Regulatory Guide 1.155

From kanterella
(Redirected from ML003740034)
Jump to navigation Jump to search
(Task SI 501-4) Station Blackout
ML003740034
Person / Time
Issue date: 08/31/1988
From:
Office of Nuclear Regulatory Research
To:
References
RG-1.155
Download: ML003740034 (24)


U.S. NUCLEAR REGULATORY COMMISSION

August 1988 REGULATORY GUIDE

OFFICE OF NUCLEAR REGULATORY RESEARCH

Reissued to correct REGULATORY GUIDE 1.155 Tables 1, (Task SI 5014)

5, and 6.

STATION BLACKOUT

A. INTRODUCTION

Criterion 17, "Electric Power Systems," of Appendix A, "General Design Criteria for Nuclear Power Plants,"

to 10 CFR Part 50, "Domestic Licensing of Production and Utilization Facilities," includes a requirement that an onsite electric power system and an offsite electric power system be provided to permit functioning of structures, systems, and components important to safety.

Criterion

1, "Quality Standards and Records,"

of Appendix A to 10CFR Part50 includes a requirement for a quality assurance program to provide adequate assurance that structures, systems, and components important to safety will perform their safety functions.

Criterion

18,

"Inspection and Testing of Electric Power Systems," of Appendix A to 10 CFR Part 50

includes a requirement for appropriate periodic testing and inspection of electric power systems important to safety.

The Commission has amended its regulations in 10

CFR Part 50. Paragraph (a), "Requirements," of § 50.63,

"Loss of All Alternating Current Power," requires that each light-water-cooled nuclear power plant be able to withstand and recover from a station blackout (i e,,

loss of the offsite electric power system concurrent with reactor trip and unavailability of the onsite emer gency ac electric power system) of a specified duration.

Section 50.63 requires that, for the station blackout duration, the plant be capable of maintaining core cooling and appropriate containment integrity. It also identifies the factors that must be considered in specify ing the station blackout duration.

Criteria 1 and 18 of Appendix A to 10 CFR Part 50

apply-to safety-related equipment needed to cope-with sta tion blackout and other safety functions. Appendix A of this regulatory guide provides quality assurance guidance for non-safety systems and equipment used to meet the requirements of § 50.63.

This guide describes a method acceptable to the NRC

staff for complying with the Commission regulation that requires nuclear power plants to be capable of coping with a station blackout for a specified duration. This guide applies to all light-water-cooled nuclear power plants.

The Advisory Committee on Reactor Safeguards has been consulted concerning this guide and has concurred in the regulatory position.

Any information collection activities related to this regulatory guide are contained as requirements in the revision of 10 CFR Part 50 that provides the regulatory basis for this guide. The information collection require ments in Part 50 have been cleared under the Office of Management and Budget Clearance No. 3150-0011.

B. DISCUSSION

The term "station blackout" refers to the complete loss of alternating current electric power to the essential and nonessential switchgear buses in a nuclear power plant. Station blackout therefore involves the loss of offsite power concurrent with turbine trip and failure of the onsite emergency ac power system, but not the loss of available ac power to buses fed by station batteries through inverters or the loss of power from "alternate ac sources."

Station blackout and alternate ac source are defined in § 50.2. Because many safety systems required for reactor core decay heat removal and con tainment heat removal are dependent on ac power, the consequences of a station blackout could be severe. In

.the event of a station blackout, the capability to cool the reactor core would be dependent on the availability USNRC REGULATORY GUIDES

The guides are Issued in the following ten broad divisions:

Regulatory Guides are Issued to describe and make available to the public methods acceptable to the NRC staff of implementing

1. Power Reactors

6. Products specific parts of the Commission's regulations, to delineate tech-

2. Research and Test Reactors

7. Transportation niques used by the staff in evaluating specific problems or postu-

3. Fuels and Materials Facilities

8. Occupational Health iated accidents or to provide guidance to applicant

s. Regulatory

4. Environmental and Siting

9. Antitrust and Financial Review Guides are no substitutes for regulations, and compliance with

5. Materials and Plant Protection 10. General them is not required. Methods and solutions different from those set out in the guides will be acceptable if they provide a basis for the findings requisite to the issuance or continuance of a permit or Copies of issued guides may be purchased from the Government license by the Commission.

Printing Office at the current GPO price. Information on current GPO prices may be obtained by contacting the Superintendent of This guide was Issued after consideration of comments received from Documents, U.S. Government Printing Office, Post Office Box the public. Comments and suggestions for Improvements in these

37082, Washington, DC 20013-7082, telephone (202)275-2060 or guides are encouraged at all times, A nd guides will be revised, as

(202)275-2171.

appropriate, to accommodate comments and to reflect new informa tion or experience.

Issued guides may also be purchased from the National Technical Written comments may be submitted to the Rules and Procedures Information Service on a standing order basis. Details on this Branch, DRR,

ADM,

U.S.

Nuclear Regulatory Commission, service may be obtained by writing NTIS, 5285 Port Royal Road, Washington, DC 20555.

Springfield, VA 22161.

of systems that do not require ac power from the essential and nonessential switchgear buses and on the ability to restore ac power in a timely manner.

The concern about station blackout arose because of the accumulated experience regarding the reliability of ac power supplies. Many operating plants have experienced a total loss of offsite electric power, and more occurrences are expected in the future. In almost every one of these loss-of-offsite-power events, the onsite emergency ac power supplies have been available immediately to supply the power needed by vital safety equipment. However, in some instances, one of the redundant emergencyac power supplies

-has been unavailable. In a few cases there has been a com plete loss of ac power, but during these events ac power was restored in a short time without any serious consequences.

In addition, there have been numerous instances when emer gency diesel generators have failed to start and run in response to tests conducted at operating plants.

The results of the Reactor Safety Study (Ref. 1) showed that, for one of the two plants evaluated, a station blackout event could be an important contributor to the total risk from nuclear power plant accidents. Although this total risk was found to be small, the relative importance of station blackout events was established. This finding and the accumulated diesel generator failure experience increased the concern about station blackout.

In a Commission proceeding addressing station black out, it was determined that the issue should be analyzed to identify preventive or mitigative measures that can or should be taken. (See Florida Power & Light Company (St. Lucie Nuclear Power Plant, Unit No. 2) ALAB-603,

12 NRC 30 (1980); modified CLI-81-12, 13 NRC 838

(1981).)

The issue of station blackout involves the likelihood and duration of the loss of offsite power, the redundancy and reliability of onsite emergency ac power systems, and the potential for severe accident sequences after a loss of all ac power. References 2 through 7 provide detailed analyses of these topics. Based on risk studies performed to date, the results indicate that estimated coremelt frequencies from station blackout vary considerably for different plants and could be a significant risk contributor for some plants.

In order to reduce this risk, action should be taken to resolve the safety concern stemming from station blackout. The issue is of concern for both PWRs and BWRs.

This guide primarily addresses the following three areas: (1) maintaining highly reliable ac electric power systems, (2) developing procedures and training to restore offsite and onsite emergency ac power should either one or both become unavailable, and (3) ensuring that plants can cope with a station blackout for some period of time based on the probability of occurrence of a station blackout at a site as well as the capability for restoring ac power in a timely fashion for that site.

