ML033020071
| ML033020071 | |
| Person / Time | |
|---|---|
| Site: | McGuire, Mcguire |
| Issue date: | 10/10/2003 |
| From: | Ogle C NRC/RGN-II/DRS/EB |
| To: | Jamil D Duke Energy Corp |
| References | |
| FOIA/PA-2003-0358 IR-03-007 | |
| Download: ML033020071 (30) | |
See also: IR 05000369/2003007
Text
July XX, 2003
Duke Energy Corporation
ATTN: Mr. D. Jamil
Vice President
McGuire Nuclear Station
12700 Hagers Ferry Road
Huntersville, NC 28078-8985
SUBJECT:
MCGUIRE NUCLEAR STATION - NRC TRIENNIAL FIRE PROTECTION
INSPECTION REPORT 50-369/03-07 AND 50-370/03-07
Dear Mr. Jamil:
On May 23, 2003, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at
your McGuire Nuclear Station, Units 1 and 2. The enclosed report documents the inspection
findings which were discussed on May 22, 2003, with you and other members of your staff.
The inspection examined activities conducted under your license as they relate to safety and
compliance with the Commission's rules and regulations and with the conditions of your license.
The inspectors reviewed selected procedures and records, observed activities, and interviewed
personnel.
-
This report documents two findings that, combined, have potential safety significance greater
than very low significance, however, a safety significance determination has not been
completed. One finding did present an immediate safety concern and a fire watch was put in
place on June 10, 2003, as a compensatory measure.
In addition, the report documents one NRC-identified finding which was determined to involve a
violation of NRC requirements. However, the significance of this finding has not been
determined. Also, one licensee-identified violation is listed in this report. If you contest any
vvlatic.. in this report, you should provide a respoinis with iile basis for your denial, within 30
days of the date of this inspection report, to the United States Nuclear Regulatory Commission,
ATTN: Document Control Desk, Washington, D.C. 20555-0001, with copies to the Regional
Administrator, Region II; the Director, Office of Enforcement, United States Nuclear Regulatory
Commission, Washington, D.C. 20555-0001; and the NRC Resident Inspector at the McGuire
facility.
J3
It
In accordance with 10 CFR 2.790 of the NRC's "Rules of Practice," a copy of this letter and its
enclosure, and your response (if any) will be available electronically for public inspection in the
NRC Public Document Room or from the Publicly Available Records (PARS) component of
NRC's document system (ADAMS). ADAMS is accessible from the NRC Web site at
httD://www.nrc.gov/readina-rm/adams.html (the Public Electronic Reading Room).
Sincerely,
Charles R. Ogle, Chief,
Engineering Branch I
Division of Reactor Safety
Docket Nos. 50-369, 50-370
Enclosure: Inspection Report 50-369, 370/03-07
w/Attachment: Supplemental Information
cc w/encl:
C. J. Thomas
Regulatory Compliance Manager (MNS)
Duke Energy Corporation
Electronic Mail Distribution
M. T. Cash, Manager
Nuclear Regulatory Licensing
Duke Energy Corporation
526 S. Church Street
Charlotte, NC 28201-0006
County Manager of Mecklenburg County
720 East Fourth Street
Charlotte, NC 28202
Peggy Force
Assistant Attomey General
N. C. Department of Justice
Electronic Mail Distribution
Lisa Vaughan
Legal Department (PB05E)
Duke Energy Corporation
422 South Church Street
Charlotte, NC 28242
Anne Cottingham
Winston and Strawn
Electronic Mail Distribution
Beverly Hall, Acting Director
Division of Radiation Protection
N. C. Department of Environmental
Health & Natural Resources
Electronic Mail Distribution
3
ti
Distribution w/encl:
R. Martin, NRR
RIDSNRRDIPMLIPB
PUBLIC
L. Slack, Rll
T. Scarbrough, NRR
OFFICE
RII:DRS
RII:DRS
RII:DRS
RII:DRS
RII:DRS
RII:DRP
SIGNATURE
DATE
7homas
PFillion
RMaxey
RSchin
CPayne
RHaag
DATE
7/
P2003
7/
R2003
7/
a
03
7/ n
Coo3
7/
2n03
7/
203
lE-MAIL COPY?
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
IPUBLIC DOCUMENT
YES
NO
I
I
OFFICIAL RECORD COPY
DOCUMENT NAME: P:\\McG 0307 TFPI_1stdraft.wpd
Enclosure
j
!S
Enclosure
U.S. NUCLEAR REGULATORY COMMISSION
REGION II
Docket Nos:
License Nos:
Report Nos:
Licensee:
Facility:
Location:
Dates:
Inspectors:
50-369, 50-370
50-369103-07 and 50-370/03-07
Duke Energy Corporation
McGuire Nuclear Station, Units 1 and 2
12700 Hagers Ferry Road
Huntersville, NC 28078
May 5 - 9, 2003 (Week 1)
May 19 - 23, 2003 (Week 2)
P. Fillion, Reactor Inspector
R. Maxey, Reactor Inspector
B. Melly, Fire Protection Engineer (Consultant)
M. Thomas, Senior Reactor Inspector (Lead Inspector)
Approved by:
Charles R. Ogle, Chief
Engineering Branch 1
Division of Reactor Safety
Enclosure
a
SUMMARY OF FINDINGS
IR05000369/03-07, IR05000370103-07; Duke Energy Corporation; 5/9 - 23/2003; McGuire
Nuclear Station, Units 1 and 2; Triennial Fire Protection
The report covered a two-week period of inspection by regional inspectors and a consultant.
Three unresolved items with potential safety significance greater than Green were identified.
The significance of most findings is indicated by their color (Green, White, Yellow, Red) using
Inspection Manual Chapter (IMC) 0609, 'Significance Determination Process" (SDP). Findings
for which the SDP does not apply may be Green or be assigned a severity level after NRC
management review. The NRC's program for overseeing the safe operation of commercial
nuclear power reactors is described in NUREG 1649, "Reactor Oversight Process," Revision 3,
dated July 2000.
A.
InsDector Identified and Self-Revealinga Findings
Cornerstone: Mitigating Systems
TBD. The team identified a violation involving Train A and Train B cables associated
with the reactor protection were not protected from fire damage.
This finding is unresolved pending determination of the systems affected and completion
of a significance determination. The finding is greater than minor because
instrumentation important for post-fire safe shutdown would be lost. The finding
represented an operability concern, which the licensee resolved by posting a fire watch
in the area. When assessed in combination with the finding related to inadequate
protection of cables and equipment required for safe shutdown in Fire Area 16/18 (also
discussed in this inspection report), this finding may have potential safety significance
greater than very low significance. (Section 1R05.03.b.1)
TBD. The team identified a violation in that the turbine driven auxiliary feedwater
(TDAFW) pump suction supply valve 2CA0007A was not evaluated in the licensee's Fire
Protection Program (i.e., safe shutdown analysis) for potential impact on safe shutdown
in the event of a fire where the TDAFW) pump is required for safe shutdown. The valve
could spuriously close due to fire damage.
The finding is unresolved pending completion of a significance determination. The
finding is greater than minor because spurious closure of the valve could damage the
TDAFW pump and seriously degrade the decay heat removal function. (Section
1 R05.04.b.2)
B.
