FENOC FirstEnergy Nuclear Operating Company Beaver Valley Power Station P.O. Box 4 Shippingport, PA 15077 Paul A. Harden Site Vice President January 31, 2011 L-1 1-002 ATTN: Document Control Desk U.S. Nuclear Regulatory Commission Washington, DC 20555-0001
SUBJECT:
Beaver Valley Power Station, Unit No. 1 Docket No. 50-334, License No. DPR-66 Twentieth Refuelinq Outage Inservice Inspection Report 724-682-5234 Fax: 724-643-8069 Enclosed please find the Inservice Inspection (ISI) Summary Report on American Society of Mechanical Engineers (ASME) Class 1, 2, 3, and IWE examinations performed prior to and during the twentieth refueling outage at Beaver Valley Power Station Unit No. 1 (BVPS-1). The ASME Boiler and Pressure Vessel Code, Section Xl, Article IWA-6240 requires an inservice inspection summary report to besubmitted to the enforcement and regulatory authorities having jurisdiction at the plant site within ninety days of each refueling outage. The recent inservice inspection term at BVPS-1 covered the period from May 22, 2009 to November 5, 2010.
The Class 1, 2, 3, and IWE examinations are part of Interval 4, Period 1 of the BVPS-1 ISI schedule, and were performed in accordance with Section Xl of the ASME Boiler and Pressure Vessel Code, 2001 Edition, 2003 Addenda.
There are no regulatory commitments contained in this letter. If there are any questions or if additional information is required, please contact Mr. Thomas A. Lentz, Manager -
Fleet Licensing, at 330-761-6071.
Sini Paul A. Harden 47 LýW'
Beaver Valley Power Station, Unit No. 1 L-1 1-002 Page 2
Enclosure:
FirstEnergy Nuclear Operating Company, Beaver Valley Power Station, Unit No. 1, Twentieth Refueling Outage Inservice Inspection Report cc: NRC Region I Administrator NRC Resident Inspector NRR Project Manager Director BRP/DEP Site BRP/DEP Representative
FirstEnergy Nuclear Operating Company Beaver Valley Power Station, Unit No. 1 Twentieth Refueling Outage Inservice Inspection Report
BEAVER VALLEY POWER STATION UNIT 1 Route 168, Shippingport, PA Outage 20, Year 2010 Inspection Term: 5/22/2009 to 11/5/2010 Issuedate:
1-2~G-ZO' Owner: FirstEnergy 76 South Main St.
Akron, OH 44308 NRC Docket Number: 50-334 Reactor Supplier: Westinghouse Electric Corporation Commercial Service Date: September 30, 1976
<15 eviewed by:
Reviewed by:
ANII Date: /___
Date: /-
.0 -/
Approved by:
Date:
_[-Z___-
(I Manager, Technical Services Engineering
90-DAY REPORT TABLE OF CONTENTS Item Page Number Cover Page 1
Table of Contents 2
Form NIS-1 3 -4 Outage Summary 5
ASME XI Vessel, Piping and Support Examinations
- 1. Class 1 5
- 2. Class 2 5
- 3. Class 3 5
- 4. IWE 5
IWE Examinations 6
Pressure Testing 6
Deficiency Resolution 6
NIS-2 Forms 6
Appendix I - Completed Code Examinations Appendix II - Repair/Replacement Abstract and NIS-2 Forms 2
FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS As required by the Provisions of the ASME Code Rules
- 1. Owner
- 2. Plant FirstEnergy Nuclear Operating Company, Route 168, Shippingport, PA 15077 (Name and Address of Owner)
Beaver Valley Power Station, Route 168, Shippingport, PA 15077 (Name and Address of Plant)
- 3. Plant Unit 1
- 4. Owner Certificate of Authorization (if required)
N/A
- 5. Commercial Service Date 9/30/76
- 6. National Board Number for Unit N/A
- 7. Components Inspected Manufacturer or Component or Manufacturer or Installer State or National Appurtenance Installer Serial No.
Province No.
Board No.
Reactor Vessel Combustion Engineering 69103 105642B 21011 Pressurizer Westinghouse 1311 434676V 68-50 IA Steam Generator Westinghouse NP030651/1MB2 591601V 82 1A Reactor Coolant Pump Westinghouse 1-618J931GO1 N/A N/A 1 B Reactor Coolant Pump Westinghouse 2-618J931GO1 N/A N/A I1SI-22 Rockwell International N/A N/A N/A Reactor Coolant Piping Southwest Fabricating N/A N/A N/A Auxiliary Piping Schneider Power N/A N/A N/A Component Supports Various N/A N/A N/A Note: Supplemental sheets in form of lists, sketches, or dravings may be used, provided (1) size is 8Y2 in. x 1 1 in.,
(2) information in items I though 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
This form (E0029) maybe obtained from the ASME Order Dept., 22 Law Drive, Box 2300, Fairfield, NJ 070092300 3
FORM NIS-1 (Back)
- 8. Examination Dates 5/22/2009 to 11/5/2010
- 9. Inspection Period Identification:
4/1/2008 to 8/1/2011 (1st Inspection Period of 4th Interval)
- 10. Inspection Interval Identification:
4/1/2008 to 3/31/2018 (4th 10-yr Inspection Interval)
- 11. Applicable Edition of Section XI 2001 Addenda 2003
- 12. Date/Revision of Inspection Plan:
1/2-ADM-2039, Revision 11
- 13. Abstract of Examination and Tests. Include a list of examinations and tests and a statement concerning status of work required for the Inspection Plan. See Appendix I (Code Exams) for exams performed during I R20. I R20 was the second outage in the 1st Period of the 4 th Ten-Year Interval. All of the ASME XI examination percentage requirements have been fulfilled for the 1" 40-Month Period.
- 14. Abstract of Results of Examination and Tests. See text of summary report.
- 15. Abstract of Corrective Measures. The only corrective measures resulting from the scheduled ASME XI ISI examinations in 1 R20 were associated with the containment liner. All of the reported deficiencies were documented and resolved in the corrective action program. None of the reported deficiencies challenged the structural integrity of the containment liner. No liner plate repairs were necessary; only repaintingfrecaulking.
We certify that a) the statements made in this report are correct, b) the examinations and tests meet the Inspection Plan as required by the ASME Code,Section XI, and c) corrective measures taken conform to the rules of the ASME Code,Section XI.
Certificate of Authorization No. (if applicable)
N/A Expiration Date N/A Date I - N-
%I Signed FirstEnergy Nuclear Operating Co.
By (Owner)
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Connecticut have inspected the components described in this Owner's Report during the period 5/22/2009 to 11/05/2010 and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in this Owner's Report in accordance with the Inspection Plan and as required by the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer make any warranty, expressed or implied, concerning the examinations, tests, and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this i'spection,
___________4-._
'__Commissions NB 9428 ANIB, PA 2384 Inspector
-nature National Board, State, Province and Endorsements Date
/-
/ I/-1//
4
OUTAGE
SUMMARY
During the Twentieth Refueling Outage (1 R20) at the Beaver Valley Power Station, Unit 1, Inservice Inspection (ISI) examinations were performed on Class 1, 2, 3 and the containment liner components. This was the second outage in the first period of the fourth ten year interval. The examinations were based on ASME Section XI, 2001 Edition, 2003 Addenda.