One factor that affects ac power system reliability is the vulnerability to common cause failures associated with design, operational, and environmental factors. Exist ing standards and regulatory guides include specific design criteria and guidance on the independence of preferred (offsite) power circuits (see General Design Criterion 17,

"Electric Power Systems," and Section 5.1.3 of Reference

8) and the independence of and limiting interactions between diesel generator units at a nuclear station (see General Design Criterion 17, Regulatory Guide 1.6, "Inde pendence Between Redundant Standby (Onsite) Power Sources and Between Their Distribution Systems," Regula tory Guide

1.75, "Physical Independence of Electric Systems," and Reference 9). In developing the recommenda tions in this guide, the staff hasassumed that, by adhering to such standards, licensees have minimized, to the extent practical, single-point vulnerabilities in design and operation that could result in a loss of all offsite power or all onsite emergency ac power.

Onsite emergency ac power system unavailability can be affected by outages resulting from testing and main

-tenance. Typically, this unavailability is about 0.007 (Reference 5), which is small compared to the minimum emergency diesel generator reliability specified in Regula tory Position 1.1 of this regulatory guide (ie., 0.95 or

0.975 reliability per demand). However, in some cases outages due to maintenance can be a significant con tributor to emergency diesel generator unavailability.

This contribution can be kept low by having high-quality test and maintenance procedures and by scheduling regular diesel generator maintenance at times when the reactor is shut down. Also, limiting conditions for operation in the technical specifications are designed to limit the diesel generator unavailability when the plant is operating. As long as the unavailability due to testing and maintenance is not excessive, the maximum emergency diesel generator failure rates for each diesel generator specified in Regulatory Position 1.1 would result in acceptable overall reliability for the emergency ac power system.

Based on § 50.63, all licensees and applicants are required to assess the capability of their plants to maintain adequate core cooling and appropriate containment integrity during a station blackout and to have procedures to cope with such an event. This guide presents a method accept able to the NRC staff for determining the specified dura tion for which a plant should be able to withstand a station blackout in accordance with these requirements. The application of this method results in selecting a minimum acceptable station blackout duration capability from 2 to

16 hours1.851852e-4 days <br />0.00444 hours <br />2.645503e-5 weeks <br />6.088e-6 months <br />, depending on a comparison of the plant's charac teristics with those factors that have been identified as significantly affecting the risk from station blackout. These factors include redundancy of the onsite emergency ac power system (ie., the number of diesel generators available for decay heat removal minus the number needed for decay heat removal), the reliability of onsite emergency ac power sources (e.g., diesel generators), the frequency of loss of offsite power, and the probable time to restore offsite power.

Licensees may propose durations different from those specified in this guide. The basis for alternative durations

1.155-2

would be predicated on plant-specific factors relating to the reliability of ac power systems such as those discussed in Reference 2.

The information submitted to comply with § 50.63 is also required to be incorporated in an update to the FSAR in accordance with paragraph 50.71(e)(4), It is expected that the applicant or licensee will have available for review, as required, the analyses and related informa tion supporting the submittal.

Concurrent with the development of this regulatory guide, and consistent with discussions with the NRC

staff, the Nuclear Management and Resource Council (NUMARC) has developed guidelines and procedures for assessing station blackout coping capability and duration for light water reactors (NUMARC-8700, Ref. 10). The NRC staff has reviewed these guidelines and analysis methods and concludes that NUMARC-8700 provides guidance for conformance to § 50.63 that is in large part identical to the guidance provided in this regulatory guide. Table 1 of this regulatory guide provides a section by-section comparison between Regulatory Guide 1.155 and NUMARC-8700.

The use of NUMARC-8700 is further discussed in Section C, Regulatory Position, of this guide.

C. REGULATORY POSITION

This regulatory guide describes a means acceptable to the NRC staff for meeting the requirements of

§ 50.63 of 10 CFR Part 50. NUMARC-8700 (Ref. 10)

also provides guidance acceptable to the staff for meet ing these requirements. Table I provides a cross-reference to NUMARC-8700 and notes where the regulatory guide takes precedence.

1. ONSITE EMERGENCY AC POWER SOURCES

(EMERGENCY DIESEL GENERATORS)

1.1 Emergency Diesel Generator Target Reliability Levels The minimum emergency diesel generator (EDG)

reliability should be targeted at 0.95 per demand for each EDG for plants in emergency ac (EAC) Groups A,

B, and C and at 0.975 per demand for each EDG for plants in EAC Group D (see Table 2). These reliability levels will be considered minimum target reliabilities and each plant should have an EDG reliability program containing the principal elements, or their equivalent, outlined in Regulatory Position 1.2. Plants that select a target EDG reliability of 0.975 will use the higher level as the target in their EDG reliability programs.

The EDG

reliability for determining the coping duration for a station blackout will be determined as follows:

1. Calculate the most recent EDG reliability for each EDG based on the last 20, 50, and 100

demands using definitions and methodology in Section 2 of NSAC-108, "Reliability of Emergency Diesel Generators at U.S. Nuclear Power Plants"

(Ref. 11), or equivalent.'

2. Calculate the nuclear unit "average" EDG reliability for the last 20, 50, and 100 demands by averaging the results from step 1 above.

3. Compare the calculated

"average"

nuclear unit EDG reliability from step 2 above against the following criteria:

Last 20 demands > 0.90 reliability Last 50 demands > 0.94 reliability Last 100 demands > 0.95 reliability

4. If the EAC group is A, B, or C AND any of the three evaluation criteria in step 3 are met, the nuclear unit may select an EDG reliability target of either 0.95 or 0.975 for determining the appli cable coping duration from Table 2.

If the EAC group is D and any of the three evaluation criteria in step 3 are met, the allowed EDG reliability target is 0.975.

5. If the EAC group is A, B, or C and NONE of the selection criteria in step 3 are met, an EDG

reliability level of 0.95 must be used for determin ing the applicable coping duration from Table 2.

Additionally, if the "averaged"

nuclear unit EDG

reliability is less than 0.90 based on the last 20

demands, the acceptability of a coping duration based on an EDG reliability of 0.95 from Table 2 must be further justified.

If the EAC group is D and NONE of the three evaluation criteria in step 3 are met, the required coping duration (derived by using Table 2) should be increased to the next highest coping level (i.e.,

4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> to 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> to 16 hours1.851852e-4 days <br />0.00444 hours <br />2.645503e-5 weeks <br />6.088e-6 months <br />).

1.2 Reliability Program The reliable operation of onsite emergency ac power sources should be ensured by a reliability program designed to maintain and monitor the reliability level of each power source over time for assurance that the selected reliability levels are being achieve

d. An EDG

reliability program would typically be composed of the following elements or activities (or their equivalent):

1. Individual EDG reliability with the plant category selected from Table 2.

target levels consistent and coping duration

2. Surveillance testing and reliability monitoring programs designed to track EDG performance and to support maintenance activities.

