ML062960413
| ML062960413 | |
| Person / Time | |
|---|---|
| Site: | Calvert Cliffs |
| Issue date: | 10/24/2006 |
| From: | Dave Solorio, Trocine L NRC/OE |
| To: | |
| Trocine L | |
| References | |
| EA-06-198 EN-06-052 | |
| Download: ML062960413 (2) | |
Text
PRELIMINARY INFORMATION - NOT FOR PUBLIC DISCLOSURE UNTIL VERIFICATION THAT LICENSEE HAS RECEIVED ACTION PRELIMINARY INFORMATION - NOT FOR PUBLIC DISCLOSURE UNTIL VERIFICATION THAT LICENSEE HAS RECEIVED ACTION October 24, 2006 EN-06-052 OFFICE OF ENFORCEMENT NOTIFICATION OF SIGNIFICANT ENFORCEMENT ACTION Licensee:
Constellation Generation Group, LLC (EA-06-198)
Calvert Cliffs Nuclear Power Plant Docket No. 05000317
Subject:
ISSUANCE OF FINAL SIGNIFICANCE DETERMINATION AND NOTICE OF VIOLATION This is to inform the Commission that a Notice of Violation associated with a White significance determination process (SDP) finding will be issued on or around October 27, 2006, to Constellation Generation Group, LLC, as a result of inspections at Calvert Cliffs Nuclear Power Plant. This self-revealing White finding, an issue of low to moderate safety significance which may require additional NRC inspection, involved inadequate design control during the establishment of the over-current trip setting for an electrical circuit breaker that supplies power to the support systems for the 1A Emergency Diesel Generator (EDG). The low over-current trip setting would have impacted the capability of the 1A EDG to perform its intended safety function during certain design basis events at Calvert Cliffs Unit 1.
A Notice of Violation is included based on a violation of 10 CFR Part 50, Appendix B, Criterion III, "Design Control," because the licensee failed to ensure that design control measures provided for verifying or checking the adequacy of the design when Calvert Cliffs modified the on-site electrical distribution design by installing a new 1A EDG in 1996.
Specifically, calculation D-E-94-001, dated August 26, 1994, did not account for all the loads that can simultaneously start after an undervoltage event when establishing the short-term over-current trip setting for electrical circuit breaker 1MCC123, the electrical supply for the 1A EDG support systems. In addition, neither adequate design reviews, alternate calculations, nor suitable testing was done to identify that the over-current trip setting was incorrect.
It should be noted that the licensee has not been specifically informed of the enforcement action. The schedule of issuance and notification is:
Mailing of Final Significance Determination October 27, 2006 Telephone Notification of Licensee October 27, 2006 The State of Maryland will be notified.
The licensee has 30 days from the date of the letter in which to respond.
Contacts:
Leigh Trocine, OE, 301-415-2319 David Solorio, OE, 301-415-2741
EN-06-052 PRELIMINARY INFORMATION - NOT FOR PUBLIC DISCLOSURE UNTIL VERIFICATION THAT LICENSEE HAS RECEIVED ACTION PRELIMINARY INFORMATION - NOT FOR PUBLIC DISCLOSURE UNTIL VERIFICATION THAT LICENSEE HAS RECEIVED ACTION Distribution:
OWFN Chairman Klein Comm. McGaffigan Comm. Merrifield Comm. Jaczko Comm. Lyons SECY OCA PA IP OWFN EDO DEDR DEDMRS OE OGC NRR NSIR OI STP TWFN OCFO OP CENTER NMSS OIG OCIO RES ACRS Regional Offices RI RII RIII RIV MAIL ADAMS File Name: C:\\FileNet\\ML062960413.wpd ADAMS ML062960413 OE:ES OE:SC LTrocine DSolorio 10/23/06 10/24/06