 SG13 43 66 TWD 19 AV5 0.06 SG13 43 66 TWD 36 AV4 0.12 SG13 43 66 TWD 18 AV3 0.23 SG13 43 66 TWD 24 AV2
-0.02 SG13 43 68 TWD 33 AV5
-0.1 SG13 43 68 TWD 33 AV3 0.08 SG13 43 68 TWD 36 AV4 0.19 SG13 43 68 TWD 38 AV2
-0.13 SG13 43 69 TWD 16 AV6
-0.12 SG13 43 69 TWD 21 AV5 0.1 SG13 43 69 TWD 16 AV4 0.04 SG13 43 69 TWD 13 AV3 0.1 Page 26 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
SG13 43 71 TWD 18 AV5 0.08 SG13 43 72 TWD 13 AV4 0.25 SG13 43 72 TWD 23 AV6 0.21 SG13 43 73 TWD 15 AV5 0.12 SG13 43 73 TWD 18 AV3
-0.31 SG13 43 73 TWD 12 AV6 0.12 SG13 43 75 TWD 15 AV6 0.12 SG13 43 75 TWD 11 AV3 0.39 SG13 43 75 TWD 11 AV4 0.52 SG13 43 75 TWD 22 AV5 0.04 SG13 43 77 TWD 10 AV4
-0.04 SG13 43 77 TWD 13 AV5
-0.1 SG13 43 80 TWD 13 AVI 0.1 SG13 43 80 TWD 25 AV5 0.17 SG13 43 80 TWD 28 AV4
-0.04 SG13 43 80 TWD 23 AV2 0.17 SG13 43 80 TWD 25 AV3
-0.12 SG13 43 81 TWD 29 AV6 0.02 SG13 43 81 TWD 16 AV5
-0.08 SG13 43 81 TWD 15 AV3 0.29 SG13 43 81 TWD 25 AV2 0.06 SG13 43 83 TWD 10 AVI 0.17 SG13 43 85 TWD 18 AV2 0.14 SG13 43 91 TWD 16 AV4 0.02 SG13 43 91 TWD 17 AV3 0.02 SG13 43 93 TWD 16 AV2
-0.12 SG13 43 96 TWD 12 AV4 0.04 SG13 43 99 TWD 11 AV2 0.02 SG13 43 99 TWD 29 AV5 0.19 SG13 43 99 TWD 19 AV3 0.1 SG13 43 99 TWD 40 AV4 0.08 SG13 44 25 TWD 10 AV3
-0.08 SG13 44 25 TWD 14 AV2
-0.1 SG13 44 26 TWD 17 AV2
-0.18 SG13 44 26 TWD 14 AV3
-0.1 SG13 44 26 TWD 14 AV4
-0.12 SG13 44 59 TWD 13 AV2 0.08 SG13 44 60 TWD 19 AV3
-0.04 SG13 44 65 TWD 39 AV6 0.29 SG13 44 65 TWD 21 AV4 0.19 SG13 44 65 TWD 12 AV5
-0.04 Page 27 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
SG RowT Co)l 11d~ %§IWJ Spp)J Iinch 2 SG13 44 65 TWD 46 AV2
-0.06 SG13 44 65 TWD 40 AV3 0.08 SG13 44 65 TWD 12 AVI
-0.12 SG13 44 67 TWD 10 AV5 0.1 SG13 44 68 TWD 27 AVI 0.1 SG13 44 68 TWD 24 AV3 0.02 SG13 44 68 TWD 23 AV4 0.15 SG13 44 68 TWD 27 AV5 0.35 SG13 44 68 TWD 24 AV2
-0.04 SG13 44 71 TWD 11 AV2 0.15 SG13 44 76 TWD 16 AV3
-0.27 SG13 44 77 TWD 12 AV2 0.08 SG13 44 77 TWD 16 AV3
-0.02 SG13 44 77 TWD 10 AV4 0.08 SG13 44 85 TWD 8 AV4
-0.38 SG13 44 95 TWD 13 AV4 0.04 SG13 44 100 TWD 13 AV5 0.04 SG13 44 102 TWD 38 AV5 0.06 SG13 44 102 TWD 13 AV4 0.08 SG13 44 102 TWD 8 AVI 0.23 SG13 44 102 TWD 42 AV6 0.04 SG13 45 22 TWD 12 AV5
-0.47 SG13 45 23 TWD 12 AV6
-0.41 SG13 45 65 TWD 22 AV3
-0.19 SG13 45 65 TWD 44 AV4 0.14 SG13 45 65 TWD 17 AV2 0.21 SG13 45 65 TWD 31 AV5 0.21 SG13 45 65 TWD 29 AV3 0.14 SG13 45 65 TWD 12 AV6