ASME XI Class 1, 2, 3 and IWE Credited Exams (See Appendix I)
- 1. Forty-six (46) Class 1 exams were performed and are divided as follows:
- a. Welds (vessels, piping, and attachments)
Ultrasonic Exams 19 Penetrant Exams 2
Visual Exams 4
- b. Class 1 bolting Visual Exams 3
- c. Visual Examinations (VT-3)
Pipe Supports 5
Component Supports 2
- d. RI-ISI piping VT-2 Exams 11
- 2. Forty-seven (47) Class 2 exams were performed and are divided as follows:
- a. Welds (vessels, pumps, piping, and attachments)
Ultrasonic Exams 16 Penetrant Exams 1
- b. Visual Examinations (VT-3)
Pipe Supports 5
- c. RI-ISI piping VT-2 exams 25
- 3. Five (5) visual exams of Class 3 components were performed and are divided as follows:
- a. Supports, visual exams 4
- b. Attachments, visual exam 1
- 4. Fifty-one (51) IWE exams were performed as follows:
- a. Liner 1 (General Visual)
- b. Moisture Barrier 1 (General Visual)
- c. Previous liner repair 1 (UTT)
- d. Non-Random liner exams 10 (UTT)
- e. Random liner exams 38 (UTT)
Examinations were performed by FirstEnergy Nuclear Operating Company (FENOC) NDE Technicians, supplemented with contracted NDE technicians from IDDEAL Concepts, Integrated Technologies, Inc.
(iTi), and Wesdyne. Appendix I compiles the examinations that have been credited toward fulfilling the Ten Year Plan requirements.
5
IWE Examinations The 1R20 IWE examinations included a general visual of the accessible areas of the liner plate and moisture barrier. This examination was performed per a corrective action associated with the containment liner through-wall discovered during 1 Ri 9. The corrective action also included a thickness examination of the replacement plate. Both examinations found no conditions that would challenge the structural integrity of the containment liner. Paint repairs were required.
According to licensing renewal commitments, UT thickness examinations were performed on the BV1 containment liner. Ten (10) non-random and thirty-eight (38) random locations were completed. There was no evidence of material loss in any of these examinations. A summary report of these examinations, separate from this report, has been submitted to the NRC.
Pressure Testing The Class 1 piping System Leakage Test was performed prior to plant start-up from 1R20. All Class 1 bolted connections associated with insulated components were examined during 1R20. Also, Class 2 and 3 system functional and system inservice tests were performed in accordance with 40-month pressure testing requirements.
Deficiency Resolution The deficiencies associated with the 1R20 containment liner general visual examination were documented and resolved on Condition Reports 10-83594, 10-84446, 10-84569, 10-84570, and 10-84791. The conditions identified were surface related and did not constitute structural deficiencies. All but three of the forty deficiencies were repaired in 1 R20. The repair activities were limited to re-painting and one caulking repair. The three deficiencies deferred until the next outage were evaluated by the coating engineer and determined to have no impact on the integrity of the liner. The deficiencies that required paint removal prior to repair were examined by a qualified VT-3 examiner and UT examinations were performed on deficiencies where evidence of corrosion (rust) was present. The visual examination did not identify any evidence of liner plate degradation and the ultrasonic thickness measurements found the liner thickness greater than the nominal wall plate thickness in these areas.
NIS-2 Forms Included as Appendix II are the NIS-2 Forms associated with ASME XI repairs and replacements performed since the last 90-Day ISI Summary Report 6
APPENDIX I 1 R20 COMPLETED CODE EXAMS SummaryNo 033350 036750 040050 078650 084100 085450 089000 089100 089200 089300 094200 094300 095100 095200 095500 095600 096500 096600 097900 098000 109001 109002 109003 109004 109005 109006 109007 109008 109009 109010 109030 109035 109036 109039 109040 109041 Component ID CH-102 CH-103 CH-104 RC-055 RC-72-R-6 RC-056 RC-72-7-F-09 RC-72-7-E-01 RC-104-1-E-01 RC-104-1-F-01 RC-1 04-2-PSSP-1 22A RC-104-2-PSSP-122B RC-97-1-E-01 RC-97-1-F-01 RC-97-1-A-01 RC-97-SH-50 RC-98-1 -E-02 RC-98-1-F-01 RC-99-1 -E-03 RC-99-1-F-01 1NR-01 1N R-02 1NR-03 1NR-04 1NR-05 1NR-06 1NR-07 1NR-08 1NR-09 1NR-10 1 RN-020 1 RN-025 1 RN-026 1 RN-029 1RN-030 1 RN-031 Description RI-ISI SEGMENT RI-ISI SEGMENT RI-ISI SEGMENT RI-ISI SEGMENT SUPPORT RI-ISI SEGMENT BUTT WELD NOZZLE TO SAFE END NOZZLE TO SAFE END BUTT WELD SNUBBER SNUBBER NOZZLE TO SAFE END BUTT WELD WELDED ATTACHMENT SUPPORT SH-50 SUPPORT NOZZLE TO SAFE END BUTT WELD NOZZLE TO SAFE END BUTT WELD NON-RANDOM LINER 01 NON-RANDOM LINER 02 NON-RANDOM LINER 03 NON-RANDOM LINER 04 NON-RANDOM LINER 05 NON-RANDOM LINER 06 NON-RANDOM LINER 07 NON-RANDOM LINER 08 NON-RANDOM LINER 09 NON-RANDOM LINER 10 RANDOM LINER 20 RANDOM LINER 25 RANDOM LINER 26 RANDOM LINER 29 RANDOM LINER 30 RANDOM LINER 31 Class 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 MC MC MC MC MC MC MC MC MC MC MC MC MC MC MC MC Category R-A R-A R-A R-A F-A R-A R-A R-A R-A R-A F-A F-A R-A R-A B-K F-A R-A R-A R-A R-A IWE IWE IWE IWE IWE IWE IWE IWE IWE IWE IWE IWE IWE IWE IWE IWE Item R1.12 R1.12 R1.12 R1.12 F1.10R R1.12 R1.11 R1.11 R1.11 R1.11 F1.10N F1.10N R1.11 R1.11 B10.20 F1.10S R1.11 R1.11 R1.1I R1.11 E4.12 E4.12 E4.12 E4.12 E4.12 E4.12 E4.12 E4.12 E4.12 E4.12 E4.12 E4.12 E4.12 E4.12 E4.12 E4.12 Method VT-2 VT-2 VT-2 VT-2 VT-3 VT-2 UT UT UT UT VT-3 VT-3 UT UT PT VT-3 UT UT UT UT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT ISO 0246A-3 0247A-3 0248A-3 0348B-2 0348C-1 0348D-1 0348D-1 0348D-1 0350A-4 0350A-4 0350A-4 0350A-4 0350B-3 0350B-3 0350B-3 0350B-3 0350B-3 0350B-3 0350B-3 0350B-3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A Plate J5 Plate K8 Plate K11 Plate L4 Plate L5 Plate L7 Status B