Licensee Identified Violations
TBD. The physical protection of cables and equipment relied upon for safe shutdown
(SSD) of Unit 2 during a fire in the Train A Switchgear Room/Electrical Penetration
Room (Fire Area 16/18) was not adequate. Train B electrical cables, associated with
the 2B motor driven auxiliary feedwater pump discharge valve 2CA0042B to steam
generator 2D, were located in the Train A Electrical Penetration Room (Fire Area 16/18)
without adequate spatial separation or fire barriers as required by the Fire Protection
Program. Local, manual operator actions (which had not been reviewed and approved
by NRC) would be used to achieve and maintain SSD of Unit 2 in lieu of providing
adequate physical protection for the electrical cables associated with valve 2CA0042B.
This finding is unresolved pending completion of a significance determination. The
finding is greater than minor because fire damage to the unprotected cables could
prevent operation of SSD equipment from the main control room and because it affects
the mitigating systems cornerstone objective. When assessed in combination with the
inadequate reactor protection system cable separation finding (also discussed in this
inspection report), this finding may have potential safety significance greater than very
low significance. (Section 1R05.03.b.2)
"a4
Report Details
1.
REACTOR SAFETY
Cornerstones: Initiating Events, Mitigating Systems and Barrier Integrity
1RO5 FIRE PROTECTION
.01
Systems Reauired to Achieve and Maintain Post-Fire Safe Shutdown
a.
Inspection ScoDe
Ylhlyks
The team evaluated the licensee's fire protection program (FPP) against applicable
requirements, including Operating License Conditions 2.C.4 and 2.C.7, Fire Protection
Program, for Units 1 and 2, respectively; Title 10 of the Code of Federal Regulations
Part 50 (10 CFR 50), Appendix R, Sections G, J, L, and 0; 10 CFR 50.48; Appendix A
to Branch Technical Position (BTP) Auxiliary and Power Conversion Systems Branch
(APCSB) 9.5-1, Guideline for Fire Protection for Nuclear Power Plants; related NRC
Safety Evaluation Reports (SERs); McGuire Nuclear Station (MNS) Updated Final
Safety Analysis Report (UFSAR), Section 9.5.1; UFSAR Section 16.9, Selected
Licensee Commitments (SLC); and plant Technical Specifications (TS). The team
evaluated all areas of this inspection, as documented below, against these
requirements. The team reviewed the licensee's Individual Plant Examination for
External Events (IPEEE) and performed in-plant walk downs to choose four risk-
significant fire areas for detailed inspection and review. The four fire areas selected
were:
Fire Area 4: Auxiliary Building Common Area - a fire in this area would involve
alternative shutdown from the standby shutdown facility (SSF) using the standby
shutdown system (SSS)
Fire Area 13: Battery Rooms Common Area - a fire in this area would involve
alternative shutdown from the SSF using the SSS
Fire Area 16118: Unit 2 Train A 4160 Volt Switchgear Room/Electrical
Penetration Room - a fire in this area would involve shutdown from the main
control room using Train B equipment
Fire Area 24: Main Control Room (MCR) - a fire in this area would involve
alternative shutdown from the SSF using the SSS
The team reviewed the licensee's FPP documented in UFSAR Section 9.5.1; the MNS
Fire Protection Review; safe shutdown analysis (SSA); fire hazards analysis (FHA); safe
shutdown (SSD) essential equipment list; and system flow diagrams to identify the
components and systems necessary to achieve and maintain safe shutdown conditions.
Specific licensee documents, calculations, and drawings reviewed during this inspection
are listed in Attachment 1. The objective of this evaluation was to assure the SSD
equipment and post-fire SSD analytical approach were consistent with and satisfied the
Appendix R reactor performance criteria for SSD. For each of the selected fire areas,
the team focused on the fire protection features, and on the systems and equipment
necessary for the licensee to achieve and maintain SSD in the event of a fire in those
fire areas. Systems and/or components selected for review included: standby shutdown
system (SSS); Unit 2 standby makeup pump (SMP) 2NVPU0046 and SMP suction
supply motor operated valve (MOV) 2NV842AC; auxiliary feedwater (AFW) suction
supply MOVs 2CA007A, 2CA009B, 2CA1 61 C, and 2CA1 62C; reactor coolant pump
(RCP) seal water return isolation valve 2NV94AC; pressurizer power operated relief
valve (PORV) 2NC34A and PORV isolation valves 2NC33A; Unit 2 pressurizer heater
Nos. 28,55, and 56; reactor vessel head vent valves 2NC272AC and 2NC273AC; and
heating, ventilation, and air conditioning (HVAC).
b.
Findings
No findings of significance were identified.
.02
Fire Protection of Safe Shutdown Capability
a.
Insgecdion Scone
Vd-N .
The team reviewed the fire detection system protecting Fire Areas 4, 13, 16, 18 and 24
to assess the adequacy of the design and installation. This was accomplished by
reviewing design drawings, ceiling beam location drawings, and National Fire Protection
Association (NFPA) 72E (code of record 1974 edition) for detector location
requirements. The team reviewed the McGuire Fire Protection Code Deviation
Calculation to determine if there were any outstanding code detector deviations for the
selected areas. The team walked down the fire detection and alarm systems in Fire
Areas 13, 16, and 18 to evaluate the installed detector locations relative to the NFPA
72E location requirements. Additionally, the team reviewed the surveillance test
procedures for the detection and alarm systems to determine compliance with the
UFSAR Sections 9.5.1 and 16.9.
The team reviewed the adequacy of the design and installation of the fire suppression
system protecting the nuclear service water (RN) pump area in Fire Area 4. This was
accomplished by reviewing the engineering design drawings, suppression system
hydraulic calculations, as-built system configuration and NFPA 13 (code of record 1978
edition) for sprinkler system location requirements. The team also reviewed the
McGuire Fire Protection Code Deviation Calculation for the RN pump sprinkler system to
determine the adequacy of the system to control a fire in this area utilizing the 2-1/2 inch
by-pass lines as the sole means of supplying the sprinkler system.
The team reviewed the fire hose stations in Fire Areas 4, 13, 16, 18 and 24 to assess
the adequacy of the design and installation. This was accomplished by reviewing the
fire plan drawings, engineering mechanical equipment drawings, pre-fire strategies and
NFPA 14 (code of record 1976 edition) for hose station location requirements and
effective reach capability. Team members also performed a field walkdown of the
selected fire areas to ensure that hose stations were not blocked and to compare hose
station location drawings with as-built plant locations.
b.
Findings
41M~
The team identified an unresolved item (URI) involving the adequacy of the suppression
system for Fire Area 4. Alternative shutdown using the SSS was designated by the
licensee for a fire in this area. 10 CFR 50, Appendix R, Section III.G.3 (alternative or
dedicated shutdown) requires that fire detection and a fixed fire suppression system
shall be installed in the area, room, or zone under consideration. The fire suppression
system for Fire Area 4 was not installed in accordance with 10 CFR 50, Appendix R,
Section III.G.3. The system in Fire Area 4 was a partial automatic sprinkler system
effectively protecting the RN pumps and 20 feet north of these pumps. The area
protected by this sprinkler system was located between Column lines 54-58 and EE-GG.
The majority of Fire Area 4 was not provided with automatic sprinkler protection as
required by 10 CFR 50, Appendix R, Section III.G.3 for alternative and dedicated
shutdown.