-0.1 SG13 45 66 TWD 10 AV2 0.02 SG13 45 95 TWD 18 AV6 0.08 SG13 45 95 TWD 13 AV4 0.06 SG13 45 96 TWD 36 AV6 0.06 SG13 45 96 TWD 13 AV3 0.1 SG13 45 96 TWD 15 AV4 0.1 SG13 45 97 TWD 21 AV4 0.06 SG13 46 24 TWD 12 AV6 0.06 SG13 46 24 TWD 25 AV5
-0.1 SG13 46 62 TWD 41 AV3
-0.1 SG13 46 62 TWD 38 AV4 0.1 SG13 46 62 TWD 22 AV2 0.19 Page 28 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
SG Ro4 C65 WD 33 AV pp- 0.0 SG13 46 65 TWD 33 AV5
-0.08 SG13 46 65 TWD 17 AV3
-0.06 SG13 46 65 TWD 32 AV3
-0.15 SG13 46 65 TWD 28 AV6 0.35 SG13 46 65 TWD 21 AV2 0.23 SG13 46 65 TWD 25 AV4
-0.02 SG13 46 73 TWD 24 AV2
-0.02 SG13 46 73 TWD 12 AV3 0.25 SG13 46 77 TWD 6 AV4 0.081 SG13 46 77 TWD 10 AV5
-0.1 SG13 47 24 TWD 13 AV3
-0.04 SG13 47 24 TWD 39 AV5
-0.06 SG13 47 24 TWD 30 AV6 0.02 SG13 47 25 TWD 22 AV5 0.02 SG13 47 25 TWD 18 AV6
-0.1 SG13 47 25 TWD 12 AV4
-0.08 SG13 47 26 TWD 10 AV5 0.08 SG13 47 26 TWD 15 AV6 0.08 SG13 47 96 TWD 18 AV6 0.04 SG13 47 96 TWVD 38 AV4 0.08 SG13 47 96 TWD 27 AV2
-0.06 SG13 47 99 TWD 13 AV1 0.19 SG13 47 99 TWD 20 AV5 0.04 SG13 47 99 TWD 40 AV6
-0.02 SG13 48 25 TWD 12 AV4
-0.35 SG13 48 25 TWD 13 AV2
-0.1 SG13 48 26 TWD 8 AVI 0.47 SG13 48 91 TWD 22 AV3 0.06 SG13 48 91 TWD 15 AV2 0.04 SG13 48 91 TWD 33 AV4 0.04 SG13 48 91 TWD 10 AV6
-0.04 SG13 48 94 TWD 10 AV2 0.08 SG13 48 95 TWD 14 AV3 0.02 SG13 48 97 TWD 43 AV5 0.04 SG13 48 97 TWD 29 AV4 0.08 SG13 48 97 TWD 27 AV2 0.1 SG13 48 98 TWD 11 AV6
-0.02 SG13 49 27 TWD 12 AV1 0.24 SG13 49 31 TWD 35 AV6 0.02 SG13 49 31 T"D 35 AV5 0.02 SG13 49 31 TWD 22 AV3 0.04 Page 29 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
SG Row C'o Ind
%"(TW\\ Sipp Ic SG13 49 31 TWD 34 AV4
-0.04 SG13 49 31 TWD 19 AV2
-0.1 SG13 49 32 TWD 10 AV5
-0.02 SG13 49 32 TWD 12 AV4
-0.12 SG13 49 53 TWD 16 AV5 0.16 SG13 49 92 TWD 12 AV4 0.04 SG13 49 93 TWD 11 AV6 0.01 SG13 49 94 TWD 21 AV5
-0.02 SG13 49 94 TWD 25 AV6 0.02 SG13 49 95 TWD 22 AV4 0.08 SG13 49 96 TWD 42 AV4 0.04 SG13 49 96 TWD 37 AV5 0.02 SG13 49 96 TWD 29 AV6 0.06 SG13 49 96 TWD 44 AV3 0.08 SG13 49 96 TWD 20 AV2 0.08 SG13 50 28 TWD 15 AV4
-0.18 SG13 50 28 TWD 13 AV5
-0.41 SG13 50 79 TWD 39 AV2 0.06 SG13 50 79 TWD 11 AVI
-0.1 SG13 50 79 TWD 22 AV4 0.12 SG13 50 79 TWD 39 AV3 0.21 SG13 50 84 TWD 23 AV4 0.35 SG13 50 84 TWD 12 AVI 0.08 SG13 50 84 TWD 18 AV2 0.21 SG13 50 84 TWD 25 AV2
-0.1 SG13 50 84 TWD 38 AV3 0.29 SG13 50 87 TWD 11 AV5 0.1 SG13 50 88 TWD 17 AV4 0.08 SG13 50 88 TWD 36 AV5
-0.02 SG13 50 88 TWD 10 AV3 0.06 SG13 50 92 TWD 35 AV4 0.08 SG13 50
- 92.