B B
B c
B c
c c
c c
c c
c c
c c
c c
c c
c c
c c
c c
c c
c C
c c
c c
c Page Al-1
APPENDIX I 1R20 COMPLETED CODE EXAMS SummaryNo 109044 109046 109047 109049 109050 109051 109052 109057 109058 109060 109062 109063 109064 109065 109066 109067 109068 109069 109070 109072 109073 109074 109075 109077 109078 109079 109080 109081 109082 109083 109084 109085 130950 133050 135050 148000 Component ID 1 RN-034 1 RN-036 1 RN-037 1 RN-039 1 RN-040 1 RN-041 1 RN-042 1 RN-047 1 RN-048 1RN-050 1 RN-052 1 RN-053 1 RN-054 1 RN-055 1 RN-056 1 RN-057 1 RN-058 1 RN-059 1 RN-060 1 RN-062 1 RN-063 1 RN-064 1 RN-065 1 RN-067 1 RN-068 1 RN-069 1 RN-070 1 RN-071 1 RN-072 1 RN-073 1 RN-074 1 RN-075 RC-026 RC-027 RC-028 DLW-PRESS-2-F-38 Description RANDOM LINER 34 RANDOM LINER 36 RANDOM LINER 37 RANDOM LINER 39 RANDOM LINER 40 RANDOM LINER 41 RANDOM LINER 42 RANDOM LINER 47 RANDOM LINER 48 RANDOM LINER 50 RANDOM LINER 52 RANDOM LINER 53 RANDOM LINER 54 RANDOM LINER 55 RANDOM LINER 56 RANDOM LINER 57 RANDOM LINER 58 RANDOM LINER 59 RANDOM LINER 60 RANDOM LINER 62 RANDOM LINER 63 RANDOM LINER 64 RANDOM LINER 65 RANDOM LINER 67 RANDOM LINER 68 RANDOM LINER 69 RANDOM LINER 70 RANDOM LINER 71 RANDOM LINER 72 RANDOM LINER 73 RANDOM LINER 74 RANDOM LINER 75 RI-ISI SEGMENT RI-ISI SEGMENT RI-ISI SEGMENT BUTT WELD Class MC MC MC MC MC MC MC MC MC MC MC MC MC MC MC MC MC MC MC MC MC MC MC MC MC MC MC MC MC MC MC MC 1
1 1
1 Category Item IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 IWE E4.12 R-A R1.12 R-A R1.12 R-A R1.12 R-A R1.11 Method Iso Status UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT UTT VT-2 VT-2 VT-2 UT Plate N2 Plate N7 Plate N8 Plate 04 Plate 09 Plate 011 Plate 011 Plate Q8 Plate Q8 Plate Q11 Plate R5 Plate R5 Plate R7 Plate R8 Plate R9 Plate S3 Plate S7 Plate S8 Plate S9 Plate T7 Plate T10 Plate U2 Plate U5 Plate U11 Plate V2 Plate W1 Plate W4 Plate W5 Plate W6 Plate W9 Plate W11 Plate W12 0354A-1 03541B-1 0354C-1 0999D-2 Page AI-2
APPENDIX I 1R20 COMPLETED CODE EXAMS Summary-No 151050 169440 175240 180950 191500 192600 192700 192800 192900 193000 193100 193150 194900 195000 199800 207600 273600 317600 320250 324350 328550 329700 371400 391150 397750 397950 420150 420250 422650 422750 425050 425250 434750 436050 440050 443850 Component ID Description 1RV-BMI-PENE-OD RC-R-1-NUT-1 TO 19 RC-R-1-WASHER-1 TO 19 1RV-HEAD-OD RC-E-1A-C-1 RC-TK-1-RADIUS-1 RC-TK-1-RADIUS-2 RC-TK-1-RADIUS-3 RC-TK-1-RADIUS-4 RC-TK-1-RADIUS-5 RC-TK-1-RADIUS-6 RC-TK-1-HTR-SLEEVES RC-TK-1-SS-1 RC-TK-1-SS-2 RC-P-1B-B(S)-I TO 12 RC-P-1A-A-2 RH-1-3-F-05 1SI-22 SI-047B SI-045B SI-046B SI-73-7-HSS-418 WFPD-23-3-HSS-207 SI-056B SI-051A SI-051C CH-021C CH-021 B CH-020B CH-020C CH-019B CH-019C SI-061 B CH-121 CH-1 22 CH-123 RV LOWER HEAD BMI NOZZLES BOLTING BOLTING VESSEL HEAD OD SURFACE CIRCUMFERENTIAL WELD NOZZLE INSIDE RADIUS NOZZLE INSIDE RADIUS NOZZLE INSIDE RADIUS NOZZLE INSIDE RADIUS NOZZLE INSIDE RADIUS NOZZLE INSIDE RADIUS PZR HEATER SLEEVE SKIRT SUPPORT STRUCTURAL SUPPORT BOLTING WELDED SUPPORT BUTT WELD VALVE BODY RI-ISI SEGMENT RI-ISI SEGMENT RI-ISI SEGMENT SNUBBER SNUBBER RI-ISI SEGMENT RI-ISI SEGMENT RI-ISI SEGMENT RI-ISI SEGMENT RI-ISI SEGMENT RI-ISI SEGMENT RI-ISI SEGMENT RI-ISI SEGMENT RI-ISI SEGMENT RI-ISI SEGMENT RI-ISI SEGMENT RI-ISI SEGMENT RI-ISI SEGMENT Class 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 2
2 2
2 2
2 2
2 2
2 2
2 2
2 Categlory N-722 B-G-1 B-G-1 N-729 B-B B-D B-D B-D B-D B-D B-D WCAP F-A F-A B-G-2 B-K R-A B-M-2 R-A R-A R-A F-A F-A R-A R-A R-A R-A R-A R-A R-A R-A R-A R-A R-A R-A R-A Item B15.80 B6.10 B6.50 B4.30 B2.40 B3.120 B3.120 B3.120 B3.120 B3.120 B3.120 0G09140 F1.40E FI.40E B7.60 B10.30 R1.11 B12.50 R1.12 R1.12 R1.12 FI.10N F1.20N R1.12 R1.12 R1.12 R1.12 R1.12 R1.12 R1.12 R1.12 R1.12 R1.12 R1.12 R1.12 R1.12 Method UT VT-3 VT-3 VE UT UT UT UT UT UT VT-2 VT-2 VT-3 VT-3 VT-i PT UT VT-3 VT-2 VT-2 VT-2 VT-3 VT-3 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 ISO E-001 D-2 E-001L-1 E-001L-i E-001D-2 E-001 N-4 E-001P-3 E-001P-3 E-001 P-3 E-001 P-3 E-001 P-3 E-001P-3 E-001 P-3 E-001P-3 E-001 P-3 E-001R-1 E-001T-2 0074A-3 0223B-5 0375C-5 0375E-5 0375F-7 0375F-7 0062B-5 01 92A-6 01 92A-6 01 92A-6 0265A-7 0265A-7 0265A-7 0265A-7 0265A-7 0265A-7 0275A-3 0267A-5 0267A-5 0267A-5 Status B
c c
B c
c c
c c
c B
B c
c c
c L
c B
B B
c C
B B
B B
B B
B B
B B
B B
B Page AI-3
APPENDIX I 1R20 COMPLETED CODE EXAMS Summary No 470350 496950 509250 520950 593400 614800 658900 659100 681400 685350 707550 709250 711650 718350 789774 789775 789846 789847 853100 853200 865500 888300 888400 903250 903300 903997 908200 908250 908300 910550 910600 913850 913870 914850 916250 929500 Component ID CH-130 SI-062B CH-028 SI-058B SI-7-1-A-01 SI-2-6-S-03 SHP-56-3-HSS-202 SHP-56-3-HSS-203 SHP-58-5-S-48 SHP-31-1-F-13 RH-009 RH-004 RH-13-1-F-02 RH-14-7-SH-41 RS-7-2-L-285 RS-7-2-F-03 RS-8-2-L-271 RS-8-2-F-07 CC-527-PSSP-300A CC-527-PSSP-300B FC-5-RH-2 WR-53-3-A-01 TO 02 WR-53-A-92 QS-P2-K-L-53 QS-P2-K-S-OJ QS-4-10G-HSS-202 QS-3-13A-S-02 QS-3-13A-L-197 QS-3-13A-S-01 QS-P-2D-L-1 78 QS-P2-D-S-ON QS-9-1-F-01 CH-120 CH-051 CH-050A CH-095 Description RI-ISI SEGMENT RI-ISI SEGMENT RI-ISI SEGMENT RI-ISI SEGMENT WELDED ATTACHMENT SUPPORT VS-13 PIPE WELD SNUBBER SNUBBER PIPE WELD PIPE WELD RI-ISI SEGMENT RI-ISI SEGMENT PIPE WELD SUPPORT LONGITUDINAL WELD PIPE WELD LONGITUDINAL WELD PIPE WELD SNUBBER SNUBBER SUPPORT WELDED ATTACHMENT SUPPORT A-92 SUPPORT LONGITUDINAL WELD PIPE WELD SNUBBER PIPE WELD LONGITUDINAL WELD PIPE WELD LONGITUDINAL WELD PIPE WELD PIPE WELD RI-ISI SEGMENT RI-ISI SEGMENT RI-ISI SEGMENT RI-ISI SEGMENT Class 2