IThis EDG reliability is not suitable for probabilistic risk analyses for design basis accidents because of the differing EDG start-rel/ability requirement that would be applicable for such probabilistic risk analyses.

1.155-3

3. A maintenance program that ensures that the target EDG reliability is being achieved and that provides a

capability for failure analysis and root-cause investigations.

4. An information and data collection system that services the elements of the reliability program and that monitors achieved EDG

reliability levels against target values.

5. Identified responsibilities for the major program elements and a management oversight program for reviewing reliability levels being achieved and ensuring that the program is functioning properly.

1.3 Procedures for Restoring Emergency AC Power Guidelines and procedures for actions to restore emergency ac power when the emergency ac power system is unavailable should be integrated with plant specific technical guidelines and emergency operating procedures developed using the emergency operating procedure upgrade program established in response to Supplement 1, "Requirements for Emergency Response Capability" (Generic Letter No. 82-33),2 to NUREG-0737,

"Clarification of TMI

Action Plan Requirements"

(Ref. 12).

2. OFFSITE POWER

Procedures should include the actions necessary to restore offsite power and use nearby power sources 3 when offsite power is unavailable. As a minimum, the following potential causes for loss of offsite power should be considered:

Grid undervoltage and collapse Weather-induced power loss Preferred power distribution system faults4 that could result in the loss of normal power to essen tial switchgear buses

3. ABILITY TO COPE WITH A STATION BLACKOUT

The ability to cope with a station blackout for a certain time provides additional "defense-in-depth should both offsite and onsite emergency ac power systems fail concurrently. Regulatory Position 3.1 provides a method to determine an acceptable minimum time that a plant should. be able to cope.with a station blackout based on

2 Modifications or additions to generic technical guide lines that are necessary to deal with a station blackout for the specific plant design should be identified as deviations in the plant-specific technical guidelines as required by Supplement 1 to NUREG-0737 (Ref. 12) and outlined in NIREG-0899, "Guidelines for the Preparation of Emer gency Operating Procedures ".(Ref. 13).

3ThIs includes such items as nearby or onsite gas turbine lenerators, portable generators, hydro generators, and ack-start fossil power plants.

4Includes such failures as the distribution system hard ware, switching and maintenance errors, and lightning induced faults.

the probability of a station blackout at the site as well as the capability for restoring ac power for that site. Each nuclear power plant has the capability to remove decay heat and maintain appropriate containment integrity without ac power for a limited period of time.

Regulatory Position3.2 provides guidance for determining the length of time that a plant is actually able to cope with a station blackout. If the plant's actual station blackout capability is significantly less than the accept able minimum duration, modifications may be necessary to extend the plant's ability to cope with a station blackout.

Should plant modifications be necessary, Regulatory Position 3.3 provides guidance on making such modifications. Whether or not modifications are necessary, procedures and training for station blackout events should be provided according to the guidance in Regulatory Position 3.4.

3.1 Minimum Acceptable Station Blackout Duration Capability Each nuclear power plant should be able to withstand and recover from a station blackout lasting a specified minimum duration. The specified duration of station blackout should be based on the following factors:

1. The redundancy of the onsite emergency ac power system (i.e., the number of power sources available minus the number needed for decay heat removal),

2. The reliability of each of the onsite emergency ac power sources (e.g., diesel generator),

3. The expected frequency of loss of offsite power, and

4. The probable time needed to restore offsite power.

A method for determining an acceptable minimum station blackout duration capability as a function of the above site- and plant-related characteristics is given in Table 2. Tables 3 through 8 provide the necessary detailed descriptions and definitions of the various factors used in Table 2. Table 3 identifies different levels of redundancy of the onsite emergency ac power system used to define the emergency ac power configuration groups in Table 2. Table 4 provides definitions of the three offsite power design characteristic groups used in Table 2. The groups are defined according to various combinations of the following factors: (1) independence of offsite power (1), (2) severe weather (SW), (3) severe weather recovery (SWR),

and

(4) extremely severe weather (ESW). The definitions of the factors I, SW,

SWR, and ESW are provided in Tables 5 through 8, respectively. After identifying the appropriate groups from Tables 3 and 4 and the reliability level of the onsite emergency ac power soUrces (determined in accor dance with Regulatory Position 1.1), Table 2 can be used to determine the acceptable minimum station blackout duration capability for each plant.

1.155-4

3.2 Evaluation of Plant-Specific Station Blackout Capability Each nuclear power plant should be evaluated to determine its capability to withstand and recover from a station blackout of the acceptable duration determined for that plant (see Regulatory Position 3.1). The follow ing considerations should be included when determining the plant's capability to cope with a station blackout.

3.2.1. The evaluation should be performed assuming that the station blackout event occurs while the reactor is operating at 100% rated thermal power and has been at this power level for at least 100 days.

3.2.2. The capability of all systems and components necessary to provide core cooling and decay heat removal following a station blackout should be deter mined, including station battery capacity, condensate storage tank capacity, compressed air capacity, and instrumentation and control requirements.

3.2.3. The ability to maintain adequate reactor coolant system inventory to ensure that the core is cooled should be evaluated, taking into consideration shrinkage, leakage from pump seals, and inventory loss from letdown or other normally open lines dependent on ac power for isolation.

3.2.4. The design adequacy and capability of equip ment needed to cope with a station blackout for the required duration and recovery period should be addressed and evaluated as appropriate for the associated environ mental conditions. This should include consideration as appropriate of the following:

1. Potential failures of equipment necessary to cope with the station blackout,

2. Potential environmental effects on the operability and reliability of equipment necessary to cope

-with the station blackout, including possible effects of fire protection systems,

3. Potential effects of other hazards, such as weather, on station blackout response equipment (e.g.,

auxiliary equipment to operate onsite buses or to recover EDGs and other equipment as needed),

4. Potential habitability concerns for those areas that would require operator access during the station blackout and recovery period.

Evaluations that have already been performed need not be duplicated. For example, if safety-related equip ment required during a total loss of ac power has been qualified to operate under environmental conditions exceeding those expected under a station blackout (e.g.,

loss of heating, ventilation, and air conditioning), addi tional analyses need not be performed. Equipment will be considered acceptable for station blackout temperature environments if an assessment has been performed that provides reasonable assurance that the required equip ment will remain operable.

3.2.5. Consideration should be given to using available non-safety-related equipment, as well as safety-related equipment, to cope with a station blackout provided such equipment meets the recommendations of Regula tory Positions 3.3.3 and 3.3.4. Onsite or nearby alternate ac (AAC) power sources that are independent and diverse from the normal Class IE emergency ac power sources (e.g., gas turbine, separate diesel engine, steam supplies) will constitute an acceptable station blackout coping capability provided an analysis is performed that demonstrates the plant has this capability from the onset of station blackout until the AAC power source or sources are started and lined up to operate all equip ment necessary to cope with station blackout for the required duration.

In general, equipment required to cope with a station blackout during the first 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> should be available on the site. For equipment not located on the site, consid eration should be given to its availability and accessibility in the time required, including consideration of weather conditions likely to prevail during a loss of offsite power.