TWD 38 AV5 0.02 SG13 50 92 TWD 35 AV6 0.04 SG13 50 92 TWD 28 AV3
-0.04 SG13 50 92 TWD 16 AV2 0.06 SG13 50 93 TWD 20 AV5 0.02 SG13 50 94 TWD 19 AV1 0.04 SG13 50 94 TWD 27 AV2 0.04 SG13 50 94 TWD 13 AV6
-0.02 SG13 51 50 TWD 19 AV6
-0.02 SG13 51 50 TWD 16 AV4
-0.12 Page 30 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
SG13 51 50 TWD 18 AV5
-0.14 SG13 51 55 TWD 12 AV4
-0.17 SG13 51 55 TWD 10 AV6
-0.14 SG13 51 55 TWD 24 AV5
-0.02 SG13 51 57 TWD 11 AV5 0.02 SG13 51 79 TWD 10 AV2 0.08 SG13 51 79 TWD 12 AV1
-0.08 SG13 51 91 TWD 17 AV4 0.04 SG13 51 92 TWD 19 AV2
-0.12 SG13 51 92 TWD 10 AV4 0.06 SG13 51 92 TWD 25 AV5
-0.02 SG13 52 32 TWD 10 AV3
-0.02 SG13 52 34 TWD 22 AV6
-0.04 SG13 52 34 TWD 9 AV5
-0.06 SG13 52 89 TWD 22 AV3 0.06 SG13 52 89 TWD 15 AV5 0.04 SG13 52 89 TWD 25 AV2 0.1 SG13 52 89 TWD 12 AV1
-0.04 SG13 53 57 TWD 22 AV3 0.02 SG13 53 57 TWD 16 AV2
-0.08 SG13 53 57 TWD 16 AV4
-0.04 SG13 53 57 TWD 12 AV1
-0.21 SG13 53 58 TWD 11 AV2
-0.06 SG13 53 69 TWD 13 AV2 0.05 SG13 53 72 TWD 24 AV4 0.12 SG13 53 72 TWD 12 AV5 0.06 SG13 53 88 TWD 16 AV4 0.12 SG13 53 88 TWD 21 AV5 0.08 SG13 53 89 TWD 12 AV6
-0.08 SG13 54 35 TWD 20 AV3 0.04 SG13 54 35 TWD 26 AV4 0.02 SG13 54 35 TWD 26 AV5 0.06 SG13 54 37 TWD 16 AV5
-0.08 SG13 54 37 TWD 12 AV2
-0.06 SG13 54 37 TWD 16 AV3
-0.02 SG13 54 37 TWD 23 AV4
-0.02 SG13 54 65 TWD 19 AV2 0.08 SG13 54 65 TWD 71 AV3 0.21 SG13 54 65 TWD 49 AV4 0.12 SG13 54 65 TWD 30 AV6 0.14 SG13 54 65 TWD 28 AV5 0.19 Page 31 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
ýSQ
(,R)]
111d
'ýJW SLupp1 InCeb SG13 54 65 TWD 13 AVI
-0.02 SG13 54 71 TWD 13 AV5
-0.02 SG13 54 72 TWD 15 AV5
-0.02 SG13 54 73 TWD 45 AV3 0.06 SG13 54 73 TWD 32 AV6
-0.04 SG13 54 73 TWD 30 AV4
-0.12 SG13 54 73 TWD 52 AV5 0.06 SG13 54 73 TWD 33 AV4 0.19 SG13 54 75 TWD 24 AV2 0.06 SG13 54 75 TWD 12 AV3
-0.15 SG13 54 76 TWD 11 AVI
-0.04 SG13 54 86 TWD 11 AVI 0.06 SG13 54 86 TWD 10 AV3 0.06 SG13 55 84 TWD 10 AV5 0.08 SG13 56 66 TWD 11 AV3 0.08 SG13 56 81 TWD 12 AV6 0.08 SG13 57 73 TWD 11 AV3
-0.08 SG13 57 78 TWD 13 AV6
-0.02 SG13 57 78 TWD 14 AV2 0.06 SG13 57 78 TWD 11 AVI 0.08 SG13 57 79 TWD 13 AV2