This issue was previously identified by the NRC (URI 50-369/84-28-01, 370184-25-01) in
1984 during an Appendix R inspection. The licensee considered this issue to be a
potential backfit per 10 CFR 50.109 (letter dated September 4, 1984, from H.B. Tucker,
Duke Power Company, to H.R. Denton, NRC Office of Nuclear Reactor Regulation).
The URI was reviewed and closed in NRC inspection report 50-369, 370/87-34. The
team noted that, subsequent to closure of the URI, licensee Fire Protection Functional
Audit SA-99-04(MC)(RA)(FPFA) dated April 9, 1999, identified that MNS did not meet
separation and detection/suppression criteria for alternative or dedicated shutdown
capability required by 10 CFR 50, Appendix R, Section III.G.3. During this inspection,
the team questioned whether the previous reviews of the sprinkler system for this fire
area included an evaluation of the risk impact associated with not providing adequate
sprinkler coverage for the RN cabling in this fire area. The team informed the licensee
that this issue will be reviewed further to determine if the lack of sprinkler coveraae in
this fire area has an impact on risk. This issue is identified as URI 50-369,370/03-07-01,
Fire Suppression System for Alternative Shutdown Areas not in Accordance with 10 CFR 50, Appendix R, Section III.G.3. The team noted that similar conditions, regarding
the fixed fire suppression system complying with 10 CFR 50, Appendix R, Section
III.G.3, was applicable to other MNS fire areas where alternative shutdown capability
using the SSS was designated by the licensee (examples include Fire Areas 14 and 21).
This issue is unresolved pending further NRC review using risk insights to determine if a
10 CFR 50.109 (backfit) evaluation is warranted.
.03
Post-Fire Safe Shutdown Circuit Analysis
a.
Inspection Scope
D s
ehe team reviewed the adequacy of separation and fire barriers provided for the power
PO' D X
and control cabling of equipment relied on for SSD during a fire in the selected fire
areas/zones. On a sample basis, the team reviewed the SSA and the electrical
schematics for power and control circuits of SSD components, and looked for the
potential effects of open circuits, shorts to ground, and hot shorts. This review focused
on the cabling of selected components for the charging/safety injection system, RCS
and AFW system. The team traced the routing of cables by using the cable schedule
and conduit and tray drawings. Walkdowns were performed to compare cables
indicated on the drawings with actual plant installation. Circuit and cable routings were
reviewed for the following equipment:
ORN4AC, Turbine-driven AFW Suction Supply Valve
2CA0007A, Turbine-driven AFW Suction Isolation Valve
2CA009B, Motor-driven AFW Suction Isolation Valve
- 2CFLT6080, 6090, 6100, 6110, Steam Generator Level Transmitters
2NCLT5151, Pressurizer Level Transmitter
2NC34A, 33A, Pressurizer PORV and PORV Isolation Valve
2NC272AC, 273AC, Reactor Vessel Head Vent Valves
2NVPU0046, Standby Makeup Pump (SMP)
2NV94AC, RCP Seal Water Return Isolation Valve
2NV842AC, SMP Suction Isolation Valve
2NV1012C, SMP Discharge to Containment Sump Isolation Valve
Pressurizer Heaters Nos. 28, 55, 56
The team also reviewed studies of overcurrent protection on both alternating current
(AC) and direct current (DC) systems to identify whether fire induced faults could result
in defeating the safe shutdown functions.
b.
Findings
Findings associated with valves 2CA0007A, 2NC34A, and 2NC33A are discussed in
Section 1 R05.04 of this inspection report.
1.
,;t
Introduction: A finding potentially greater than very low safety significance was identified
in that instrumentation (and possibly other equipment) important to safe shutdown couid
have been damaged by a fire in Fire Area 16/18. This finding involved a violation of
NRC requirements. This finding is an URI pending completion of the SDP.
Description: Fire Area 16/18 is the Unit 2 Train A switchgear room, and Train B
equipment controlled from the main control room was intended to be used for a fire in
this area according to the analysis and procedures.
During a walkdown of Fire Area
16/18, the team identified that room 805A in Fire Area 16/18 lacked fire detection and
fire suppression. Room 805A is the HVAC equipment room providing ventilation to the
Unit 2 Train A 4160V Switchgear Room 2ETA. This area has a moderate to high fire
loading consisting principally of cables. The team identified that a similar condition also
existed for room 803A, which is the HVAC equipment room providing ventilation for the
Unit 1 Train A 4160V Switchgear Room 1 ETA in Fire Area 17. The team also observed
Train B cables routed in this room. Many of the identified cables were in a cable tray
near the ceiling and were going from/to the cable spread room, which is on the same
elevation, to/from the control room, which was above the switchgear room. The
.a~f
D
licensee had not been aware of all of these uopposite train' cables, and they initiated
PIP M-03-02106 . On June 10, 2003, the licensee reported these cables represented
an unanalyzed condition (Event No. 39915).
As many as 74 'opposite train' cables are involved related to the reactor protection
system. Preliminary investigation by the licensee revealed that cables for primary and
backup power supplies for all four RPS channels were routed in close proximity and
could be damaged. One consequence of this is that many RPS protective functions
would spuriously go to the trip condition. Subsequently, a safety injection signal would
be generated due to spurious Thigh containment pressure." A safety injection signal
would in turn trigger a reactor trip and Phase A isolation. At the same time, many
important main control panel instruments would be lost. For example, pressurizer level
and all four steam generator level, which are instruments necessary to achieve and
maintain hot shutdown. The licensee also stated that a similar situation exists for the
Unit 1 Train A switchgear room (Fire Area 17).
Analysis: The fact that instrumentation necessary to achieve and maintain hot shutdown
could be lost due to a credible fire in one area as described above constitutes a violation
of 10 CFR 50, Appendix R, Section III.G.2. This section requires that one train of
systems necessary to achieve and maintain hot shutdown shall be free of fire damage.
The fact that the area presented an exposure fire hazard to safe shutdown equipment
and did not have automatic fire detection systems represents a violation of 10 CFR 50,
Appendix R,Section III.F. The team determined that this finding was associated with
the "equipment performance" attribute and affected the objective of the mitigating
systems cornerstone to ensure the availability, reliability and capability of systems that
respond to initiating events, and is therefore greater than minor. The finding did present
an operability concern, which the licensee resolved by posting a fire watch in the area of
concern. Once the licensee has fully analyzed the manner in which plant systems would
have been affected by damage to the "opposite train" cables and reviewed the abnormal
operating procedures in light of the degraded instrumentation and any automatic actions
that would be initiated, the NRC will review this analysis. Once the equipment
degradations and relevant procedures are understood, a significance determination
process (SDP) will be performed to determine the !eve! of significance. When assessed
in combination with the finding related to inadequate protection of cables and equipment
required for safe shutdown in Fire Area 16/18 (also discussed in this inspection report),
this finding may have potential safety significance greater than very low significance.
Enforcement: As described above, the finding is a violation of Appendix R requirements
of greater than minor significance.. Pendina determination of the safety significance, the
finding is identified as URI 50-369,370/03-07-02, Failure to Protect Reactor Protection
System Cables Results in Loss of Required Shutdown Instrumentation.
2.
Inadequate Protection of Eguigment and Cables Required for Safe Shutdown
Introduction: A finding was identified in that physical protection of the associated
electrical cables for valve 2CA0042B (2B motor driven AFW pump discharge supply to
steam generator 2D) did not meet the requirements of 10 CFR 50, Appendix R, Section
III.G.2. Instead, the licensee substituted the use of a local manual operator action,
I
which had not received prior NRC approval, to achieve and maintain SSD. This is a URI
pending completion of the SDP.
