Regulatory Guide 1.137

From kanterella
(Redirected from ML003740180)
Jump to navigation Jump to search
Fuel-Oil Systems for Standby Diesel Generators
ML003740180
Person / Time
Issue date: 10/31/1979
From:
Office of Nuclear Regulatory Research
To:
References
RG-1.137, Rev 1
Download: ML003740180 (3)


U.S. NUCLEAR REGULATORY COMMISSION

Revision 1 October 1979 REGULATORY GUIDE

OFFICE OF STANDARDS DEVELOPMENT

REGULATORY GUIDE 1.137 FUEL-OIL SYSTEMS FOR STANDBY DIESEL GENERATORS

A. INTRODUCTION

General Design Criterion 17, "Electric Power Systems,"

of Appendix A, "General Design Criteria for Nuclear Power Plants," to 10 CFR Part 50, "Domestic Licensing of Produc tion and Utilization Facilities," requires that an onsite elec tric power system and an offsite electric power system be provided to permit functioning of structures, systems, and components important to safety. In addition, Criterion 17 contains requirements concerning system capacity, capabil ity, independence, redundancy, availability, testability, and reliability. Appendix B, "Quality Assurance Criteria for Nu clear Power Plants and Fuel Reprocessing Plants," to 10 CFR

Part 50 establishes overall quality assurance requirements for the design, construction, and operation of structures, sys tems, and components important to safety. This regulatory guide describes a method acceptable to the NRC staff for complying with the Commission's regulations regarding fuel

  • oil systems for standby diesel generators and assurance of adequate fuel-oil quality.

The Advisory Committee on Reactor Safeguards has been consulted concerning this guide and has concurred in the regulatory position.

B. DISCUSSION

Working Group ANS-59.51 of Subcommittee ANS-50, Nu clear Power Plant Systems Engineering, of the American National Standards Committee NI8, Nuclear Design Cri teria, has prepared a standard that provides design require ments for the fuel-oil systems for standby diesel generators.

This standard was approved by the American National Stand ards Committee N18 and its Secretariat, and it was subse quently approved and designated ANSI N195-1976 by the American National Standards Institute on April 12, 1976.

For proper operation of the standby diesel generators, it is necessary to ensure the proper quality of the fuel oil. Appen dix B to ANSI N195-1976 addresses the recommended fuel oil practices. Although not a mandatory part of the stand ard, the staff believes Appendix B can serve as an accept able basis for a program to maintain the quality of fuel oil, as supplemented by regulatory position 2 of this guide.

Lines indicate substantive changes from previous issue.

USNRC REGULATORY GUIDES

Regulatory Guides are issued to describe and make available to the public methods acceptable to the NRC staff of Implementing specific parts of the Commission's regulations, to delineate tech niques used by the staff In evaluating specific problems or postu lated accidents, or to provide guidance to applicants. Regulatory Guides are not substitutes for regulations, and compliance with them Is not required. Methods and solutions different from those set out in the guides will be acceptable If they provide a basis for the findings requisite to the issuance or continuance of a permit or license by the Commission.

Comments and suggestions for improvements in these guides are encouraged at all times, and guides will be revised, as appropriate, to accommodate comments and to reflect new Information or experience. This guide was revised as a result of substantive com ments received from the public and additional staff review.

C. REGULATORY POSITION

1. The requirements for the design of fuel-oil systems for diesel generators that provide standby electrical power for a nuclear power plant that are included in ANSI N 195

1976, "Fuel Oil Systems for Standby Diesel-Generators,"1 provide a method acceptable to tile NRC staff for comply ing with the pertinent requirements of General Design Criterion 17 of Appendix A to 10 CFR Part 50, subject to the following:

a. Throughout ANSI N195-1976, other documents required to be included as part of the standard are either identified at the point of reference or described in Section

7.4, "Applicable Codes, Standards, and Regulations," or in Section 11, "References," of the standard. The specific ac ceptability of these listed documents has been or will be addressed separately in other regulatory guides or in Com mission regulations, where appropriate.

b. Section 1, "Scope,"

of ANSI N195-1976 states that the standard provides the design requirements for the fuel-oil system for standby diesel generators and that it sets forth other specific design requirements such as safety class, materials, physical arrangement, and applicable codes and regulations.