-0.02 SG13 58 47 TWD 39 AV4 0.04 SG13 58 47 TWD 32 AV5
-0.08 SG13 58 47 TWD 15 AV3
-0.02 SG13 58 52 TWD 11 AV6 0.1 SG13 58 55 TWD 14 AV1
-0.1 SG13 58 67 TWD 11 AVI
-0.18 SG13 58 73 TWD 11 AV6 0.04 SG13 58 75 TWD 15 AV3 0.12 SG13 58 75 TWD 8 AV2
-0.04 SG13 58 76 TWD 11 AV5 0.01 SG13 58 76 TWD 11 AV3 0.21 SG13 58 76 TWD 10 AV6 0.12 SG13 59 61 TWD 9 AV6 0.48 SG13 59 61 TWD 14 AVI
-0.14 SG14 20 5
TWD 9 AV1 0.01 SG14 23 6
TWD 17 AVI 0.53 SG14 24 6
TWD 23 AVI
-0.16 SG14 24 7
TWD 15 AV6
-0.25 SG14 24 8
TWD 17 AV1
-0.22 SG14 24 116 TWD 27 AVI
-0.23 Page 32 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
SG-Roxýi (C& Ind~ ""7A
~ppj Incl~
SG14 24 116 TWD 17 AV6 0.48 SG14 24 117 TWD 6 AV6 0.36 SG14 25 7
TWD 19 AVI
-0.27 SG14 25 7
TWD 19 AV6
-0.2 SG14 25 8
TWD 32 AVI
-0.29 SG14 25 9
TWD 11 AV5 0.18 SG14 25 35 TWD 12 AV6
-0.25 SG14 25 36 TWD 21 AV6
-0.1 SG14 25 44 TWD 16 AV5 0.03 SG14 25 109 TWD 14 AV6 0.19 SG14 25 115 TWD 23 AV6 0.02 SG14 26 7
TWD 16 AV6
-0.27 SG14 26 7
TWD 24 AVI
-0.27 SG14 26 8
TWD 34 AVI
-0.24 SG14 26 8
TWD 12 AV6
-0.24 SG14 26 109 TWD 9 AV5 0.32 SG14 26 113 TWD 10 AV5 0.06 SG14 26 114 TWD 12 AV2
-0.08 SG14 26 115 TWD 17 AV6 0.02 SG14 26 115 TWD 32 AVI 0.06 SG14 26 116 TWD 14 AV1
-0.25 SG14 26 116 TWD 10 AV6 0.42 SG14 27 8
TWD 14 AV6 0.1 SG14 27 8
TWD 19 AV6
-0.24 SG14 27 8
TWD 19 AV1 0.31 SG14 27 8
TWD 29 AVI
-0.12 SG14 27 79 TWD 18 AV6 0.02 SG14 27 79 TWD 24 AV5 0.42 SG14 27 79 TWD 24 AV2 0.08 SG14 27 114 TWD 19 AV2
-0.08 SG14 28 9
TWD 15 AV6 0.04 SG14 28 9
TWD 28 AV2 0.49 SG14 28 9
TWD 20 AV5
-0.26 SG14 28 12 TWD 16 AV6 0.12 SG14 28 14 TWD 12 AV6 0.06 SG14 28 38 TWD 23 AV2 0.08 SG14 28 38 TWD 16 AV5 0.14 SG14 28 81 TWD 16 AV5 0.25 SG14 28 109 TWD 11 AV1 0.02 SG14 28 111 TWD 14 AV2 0.06 SG14 28 111 TWD 9 AV5 0.1 Page 33 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
SG Row Col111
,,,\\ WSuppnchih SG14 28 11,3 TWD 10 AV6 0.08 SG14 28 113 TWD 15 AV2
-0.1 SG14 28 113 TWD 18 AV5 0.1 SG14 29 11 TWD 10 AV6
-0.04 SG14 29 109 TWD 15 AV6
-0.11 SG14 29 109 TWD 11 AV2
-0.2 SG14 29 110 TWD 20 AV5
-0.11 SG14 29 110 TWD 10 AVI
-0.25 SG14 29 110 TWD 11 AV2 0.03 SG14 29 111 TWD 11 AVI 0.04 SG14 29 111 TWD 18 AV5