Description: On April 2, 2003, the licensee identified that MNS relied on manual operator
actions outside the MCR for SSD in non-alternative shutdown fire areas (i.e., areas
designated as complying with 10 CFR 50, Appendix R, Section III.G.2) and the manual
actions did not have prior NRC approval. The licensee documented this issue in PIP M-
03-02311. The team reviewed the local, manual operator actions for the Section III.G.2
area selected for this inspection (Fire Area 16/18).
The team found that the associated electrical cables for Train B valve 2CA0042B were
located in the Train A 2ETA/Electrical Penetration Room (Fire Area 16/18) without
adequate spatial separation or fire barriers. The licensee's SSA stated that de-
energizing this valve after verifying that it was open was a time critical action because
spurious closure of this valve would limit the secondary heat sink to only one steam
generator instead of the two required for SSD. However, rather than providing adequate
physical protection for redundant trains of equipment/systems necessary to achieve and
maintain SSD (as specified for Appendix R,Section III.G.2 areas), the licensee
substituted the use of manual operator actions outside the MCR. The use of local
manual operator actions, in fire areas designated as complying with the provisions of
Appendix R,Section III.G.2, requires prior NRC review and approval. These local
manual actions had not received NRC approval.
Analysis: The team determined that this finding was associated with the "equipment
performance" attribute of the mitigating systems cornerstone. It affected this
cornerstone's objective to ensure the availability, reliability, and capability of systems
that respond to initiating events, and is therefore greater than minor. When assessed in
combination with the inadequate reactor protection system cable separation finding (also
discussed in this inspection report), this finding may have potential safety significance
greater than very low significance.
Enforcement: The licensee's Fire Protection Program commits to 10 CFR 50, Appendix
R,Section III.G.Section III.G.2 states in part, that,
.... where cables or equipment, including associated non-safety circuits that could
prevent operation or cause maloperation due to hot shorts, open circuits, or shorts to
ground, of redundant trains of systems necessary to achieve and maintain hot shutdown
conditions are located within the same fire area outside of primary containment, one of
the following means of ensuring that one of the redundant trains is free of fire damage
shall be provided: (1) separation of cables and equipment of redundant trains by a fire
barrier having a 3-hour rating; (2) separation of cables and equipment of redundant
trains by a horizontal distance of more than 20 feet with no intervening combustibles or
fire hazards. In addition, fire detectors and an automatic fire suppression system shall
be installed in the fire area; (3) enclosure of cables and equipment of one redundant
train in a fire barrier having a 1-hour rating. In addition, fire detectors and an automatic
fire suppression system shall be installed in the fire area."
Contrary to the above, on May 23, 2003, the team found that the licensee failed to
protect cables of redundant equipment located within the Train A Switchgear
Room/Electrical Penetration Room (Fire Area 16/18) with an adequate barrier or to
provide 20 feet of separation.. Pendina determination of the finding's safety significance,
this finding is identified as URI 50-370/03-07-05, Failure to Provide Adequate Protection
for Cables of Redundant Safe Shutdown Equipment in Fire Area 16/18.
.04
Alternative Post-Fire Safe Shutdown Capability
a.
Inspection Scope
SlAwkcr
The team reviewed the licensee's procedures for fire response, abnormal procedures for
alternative shutdown (ASD), and the licensee's Appendix R manual action requirements
analyses for a fire in the selected Fire Areas 4, 13, and 24. The team also walked down
selected portions of the procedures. The reviews focused on ensuring that the required
functions for post-fire safe shutdown and the corresponding equipment necessary to
perform those functions were included in the procedures. The review also included
assessing whether hot and cold shutdown from outside the MCR could be implemented,
and that transfer of control from the MCR to the SSF could be accomplished within the
performance goals stated in 10 CFR 50, Appendix R, Section III.L. The components
listed in Section 1 R05.03.a. of this inspection report were also reviewed in relation to
alternative post-fire safe shutdown capability. The team reviewed the most recently
completed surveillances for selected instruments required during SSS operation to verify
that surveillances were being completed in accordance with MNS SLC 16.9.7, Standby
Shutdown System. The walk downs focused on ensuring that the procedures could
reasonably be performed within the required times, given the minimum required staffing
level of operators and with or without offsite power available. The team also reviewed
the electrical isolation of selected motor operated valves from the control room to verify
that operation of the SSS from the SSF and remote locations would not be prevented by
a fire-induced circuit fault. The objective of these reviews was to assure that the post-
fire safe shutdown analytical approach, safe shutdown equipment, and procedures were
consistent and complied with the Appendix R reactor performance criteria for safe
shutdown.
b.
Findings
6
7XM
1.
Reauirements Relative to the Number of SDurious Operations that Must be
Postulated
Introduction: An unresolved item was identified involving the number of concurrent
spurious operations associated with a particular component or set of components that
must be postulated. Resolution of the unresolved item is pending review by NRC staff.
DescriDtion: The licensee's fire protection analysis included the concept that only one
spurious operation due to fire damage need be postulated. This concept became
evident during review of the pressurizer PORVs. There are three sets of PORV/PORV
isolation valves on the pressurizer of each unit. Should operators in the control room
become aware of a fire in any area of the plant through a fire alarm or the plant
communications system, they would respond by following the instructions in abnormal
procedure AP/O/AN5500/045, Plant Fire. Depending on the fire location, procedure
AP/O/A15500/045 directed the operator to close the PORV isolation valves within ten
minutes. The basis for this time critical action is that spurious opening of the PORV or
damage to the isolation valve circuit would not occur in the first ten minutes of a fire
being detected. Then with the block valve closed it would take two spurious operations
to breach the RCS pressure boundary, namely one block valve opening and its
associated PORV opening. The concept of only one spurious operation need be
postulated meant that closing the block valve was sufficient in itself to ensure the
desired result. The licensee considered that there was no need to take any other action
such as de-energizing the isolation valves after they were closed. This concept was not
necessarily consistent with NRC requirements for protection of cables.
The team reviewed the control circuits and cable routing information for valve 2NC34A,
pressurizer PORV, and 2NC33A its associated isolation valve. They observed that
cables for both the PORV and isolation valve are routed in Fire Areas 13, 16/18 and 24.
When the control circuit for the PORV is analyzed and considering that the cables are
armored type cables (except in the control room) one can conclude that, for these three
fire areas, spurious opening of the PORV could only occur for the fire in Fire Area 24,
the control room. Considering this information, the team postulated the following
scenario. A fire starts in the control room. Operators close the isolation valves per
procedure API0I/N5500/045 within ten minutes. Later, isolation valve 2NC33A
spuriously opens due to a fire induced short-circuit. Operators take no action to counter
the spurious opening of the isolation valve because they have no information that it
occurred. Subsequently PORV 2NC34A spuriously opens due to a fire induced short-
circuit. At this point, it would be possible to close the PORV by opening the appropriate
circuit breaker at the 125 VDC distribution panel. This would take time, and it is not
covered by the fire response procedure. Before the PORV can be re-closed, the fire
has progressed and the decision is made to abandon the control room and shutdown
using the SSS. The PORV would now be closed by operating the control room/SSS
transfer switch as directed by abnormal procedure AP/2/A15500/024, Loss of Plant
Control Due to Fire or Sabotage. The situation now is that the PORV/isolation valves
were opened for a period of time and the RCS is may not be at normal level and
pressure. The standby makeup pump has relatively low capacity and may not have the
capacity to maintain hot shutdown in this scenario, and RCS variable parameters may
be outside the requirements of Appendix R, i.e. outside the range predicted for a loss of
offsite power. For example, an open PORV following a reactor trip could result in
pressurizer level lower than that predicted for a trip caused by a loss of offs~ite power.