If the AAC source or sources meet the recommenda tions of Section 3.3.5 and can be demonstrated by test to be available to power the shutdown buses within 10

minutes of the onset of station blackout, no coping analysis is required.

3.2.6. Consideration should be given to timely opera tor actions inside or outside the control room that would increase the length of time that the plant can cope with a station blackout provided it can be demon strated that these actions can be carried out in a timely fashion. For example, if station battery capacity is a limiting factor in coping with a station blackout, shed ding nonessential loads on the batteries could extend the time until the battery is depleted. If load shedding or other operator actions are considered, corresponding procedures should be incorporated into the plant-specific technical guidelines and emergency operating procedures.

3.2.7. The ability to maintain "appropriate contain ment integrity"

should be addressed.

"Appropriate containment integrity" for station blackout means that adequate containment integrity is ensured by providing the capability, independent of the preferred and blacked out unit's onsite emergency ac power supplies, for valve position indication and closure for containment isolation valves that may be in the open position at the onset of a station blackout. The following valves are excluded from consideration:

1. Valves normally locked closed during operation,

2. Valves that fail closed on a loss of power,

1.155-5

3. Check valves,

4. Yalves in nonradioactive closed-loop systems not expected to be breached in a station blackout (this does not include lines that communicate directly with containment atmosphere), and

5. Valves of less than 3-inch nominal diameter.

3.3 Modifications To Cope with Station Blackout If .the plant's station blackout capability, as deter mined according to the guidance in Regulatory Position

3.2, is significintly less than the minimum acceptable plant-specific station blackout duration (as developed according to Regulatory Position 3.1 or as justified by the licensee or applicant on some other basis and accepted by the staf), modifications to the plant may be necessary to extend the time the plant is able to cope with a station blackout. If modifications are needed, the following items should be considered:

3.3.1. If, after considering load shedding to extend the time until battery depletion, battery capacity must be extended further to 'meet the station blackout dura tion recommended in Regulatory Position3.1, it is considered acceptable either to add batteries or to add a charging system for the existing batteries that is inde pendent of both the offsite and the blacked-out unit's onsite emergency ac power systems, such as a dedicated diesel generator.

3.3.2. If the capacity of the condensate storage tank is not sufficient to remove decay heat for the station blackout duration recommended in Regulatory Position 3.1, a system meeting the requirements of Regulatory Posi tion 3.5 to resupply the tank from an alternative water source is an acceptable means to increase its capacity provided any power source necessary to provide addi tional water is independent of both the offsite and the blacked-out unit's onsite emergency ac power systems.

3.3.3. If the compressed air capacity is not sufficient to remove decay heat and to maintain appropriate containment integrity for the station blackout duration recommended in Regulatory Position 3.1, a system to provide sufficient capacity from an alternative source that meets Regulatory Position 3.5 is an acceptable means to increase the air capacity provided any power source necessary to provide additional air is independent of both the offsite and the blacked-out unit's onsite emergency ac power systems.

3.3.4. If a system is required for primary coolant charging and makeup, reactor coolant pump seal cooling or injection, decay heat removal, or maintaining appro priate containment integrity specifically to meet the station blackout duration recommended in Regulatory Position 3.1, the following criteria should be met:

1. The system should be capable of being actuated and controlled from the control room, or if other means of control are required, it should be demonstrated that these steps can be carried out in a timely fashion, and

2. If the system must operate within 10 minutes of a loss of all ac power, it should be capable of being actuated from the control room.

3.3.5. If an AAC power source is selected specifically for satisfying the requirements for station blackout, the design should meet the following criteria:

1. The AAC

power source should not normally be directly connected to the preferred or the blacked-out unit's onsite emergency ac power system.

2. There should be a minimum potential for common

-cause failure with the preferred or the blacked-out unit's onsite emergency ac power sources. No single-point vulnerability should exist whereby a weather-related event or single active failure could disable any portion of the blacked-out unit's onsite emergency ac power sources or the preferred power sources and simultaneously fail the AAC power source.

3. The AAC power source should be available in a timely manner after the onset of station blackout and have provisions to be manually connected to one or all of the redundant safety buses as required.

The time required for making this equipment available should not be more than

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> as demonstrated by test. If the AAC power source can be demonstrated by test to be available to power the shutdown buses within 10 minutes of the onset of station blackout, no coping analysis is required.

4. The AAC power source should have sufficient capacity to operate the systems necessary for coping with a station blackout for the time required to bring and maintain the plant in safe shutdown.

5. The AAC power system should be inspected, maintained, and tested periodically to demonstrate operability and reliability. The reliability of the AAC power system should meet or exceed 95 per cent as determined in accordance with NSAC-108 (Ref. 11) or equivalent methodology.

An AAC power source serving a multiple-unit site where onsite emergency ac sources are not shared between units should have, as a minimum, the capacity and capability for coping with station blackout in any of the units.

At sites where onsite emergency sources are shared between units, the AAC power sources should have the capacity and capability to ensure that all units can be brought to and maintained in safe shutdown (i.e., those plant conditions defined in plant technical specifications

1.155-6

as Hot Standby or Hot Shutdown, as appropriate). Plants have the option of maintaining the RCS at normal operating temperatures or at reduced temperatures.

Plants that have more than the required redundancy of emergency ac sources for loss-of-offsite-power condi tions, on a per nuclear unit basis, may use one of the existing emergency sources as an AAC power source provided it meets the applicable criteria for an AAC

source. Additionally, emergency diesel generators with

1-out-of-2-shared and 2-out-of-3-shared ac power configura tions may not be used as AAC power sources.

3.3.6. If a system or component is added specifically to meet the recommendations on station blackout duration in Regulatory Position 3.1, system walk downs and initial tests of new or modified, systems or critical components should be performed to verify that the modifications were performed properly.

Failures of added components that may be vulnerable to internal or external hazards within the design basis (e.g., seismic events) should not affect the operation of systems required for the design basis accident.

3.3.7. A system or component added specifically to meet the recommendations on station blackout duration in Regulatory Position 3.1 should be inspected, main tained, and tested periodically to demonstrate equipment operability and reliability.

3.4 Procedures and Training To Cope with Station Blackout Proceduress and training should include all operator actions necessary to cope with a station blackout for at least the duration determined according to Regulatory SProcedures should be integrated with plant-specific technical guidelines and emergency operating procedures developed using the emergency operating procedure up grade program established in response to Supplement 1 of NUREG-0737 (Ref. 12). The task analysis -portion of the emergency operating procedure upgrade program should include an analysis of instrumentation adequacy during a station blackout.

Position 3.1 and to restore normal long-term core cooling/

decay heat removal once ac power is restored.

3.5 Quality Assurance and Specification Guidance for Station Blackout Equipment That Is Not Safety Related Appendices A and B provide guidance on quality assurance (QA) activities and specifications respectively for non-safety related equipment used to meet the requirements of § 50.63 and not already covered by existing QA requirements in Appendix B or R of Part 50. Appropriate activities should be implemented from among those listed in these appen dices depending on whether the non-safety equipment is being added (new) or is existing. This QA guidance is applicable to non-safety systems and equipment for meet ing the requirements' of " 50.63 of )l0 CFR Part 50.