2 2
2 2
2 2
2 2
2 2
2 2
2 2
2 2
2 3
3 3
3 3
2 2
2 2
2 2
2 2
2 2
2 2
2 Category R-A R-A R-A R-A C-C R-A F-A F-A R-A R-A R-A R-A R-A F-A R-A R-A R-A R-A F-A F-A F-A D-A F-A R-A R-A F-A R-A R-A R-A R-A R-A R-A R-A R-A R-A R-A Item R1.12 R1.12 R1.12 R1.12 C3.20 R1.11 F1.20N F1.20N R1.11 R1.11 R1.12 R1.12 R1.11 F1.20S R1.11 R1.11 R1.11 R1.11 F1.30N F1.30N FI.30H D1.20 F1.30A R1.11 R1.11 F1.20N R1.11 R1.11 R1.11 R1.11 R1.11 R1.11" R1.12 R1.12 R1.12 R1.12 Method VT-2 VT-2 VT-2 VT-2 PT UT VT-3 VT-3 UT UT VT-2 VT-2 UT VT-3 UT UT UT UT VT-3 VT-3 VT-3 VT-r VT-3 UT UT VT-3 UT UT UT UT UT UT VT-2 VT-2 VT-2 VT-2 Iso 0268A-5 0272A-5 0273A-3 0273B-7 0083A-3 0083C-6 0001A-1 0001A-1 0002C-1 0082A-1 0075A-5 0075A-5 0075B-3 0207A-3 0084A-3 0084A-3 0084A-3 0084A-3 0285A-3 0285A-3 0071A-1 0224A-2 0224A-2 0111A-9 0111A-9 0111A-9 0113A-10 0113A-10 0113A-10 0113B-3 0113B-3 0111C-3 0170B-3 1254A-4 1254A-4 1518A-1 Status B
B B
B c
c c
c c
c B
B B
c c
L c
L c
c c
c c
c c
c L
c L
c c
L B
B B
B Page AI-4
APPENDIX I 1R20 COMPLETED CODE EXAMS SummaryNo Component ID Description 929600 929700 930000 930015 930100 CH-096 CH-097 1CNMT-LINER 1CNMT-LINER-AREA-R 1CNMT-MOISTBARR RI-ISI SEGMENT RI-ISI SEGMENT CONTAINMENT LINER 1R19 LINER REPLACEMENT MOISTURE BARRIER Class Category Item 2
R-A R1.12 2
R-A R1.12 MC E-A E1.11 MC E-A E1.11 MC E-A E1.30 Method Iso Status VT-2 VT-2 GV UTT GV 1538A-1 151 OA-1 N/A N/A N/A B
B B
C B
Page AI-5
APPENDIX II REPAIR / REPLACEMENT ABSTRACT AND NIS-2 FORMS 7
FORM NO.
1850 2063 2091 2092 3009 3129 3149 3164 3210 3211 3212 3213 3216 3236 3239 3248 3252 3254 3256 3257 3273 3275 3286 3291 3293 3294 3295 3296 3297 3303 3304 3305 3306 3309 3312 ASSET NUMBER REJ-1 RW-24A 1RW-57 1CCR-5 1CCR-6 1 RW-59 1SI-24 1RH-P-1B RV-1RC-551A 1MS-18 REJ-1 RW-4A1 1RS-E-1A 1 RS-E-1C 1VS-E-4B 1 RW-106 NRV-1MS-101B 1 DLO-28 1 RW-32 1 RW-30 1EE-EG-1-ENGINE 1 EE-EG-2-ENGINE WR-610 1 CH-84 WR-560 WR-5 1 RH-E-1A 1 RH-200 MOV-1RW-103B 1 FW-627 1SI-22 RV-1CH-203 RV-1 RH-721 RV-1 CH-382B RC-HC-1 OC 1QS-4 RV-1 QS-1 00B NIS-2 ABSTRACT ORDER NO.
200135466 200233562 200267243 200274642 200250894 200298746 200209848 200372718 200383397 200339325 200375743 200375745 200323026 200375747 200308441 200387923 200383348 200383347 200373908 200373909 200402653 200412068 200415220 200425159 200429434 200432353 200368067 200432665 200432381 200410051 200296268 200369665 200371901 200432540 200372724 COMMENTS Installed Installed Installed Installed Corrected Installed Installed Installed Installed Installed Corrected Corrected Installed Installed Installed Installed Installed Installed Corrected Corrected Installed Corrected Corrected Corrected Corrected Corrected Corrected Installed Installed Installed Installed Corrected Installed Installed Corrected Page 1 of 1
FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 1850 RTL #A4.414A
- 1. Owner F.E.N.O.C Date 12/01/2010 (NAME) 76 South Main Street-Akron, OH 44308 Sheet 1
of 1
(ADDRESS)
Unit No.
1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shippinqport, PA 15077 WO# 200135466 (ADDRESS)
Repair/Replacement Organization P.O. No., Job No., etc.
- 3. Work Performed By BVPS - Construction Type Code Symbol Stamp N/A (NAME)
Shippinqport, PA 15077 Authorization No.
N/A (ADDRESS)
Expiration Date N/A
- 4. Identification of System River Water (Q3)
- 5. (a) Applicable Construction Code ANSI B31.1 1967 Edition, S'71 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c)
Applicable Section XI Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Expansion Garlock 04-3532 N/A REJ-1RW-1994 Removed No Joint 24A Expansion Garlock 06-0089 N/A REJ-1RW-2006 Installed No Joint 24A Stud Nova Machine N/A N/A HT# P918 2005 Installed No
- 7. Description of Work Replacement of REJ and Flange Studs with like kind
- 8. Tests Conducted:
Hydrostatic* n]
Pneumatic* []
Nominal Operating Pressure 0 Exempt E]
Other LI Pressure psi Test Temp.
°_F
- Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl NOP-CC-5703-02 Rev. 00 Report Number 1850 RTL #A4.414A
- 9. Remarks Previous NIS-2 Data Report # 631. Expansion Joint PO# 45177541 and Stud PO# 47082958 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed J. Sciulli Nuclear Specialist Date December 1, 20 10 Owner or Owr r's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period
-,/-- /
p to
//-
y -/0
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
___Commissions LJ2 2-,-
,T qJz-d
,'A,3 ý Inspect Signature National Board, State, Province, and Endorsements Date
/,L - 3
,20
'/0 Page 2 of 2
FORM 1/2-ADM-080IF02 REV 3 RTL # A4.414-A Form No.
2063 FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner F.E.N.O.C (NAME) 76 South Main Street -Akron.
OH 44308 Date Sheet April 12, 2010 1
of 2
(ADDRESS)
- 2. Plant Beaver Valley Power Station (BVPS)
Unit No.
1 (NAME)
Shippingport, PA 15077 (ADDRESS)
- 3. Work Performed By BVPS Maintenance (NAME)
Shiooinaoort. PA 15077 Work Order #200233562 Repair/Replacement Organization P.O. No., Job No., etc.
Type Code Symbol Stamp Authorization No.
Expiration Date N/A N/A (ADDRESS) 11
- 4. Identification of System River Water (Q3)
- 5. (a) Applicable Construction Code Section II1 1974 Edition, S'74 Addenda, N/A Code Case (b)
Applicable Edition of Section X1 Utilized for Repair/Replacement Activity 2001 E-2003A (c)
Applicable Section XI Code Case(s): N/A
- 6. Identification of Components Corrected, ASME
- Removed, Code Name of Name of Manufacturer National Board Other Year 0r Stamped Component Manufacturer Serial No.