-0.14 SG14 30 10 TWD 14 AVI
-0.1 SG14 30 10 TWD 21 AV5 0.96 SG14 30 10 TWD 14 AV5
-1.0 SG14 30 10 TWD 38 AV2
-1.0 SG14 30 14 TWD 10 AV6 0.1 SG14 30 18 TWD 11 AV6
-0.14 SG14 30 63 TWD 12 AVI 0.02 SG14 30 63 TWD 25 AV5 0.32 SG14 30 63 TWD 32 AV2 0.02 SG14 30 72 TWD 20 AV2 0.25 SG14 30 72 TWD 13 AV6 0.02 SG14 30 76 TWD 16 AV5 0.02 SG14 30 107 TWD 7 AV1 0.02 SG14 30 107 TWD 17 AV5 0.27 SG14 30 111 TWD 13 AV2 0.1 SG14 30 114 TWD 10 AV2
-0.5 SG14 31 10 TWD 39 AV2 0.78 SG14 31 10 TWD 18 AV1
-0.17 SG14 31 10 TWD 11 AV6 0.04 SG14 31 10 TWD 39 AV5
-0.8 SG14 31 10 TWD 24 AV5 0.68 SG14 31 11 TWD 16 AV6
-0.06 SG14 32 12 TWD 26 AV4
-0.06 SG14 32 12 TWD 28 AV5 0.12 SG14 32 84 TWD 12 AV3
-0.17 SG14 32 84 TWD 25 AV5 0.06 SG14 32 84 TWD 26 AV2 0.08 SG14 32 109 TWD 17 AV2 0.02 SG14 32 111 TWD 20 AV2 0.02 SG14 32 111 TWD 13 AV6 0.06 Page 34 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
SG4 Ro Col 111d AT V
1 0.0 6 SG14 32 111 TWD 12 AV5 0.06 SG14 32 111 TWD 39 AV5 0.17 SG14 32 112 TWD 10 AV5 0.52 SG14 33 12 TWD 19 AV5 0.18 SG14 33 12 TWD 28 AV2 0.04 SG14 33 12 TWD 20 AV6 0.1 SG14 34 108 TWD 9 AV2 0.13 SG14 34 108 TWD 13 AV3 0.1 SG14 34 108 TWD 12 AV6
-0.02 SG14 34 108 TWD 23 AV4
-0.04 SG14 34 109 TWD 28 AV3 0.13 SG14 34 109 TWD 28 AV4 0.33 SG14 34 111 TWD 11 AV2
-0.61 SG14 34 111 TWD 10 AV6 0.38 SG14 37 83 TWD 13 AV6 0.13 SG14 37 83 TWD 10 AV2 0.08 SG14 37 83 TWD 10 AV4 0.36 SG14 37 83 TWD 38 AV5 0.32 SG14 37 83 TWD 11 AVI 0.11 SG14 37 102 TWD 10 AV5 0.17 SG14 37 103 TWD 17 AV5 0.04 SG14 38 32 TWD 15 AV3 0.02 SG14 38 40 TWD 10 AV1
-0.22 SG14 38 40 TWD 40 AV2 0.03 SG14 38 40 TWD 37 AV4 0.1 SG14 38 40 TWD 13 AV5 0.08 SG14 38 40 TWD 11 AV6
-0.12 SG14 38 40 TWD 34 AV3 0.1 SG14 38 92 TWD 11 AV3 0.04 SG14 38 99 TWD 17 AV5
-0.17 SG14 38 101 TWD 14 AV2 0.06 SG14 38 101 TWD 18 AV5 0.1 SG14 38 101 TWD 24 AV4 0.02 SG14 38 101 TWD 28 AV3 0.02 SG14 38 103 TWD 10 AV5 0.08 SG14 38 103 TWD 12 AV2 0.06 SG14 38 103 TWD 12 AV4 0.12 SG14 38 104 TWD 20 AV4
-0.05 SG14 38 108 TWD 14 AV6 0.33 SG14 38 108 TWD 10 AV5 0.29 SG14 38 108 TWD 11 AV3
-0.1 Page 35-of41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