The guidance on QA and specifications incorporates a lesser degree of stringency by eliminating requirements for involvement of parties outside the normal line organization.

NRC inspections will focus on the implementation and effectiveness of the quality controls 'described in Appen dices A and B. Additionally, the equipment installed to meet the station blackout rule must be implemented such that it does not degrade the existing safety-related systems. This is to be accomplished by making the non safety-related equipment as independent as practicable from existing safety-related systems.

The non-safety systems identified in Appendix B are acceptable to the NRC staff for responding to a station blackout.

D. IMPLEMENTATION

The purpose of this section is to provide information to applicants and licensees regarding the NRC staffs plans for using this regulatory guide. Except in those cases in which the applicant or licensee proposes an acceptable alternative method for complying with specified portions of the Commission's regulations, the method described in this guide may be used in the evaluation of submittals by applicants for construction permits and operating licenses (as appropriate) and will be used to evaluate licensees who are required to comply with § 50.63, "Loss of All Alter nating Current Power," of 10 CFR Part 50.

1.155-7

TABLE 1 CROSS-REFERENCE BETWEEN REGULATORY

GUIDE 1.155 AND NUMARC-8700

Regulatory Position in R.G. 1.155 Section in NUMARC-8700

1.1

3.2.3, 3.2.4

1.2 Appendix D

1.3

4.2.1,4.3.1

2

4.2.2, 4.3.2

3.1

3

3.2.1

2.2.1, 2.2.2

3.2.2

2.9, 7.2.1, 7.2.2, 7.2.3

3.2.3

2.5

3.2.4

2.7, 4.2.1,4.2.2, 7.2.4, Appendices E and F

3.2.5

7.1.1, 7.1.2, Appendices B and C

3.2.6

4.2.1, 4.3.1, 7.2.1, 7.2.2, 7.2.3

3.2.7

2.10, 7.2.5

3.3.1

7.2.2

3.3.2

7.2.1

3.3.3

7.2.3

3.3.4

2.5

3.3.5

2.3.1, 7.1.1, 7.1.2, Appendices A,

B, and C

3.3.6 None (Use Regulatory Guide 1.155)

3.3.7

4 .2 .1(12),4.3.1(12), Appendices A

and B

3.4

4

3.5 None (Use Regulatory Guide 1.155)

Appendix A

None (Use Regulatory Guide 1.155)

Appendix B

None (Use Regulatory Guide 1.155

1.155-8

TABLE 2 ACCEPTABLE STATION BLACKOUT DURATION CAPABILITY (HOURS)a Emergency AC Power Configuration Groupb Unit "Average" EDG Reliabilityc Offsite Power Designd

0.975

0.95

0.975

0.95

0.975

0.95

0.975 Characteristic Groupd P1

2

2

4

4

4

4

4 P2

4

4

4

4

4

8

8 P3

4

8

4

8

8

16

8 aVariations from these times will be considered by the staff if justification, including a cost-benefit analysis, is provided by the licensee. The methodology and sensitivity studies presented in NUREG-1032 (Ref. 2) are acceptable for use in this justification.

bsee Table 3 to determine emergency ac power configuration group.

cSee Regulatory Position 1. 1.

dSee Table 4 to determine groups P1, P2, and P3.

1.155-9

TABLE 3 EMERGENCY AC POWER CONFIGURATION GROUPSa EAC Power Number of EAC Power Sources Configuration Number of EAC

Required To Operate AC-Powered Group Power Sourcesb Decay Heat Removal Systemsc A

3 d

1

4

'1 B

4

2

5

2 C

2 d

1

3e1 D

2f1

3

2

4

3

5

3 aSpecial-purpose dedicated diesel generators, such as those associated with high-pressure core spray systems at some BWRs, are not counted in the determination of EAC power configuration groups.

1 b1f any of the EAC power sources are shared among units at a multi-unit site, this is the total number of shared and dedicated sources for those units at the site.

cThis number is based on all the ac loads required to remove decay heat (including ac-powered decay heat removal systems) to achieve and maintain safe shutdown at all units at the site with offsite power unavailable.

dFor EAC power sources not shared with other units.

eFor EAC power sources shared with another unit at a multi-unit site.

fFor shared EAC power sources in which each diesel generator is capable of providing ac power to more than one unit at a site concurrently.

1.155-10

TABLE 4 OFFSITE POWER DESIGN CHARACTERISTIC GROUPS

Group Offsite Power Design Characteristics Sites that have any combination of the following factors:

,a Swb SWRc ESWd P1 lor2 lor2 lor2 lor2

1 or2

1

1 or2

3

1 or2

3

1

1 or2 P2 All other sites not in PI or P3.

Sites that expect to experience a total loss of offsite power caused by grid failures at a frequency equal to or greater than once in 20 site-years, unless the site has procedures to recover ac power from reliable alternative (nonemergency) ac power sources within approximately one-half hour following a grid failure.

or Sites that have any combination of the following factors:

P3 I

SW

SWR

ESW

Any 1

5

2 Any ESW

Any 1

1,2,3, or 4

1 or 2

5 Any 1

5

1 Any ESW

Any 1

4

2

1,2,3, or 4

1 or2

3

2

4

3

3

2

3 or4 aSee Table 5 for definitions of independence of offsite power (I) groups.

bSee Table 6 for definitions of severe weather (SW) groups.

cSee Table 7 for definitions of severe weather recovery (SWR) groups.

dSee Table 8 for definitions of extremely severe weather (ESW) groups.

1.155-11

TABLE 5 DEFINITIONS OF INDEPENDENCE OF OFFSITE POWER GROUPS

Category

23

1.

All offsite power sources are L.a. All offsite power sources are connected to the connected to the plant plant through one switchyard.

through two or more switchyards or separate OR

incoming transmission

1.

Independence of offsite lines, but at least one of

1.b. All offsite power sources are connected to the power sources the ac sources is electrically plant through two or more switchyards, and independent of the others.

the switchyards are electrically connected.

(The independent 69-kV

(The 345- and 138-kV switchyards in Figures line in Figure 1 is

2 and 3 represent this design feature.)

representative of this design feature.)

OR

AND

AND

2.

Automatic and manual

2.a. After loss of the normal ac

2.a. After loss of the normal

2.a. If the normal transfer schemes for the source, ac power source, there is source of ac Class 1 E buses when the an automatic transfer of power fails, there normal source of ac power

(1) There is an automatic all safe-shutdown buses are no automatic fails and when the back- transfer of all safe- to one preferred alter- transfers and up sources of offsite shutdown buses to nate power source. If one or more power fail.

a separate preferred this source fails, there manual transfers alternate power source.

may be one or more of all safe-shut a.

The normal source of manual transfers of down buses ac power is assumed

(2) There is an automatic power source to the to preferred or to be the unit main transfer of all safe- remaining preferred alternate off generator.

shutdown buses to one or alternate offsite site power preferred power source.

power sources, sources.