No.
Identification Built tnstalled (Yes or No)
Check Valve C & S Valve 92-2019-059-012 N/A IRW-57 1992 Removed No Check Valve Crane Nuclear D8081 N/A 1RW-57 2008 Installed Yes
- 7. Description of Work Replaced valve, studs/nuts.
- 8. Tests Conducted:
Hydrostatic* El Pneumatic* []
Nominal Operating Pressure E Exempt LI Other LI Pressure psi Test Temp.
OF
- Record test pressure and temperature
FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)
- 9. Remarks Code Data Report attached. Previous NIS-2 Data Report Nos: 1550, 1458, and 508.
Applicable Manufacturer's Data Reports to be attached An ASME Section 1II. Class 3. 1974E-S'74A valve was installed into an ANSI B31.1 svstem.
Reolacement 1-1/8" Studs: PO 45243289 / Ht. #OZ84. PO 45189502 / Ht. #191C. PO 7123870 /
Ht. #J218: Nuts: PO 47176549 / Ht. #Z149.
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed Thomas Whit Staff Specialist Date April 23
,20 10 CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period 3 -,. / - 0 9 to
.7/-
2 0 -(/0
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
nsSiaueNtodtePricadnosmnCommissions Nl-Inspe ýus Signature National Board, State, Province, and Endorsements Date a 20 /0
FORM NPV-1 CERTIFICATE HOLDERS' DATA REPORT FOR NUCLEAR PUMPS OR VALVES*
As Required by the Provisions of the ASME Code,Section III, Division 1 Pg. 1 of 2
- 1.
Manufactured and cerlified by CRANE Nuclear, Inc., 860 Remington Boulevard, Bolingbrook, IL 60440 (name and address of N Certificate H1ider)
- 2.
Manufactured for First Energy, PO Box 4, Shippingport, PA 15077 (name and address of purchaser)
- 3.
Location of installation Beaver Valley Nuclear Power Plant. Route 168. Shippingport, PA 15077 (name and address)
- 4. Model No., Series No., or Type D000-M1291-00 Drawing -
CB02778 Rev.
C CRN NIA
- 5.
ASME Code,Section III. Division 1:
1974 Summer 1974 3
N/A (edit(on) addenda date)
(class)
(Code Case no.)
- 6.
Pump or valve Duo-Check Nominal inlet size 20" Outlet size 20"
- 7.
Material:
(a) valve Body SA351 CF3M Bonnet N/A Disk SA3S1 CF3M Bolting MIA (b) pump Casting Cover Bolting
"(a)
(b)
(c)
(d)
(e)
Cert.
Nat'l Body/Casing Bonnet/Cover Disk Holder's Board Serial Serial Serial Serial No.
No.
No.
No.
No.
D8081 N/A D8082 NfA D8083 D8084 Supplemental information in the form of lists, sketches, or dravvngs may be used provided (1) size is 8 'Ax 11, (2) Information In Items 1 through 4 on this Data Report is included on each sheet. (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
FORM NPV-1 (Back) -- Pg. 2 of 2 Certificate Holder's Serial No.
08081 8
Design conditions N/A (pressure N/A or valve pressure class 150 (1)
(temperature)
- 9.
. Cold working pressure 275
- 10.
Hydrostatic test 425 Disk differential test pressure 305
- 11.
Remarks:
S/O No. 33494-01. PO No. 45272566, Item No. 00001 Pin Retainer material SA 479 GR 3M6, HL# AUH CERTIFICATION OF DESIGN Design Specifications certified by W.J. Parker PE. State PA Reg. no.
29003-E Design Report certified by N/A PRE. State N/A Reg. no.
N/A CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this pump or valve conforms to the rules for construction of the ASME Code,Section III, Division 1.
N Certificate of Authorization No.
N-2899 Expires September 24, 2011 Date 12/30/08 Name CRANE Nuclear, Inc.
- Signed, (atorized representative)
JonESiro~'atka (N Certifcale Haider)
CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by HSBCT of Hartford, CT have inspected the pump, or valve. described in this Data Report on 12/30/08 and state that to the best of my knowledge and belief, the Certificate Holder has constructed this pump, or valve, in accordance with the ASME Code,Section III, Division 1.
By signing this certificate, neither the inspector nor his employer makes any warranty, eKpressed or implied, concerning the component described in this Data Report. Furthermore. neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or loss of any kind arising from or connected with this inspection.
Date 12/30/08 Signed Commissions Robert Rainey IL 932 (Nail. *d. Oind. endorsements) and state or prov. and no.)
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl 3-02 Rev. 00 Report Number 2091 NOP-CC-5703
- 1. Owner F. E. N.O.C I Date 10/23/10 (NAME) 76 South Main Street - Akron, OH 44308 (ADDRESS)
Sheet 1
of Unit No.
1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shipoinaoort, PA 15077 Work Order #2.-.,/7 (ADDRESS)
- 3. Work Performed By FENOC Maintenance (NAME)
ShiDDinaDort. PA 15077 Repair/Replacement Organization P.O. No., Job No., etc.
Type Code Symbol Stamp N/A (ADDRESS)
Authorization No.
Expiration Date N/A N/A
- 4. Identification of System Component Coolinq (Q3)
- 5. (a) Applicable Construction Code ANSI B31.1 19 73Edition, S'73 AddendaCode Case -
(b)
Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c)
Applicable Section Xl Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Check Valve Mission Drilling N/A 1CCR-5 1976 Removed No Check Valve Mission Drilling 34709 N/A 1CCR-5 1976 Installed No
- 7. Description of Work Replaced valve with spare.
- 8. Tests Conducted.
Hydoeatttic* ]
Pneumatic* [L Nominal Operating Pressure M Exempt [1 Other []
Pressure psi Test Temp. ---
-F tRecord est pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl NOP-CC-5703-02 Rev. 00 Report Number 2091
- 9. Remarks No Code Data Report available.
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization
- o.
N/A Expiration Date N/A Signed T. White
(
Staff Specialist Date October 24, 2010 Owner or Ow er's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period d_ / - 0 ?
to
/ tJ - L-, -( 0
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
/-
Commissions -Z--,
J,
-2 F y Inspec Signature National Board, State, Province, and Endorsements Date
/O
, 20 / 0 Page-.2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 2092
- 1. Owner F.E.N.O.C Date 10/23/10 (NAME) 76 South Main Street -Akron, OH 44308 Sheet I
of I
(ADDRESS)
Unit No.
1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shippinqport, PA 15077 Work Order #200274642 (ADDRESS)
Repair/Replacement Organization P.O. No., Job No., etc.
- 3. Work Performed By FENOC Maintenance Type Code Symbol Stamp N/A (NAME)
Shippingport, PA 15077 Authorization No.
N/A (ADDRESS)
Expiration Date N/A
- 4. Identification of System Component Coolinq (Q3)
- 5. (a) Applicable Construction Code ANSI B31.1 19 73Edition, S'73 AddendaCode Case -
(b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section X1 Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Check Valve Mission Drilling 34709 N/A 1CCR-6 1976 Removed No Check Valve Crane Nuclear D9028 N/A 1CCR-6 2010 Installed No
- 7. Description of Work Replaced valve with spare.
- 8. Tests Conducted:
Hydrostatic* LI Pneumatic* E]
Nominal Operating Pressure 0 Exempt [l Other l]
Pressure psi Test Temp. ---
_oF
- Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 2092
- 9. Remarks No Code Data Report available.