Analysis: The team was not certain whether the licensee's analysis of circuits for
spurious operation was consistent with the requirements for independence of cables,
systems or components in the area under consideration as stipulated by Appendix R,
III.G.3 and III.L. In the example of the PORVs described above, if more than one
spurious operation would occur, the dedicated shutdown capability (SSS) would not be
independent from the control room in that a fire in the control room could result in
conditions outside of those specified in III.L. If more than one spurious operation must
be considered then there would be a violation of Appendix R requirements having more
than minor significance. The equipment reliability objective of the cornerstones of
mitigating systems and barrier integrity could be affected.
Enforcement: In the case of the PORV/isolation valve circuits, operation of the SSS may
not be independent of the fire area as required by III.G.3 depending on whether more
than one spurious operation must be postulated. Review of this matter by the NRC will
determine whether a violation has occurred. If a violation has occurred, the significance
will be determined. The issue is identified as URI 50-369,370/03-07-03, Requirements
Relative to the Number of Spurious Operations that must be Postulated.
2.
Valve 2CA0007A
Introduction: A finding of potentially greater than very low safety significance was
identified in that a valve in the auxiliary feedwater system was not included in the safe
shutdown analysis and it could spuriously close due to a fire in the main control room.
Spurious closure of this valve could damage the turbine driven auxiliary feedwater
pump, thus seriously degrading the core residual heat removal function of the safe
shutdown system. This is a URI pending completion of the SDP.
DescriDtion: Valve 2CA0007A is a motor operated valve in the flow path from the
300,000 gallon auxiliary feedwater storage tank to the turbine driven auxiliary feedwater
pump. The valve is open during normal plant operation. 2CA0007A is important to safe
shutdown for fire areas where the safe shutdown system (SSS) will be used. The
importance is derived from fact that the SSS uses the TDAFW pump for decay heat
removal and potential for spurious closure of the valve. The team found that the safe
shutdown analysis for Unit 2 did not recognize valve 2CA0007A. It was not listed in
Appendix E, list of important equipment, nor Appendix F, list of potential problem cables.
One scenario could be a fire starts in the control room which leads to a plant trip and
loss of offsite power. In this case, the TDAFW pump would receive an automatic start
from the 'LOOP on safety-related bus" logic or possibly 'low steam generator level" due
to loss of the feedwater pump. Even though the safe shutdown analysis for a fire in the
control room ultimately relies on the SSS, operators may remain in the control room if
they believe the plant is still under control. The TDAFW pump could be running and
taking suction from the auxiliary feedwater storage tank with flow through 2CA0007A.
Since control wires to the open/close control switch for this valve run in the control room
(in single-conductor plug cable, bundled in groups of approximately 30 wires), the valve
could spuriously close due to fire induced short-circuit between two of the wires.
Spurious closure of the valve would immediately reduce suction pressure and quickly
shut off all flow through the pump. Assuming that the TDAFW pump is damaged by
spurious closure of 2CA0007A and if plant conditions deteriorated due to progressing
fire in the control room forcing evacuation and transfer of plant shutdown to the SSS, the
ability to remove decay heat would be seriously degraded.
Besides the control room, there are open/close switches for this valve at auxiliary
feedwater panel 2A and the auxiliary feedwater turbine control panel (2AFPT). Cable
2*CA517 runs between area terminal cabinet 2ATC2 and the auxiliary feedwater panel
2A, and it runs through fire area FA4. Cable 2*CA519 runs between area terminal
t
.
6
cabinet 2ATC2 and panel 2AFPT, and it runs through fire area FA-4. Cable 2*CA557
contains power and control for the valve, and represents a potential for spurious
operation of the valve. Therefore a fire in FA-4 could also result in spurious closure of
valve 2CA0007A. This could lead to problems similar to that described above for the
control room fire. It is not expected that a fire in FA-4 would lead to a loss of offsite
power. However, a problem scenario could be as follows: If the fire becomes severe
and the decision is made to use the SSS, procedures direct the operator to trip the
normal feedwater pump. This could cause low steam generator level which in turn will
auto start the TDAFW pump. If 2CA0007A has already spuriously closed, the pump has
no through flow upon starting.
The licensee initiated a corrective action document for this issue, PIP M-03-02084, and
they took prompt action to restore operability. They revised AP-24 to specify that the
operator check that valve 2CA007A is open and remove power from 2CA0007A within
the first ten minutes of a fire.
Analysis: The team determined that this finding was associated with the 'equipment
performance" attribute and affected the objective of the mitigating systems cornerstone
to ensure the availability, reliability and capability of systems that respond to initiating
events, and is therefore greater than minor. For a severe fire in the control room, the
control room would be abandoned and the safe shutdown facility would be used to
maintain hot shutdown. The safe shutdown facility relies on the turbine driven auxiliary
feedwater pump for the decay heat removal function. With the decay heat removal
function seriously degraded and other mitigating systems potentially affected by a
severe control room fire or Fire Area 4, the finding had a potential safety significance
greater than very low. The team was aware that system design provided for automatic
transfers to alternate suction sources initiated by pressure switches in the pump suction
line. There were three separate alternate suction flow paths. Path 1 was through
valves 2CA161C, 2CA162C and ORN4AC; Path 2 was through valves 2CA086A and
2RN069A; and Path 3 was through valves 2CA116B and 2RN162B. However, key
information related to these automatic transfers was not available to the team at the
time of this inspection report issuance. One question was whether the automatic
transfer on low suction pressure would occur fast enough to protect the pump for the
case of valve 2CA0007A closing since this valve was close to the pump. In answering
this question, the licensee stated, and presented some information, that a few events
had occurred over the years where suction valves were inadvertently closed while motor
driven AFW pumps were running, and the pump was not damaged. Details of these
events and similarity of the motor driven and turbine driven pumps have not been
reviewed by the team. Secondly, the licensee provided information to the team,
subsequent to the inspection, on the routing of all the valves involved in the automatic
transfers. However, this information has not yet been fully reviewed by team to
determine whether or not the transfers could be affected by the same fire which caused
the 2CA0007A valve to spuriously close. This information would be needed to complete
the significance determination process.
Enforcement: 10 CFR 50, Appendix R, Section II.B. requires that a fire hazards analysis
shall be performed by qualified fire protection and reactor systems engineers to
determine the consequences of fire in any location of the plant on the ability to safely
shutdown the reactor. The licensee's analysis designated the MCR and Fire Area 4 as
dedicated/alternative shutdown areas. Appendix R,Section III.G.3 requires that the
dedicated/alternative shutdown capability and its associated circuits be'independent of
cables, systems or components in the area under consideration. Contrary to these
requirements, valve 2CA0007A was not included in the fire hazards analysis resulting in
the alternative/dedicated shutdown system (SSS) not being independent from Fire
Areas 4 and 24 in that a fire in these areas could result in spurious closure of the valve.