If this preferred power source fails, there is OR

another automatic transfer to the There is one auto remaining matic transfer preferred power and no manual sources or to alter- transfer of all nate offsite power safe-shutdown source.

buses to one preferred or one alternate offsite power source.

OR

OR

b.

If the Class 1E buses

2.b. Each safe-shutdown bus is

2.b. The safe-shutdown buses are normally aligned are normally designed normally connected to a to the same preferred power source with to be connected to the separate preferred alter- either an automatic or manual transfer to the preferred or alternate nate power source with remaining preferred or alternate ac power power sources.

automatic or manual source.

transfer capability between the preferred or alternate sources.

t-

1.155-12

TABLE 6 DEFINITIONS OF SEVERE WEATHER (SW) GROUPS

Estimated Frequency of Loss of Offsite Power Due to SW Group Severe Weather, f (per Site-Year)*

1 f <3.3 x 10-3

2

3.3x10 3

<f<

lx10-2

3

1x10-2

<f<3.3x10-2

4

3.3x10-2

<f< 1xl0"1

5

1x10"1

<f

  • The estimated frequency of loss of offsite power due to severe weather, f, is determined by the following equation:

f = (1.3 x 10"4)hl + (b)h 2 + (0.012)h 3 + (c)h 4 where h 1 = annual expectation of snowfall for the site, in inches h2 = annual expectation of tornadoes (with wind speeds greater than or equal to 113 miles per hour) per square mile at the site b = 12.5 for sites with transmission lines on two or more rights of-way spreading out in different directions from the switch yard, or b = 72.3 for sites with transmission lines on one fight-of-way h3= annual expectation of storms at the site with wind velocities between 75 and 124 mph h4= annual expectation of hurricanes at the site c = 0 if switchyard is not vulnerable to the effects of salt spray c = 0.78 if switchyard is vulnerable to the effects of salt spray The annual expectation of snowfall, tornadoes, and storms may be obtained from National Weather Service data from the weather station nearest to the plant or by interpolation, if appropriate, between nearby weather stations.

The basis for the empirical equation for the frequency of loss of offsite power due to severe weather, f, is given in Appendix A to Reference 2.

1.155-13

TABLE 7 DEFINITIONS OF SEVERE WEATHER RECOVERY (SWR) GROUPS

SWR Group Definition I

Sites with enhanced recovery (i.e., sites that have the capability and procedures for restor ing offsite (nonemergency) ac power to the site within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> following a loss of offsite power due to severe weather).

2 Sites without enhanced recovery.

TABLE 8 DEFINITIONS OF EXTREMELY SEVERE WEATHER (ESW) GROUPS

ESW Group Annual expectation of storms at a site with wind velocities equal to or greater than 125 miles per hour (e)*

1 e <3.3x 10-4

2

3.3x 10-4 <e<1x 10-3

3

1x10-3 <e<3.3x10-3

4

3.3x10-3 <e <1x10-2

5

1 x 10-2 <e

  • The annual expectation of storms may be obtained from National Weather Service data from the weather station nearest to the plant or by interpola tion, if appropriate, between nearby weather stations.

--L-

1.155-14

69 kV

MAIN

GENERATOR

NM

U UI

UMPI ILI

TRANSFER

7AUTOMATIC

NC

NC

NO

NO TRANSFER

CLASS 1E

NONSAFETY

CLASS 1E

NONSAFETY

I .. AUTOMATIC TRANSFER4 4 I

I

L

AUTOMATIC TRANSFER

_.

Figure 1. Schematic Diagram of Electrically Independent Transmission Line

1.155-15

ttt4t

138 kV

NC

NC

CLASS IE

CLASS IE

DIVISION I

DIVISION 2 NONSAFETY

NO

CLASS 1E

DIVISION I

NONSAFETY

NO

CLASS I E

DIVISION 2 I

I

I

4 IIL

AUTOMATIC TRANSFER

I

-AUTOMATIC TRANSFER

J

Figure 2. Schematic Diagram of Two Switchyards Electrically Connected (One-Unit Site)

GENERATOR 2 NC

NC

NC TO

NONSAFETY

SOME

UNIT 2 UNIT 2 CLASS I E

BUSES,

NO TO

OTHERS

NC TO

SOME

UNIT 2 CLASS 1E

BUSES,

NO TO

OTHERS

t t NC TO

NC TO

SOME

SOME

UNIT I

UNIT I

CLASS I E CLASS I E

BUSES,

BUSES,

NO TO

NO TO

OTHERS OTHERS

+

NC

NC

GENERATOR I

NONSAFETY

UNIT 1 Figure 3. Schematic Diagram of Two Switchyards Electrically Connected (Two-Unit Site)

1.155-16

4 I

345 kV

C W

Att MAIN

GENERATOR

230 kV

MM

MM

I

500 kV

td'V

REFERENCES

1.

U.S.

Nuclear Regulatory Commission,

"Reactor Safety Study," WASH-1400, October 1975.1

2.

U.S. Nuclear Regulatory Commission, "Evaluation of Station Blackout Accidents at Nuclear Power Plants, Technical Findings Related to Unresolved Safety Issue A-44," NUREG-1032, June 1988.1

3.

A. M. Rubin, "Regulatory/Backfit Analysis for the Resolution of Unresolved Safety Issue A-44, Station Blackout,"

U.S. Nuclear Regulatory Commission, NUREG-1109, June 1988.1

4.

U.S. Nuclear Regulatory Commission, "Collection and Evaluation of Complete and Partial Losses of Offsite Power at Nuclear Power Plants," NUREG/

CR-3992 (ORNL/TM-9384), February 1985.1

5.

U.S. Nuclear Regulatory Commission, "Reliability of Emergency AC Power System at Nuclear Power Plants," NUREG/CR-2989 (ORNL/TM-8545), July

1983.1

6.

U.S. Nuclear Regulatory Commission, "Emergency Diesel Generator Operating Experience, 1981-1983,"

NUREG/CR-4347 (ORNL/TM-9739), December 1985.1

7.

U.S. Nuclear Regulatory Commission, "Station Black out Accident Analyses (Part of NRC Task Action Plan A-44)," NUREG/CR-3226 (SAND82-2450), May

1983.1

1NRC publications may be obtained from the Super intendent of Documents, U.S. Government Printing Office, Post Office Box 37082, Washington, DC 20013-7082; or from the National Technical Information Service, Spring field, VA 22161.

8.

Institute of Electrical and Electronics Engineers,

"IEEE Standard for Preferred Power Supply for Nuclear Power Generating Stations," IEEE Std 765-1983, June 1983.2

9.

Institute of Electrical and Electronics Engineers,

"IEEE Standard Criteria for Diesel-Generator Units Applied as Standby Power Supplies for Nuclear Power Generating Stations," IEEE Std 387-1984.

June 1984.2

10.

Nuclear Management and Resources Council, "Guide lines and Technical Bases for NUMARC Initiatives Addressing Station Blackout at Light Water Reactors,"

NUMARC-8700, November 1987.3

11.

Electric Power Research institute, "Reliability of Emergency Diesel Generators at U.S. Nuclear Power Plants," NSAC-108, September 1986.4

12.