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed T. White 4
6Z Staff Specialist Date October 23, 20 10 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania -_and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period J--- )-. / - 0?
to
/ 0 -,A 6 -/0, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with therequirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
s Commissions --
-~~(
Inspector ignature National Board, State, Province, and Endorsements Date
-__21 G 20
/ )
Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3009 RTL #A4.414A
- 1. Owner F.E.NO.C Date November 12, 2010 (NAME) 76 South Main Street -Akron, OH 44308 Sheet 1
of 2
(ADDRESS)
Unit No.
1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shippinqport, PA 15077 Work Order #200250894 (ADDRESS)
Repair/Replacement Organization P.O. No., Job No., etc.
- 3. Work Performed By BVPS Valve Team Type Code Symbol Stamp N/A (NAME)
Shippincqport, PA 15077 Authorization No.
N/A (ADDRESS)
Expiration Date N/A
- 4. Identification of System River Water (Q3)
- 5. (a) Applicable Construction Code Section III 19 74 Edition, S'74 Addenda, -- Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c)
Applicable Section XI Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Check Valve Crane Nuclear D0479 N/A 1 RW-59 2002 Corrected Yes
- 7. Description of Work Replaced valve flange studs/nuts.
- 8. Tests Conducted:
Hydrostatic* EL Pneumatic* LI Nominal Operating Pressure LI Exempt [
Other L]
Pressure psi Test Temp.
oF Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl NOP-CC-5703-02 Rev. 00 Report Number 3009 RTL #A4.414A
- 9. Remarks Code Data Report attached. Previous NIS-2 Data Report No. 1562. Replaced 1-1/8" Studs:
Applicable Manufacturer's Data Reports to be attached PO 45305063 / Ht. # 3B26, PO 47217400 / Ht. # 2K15: Nuts: PO 45339118 / Ht. #4H71 ASME Section III valve installed into an ANSI B31.1 system.
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.
Type CodeSymbol Stamp N/A Certificate of Authorization No.
N/A Sinned T White Expiration Date N/A Staff Specialist Date December 1, 20 10 v-.2*....
Owner or Obwner'sDesnee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period d-I-
/ - 0 7 to
/( - L/-/
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions J4 ý/ y,'z-_ e
,/f d
InspectoýKSignature Date
/4
-/
National Board, State, Province, and Endorsements
,20 16 Page 2 of 2
FORM NPV-1 CERTIFICATE HOLDERS' DATA REPORT FOR NUCLEAR PUMPS OR VALVES*
As Required by the Provisions of the ASME Code, Section I11, Division I Pg. 1 of 2
- 1.
Manufactured and certified by CRANE Nuclear, Inc., 860 Remington Boulevard, Bolingbrook, IL 60440 (name and address of NPT Certificate Holder)
- 2.
Manufactured for First Energy Corporation, PO Box 345 Shippingport, PA 15077 (name and address of purch'aser)
- 3.
Location of installation Beaver Valley Nuclear Plant. Route 168. On-Site Storeroom, Shippingport, PA 15077 (name and address)
- 4.
Model No., Series No., or Type D00-M1291-00 Drawing CB02778 Rev.
C CRN N/A
- 5.
ASME Code, Section Ill, Division 1:
1974 Summer 1974 3
(edition)
(addenda date)
(class)
. N/A (Code Case no.)
20 (in.)
- 6.
Pump or valve Duo-Chek Valve Nominal inlet size 20 (in.)
Outlet size
- 7.
Material:
(a) valve Body (b) pump Casting (a)
Cert.
Holder's Serial No.
SA351 CF3M (b)
Nat'l Board No.
Bonnet N/A Cover (c)
Body/Casing Serial No.
Disk SA351 CF3M Bolting (d)
Bonnet/Cover Serial No.
Bolting SA479 TP 316A (e)
Disk Serial No.
00479 N/A D0480 N/A 00481 & D0482
. Supplemental information in the form of lists, sketches, or drawings may be used provided (1) size is 8 '% x 11, (2) information in items 1 through 4 on this Data Report is included on each sheet. (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
This form (E00037) may be obtained from the Order Dept. ASME, 22 Law Drive, Box 2300, Fairfield, NJ 07007-2300.
FORM NPV-1 (Back) --- Pg. 2 of 2 Certificate Holder's Serial No.
D0479 8
Design conditions (pressure psi (temperature)
°F or valve pressure class ANSI 150 (1)
- 9.
Cold working pressure 275 psi at 100°F
- 10.
Hydrostatic test 425 psi.
Disk differential test pressure 305 psi
- 11.
Remarks:
PO No. 7073812, Rev.
Mark No.:
Valve ID: VC1015-C-3 0, Item No. 1 SO No. 13665-01 CERTIFICATION OF DESIGN Design Specifications certified by Walter Joseph Parker, Jr.
P.E. State
" PA Reg. no.
29003-E Design Report certified by N/A P.E. State N/A Reg. no.'
N/A CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this pump or valve conforms to the rules for construction of the ASME Code,Section III, Division 1.
N Certificate of Authorization No.
N-2899 Expires September 24, 2002 Signed
. _/Zzý Date
_02/22/02 Name CRANE Nuclear, Inc.
(N Certificate Holder)
Je"thorioe A.
rwse*eie PE)
Jerome A. Kurowski, P.E.
CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel lnspectors and the State or Province of Illinois and employed by Factory Mutual Insurance Company of Johnston, RI have inspected the pump, or valve, described in this Data Report on 02/22/02 and state that to the best of my knowledge and belief, the Certificate Holder has constructed this pump, or valve, in accordance with the ASME Code,Section III, Division 1.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the component described in this Data Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or loss of any kind arising from or connected with this inspection.
Date 02/22/02 Signed Commissions IAoized -Nuclear Inspector)I Jaomes Bush IL 1077 (Na'l. Bd. (incl. endorsements) and state or pro'. and no.)
(1) For manually operated valves only.
FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3129 RTL #A4.414A
- 1. Owner F.E.N.O.C Date October 31, 2010 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1
of 1
(ADDRESS)
Unit No.
1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shippinqport, PA 15077 Work Order #200298746 (ADDRESS)
Repair/Replacement Organization P.O. No., Job No., etc.
- 3. Work Performed By BVPS Maintenance Type Code Symbol Stamp N/A (NAME)
Shippinqport, PA 15077 Authorization No.
N/A (ADDRESS)
Expiration Date N/A
- 4. Identification of System Safety Injection (Q1)
- 5. (a) Applicable Construction Code ANSI B16.5 19 68 Edition, ___ Addenda, ----Code Case (b) Applicable Edition of Section Xi Utilized for Repair/Replacement Activity 2001 E-2003A (c)
Applicable Section Xl Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Check Valve Velan N/A N/A 1SI-24 1976 Corrected No Disc Velan N6948 N/A Ht. #2AXP 2002 Installed No
- 7. Description of Work Replaced valve disc.
- 8. Tests Conducted:
Hydrostatic* LI Pneumatic* LI Nominal Operating Pressure [l Exempt M Other L]
Pressure psi Test Temp.
oF
- Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3129 RTL #A4.414A
- 9. Remarks No Code Data Reports available.
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed T. White Staff Specialist Date November 12, 20 10 Owner or Owhor's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period d-o2-
/- 0 q9 to
// -
//0
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
1b-1~
J.,ýJ Commissions J
VFf-J-rYt Af'cZ3JY Inspector's, nature National Board, State, Province, and Endorsements Date
//.-#
. 20 /0 I
Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3149 RITL #A4.414A
- 1. Owner F.E.N.O.C Date 12/02/2010 (NAME) 76 South Main Street-Akron, OH 44308 (ADDRESS)
Beaver Valley Power Station (BVPS)
Sheet 1
of Unit No.
1
- 2. Plant (NAME)
Shippinqport, PA 15077 (ADDRESS)
- 3. Work Performed By BVPS - Maintenance (NAME)
Shiorinaoort. PA 15077 WO# 200209848 Repair/Replacement Organization P.O. No., Job No., etc.