This in turn could lead to damage to the turbine driven auxiliary feedwater pump which
was required for alternative shutdown using the SSS. Pendina determination of the
safety significance, this finding is identified as URI 50-370/03-07-06, Spurious Closure of
Valve 2CA0007A Could Lead to Damage of the TDAFW Pump.
.05
Operational Implementation of Post-Fire Safe Shutdown Capability
a.
Inspection Scone
The team reviewed the operational implementation of the alternative shutdown capability
for a fire in Fire Areas 4, 13, or 24 to verify that: (1) the training program for licensed
personnel included alternative or dedicated safe shutdown capability; (2) personnel
required to achieve and maintain the plant in hot standby following a fire using the SSS
could be provided from normal onsite staff, exclusive of the fire brigade; (3) the licensee
had incorporated the operability of alternative shutdown transfer and control functions
into plant TS and/or SLCs; and (4) the licensee periodically performed operability testing
of the alternative shutdown instrumentation and transfer and control functions. The
team reviewed abnormal procedures AP/l/A15500/24 and AP/2/NA5500/024, Loss of
Plant Control Due to Fire or Sabotage, and AP/O/A15500/045, Plant Fire. The reviews
focused on ensuring that all required functions for post-fire safe shutdown, and the
corresponding equipment necessary to perform those functions, were included in the
procedures. The objective of this review was to assure that the safe shutdown
equipment, shutdown procedures, and the post-fire safe shutdown analytical approach
were consistent and satisfied the Appendix R reactor performance criteria for safe
shutdown.
b.
Findings
Jf)ranV-1-
The licensee identified that manual operator actions outside the MCR were used in lieu
of physical protection of equipment and cables relied on for SSD during a fire, without
obtaining prior NRC approval. Findings related to this issue are discussed in Section
1 R05.03.b.2 of this inspection report for Fire Area 16/18.
The team identified a URI regarding the adequacy of the licensee's method for
controlling RCS pressure during operation from the SSF in the event of a fire.
During review of procedures AP/1/A/5500/024 and AP/2/A/5500/024, the team
questioned the adequacy of the 70 kilowatts (kw) pressurizer heater capacity per unit
powered from the SSF to maintain and control RCS pressure in hot standby during a fire
in plant areas which require use of the SSS. The question was raised when the team
observed that a procedural note in both AP/1/A/5500/024 and AP/2/NA5500/024
provided guidance to the operators which stated that it was acceptable to allow the RCS
to go solid in order to maintain subcooling and, with the RCS solid, the reactor vessel
head vents would be used to control pressure. The team questioned why this guidance
was in these procedures. Allowing the pressurizer to go water solid for controlling RCS
pressure during hot standby conditions while operating from the SSF was not consistent
with Appendix R, Section lll.L, for alternative shutdown capability, nor the design basis
description for the SSF as stated in the licensee's letter to the NRC dated March 31,
1980. Also, solid plant operation from the SSF for controlling RCS pressure was neither
reviewed nor discussed in any NRC SER/SER Supplements relative to acceptability of
the SSF design for alternative shutdown capability. The team requested information
from the licensee (e.g., analyses, calculations, etc.) which demonstrated the following:
Adequacy of the 70 kw pressurizer heater capacity powered from the SSF for
maintaining and controlling RCS pressure in hot standby.
Are the assumptions for pressurizer heat loss stated in the October 21, 1980,
letter still valid (based on insulation degradation and/or degraded capacity of the
heaters powered from SSF) for assuming current pressurizer heat loss and for
determining when the heaters will be needed.
SMP capacity to achieve and control solid plant operation from the SSF within
the required time to maintain subcooling.
Operator training (JPMs, simulator, etc.) on solid plant operation from the SSF.
The licensee indicated that there were no specific calculations documented which
provided the basis for the number of heaters to be powered from the SSF. The licensee
further stated that there was no calculation which demonstrated the performance
capability of the SMP during solid plant operation from the SSF. The licensee also
indicated that training provided to operators on solid plant operation from the SSF
consisted primarily of classroom discussions and tabletop walk-throughs of procedures
AP11A/5500/024 and AP/2/A/5500/024. The team concluded that sufficient information
was not provided to resolve the questions r3 sed above nor to determine the licensee's
ability to safely operate the SSF with the pressurizer in a water solid condition during
fire events in areas where the SSF is used to achieve SSD. This issue is identified as
URI 50-369,370/03-07-04, Reactor Coolant System Pressure Control During SSF
Operation, pending further NRC review of additional licensee information.
.06
Communications
JYC->I4 a.
Inspection ScoDe
The team reviewed plant communication capabilities to verify that they were adequate
to support unit shutdown and fire brigade duties. This included verifying that site paging
(PA), portable radios, and sound-powered phone systems were consistent with the
licensing basis and would be available during fire response activities. The team
reviewed the licensee's communications features to assess whether they were properly
evaluated in the licensee's SSA (protected from exposure fire damage) and properly
a
integrated into the post-fire SSD procedures. The team also walked down sections of
the post-fire SSD procedures to verify that adequate communications equipment would
be available to support the SSD process.
b.
Findings
No findings of significance were identified.
.07
a.
Inspection ScoDe
.Jrtvr1AvA4
The team compared the installation of the licensee's emergency lighting systems to the
requirements of 10 CFR 50, Appendix R, Section IIl.J, to verify that 8-hour emergency
lighting coverage was provided in areas where manual operator actions were required
during post-fire SSD operations, including the access and egress routes. The team's
review also included verifying that emergency lighting requirements were evaluated in
the licensee's SSA and properly integrated into the post-fire SSD procedures. During
plant walk downs of selected areas where local manual operator actions would be
performed, the team inspected area emergency lighting units (ELUs) for operability and
checked the aiming of lamp heads to determine if adequate illumination was available to
correctly and safely perform the actions directed by the procedures.
b.
Findings
No findings of significance were identified.
.08
Cold Shutdown Renairs
a.
Inspection Scone
The team reviewed the licensee's SSA and existing plant procedures to determine if any
repairs were necessary to achieve cold shutdown, and if needed, the equipment and
procedures required to implement those repairs were available onsite.
b.
Findings
No findings of significance were identified.
.09
Fire Barriers and Fire Area/Zone/Room Penetration Seals
7m1ee~ a.
Inspection Scope
The team reviewed the selected fire areas to evaluate the adequacy of the fire
resistance of fire area barrier enclosure walls, ceilings, floors, fire barrier mechanical
and electrical penetration seals, fire doors, and fire dampers. This was accomplished by
observing the material condition and configuration of the installed fire barrier features,
as well as, construction details and supporting fire endurance tests for the installed fire
S.
a
barrier features to verify the as-built configurations were qualified by appropriate fire
endurance tests. The team also reviewed the fire hazards analysis to verify the fire
loading used by the licensee to determine the fire resistive rating of the fire barrier
enclosures. The team also reviewed the design specification for mechanical and
electrical penetrations; fire flood and pressure seals, penetration seal database and
Generic Letter (GL) 86-10 evaluations and the calculation for the technical basis of fire
barrier penetration seals to verify that the fire barrier installations met licensing basis
commitments.
The team reviewed fire barriers shown on the fire plan drawings. The station has
eliminated fire barriers from the approved fire protection program and designates these
fire barriers as 'Sealed Firewall - Non Committed". These barriers are no longer
included in any surveillance and testing program. Therefore, doors, dampers, fire
proofing, etc. that exist in these declassified barriers are no longer included in any
station surveillance procedures and effectively cannot be relied upon for the fire
protection program. Two walls associated with Fire Area 18 have been declassified.