SG14 38 108 TWD 14 AV2
-0.31 SG14 39 56 TWD 20 AV4 0.18 SG14 39 56 TWD 22 AV3 0.37 SG14 39 56 TWD 16 AV5
-0.2 SG14 39 68 TWD 14 AV3 0.19 SG14 39 68 TWD 21 AV6
-0.17 SG14 39 77 TWD 24 AV4
-0.17 SG14 39 77 TWD 21 AV3
-0.06 SG14 39 77 TWD 12 AV2
-0.02 SG14 39 78 TWD 9 AV3 0.42 SG14 39 78 TWD 11 AV2
-0.02 SG14 39 79 TWD 16 AV3
-0.4 SG14 39 81 TWD 14 AV2
-0.19 SG14 39 82 TWD 9 AV3 0.02 SG14 39 89 TWD 10 AV3 0.02 SG14 39 89 TWD 10 AV5 0.04 SG14 39 89 TWD 11 AV4
-0.06 SG14 39 95 TWD 12 AV3 0.1 SG14 39 96 TWD 12 AVI
-0.27 SG14 39 96 TWD 16 AV4 0.02 SG14 39 96 TWD 19 AV3 0.04 SG14 39 96 TWD 22 AV2 0.08 SG14 39 97 TWD 22 AV3 0.02 SG14 39 98 TWD 12 AV5 0.06 SG14 39 98 TWD 16 AV3
-0.02 SG14 39 100 TWD 21 AV3 0.08 SG14 39 100 TWD 8 AV5 0.04 SG14 39 100 TWD 16 AV2 0.02 SG14 40 33 TWD 9 AV2 0.08 SG14 40 48 TWD 18 AV4
-0.24 SG14 40 48 TWD 20 AV6
-0.1 SG14 40 48 TWD 18 AV1
-0.02 SG14 40 48 TWD 14 AV3 0.06 SG14 40 48 TWD 28 AV5
-0.12 SG14 40 51 TWD 38 AV3 0.02 SG14 40 51 TWD 13 AV1 0.07 SG14 40 51 TWD 12 AV6 0.12 SG14 40 51 TWD 30 AV4 0.25 SG14 40 51 TWD 16 AV2
-0.08 SG14 40 52 TWD 42 AV5 0.04 SG14 40 52 TWD 14 AV2 0.12 Page 36 of 41
I.,
Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
ýSGj Row qol Kji o-,V L
Inch~
SG14 40 52 TWD 26 AV3
-0.08 SG14 40 52 TWD 18 AV2
-0.15 SG14 40 52 TWD 21 AV6 0.06 SG14 40 52 TWD 36 AV4 0.22 SG14 40 52 TWD 19 AV1 0.04 SG14 40 56 TWD 23 AV4
-0.31 SG14 40 56 TWD 20 AV2 0.1 SG14 40 56 TWD 30 AV3
-0.2 SG14 40 56 TWD 35 AV5 0.02 SG14 40 56 TWD 22 AV4 0.18 SG14 40 56 TWD 19 AV6 0.1 SG14 40 58 TWD 14 AV4
-0.21 SG14 40 58 TWD 18 AV2
-0.27 SG14 40 60 TWD 15 AV1
-0.04 SG14 40 60 TWD 13 AV2
-0.23 SG14 40 60 TWD 21 AV3
-0.39 SG14 40 60 TWD 17 AV4
-0.16 SG14 40 60 TWD 15 AV6 0.24 SG14 40 60 TWD 15 AV4 0.41 SG14 40 76 TWD 20 AV2
-0.31 SG14 40 76 TWD 26 AV5
-0.08 SG14 40 76 TWD 24 AV3 0.15 SG14 40 76 TWD 34 AV4 0.33 SG14 40 78 TWD 13 AV5 0.19 SG14 40 78 TWD 10 AV4
-0.02 SG14 40 80 TWD 15 AV2 0.06 SG14 40 80 TWD 19 AV3
-0.06 SG14 40 80 TWD 27 AV4
-0.15 SG14 40 80 TWD 27 AV5 0.42 SG14 40 80 TWD 22 AV6 0.21 SG14 40 81 TWD 36 AV4 0.33 SG14 40 81 TWD 16 AV5
-0.27 SG14 40 81 TWD 29 AV5 0.33 SG14 40 81 TWD 18 AV4