U.S. Nuclear Regulatory Commission, "Clarification of TMI Action Plan Requirements: Requirements for Emergency Response Capability" (Generic Letter 82-33), Supplement 1 to NUREG-0737, January 1983.1

13.

U.S. Nuclear Regulatory Commission, "Guidelines for the Preparation of Emergency Operating Procedures,"

NUREG-0899, August 1982.1

2 Copies may be obtained from the Institute of Electrical and Electronics Engineers Service Center, 445 Hoes Lane, P.O. Box 1331, Piscataway, NJ 08855.

3 Copies may be obtained from the Nuclear Management and Resources Council, 1776 Eye Street NW., Washington, DC 20006.

4 Copies may be obtained from the Electric Power Research Institute, Research Reports Center, P.O.

Box

50490, Palo Alto, CA 94303.

1.155-17

APPENDIX A

QUALITY ASSURANCE GUIDANCE FOR NON-SAFETY SYSTEMS AND EQUIPMENT

The QA guidance provided here is applicable to non safety systems and equipment used to meet the requirements of § 50.63 and not already explicitly covered by existing QA requirements in 10 CFR Part 50 in Appendix B or R.

Additionally, non-safety equipment installed to meet the station blackout rule must be implemented so that it does not degrade the existing safety-related systems. This is accomplished by making the non-safety equipment as independent as practicable from existing safety-related systems. The guidance provided in this section outlines an acceptable QA program for non-safety equipment used for meeting the station blackout rule and not already covered by existing QA requirements. Activities should be imple mented from this section as appropriate, depending on whether the equipment is being added (new) or is existing.

1. Design Control and Procurement Document Control Measures should be established to ensure that all design related guidelines used in complying with § 50.63 are included in design and procurement documents, and that deviations therefrom are controlled.

2. Instructions, Procedures, and Drawings Inspections, tests, administrative controls, and training necessary for compliance with § 50.63 should be prescribed by documented instructions, procedures, and drawings and should be accomplished in accordance with these documents.

3. Control of Purchased Material, Equipment, and Services Measures should be established to ensure that purchased material, equipment, and services conform to the procure ment documents.

4. Inspection A program for independent inspection of activities required to comply with § 50.63 should be established and executed by (or for) the organization performing the activity to verify conformance with documented installa- tion drawings and test procedures for accomplishing the activities.

S. Testing and Test Control A test program should be established and implemented to ensure that testing is performed and verified by inspec tion and audit to demonstrate conformance with design and system readiness requirements. The tests should be performed in accordance with written test procedures; test results should be properly evaluated and acted on.

6. Inspection, Test, and Operating Status Measures should be established to identify items that have satisfactorily passed required tests and inspections.

7. Nonconforming Items Measures should be established to control items that do not conform to specified requirements to prevent inadvertent use or installation.

8. Corrective Action Measures should be established to ensure that failures, malfunctions, deficiencies, deviations, defective components, and nonconformances are promptly identified, reported, and corrected.

9. Records Records should be prepared and maintained to furnish evidence that the criteria enumerated above are being met for activities required to comply with § 50.63.

10.

Audits Audits should be conducted and documented to verify compliance with design and procurement documents, instructions, procedures, drawings, and inspection and test activities developed to comply with § 50.63.

1i

1.155-18

4

.L

APPENDIX B

GUIDANCE REGARDING SYSTEM AND STATION EQUIPMENT SPECIFICATIONS

Safety-Related Equipment (Compliance with IEEE-279)

Redundancy Diversity from Existing EDGs Independence from Existing Safety-Related Systems Seismic Qualification Environmental Consideration Capacity Quality Assurance Technical Specification for Maintenance, Limiting Condi tion, FSAR, etc.

Instrumentation and Monitoring Single Failure Common Cause Failure (CCF)

Alternate AC Sources Not required, but the existing Class 1E electrical systems must continue to meet all applicable safety-related criteria.

Not required.

See Regulatory Position 3.3.5 of this guide.

Required if connected to Class 1E buses. Separa tion to be provided by 2 circuit breakers in series (1 Class 1 E at the Class 1E bus and

1 non-Class 1E).

Not required.

If normal cooling is lost, needed for station blackout event only and not for design basis accident (DBA) conditions. Procedures should be in place to effect the actions necessary to maintain acceptable environmental conditions for the required equipment. See Regulatory Position 3.2.4.

Specified in § 50.63 and Regulatory Position

3.3.5.

Indicated in Regulatory Position 3.5.

Should be consistent with the Interim Commission Policy Statement on Technical Specifications (Federal Register Notice 52 FR 3789) as applicable.

Must meet system functional requirements.

Not required.

Design should, to the extent practicable, minimize CCF between safety-related and non safety-related systems.

Alternate Battery Systems Not required, but the existing Class I E battery systems must continue to meet all applicable safety-related criteria.

Not required.

Not required.

.1'

Required if connected to Class 1E battery systems. Separation to be provided by 2 circuit breakers in series (1 Class 1E at the Class 1E

bus and 1 non-Class 1E).

Not required.

If normal cooling is lost, needed for station blackout event only and not for accident condi tions. Procedures should be in place to effect the actions necessary to maintain acceptable environmental conditions for the required equipment. See Regulatory Position 3.2.4.

Specified in § 50.63 and Regulatory Position

3.3.1.

Indicated in Regulatory Position 3.5.

Should be consistent with the Interim Com mission Policy Statement on Technical Specifications (Federal Register Notice

52 FR 3789) as applicable.

Must meet system functional requirements.

Not required.

Design should, to the extent practicable, minimize CCF between safety-related and non safety-related systems.

1.155-19

APPENDIX B (Continued)

Safety-Related Equipment (Compliance with IEEE-279)

Redundancy Diversity Independence from Safety Related Systems Seismic Qualification Environmental Consideration Capacity Quality Assurance Technical Specifica tions for Mainte nance, Surveillance, Limiting Condition, FSAR, etc.

Instrumentation and Monitoring Single Failure Water Source (Existing Condensate Storage Tank or Alternative)

Not required, but the existing Class 1 E systems must continue to meet all applicable safety related criteria.

Not required.

Not required.

Ensure that the existing safety functions are not compromised, including the capability to isolate components, subsystems, or piping, if necessary.

Not required.

Need for station blackout event only and not for DBA

conditions. See Regulatory Position 3.2.4. Procedures should be in place to effect the actions necessary to maintain acceptable environmental conditions for required equipment.

Capability to provide sufficient water for core cooling in the event of a station blackout for the specified duration to meet

§ 50.63 and this regulatory guide.

As indicated in Regulatory Position 3.5.

Should be consistent with the Interim Commission Policy Statement on Technical Specifications (Federal Register Notice 52 FR 3789)

as applicable.

Must meet system functional requirements.

Not required.

Instrument Air (Compressed Air System)

Not required, but the existing Class 1 E systems must continue to meet all applicable safety related criteria.

Not required.

Not required.

Ensure that the existing safety functions are not compromised, including the capability to isolate components, subsystems, or piping, if necessary.

Not required.