The wall between the Switchgear Room (Fire Area 18) and the Electrical Penetration
Area (Fire Area 16) was declassified in Revision 9 (2000) and the wall between the
Switchgear Room (Fire Area 18) and the HVAC Equipment Area (Fire Area 18) was
declassified in Revision 3 (1982). The team requested the Licensee to provide the
engineering analyses that supports the declassification of these barriers. For the
purposes of the inspection of Fire Area 18, the Electrical Penetration Area (Fire Area 16)
was included in the inspection plan because the fire wall separating these areas has
been declassified and is no longer a 'Fire Sealed - NRC Committed" fire barrier. The
similar wall at Unit 1 Room 803A was also declassified from a "Sealed Firewall - NRC
Committed" to a "Sealed Firewall - Non Committed."
The team walked down the selected fire zones/areas to evaluate the adequacy of the
fire resistance of barrier enclosure walls, ceilings, floors, and cable protection. The
team selected several fire barrier features for detailed evaluation and inspection to verify
proper installation and qualification. These features included fire barrier penetration fire
stop seals, fire doors, fire dampers, fire barrier partitions, and Thermo-Lag electrical
raceway fire barrier system (ERFBS) enclosures.
The team observed the material condition and configuration of the selected fire barrier
features and also reviewed construction details and supporting fire endurance tests for
the installed fire barrier features. This review was performed to verify that the observed
fire barrier penetration seal and ERFBS configurations conformed with the design
drawings and tested configurations. The team also compared the penetration seal and
ERFBS ratings with the ratings of the barriers in which they were installed.
The team reviewed licensing documentation, engineering evaluations of Generic Letter 86-10 fire barrier features, and NFPA code deviations to verify that the fire barrier
installations met design requirements and license commitments. In addition, the team
reviewed surveillance and maintenance procedures for selected fire barrier features to
verify the fire barriers were being adequately maintained.
b.
Findings
- (
No findings of significance were identified.
.10
Fire Protection Systems. Features, and Equipment
a.
InsDection ScoDe
d7 Q1
The team reviewed UFSAR Section 9.5.1, Design Basis Specification for Fire Protection,
Fire Protection Code Deviations, and Administrative procedures used to prevent fires
and control combustible hazards and ignition sources. This review was performed to
verify that the objectives established by the NRC-approved FPP were satisfied. The
team also toured the selected plant fire areas to observe the licensee's implementation
of these procedures.
The team reviewed the adequacy of the design and installation of the automatic wet
pipe sprinkler system protecting the RN pumps in Fire Area 4. Team members
performed a walk down of the system to ensure proper placement and spacing of the
sprinkler heads and the extent of the sprinkler head obstructions. Selected engineering
evaluation for NFPA code deviations were reviewed and compared against the physical
configuration of the system. The team reviewed the sprinkler system hydraulic
calculations for this system to ensure that the system could be supplied sufficient
pressure and volume utilizing the two by-pass lines without opening the deluge valves.
The team also inspected one of the by-pass lines located in an outside pit to determine
the piping and fitting equivalent length to confirm the accurateness of the design input to
the RN pump calculation. The team reviewed the fire protection code deviations
calculation for automatic suppression systems relative to the selected areas.
The team reviewed the adequacy of the design and installation of the automatic
detection and alarm system for the selected areas. This was accomplished by
reviewing the ceiling reinforcing plans and beam schedule drawings to determine the
location of ceiling bays. After the ceiling bay locations were identified, the team
conducted a plant tour to confirm that each bay was protected by a fire detector in
accordance with the Code of Record requirements - NFPA 72E, 1974. Field tours were
conducted in fire areas 13, 16/18 to confirm detector locations. Mincr modification
package MM-12907 was reviewed where 10 new detectors were added to Fire Area 13
to conform the detection system to NFPA 72E location requirements.
The team reviewed the fire protection code deviations calculation for automatic
detection systems relative to the selected areas to determine if there were any code
deviations cited for the selected areas.
The team reviewed the fire protection pre-plans and fire strategies to ensure that hose
locations could sufficiently reach the selected areas for manual fire fighting efforts.
Hose stations in the selected area were inspected to ensure that hose lengths depicted
on the engineering documents were also the hose lengths located in the field. This was
done to ensure that manual fire fighting efforts could be accomplished in the selected
areas.
b.
Findinas
- 4
e1.
No findings of significance were identified.
4.
Other Activities
40A2 Problem Identification and Resolution
a.
Inspection Scope
The team reviewed a sample of licensee audits, self-assessments, and PIPs to verify
that items related to fire protection and to SSD were appropriately entered into the
licensee's CAP in accordance with the MNS quality assurance program and procedural
requirements. The items selected were reviewed for classification, appropriateness,
and timeliness of the corrective actions taken or initiated to resolve the issues. Included
in this review were PlPs G-99-00110, M-99-01884, M-99-01886, M-03-01675, and minor
modification MM-12907 related to the McGuire Fire Protection Functional Audit SA-99-
04(MC)(RA)(FPFA). In addition, the team reviewed the licensee's applicability
evaluations and corrective actions for selected industry experience issues related to fire
protection. The.operating experience (OE) reports were reviewed to verify that the
licensee's review and actions were appropriate.
b.
Findings
JOltld-
One licensee-identified finding (related to the use of manual operator actions in Fire
Area 16/18 without prior NRC approval) involved a violation of NRC requirements. The
enforcement considerations for this violation are discussed in Section 1 R05.03.b.2 of
this inspection report.
The team observed that the adequacy and timeliness of corrective actions to address
the findings from the Fire Protection Functional Audit SA-99-04(MC)(RA)(FPFA)
regarding fire detection in the Battery Rooms (Fire Area 13) were not commensurate
with the risk significance associated with a fire in this area. The licensee's IPEEE
identified that a fire in the Battery Rooms ranked as the top contributor to CDF. The fire
-detection findings were identified in a 1909 licensee self-initiated technical audit (SITA)
SA-99-04. However, the initial minor modification (MM-12907) scope was inadequate in
that only two additional detectors were to be installed in the battery rooms (instead of
nine required to comply with the NFPA Code). Additionally, the modification
implementation date was postponed at least twice. Also, the licensee had initiated PIP
M-03-01675 (dated April 10, 2003) regarding detectors not being installed in accordance
with NFPA codes. When the battery rooms fire area were selected by the team during
the pre-inspection information gathering visit, the team noted that the modification was
revised to install the required number of detectors and received high priority status for
implementation. The Battery Room detectors were installed prior to the first week of the
onsite inspection (May 5-9, 2003).
40A5 Other Activities
itl"4
.01
(Closed) URI 50-369.370/00-09-04: Adequacy of the Fire Rating of Mineral Insulated
Cables in Lieu of Thermo-Lag Electrical Raceway Fire Barrier Systems
a
The NRC had opened this URI for further NRC review of the adequacy of the fire
resistance rating of certain mineral insulated cables that the licensee had installed. The
licensee had replaced an inadequate 3-hour Thermo-Lag fire barrier with mineral
insulated cables, for charging pump 1A, in the Unit 1 train B switchgear room. However,
the adequacy of the testing of the mineral insulated cables, to assure their 3-hour fire
resistance ability, had not been reviewed by the NRC.