Type Code Symbol Stamp N/A Authorization No.
N/A 4.
5.
6.
(ADDRESS)
Expiration Date N/A Identification of System Residual Heat Removal (Q2)
(a) Applicable Construction Code ASME Section III 1968 Edition, S'72 Addenda, N/A Code Case (b)
Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section XI Code Case(s): N/A Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Seal Flowserve N/A N/A HT# 248991 2010 Installed No Stud Nova Machine N/A N/A HT# 268F 2006 Installed No Pump Ingersoll-Rand 1170-21 N/A 1RH-P-1B 1976 Corrected No
- 7. Description of Work Replace mechanical seal
- 8. Tests Conducted:
Hydrostatic* E]
Pneumatic* LI Nominal Operating Pressure 0 Exempt L]
Other LI Pressure psi Test Temp.
°F
- Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3149 RTL #A4.414A
- 9. Remarks Previous NIS-2 1530. Seal PO# 4532439 HT# 248991 and Stud Po# 45211480 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section X1.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed J. Sciulli Nuclear Specialist Date December 1, 20 10 Owner orOwntr's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period 5& ?
to
// -
0, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section X1.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
_J Commissions,)
9
,*,/A 4 d,-? FCe-Inspector'oignature National Board, State, Province, and Endorsements Date 20 /0 Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3164 RTL #A4.414A
- 1. Owner F.E.N.O.C Date October 27, 2010 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1
of 5
(ADDRESS)
Unit No.
1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shippinqport, PA 15077 Work Order #200372718 (ADDRESS)
Repair/Replacement Organization P.O. No., Job No., etc.
- 3. Work Performed By BVPS Construction Services Type Code Symbol Stamp N/A (NAME)
Shippinqport, PA 15077 Authorization No.
N/A (ADDRESS)
Expiration Date N/A
- 4. Identification of System Reactor Coolant (Class A)
- 5. (a) Applicable Construction Code Section I11 1968 Edition, S'68 Addenda, -
Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section XI Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Relief Valve Target Rock 1
N/A RV-1RC-551A 2005 Corrected Yes Pilot Valve Target Rock 2
N/A N/A 2005 Removed Yes Pilot Valve Target Rock 1
N/A N/A 2005 Installed Yes
- 7. Description of Work Replaced pilot valve and inlet studs.
- 8. Tests Conducted:
Hydrostatic* E]
Pneumatic* Li Nominal Operating Pressure [
Exempt L]
Other FD Pressure psi Test Temp.
°_F
- Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3164 RTL #A4.414A
- 9. Remarks Code Data Reports attached. Pilot Valve (S/N 2) was replaced by Target Rock under Purchase Order Applicable Manufacturers Data Reports to be attached 55109371/4. Pilot valve (S/N 1) from Relief Valve S/N 3 was removed and installed into Relief Valve S/N 6 previously by Target Rock. Pilot valve (S/N 1) was then removed from Relief Valve S/N 6 and installed into Relief Valve S/N 1 Code Data Report from Relief Valve S/N 3 showing pilot valve S/N 1 attached. Replacement 1-3/8" Studs: PO 45297678 I Ht. #2U86.
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed T. White Staff Specialist Date December 03 20 10 Owner or dWnEdres Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period
---,-. / - 0 7 to K/
0-(
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions 2 7)-
- K_6
/.<*-*
3 "L/
Inspector's Snature National Board, State, Province, and Endorsements Date
_,20 Page 2 of 2
FORM NV-1 CERTIFICATE HOLDERS' DATA REPORT FOR PRESSURE OR VACUUM RELIEF VALVES*
As Required by the Provisions of the ASME Code,Section III, Division 1 Pg. 1 of 3
- 1. Manufactured and certified by Target Rock; 1966E Broadhollow Rd.: E. Farmingdale, NY 11735 (name and address of NV Certificate Holder)
- 2. Manufactured for First Eneryv; Route 168; Shipping portPA (name and address of Purchaser)
- 3.
Location of installation Beaver Valley Power Station: Route 168: Shirjpinclport, PA (name and address)
- 4. Valve 0569C-001-1 Orifice size 2.443 Nom. Inlet size 6
(Model no., series no.)
(in.)
(in.)
Outlet size 6
(in.)
- 5.
ASME Code,Section III, Division 1:
1968 (edition)
Summer 1968 (addenda date)
A None (class)
(Code Case no.)
- 6. Type Pilot Operated 2485 120 650°F 3325 at 100°F max.
(spring, pilot or power operated) (set pressure, psig) (blowdown, psi)
(rated temp)
(hydro test,psig,inlet)
- 7.
Identification 1
(Cert. Holder's serial no.)
- 8.
Control ring settings _
N/A 0569C-001 Rev. B N/A 2005 (CRN)
(drawing no.)
(Natrl. Bd. no.)
(year built)
N/A
- 9.
Pressure retaining items:
Serial No. Or Identification Mat'l. Spec.
Including Type or Grade Tensile Strength Body Bonnet or Yoke Support Rods Nozzle Disk Spring Washers Adjusting Screws Spindle Spring Bolting Other Items 1
SA351 CF8M 75 ksi 8
SA105 70 ksi 3SA 564 630 140 ksi See page 2 of 3 See page 2 of 3
- 10. Relieving capacity 345,000 lbs/hr overpressure as certified by the National Board (69C) 10/07/2005 (date)
- 11. Remarks:
CERTIFICATION OF DESIGN Design Specification certified by F.W. Gardner P.E. State PA Reg. No. 036614-E Design Report certified by Not applicable P.E. State N/A Reg. No.
N/A CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this pump or valve conforms to the rules for construction of the ASME Code,Section III, Division 1.
N Certificate of Authorization No.
Date Name N-1 949 Taraet Rock Expires 12/12/2007 Signed R. E. Glazier,- A Manager (authorized representative)
(Certificate Holder)
- Supplemental information in form of lists, sketches, or drawings may be used provided (1) size is 812 x 11, (2) information in items 1 through 4 on this Data Report is included on each sheet, (3) each sheet is numbered and the number of sheets is recorded at the top of this form (12/88) This form (E00037) may be obtained from the Order Dept., ASME, 22 Law Drive, Box 2300, Fairfield, NJ 07007-2300 REPRING 6/93
FORM NV-I (Pg. 2 of 3 )
Certificate Holder's Serial No. 0569C-001-1: s/n 1 Taroet Rock: 1966E Broadhollow Rd.: E. Farminadale. NY 11735
- 1. Manufactured and ce
- 2.
Manufactured for rtified by (name and address of NV Certificate Holder)
First Enerv: Route 168; Shippingport, PA (name and address of Purchaser)
- 3.
Location of installation Beaver Valley Power Station; Rout 168; Shippinqport, PA (name and address)
- 4.
Valve 0569C-001-1 Orifice size 2.443 Nom. Inlet size 6
Outlet size 6
(Model no., series no.)
(in.)
(in.)
(in.)
Serial No.
Material Spec.
Tensile Pressure Retaining Item or Including Type Strength Identification or Grade Main Seat 200323-1 25 SA479 304L 70 ksi Pilot Body 303839-2 2
SA479 304 75 ksi Bonnet Cap 200324-1 8
SAl 05 70 ksi End Uap 3U363t-1 b
A4/Y7K 1b
/b ksi Hex Nut 100-0076 n/a SA194 2H n/a Hex Bult 100501-1 n/a SA193 B7 125 ksi Stud 206189-2 n/a SA1 93 B7 125 ksi Stud 206189-1 n/a SA1 93 B7 125 ksi Stud 100482-2 n/a SA193 B7 125 ksi Stud 100482-1 n/a SA193 B7 125 ksi
FORM NV-I (Pg. 3 of3 )
Certificate Holder's Serial No. 0569C-001-1
--/d /
Taroet Rock: 1966E Broadhollow Rd.: E. Farminadale. NY 11735
- 1. Manufactured and certified by
- 2.
