LG-18-097, Registration of Use of Casks to Store Spent Fuel

From kanterella
Jump to navigation Jump to search
Registration of Use of Casks to Store Spent Fuel
ML18236A210
Person / Time
Site: Limerick  Constellation icon.png
Issue date: 08/24/2018
From: Libra R
Exelon Generation Co
To:
Document Control Desk, Office of Nuclear Material Safety and Safeguards, Office of Nuclear Reactor Regulation
References
LG-18-097
Download: ML18236A210 (3)


Text

Exelon Generation LG-18-097 August24,2018 ATTN: Document Control Desk Director, Division of Spent Fuel Management Office of Nuclear Material Safety and Safeguards U.S. Nuclear Regulatory Commission Washington, DC 20555-0001

Subject:

Limerick Generating Station, Units 1 and 2 Renewed Facility Operating License Nos. NPF-39 and NPF-85 NRC Docket Nos. 50-352. 50-353. and 72-065 Registration of Use of Casks to Store Spent Fuel 10 CFR 72.212 In accordance with 10 CFR 72.212, "Conditions of general license issued under §72.210," paragraph (b)(2), Exelon Generation Company, LLC (EGC) is registering, with the NRC, the use of two casks under the general license to store spent fuel at Limerick Generating Station (LGS). The casks were placed into service with stored spent fuel on August 1, 2018 and August 9, 2018. This registration is required to be submitted within 30 days of the cask in-service date. Accordingly, this submittal is due by August 31, 2018.

The following information is provided in accordance with 10 CFR 72.212(b)(2).

Licensee Name: Licensee Address:

Exelon Generation Company, LLC Limerick Generating Station 3146 Sanatoga Road Pottstown, PA 19464 Renewed Reactor License Numbers:

NPF-39 and NPF-85 Reactor Docket Numbers:

50-352, 50-353 Independent Spent Fuel Storage Installation Docket Number:

72-065 Contact Name and

Title:

Robert B. Dickinson Manager - Regulatory Assurance

August24,2018 U.S. Nuclear Regulatory Commission Page 2 Cask Certificate Number:

Cask Model Number:

HSM Model Number:

Service Date:

Cask Identification Number:

HSM Identification Number:

Service Date:

Cask Identification Number:

HSM Identification Number:

1004, Amendment 1 O NUHOMS-61 BTH HSM*H August 1, 2018 LGS-61 BTH-1-D-2H-047 HSM-054 August 9, 2018 LGS-61 BTH-1-D-2H-048 HSM-056 In addition, this letter provides information for each DSC that is required by Certificate of Compliance (CoC) No. 1004, Amendment No.1 O, Attachment A, "Technical Specifications" (TS) 1.1.7, "Special Requirements for First System in Place." Specifically, TS 1.1.7 requires the submittal of a thermal performance assessment for all DSCs that are loaded with higher heat loads than previously reported.

The attachment to this letter provides this information for the DSCs listed above. This information was obtained using LGS procedure ST-6-114-360-0, "Independent Spent Fuel Storage Installation (ISFSI)

Technical Specification Testing."

If you have any questions concerning this report, please contact Mr. Robert Dickinson at 610-718-3400.

Respectfully,

~Ldv--

Richard W. Libra Vice President - Limerick Generating Station Exelon Generation Company, LLC

Attachment:

Thermal Performance Assessment Data, Limerick Generating Station, Independent Spent Fuel Storage Installation, 2018 Dry Cask Storage Campaign cc:

Administrator Region 1 - USNRC USNRC Senior Resident Inspector, LGS NRC Project Manager, NRA - Limerick Generating Station (LGS)

Decommissioning Branch Chief - NAC Region I R.R. Janati, Commonwealth of Pennsylvania, DEP

Attachment Thermal Performance Assessment Data Limerick Generating Station Independent Spent Fuel Storage Installation 2018 Dry Cask Storage Campaign Dry Storage Canister Number LGS-61 BTH-1-D-2H-047 Horizontal Storage Module Number HSM-054 Maximum Allowable Heat Load 19.40kW Actual Loaded Heat Load 14.82 kW Calculated Temperature Rise 46.0° F Measured Temperature Rise 19.5° F Dry Storage Canister Number LGS-61 BTH-1-D-2H-048 Horizontal Storage Module Number HSM-056 Maximum Allowable Heat Load 19.40kW Actual Loaded Heat Load 15.09 kW Calculated Temperature Rise 45.0° F Measured Temperature Rise 37.7° F