-0.21 SG14 40 81 TWD 32 AV3 0.31 SG14 40 81 TWD 16 AV3
-0.31 SG14 40 81 TWD 29 AV2 0.29 SG14 40 81 TWD 23 AVI 0.04 SG14 40 81 TWD 11 AV6
-0.1 SG14 40 85 TWD 16 AV6
-0.13 SG14 40 85 TWD 24 AV5
-0.02 Page 37 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
SG14 40 85 TWD 45 AV4 0.06 SG14 40 85 TWD 37 AV3 0.38 SG14 40 85 TWD 14 AV3
-0.23 SG14 40 85 TWD 13 AV2 0.23 SG14 40 85 TWD 30 AV2
-0.15 SG14 40 87 TWD 9 AV2 0.08 SG14 40 87 TWD 25 AV4 0.06 SG14 40 87 TWD 28 AV3
-0.02 SG14 40 87 TWD 13 AV6 0.15 SG14 40 87 TWD 29 AV5 0.1 SG14 40 106 TWD 11 AV6 0.21 SG14 40 106 TWD 11 AV5 0.33 SG14 40 106 TWD 9 AV3 0.02 SG14 40 106 TWD 12 AV1 0.02 SG14 41 100 TWD 14 AV5 0.02 SG14 41 100 TWD 18 AV3 0.02 SG14 41 105 TWD 10 AVI
-0.1 SG14 41 105 TWD 8 AV5 0.27 SG14 42 19 TWD 10 AV1 0.19 SG14 42 21 TWD 10 AV4
-0.13 SG14 42 21 TWD 10 AV2
-0.06 SG14 42 21 TWD 19 AV3 0.08 SG14 42 30 TWD 24 AV4 0.13 SG14 42 30 TWD 20 AV2 0.04 SG14 42 30 TWD 20 AV3 0.04 SG14 42 30 TWD 19 AV5 0.07 SG14 43 53 TWD 9 AVI
-0.28 SG14 43 53 TWD 27 AV3 0.24 SG14 43 53 TWD 13 AV2 0.1 SG14 43 53 TWD 11 AV2
-0.29 SG14 43 53 TWD 18 AV4 0.29 SG14 43 53 TWD 24 AV5
-0.1 SG14 43 54 TWD 15 AV5
-0.02 SG14 43 54 TWD 29 AV3 0.29 SG14 43 54 TWD 15 AV5 0.2 SG14 43 54 TWD 28 AV4 0.31 SG14 43 54 TWD 20 AV4
-0.33 SG14 43 54 TWD 12 AV3
-0.41 SG14 43 54 TWD 30 AV2
-0.06 SG14 43 54 TWD 13 AVI 0.02 SG14 43 54 TWD 25 AV6 0.06 Page 38 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear) 7G1/2 Row, C'()
Ind~ "oTWNSupp ffichi SG14 43 55 TWD 24 AV6 0.28 SG14 43 55 TWD 29 AV4
-0.06 SG14 43 55 TWD 36 AV2 0.16 SG14 43 55 TWD 35 AV3 0.22 SG14 43 55 TWD 27 AVI
-0.04 SG14 43 55 TWD 33 AV5 0.04 SG14 43 55 TWD 12 AV4 0.37 SG14 43 100 TWD 10 AV3 0.04 SG14 44 102 TWD 12 AV3
-0.02 SG14 44 102 TWD 11 AV2
-0.02 SG14 45 22 TWD 13 AV4 0.02 SG14 45 101 TWD 14 AVI
-0.08 SG14 45 101 TWD 14 AV3
-0.02 SG14 45 101 TWD 10 AV5 0.1 SG14 46 24 TWD 15 AV6 0.02 SG14 47 43 TWD 10 AV4 0.06 SG14 47 43 TWD 10 AVI
-0.16 SG14 47 43 TWD 18 AV3 0.04 SG14 47 57 TWD 15 AV5 0.01 SG14 47 57 TWD 14 AV2 0.01 SG14 47 57 TWD 13 AV3 0.01 SG14 47 88 TWD 9 AV4 0.08 SG14 48 26 TWD 14 AV2