The inspectors reviewed the NRC Safety Evaluation Report (SER) of January 13, 2003,
on the licensee's use of mineral insulated cables and also reviewed the licensee's 10 CFR 50.59 safety evaluation for the modification. The NRC SER evaluated the
licensee's installation and fire testing of the mineral insulated cables and concluded that
the licensee had adequately demonstrated that the protection provided by the mineral
insulated cables in the specific application was equivalent to the protection provided by
a 3-hour rated fire barrier. The NRC SER further concluded that this change to the
approved fire protection program did not adversely affect the ability to achieve and
maintain safe shutdown in the event of a fire and, therefore, did not require prior
approval of the NRC. The inspectors concluded that the licensee's 50.59 safety
evaluation for the change had adequately considered that the change did not adversely
affect the ability to achieve and maintain safe shutdown in the event of a fire.
Consequently, the licensee's installation of mineral insulated cables was not a violation
of NRC requirements. This URI is closed.
40A6 Meetinas
On May 23, 2003, the team presented the inspection results to you and other members
of your staff, who acknowledged the findings. The team confirmed that proprietary
information is not included in this report.
. 4
SUPPLEMENTAL INFORMATION
KEY POINTS OF CONTACT
Licensee Personnel
D. Bailey, Mechanical and Civil Engineering (MCE) - Civil
J. Boyle, Training Manager
S. Bradshaw, Superintendent of Operations
H. Brandes, Consulting Engineer, General Office Fire Protection Program
J. Bryant, Regulatory Compliance Engineer
B. Dolan, Safety Assurance Manager
J. Hackney, Operations
T. Harrell, McGuire Station Manager
D. Henneke, Engineer, General Office Probabilistic and Risk Assessment Group
D. Herrick, Civil Engineering Supervisor
D. Jamil, Site Vice President, McGuire Nuclear Station
R. Johansen, Standby Shutdown Facility System Engineer
J. Lukowski, Reactor Electrical Systems (RES) - Power
E. Merritt, RES - Instrumentation and Controls
J. Oldham, Fire Protection Engineer, MCE - Civil
B. Peele, Station Engineering Manager
G. Peterson, Site Vice President, Catawba Nuclear Station
C. Thomas, Regulatory Compliance Manager
NRC Personnel
J. Brady, Senior Resident Inspector, Shearon Harris
E. DiPaolo, Resident Inspector
R. Fanner, Nuclear Safety Intern (Trainee)
C. Ogle, Engineering Branch Chief, Division of Reactor Safety, Region II
R. Rodriguez, Nuclear Safety Intern (Trainee)
S. Shaeffer, Senior Resident Inspector
LIST OF ITEMS OPENED, CLOSED, AND DISCUSSED
Opened
50-369,370/03-07-01
Fire Suppression System for Alternative Shutdown Areas
not in Accordance with 10 CFR 50, Appendix R, Section
llI.G.3 (Section 1R05.02.b)
50-369,370/03-07-02
Failure to Protect Reactor Protection System Cables
Results in Loss of Required Instrumentation (Section
1 R05.03.b.1)
Attachment
, a
.0
50-369,370/03-07-03
50-369,370/03-07-04
50-370/03-07-05
50-370/03-07-06
Requirements Relative to the Number of Spurious
Operations that must be Postulated (Section 1R05.04.b.1)
Methods for Reactor Coolant System Pressure Control
During SSF Operation (Section 1 R05.05.b)
Failure to Provide Adequate Protection for Cables of
Redundant Safe Shutdown Equipment in Fire Area 16/18
(Section 1 R05.03.b.2)
Spurious Closure of Valve 2CA0007A Could Lead to
Damage of the TDAFW Pump (Section 1R05.04.b.2)
Closed
50-369,370/00-09-04
Adequacy of the Fire Rating of Mineral Insulated Cables in
Lieu of Thermo-Lag Electrical Raceway Fire Barrier
Systems (Section 40A5.01)
Discussed
None
Attachment
a
f
A
Attachment
.A
4 . I
LIST OF ACRONYMS
-
Air Handling Unit
-
As Low As Reasonably Achievable
-
American Nuclear Standard
ANSI
-
American National Standards Institute
-
Abnormal Procedure
-
Area Radiation Monitor
-
American Society of Mechanical Engineers
-
American Society for Testing Materials
CA
-
-
Corrective Action Program
-
Central Calibration Facility
-
CFR
-
Code of Federal Regulations
Co
-
-
Chemistry Procedure
-
Duke Power Company
-
Discrete Radioactive Particle
-
-
Electronic Dosimeter
-
-
Effluent Monitoring
EnRad
-
Environmental Radiation
-
End-Of-Cycle
-
Emergency Procedure
-
Engineered Safeguards Feature
-
Engineered Safety Feature Actuation System
EVCC
-
Vital Battery C
FWST
-
Refueling Water Storage Tank
GPM
-
Gallons Per Minute
GV
-
Governor Valve
GWR
-
Gaseous Waste Release
-
Health Physics
-
-
High Efficiency Particulate Air
-
Institute of Nuclear Power Operations
IR
-
Inspection Report
-
Independent Spent Fuel Storage Installation
LCO
-
Limiting Condition for Operation
LER
-
Licensee Event Report
-
-
Lower Limit of Detection
-
Loss of Coolant Accident
-
Liquid Waste Release
MGTM
-
Attachment
.AB 4
I . '
I
KC
ND
NEI
NI
NSD
NV
OS
PAGSS
Pi
PS
RCZ
RD
RF
RN
ROATC
SEIT
SH
SSF
SSPS
TDCA
TH
TI
-
McGuire Nuclear Station
-
Cooling water
-
Non-Cited Violation
-
-
Nuclear Energy Institute
-
Safety Injection
-
Notice of Enforcement Discretion
-
Nuclear Site Directive
-
Chemical and Volume Control
Offsite Dose Calculation Manual
-
-
Post-Accident Gas Sampling System
-
Performance Indicator
-
Problem Investigation Process report
-
Post-Maintenance Testing
-
-
Performance Test
-
Pressurized Water Reactor
-
Quality Control
-
Reactor Auxiliary Building
-
Regulated Air Pump
-
Radiologically Controlled Area
-
Radiation Control Zone
-
Radiation Dosimetry and Records Procedure
--
Radiological Environmental Monitoring Program
-
Fire System
-
Regulatory Guide
-
Nuclear Service Water
-
Reactor Operator at the Controls
-
Radiation Protection
-
Rated Thermal Power
-
Radiation Work Permit
-
Small Article Monitor
-
Self-contained Breathing Apparatus
-
Significance Determination Process
-
Significant Event Investigation Team
-
Spent Fuel Pool
-
Shared Health Physics Procedure
-
Selected Licensee Commitment
-
Structures, Systems, Components
-
Standby Shutdown Facility
-
Solid State Protection System
-
Turbine-Driven Auxiliary Feedwater
-
Total Effective Dose Equivalent
-
Temporary Health Physics Procedure
-
Temporary Instruction
Attachment
A~
I I
-
Thermoluminescent Dosimeter
TS
-
Technical Specifications
U2
-
Unit 2
-
Updated Final Safety Analysis Report
-
Volume Control Tank
-
Whole-body Count
WGDT
-
Waste Gas Decay Tank
-
Work Order
YC
-
Chilled Water (control room)
Attachment