The standard does not specifically address quality assurance, and in this regard ANSI N195-1976 should be used in conjunction with Regulatory Guide

1.28, "Quality Assurance Program Requirements (Design and Construction)," which endorses ANSI N45.2-1977,

"Quality Assurance Program Requirements for Nuclear Power Plants," for the design, construction, and mainten ance of the fuel-oil system.

c. Section 5.4, "Calculation of Fuel Oil Storage Re quirements," of the standard sets forth two methods for the calculation of fuel-oil storage requirements. These two meth ods are (1) calculations based on the assumption that the diesel generator operates continuously for 7 days at its rated capacity, and (2) calculations based on the time-dependent

1Copies may be obtained from the American Nuclear Society,

555 North Kensington Avenue, La Grange Park, Illinois 60525.

Comments should be sent to the Secretary of the Commission, U.S. Nuclear Regialatory Commission Washington, D.C. 20555, Attention: Docketing and Service Branch.

The guides are issued in the following ten broad divisions:

1. Power Reactors

6. Products

2. Research and Test Reactors

7. Transportation

3. Fuels and Materials Facilities

8. Occupational Health

4. Environmental and Siting

9. Antitrust and Financial Review

5. Materials and Plant Protection 10. General Copies of issued guides may be purchased at the current Government Printing Office price. A subscription service for future guides In spe cific divisions Is available through the Government Printing Office.

Information on the subscription service and current GPO prices may be obtained by writing the U.S. Nuclear Regulatory Commission, Washington, D.C. 20555, Attention: Publications Sales Manager.

loads of the diesel generator. For the time-dependent load method, the minimum required capacity should include the capacity to power the engineered safety features.

d. Section 7.3, "Physical Arrangement," of ANSI

N195-1976 states that "the location of day tanks shall be as required by the diesel-engine manufacturer." In addition to this requirement, the physical location of the day tank relative to the engine and design of the engine fuel system should take into account such items as net positive suction head requirements and the potential need for electric fuel pumps powered from a reliable power supply to ensure that the diesel-generator unit can start automatically and attain the required voltage and frequency within acceptable limits and time.

e. Section 7.3 of ANSI N195-1976 states that the arrangement of the fuel-oil system "shall provide for inservice inspection and testing in accordance with ASME Boiler and Pressure Vessel Code,Section XI, 'Rules for Inservice In spection of Nuclear Power Plant Components.' " For those portions of the fuel-oil systems for standby diesel generators that are designed to Section III, Subsection ND of the Code, an acceptable method of meeting the requirements of Sec tion 7.3 is to ensure that the system arrangement would allow:

(1) Pressure testing of the fuel-oil system to a pressure 1.10 times the system design pressure at 10-year intervals. In the case of storage. tanks, recommendations of the tank vendor should be taken into account when estab lishing the test pressure.

(2) A visual examination to be conducted during the pressure test for evidence of component leakages, structural distress, or corrosion.

In the case of buried components, a loss of system pressure during the test constitutes evidence of component leakage.

f. Section 7.3 of ANSI N195-1976 requires that adequate heating be provided for the fuel-oil system.

Assurance should be provided that the fuel oil can be sup plied and ignited at all times under the most severe environ mental conditions expected at the facility. This may be accomplished by use of an oil with a "cloud point" lower than the 3-hour minimum soak temperature 2 expected at the site during the seasonal periods in which the oil is to be used, and/or by maintenance of the onsite fuel oil above the "cloud point" temperature.

g. Section 7.5, "Other Requirements," of the standard states that "protection against external and internal corro sion shall be provided" for the fuel-oil system. To amplify this requirement for buried supply tanks not located within a vault and other buried portions of the system, a protec tive coating and an impressed current-type cathodic protec tion system should be provided in accordance with NACE

Standard RP-01-69

(1972 Revision),

"Recommended

2J.P. Doner, "A Predictive Study for Defining Limitin; Tempera tures and their Application in Petroleum Product Specifications," U.S.

Army, Mobility Equipment Research and Development Center, Coat ing and Chemical Laboratory, Aberdeen Proving Ground, Maryland, CCL Report No. 316.

Practice-Control of External Corrosion on Underground or Submerged Metallic Piping Systems." 3 In addition, the impressed current-type cathodic protection system should be designed to prevent the ignition of combustible vapors or fuel oil present in the fuel-oil systems for standby diesel generators.

h. Section 7.5 of the standard includes requirements for fire protection for the diesel-generator fuel-oil system.

The requirements of Section 7.5 are not considered a part of this regulatory guide since this subject is addressed separately in more detail in other NRC documents. Thus a commitment to follow this regulatory guide does not imply a commitment to follow the requirements of Section 7.5 concerning fire protection.