Needed for station blackout event only and not for DBA

conditions. See Regulatory Position 3.2.4. Procedures should be in place to effect the actions necessary to maintain acceptable environmental conditions for required equipment.

Sufficient compressed air to components, as necessary, to ensure that the core is cooled and appropriate containment integrity is maintained for the specified duration of station blackout to meet § 50.63 and this regulatory guide.

As indicated in Regulatory Position 3.5.

Should be consistent with the Interim Commission Policy Statement on Technical Specifications (Federal Register Notice 52 FR 3789)

as applicable.

Must meet system functional requirements.

Not required.

Water Delivery System (Alternative to Auxiliary Feedwater System, RCIC

System, or Isolation Condenser Makeup)

Not required, but the existing Class 1 E systems must continue to meet all applicable safety related criteria.

Not required.

Not required.

Ensure that the existing safety functions are not compromised, including the capability to isolate components, subsystems, or piping, if necessary.

Not required.

Needed for station blackout event only and not for DBA

conditions. See Regulatory Position 3.2.4. Procedures should be in place to effect the actions necessary to maintain acceptable environmental conditions for required equipment.

The capacity to provide suffi cient cooling water flow to ensure that the core is cooled in the event of a station black out for the specified duration to meet § 50.63 and this regulatory guide.

As indicated in Regulatory Position 3.5.

Should be consistent with the Interim Commission Policy Statement on Technical Specifications (Federal Register Notice 52 FR 3789)

as applicable.

Must meet system functional requirements.

Not required.

1.155-20

APPENDIX B (Continued)

Water Source (Existing Condensate Storage Tank or Alternative)

Design should, to the extent practicable, minimize CCF

between safety-related and non-safety-related systems.

Instrument Air (Compressed Air System)

Design should, to the extent practicable, minimize CCF

between safety-related and non-safety-related systems.

Water Delivery System (Alternative to Auxiliary Feedwater System, RCIC

System, or Isolation Condenser Makeup)

Design should, to the extent practicable, minimize CCF

between safety-related and non-safety-related systems.

1.155-21 Common Cause Failure (CCF)

APPENDIX B (Continued)

Safety-Related Equipment (Com pliance with IEEE-279)

Redundancy Diversity Independence from Safety Related Systems Seismic Qualification Environmental Consideration Capacity Quality Assurance RCS Makeup System (PWRs and BWRs Without RCIC)

Not required, but the existing Class 1 E systems must continue to meet all applicable safety related criteria.

Not required.

Not required.

1.

Safety-grade isolation devices required between this RCS makeup system and existing safety-related makeup water systems.

2.

A malfunction of this non safety-grade makeup system should not affect the design safety function of any safety related systems.

Not required.

Needed for station blackout event only and not for DBA

conditions if normal cooling is lost. See Regulatory Position

3.2.4. Procedures should be in place to effect the actions necessary to maintain accept able environmental conditions for the required equipment.

Sufficient RCS makeup so that core temperatures are maintained at acceptably low values con sidering a loss of RCP water inventory through a postulated RCP seal failure during the specified duration of station blackout, with a minimum assumed RCP seal leakage of

20 gpm per RCP, unless a lower value is justified.

As indicated in Regulatory Position 3.5.

Isolation Condenser (BWRs Without RCIC)

Not required, but the existing Class 1E systems must continue to meet all applicable safety related criteria.

Not required.

Not required.

1.

Safety-grade isolation devices required between this system and existing safety-related systems.

2.

A malfunction of this non-safety-related system should not affect the design safety function of any safety-related systems.

Not required.

Needed for station blackout event only and not for DBA

conditions if normal cooling is lost. See Regulatory Position

3.2.4. Procedures should be in place to effect the actions necessary to maintain accept able environmental conditions for the required equipment.

Provide sufficient capacity for decay heat removal During the specified duration of station blackout, the isolation condenser pool side requires a water makeup system powered by sources inde pendent from onsite and offsite ac buses.

As indicated in Regulatory Position 3.5.

Instrumentation and Control Room Indications for Verifica tion of RCS Natural Circulation (PWRs and BWRs Without RCIC)

Not required, but the existing Class 1 E systems must continue to meet all applicable safety related criteria.

Not required.

Not required.

A malfunction of this instru mentation and monitoring system should not affect the design safety function of any safety-related instrumentation and monitoring systems powered by onsite or offsite ac power buses.

Not required.

Needed for station blackout event only and not for DBA

conditions if normal cooling is lost. See Regulatory Position

3.2.4. Procedures should be in place to effect the actions necessary to maintain accept able environmental conditions for the required equipment.

Provide sufficient instrumenta tion and control room indica tions for parameters required for verification of RCS natural circulation during the specified duration of station blackout.

As indicated in Regulatory Position 3.5.

1.155-22

APPENDIX B (Continued)

Technical Specifica tions for Mainte nance, Surveillance, Limiting Condition, FSAR, etc.

Instrumentation and Monitoring Single Failure Common Cause Failure (CCF)

RCS Makeup System (PWRs and BWRs Without RCIC)

Should be consistent with the Interim Commission Policy Statement on Technical Specifications (Federal Register Notice 52 FR 3789)

as applicable.

Must meet system functional requirements.

Not required.

Design should, to the extent practicable, minimize CCF

between safety-related and non-safety-related systems.

Isolation Condenser (BWRs Without RCIC)

Should be consistent with the Interim Commission Policy Statement on Technical Specifications (Federal Register Notice 52 FR 3789)

as applicable.

Must meet system functional requirements.

Not required.

Design should, to the extent practicable, minimize CCF

between safety-related and non-safety-related systems.

Instrumentation and Control Room Indications for Verifica tion of RCS Natural Circulation (PWRs and BWRs Without RCIC)

Should be consistent with the Interim Commission Policy Statement on Technical Specifications (Federal Register Notice 52 FR 3789)

as applicable.

Not required.

Design should, to the extent practicable, minimize CCF

between safety-related and non-safety-related systems.

  • U.S.GOVERNMENT

PRINTING OFFICE:1988- 20 2 - 2 9 2 s80149

1.155-23

REGULATORY ANALYSIS

A separate regulatory analysis was not prepared for this regulatory guide. The regulatory analysis prepared for the station blackout rule, NUREG-1109, "Regulatory/Backfit Analysis for the Resolution of Unresolved Safety Issue A-44, Station Blackout," provides the regulatory basis for this guide and examines the costs and benefits of the rule as implemented by the guide. A copy of NUREG-1 109 is UNITED STATES

NUCLEAR REGULATORY COMMISSION

WASHINGTON, D.C. 20555 OFFICIAL BUSINESS

PENALTY FOR PRIVATE USE, $300

available for inspection and copying for a fee at the NRC

Public Document Room, 1717 H Street NW., Washington, DC 20555. Copies of NUREG-1 109 may be purchased from the Superintendent of Documents, U.S. Government Printing Office, Post Office Box 37082, Washington, DC 20013-7082;

or from the National Technical Information Service, Springfield, VA 22161.

FIRST CLASS MAIL

POSTAGE & FEES PAID

USNRC

PERMIT No. G-67

1.155-24