-0.31 SG14 49 27 TWD 14 AV3
-0.08 SG14 49 95 TWD 8 AV3 0.06 SG14 49 96 TWD 15 AV6 0.06 SG14 50 28 TWD 18 AV5 0.02 SG14 50 28 TWD 28 AV6
-0.02 SG14 50 94 TWD 15 AV3
-0.02 SG14 50 95 TWD 14 AV2
-0.04 SG14 51 31 TWD 12 AV4
-0.08 SG14 51 31 TWD 9 AV5
-0.22 SG14 51 31 TWD 12 AV6
-0.28 SG14 52 32 TWD 11 AV4
-0.08 SG14 52 32 TWD 12 AV5
-0.08 SG14 52 32 TWD 13 AV3 0.16 SG14 52 35 TWD 19 AV5
-0.14 SG14 52 35 TWD 38 AV4 0.06 SG14 52 35 TWD 44 AV3 0.12 SG14 52 39 TWD 11 AV6
-0.08 SG14 53 33 TWD 17 AV4
-0.16 Page 39 of 41 Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
SG Row C53 3
TWd 19JN SAV5 111C11 SG14 53 33 TWD 19 AV5 0.04 SG14 53 34 TWD 15 AV6 0.01 SG14 53 34 TWD 13 AV4 0.02 SG14 53 35 TWD 9 AV6
-0.12 SG14 53 37 TWD 7 AV6
-0.1 SG14 53 38 TWD 13 AV3
-0.06 SG14 53 38 TWD 17 AV6
-0.35 SG14 53 38 TWD 16 AV4
-0.04 SG14 53 39 TWD 10 AV6
-0.08 SG14 53 90 TWD 13 AV6 0.17 SG14 54 35 TWD 10 AV5
-0.12 SG14 54 36 TWD 11 AV6
-0.1 SG14 54 38 TWD 14 AV3 0.18 SG14 54 56 TWD 9 AV5 0.04 SG14 54 86 TWD 16 AV2
-0.06 SG14 54 87 TWD 18 AV5 0.04 SG14 54 87 TWD 11 AV2 0.08 SG14 54 87 TWVD 12 AV6 0.04 SG14 55 82 TWD 12 AV2 0.08 SG14 55 83 TWD 25 AV6 0.08 SG14 55 83 TWD 12 AV4 0.02 SG14 55 83 TWD 11 AV2 0.02 SG14 56 41 TWD 37 AV4 0.02 SG14 56 41 TWD 16 AV4
-0.04 SG14 56 41 TWD 25 AV6
-0.08 SG14 56 49 TWvD 9 AV6 0.02 SG14 56 57 TWD 8 AV6 (-0.14 SG14 56 81 TWD 10 AV2 0.17 SG14 56 82 TWD 13 AV2 0.08 SG14 57 61 TWD 14 AV6 0.04 SG14 57 70 TWD 10 AV6
-0.19 SG14 57 79 TWD 14 AV2 0.06 SG14 58 47 TWD 10 AV5
-0.06 SG14 58 50 TWD 12 AVI 0.02 SG14 58 52 TWD 12 AV6
-0.04 SG14 58 57 TWD 15 AV6 0.02 SG14 58 61 TWD 10 AVI 0.12 SG14 58 63 TWD 12 AV2
-0.08 SG14 58 64 TWD 11 AV1
-0.35 SG14 58 65 TWD 11 AV6
-0.02 SG14 58 70 TWD 7 AV1 0.02 Page 40 of 41
A "I
f Document Control Desk LR-N07-0265 1R18 Service Induced Indications (AVB Wear)
SG1 wCol 58d 7
T TW Supp A
i.
SG14 58 72 TWD 6 AV1
-0.01 SG14 58 74 TWD 12 AVI
-0.1 SG14 58 76 TWD 16 AV2 0.04 SG14 59 55 TWD 13 AVI
-0.39 SG14 59 55 TWD 22 AV6 0.4 SG14 59 55 TWD 12 AV2
-0.1 SG14 59 57 TWD 13 AVI
-0.35 SG14 59 59 TWD 10 AV3
-0.08 SG14 59 63 TWD 11 AV2 0.13 SG14 59 63 TWD 11 AV6 0.57 Page 41 of 41