2. Appendix B to ANSI N195-1976 should be used as a basis for a program to ensure the initial and continuing quality of fuel oil as supplemented by the following:

a. The oil stored in the fuel-oil supply tank, and the oil to be used for filling or refilling the supply tank, should meet the requirements of Federal Fuel Oil Specification VV-F-800b (April 2, 1975); ASTM D975-77, "Standard Specification for Diesel Fuel Oils;" or the requirements of the diesel-generator manufacturer, if they are more restrict ive, as well as the fuel-oil total insolubles level specified in Appendix B to the standard. The "cloud point" should be less than or equal to the 3-hour minimum soak temperature 2 or the minimum temperature at which the fuel oil will be maintained during the period of time that it will be stored.

If test results for viscosity or for water and sediment for fuel oil contained in the supply tanks exceed the limits specified in the applicable specification, the diesel should be considered inoperable. Fuel oil contained in the supply tank not meeting remaining applicable specification require ments should be replaced in a short period of time (about a week).

b. Prior to adding new fuel oil to the supply tanks, onsite samples of the fuel oil should be taken. As a mini mum, prior to the addition of new fuel, tests for the following properties should be conducted:

(1) Specific or API gravity

(2) Water and sediment

(3) Viscosity Test results for the latter two tests should not exceed the limits specified in the applicable specification. Analysis of the other properties of the fuel oil listed in the applicable specification should be completed within 2 weeks of the addition.

c. The periodic sampling procedure for the fuel oil should be in accordance with ASTM D270-1975, "Standard Method of Sampling Petroleum and Petroleum Products." 4

3Copies may be obtained from the National Association of Corro don Engineers, 2400 West Loop South, Houston, Texas 77027.

4Also designated ANSI ZI1.33-1976. Copies may be obtained from the American National Standards Institute, 1430 Broadway, New York, N.Y. 10018.

1.137-2

d. Accumulated condensate should be removed from storage tanks on a quarterly basis or on a monthly basis when it is suspected or known that the groundwater table is equal to or higher than the bottom of buried storage tanks.

e. Day tanks and integral tanks should be checked for water monthly, as a minimum, and after each operation of the diesel where the period of operation was 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or longer. Accumulated water should be removed immediately.

If it is suspected that water has entered the suction piping from the day or integral tank, the entire fuel-oil system between the day or integral tank and the injectors should be

-flushed.

f. As a minimum, the fuel oil stored in the supply tanks should be removed, the accumulated sediment removed, and the tanks cleaned at 10-year intervals. To preclude the intro duction of surfactants in the fuel system, this cleaning should be accomplished using sodium hypochlorite solutions or their equivalent rather than soap or detergents.

g. If an event should occur that would require replenishment of fuel oil without the interruption of operation of the diesel generators, the method of adding fuel oil should be such as to minimize the creation of turbulence of the accumulated residual sediment in the bottom of the supply tank since stirring up this sediment during the addition of acceptable new incoming fuel has the potential of causing the overall quality of the fuel oil in the storage tank to become unacceptable.

h. For those facilities having an impressed current-type cathodic protection system, cathodic protection surveillance should be conducted according to the following procedures:

(1) At intervals not exceeding 12 months, tests should be conducted on each underground cathodic protec tion system to determine whether the protection is adequate.

(2) The test leads required for cathodic protection should be maintained in such a condition that electrical measurements can be obtained to ensure the system is adequately protected.

(3) At intervals not exceeding 2 months, each of the cathodic protection rectifiers should be inspected.

(4) Records of each inspection and test should be maintained over the life of the facility to assist in evaluating the extent of degradation of the corrosion protection systems.

D. IMPLEMENTATION

Except in those cases in which the applicant proposes an acceptable alternative method for complying with specified portions of the Commission's regulations, the method described herein will be used in the evaluation of all (1)

construction permit applications, (2) standard reference system preliminary design applications (PDA) or Type-2 final design applications (FDA-2), and (3)

licenses to manufacture that are docketed after November 1, 1979, except those portions of a construction permit application that:

a. Reference an approved standard reference system preliminary or final design (PDA or FDA) or an application for such approval.

b. Reference an approved standard duplicate plant preliminary or fimal design (PDDA or FDDA).

c. Reference parts of a base plant design qualified and approved for replication.

d. Reference a plant design approved or under review for approval for manufacture under a Manufacturing License, or applications for such approval.

1.137-3