Manufactured for First Ene (name and address of NV Certificate Holder)
-rav: Route 168: Shippinqport, Pa (name and address of Purchaser)
- 3.
Location of installation Beaver Valley Power Station; Route 168; Shippincqport, PA (name and address)
- 4.
Valve 0569C-001-1 Orifice size 2.443 Nom. [nlet size 6
Outlet size 6
(Model no., series no.)
(in.)
(in.)
(in.)
CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Province of New York and employed by OneBeacon America Insurance Company of Boston, MA have inspected the pump, or valve, described in this Data Report on
/2/&/,,*o-5", and state that to the best of my knowledge and belief, the Certificate Holder has constructed this purfip, or valve, in accordance with the ASME Code,Section III, Division 1.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the component described in this Data Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connectpd with this inspectio Date///O* Signed mi.,<,-,
Authorized Insp r)
(Nat'l. Bd.(incl. endorsements) and state or prov. and no.)
FORM NV-1 CERTIFICATE HOLDERS' DATA REPORT FOR PRESSURE OR VACUUM RELIEF VALVES*
As Required by the Provisions of the ASME Code, Section Ii1, Division 1 Pg. 1 of 3
- 1. Manufactured and certified by Target Rock; 1966E Broadhollow Rd.; E. Farmingdale, NY 11735 (name and address of NV Certificate Holder)
- 2.
Manufactured for First Energy; Route 168, Shippingport,PA (name and address of Purchaser)
- 3.
Location of installation Beaver Valley Power Station: Route 168; Shippingport, PA First Enerqy; Route 168; Shippinqport, PA (name and address of Purchaser)
(name 'and address)
- 4.
Valve 0569C-001-1 Orifice size 2.443 Nom. Inlet size 6
Outlet size 6
(Model no., series no.)
(in.)
(in.)
(in.)
- 5.
ASME Code,Section III, Division 1:
1968 (edition)
Summer 1968 (addenda date)
A None (class)
(Code Case no.)
- 6.
Type Pilot Operated 2485 120 650°F 3325 at 100°F max.
(spring, pilot or power operated) (set pressure, psig) (blowdown, psi)
(rated temp)
(hydro test,psig,inlet)
- 7.
Identification 3
N/A 0569C-001 Rev. B N/A 2005 (Cert. Holder's serial no.)
(CRN)
(drawing no.)
(Natl'l. Bd. no.)
(year built)
- 8.
Control ring settings N/A
- 9.
Pressure retaining items:
Serial No. Or Identification Mat'l. Spec.
Including Type or Grade Tensile Strength Body Bonnet or Yoke Support Rods Nozzle Disk Spring Washers Adjusting Screws Spindle Spring Bolting Other Items 3
SA351 CF8M 75 ksi 9
SA1 05 70 ksi 2
SA 564 630 140 ksi See page 2 of 3 See page 2 of 3
- 10. Relieving capacity 345,000 Ibs/hr overpressure as certified by the National Board (69C) 10/07/2005 (date)
- 11. Remarks:
CERTIFICATION OF DESIGN Design Specification certified by F.W. Gardner P.E. State PA Reg. No. 036614-E Design Report certified by Not applicable P.E. State N/A Reg. No.
N/A CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this pump or valve conforms to the rules for construction of the ASME Code,Section III, Division 1.
N Certificate of Authorization No.
M-1949 Date /I-/0Z-0.*'"
Name Target Rock (Certificate Holder)
Expires 12/12/2007 Signed-:--- ýý R. E. Glazier,QA Manager (authorized representative)
' Supplemental intormation in form ot lists, sketches, or drawings may be used provided (1) size is 81/2 x 11, (2) information in items 1 through 4 on this Data Report is included on each sheet, (3) each sheet is numbered and the number of sheets is recorded at the top of this form (12/88) This form (E00037) may be obtained from the Order Dept., ASMIE, 22 Law Drive, Box 2300, Fairfield, NJ 07007-2300 REPRINT 6/93
FORM NV-1 (Pg.2of3 )
Certificate Holder's Serial No. 0569C-001-1 s/n 3
- 1. Manufactured and certified by Target Rock; 1966E Broadhollow Rd.: E. Farmingdale, NY 11735 (name and address of NV Certificate Holder)
- 2.
Manufactured for First Energy; Route 168: Shippingport, PA (name and address of Purchaser)
- 3.
Location of installation Beaver Valley Power Station; Rout 168: Shippinqport, PA (name and address)
- 4.
Valve 0569C-001-1 (Model no., series no.)
Orifice size 2.443 Nom. Inlet size 6
(in.)
(in.)
Outlet size 6
(in.)
Serial No.
Material Spec.
Tensile Pressure Retaining Item or Including Type Strength Identification or Grade Main Seat 200323-1 34 SA479 304L 70 ksi Pilot Body 303839-2 1
SA479 304 75 ksi Bonnet Cap 200324-1 9
SA105 70 ksi noU L;ap 4
,..A4/1ib
/b Ksi Hex Nut 100-0076 n/a SA1 94 2H n/a Hex Bult 100501-1 n/a SA1 93 B7 125 ksi Stud 206189-2 n/a SA193 B7 125 ksi Stud 206189-1 n/a SA193 B7 125 ksi Stud 100482-2 n/a SA1 93 B7 125 ksi Stud 100482-1 n/a SA193 B7 125 ksi
FORM NV-1 (Pg.3of3 )
Certificate Holder's Serial No. 0569C-001-1 s/n 3
- 1. Manufactured and certified by Target Rock; 1966E Broadhollow Rd.; E. Farmingdale, NY 11735 (name and address of NV Certificate Holder)
- 2.
Manufactured for First Energy; Route 168: Shippingport, Pa (name and address of Purchaser)
- 3.
Location of installation Beaver Valley Power Station; Route 168; Shippinqport, PA (name and address)
- 4.
Valve 0569C-001-1 (Model no., series no.)
Orifice size 2.443 Nom. Inlet size 6
(in.)
(in.)
Outlet size 6
(in.)
CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Province of New York and employed by OneBeacon America Insurance Company of Boston, MA have inspected the pump, or valve, described in this Data Report on la - 2o-,?o.5-, and state that to the best of my knowledge and belief, the Certificate Holder has constructed this pump, or valve, in accordance with the ASME Code,Section III, Division 1.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the component described in this Data Report. Furthermore, neither the inspector nor his employer shall be liable in any manner fo ny personal injury or property damage or a loss of any kind arising from or connected with this inspectio.
Dat'/
Signe ommissions
,Y.
- /
(Authorized Ins or)
(Nat'l. Bd.(incl. endorsements) and state or prov. and no.)
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl NOP-CC-5703-02 Rev. 00 Report Number 3210 RTL #A4.414A
- 1. Owner F.E.N.O.C Date November 17, 2010 (NAME) 76 South Main Street -Akron, OH 44308 Sheet 1
of 2
(ADDRESS)
Unit No.
1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shippincqport, PA 15077 Work Order #200383397 (ADDRESS)
Repair/Replacement Organization P.O. No., Job No., etc.
- 3. Work Performed By BVPS Maintenance Type Code Symbol Stamp N/A (NAME)
Shippincqport, PA 15077 Authorization No.
N/A (ADDRESS)
Expiration Date N/A
- 4. Identification of System Main Steam (Q2)
- 5. (a) Applicable Construction Code ANSI B31.1 19 67 Edition, S'71 Addenda, -- Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section X1 Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Nozzle Check Enertech 11236 N/A 1 MS-18 2002 Removed Yes Nozzle Check Enertech 11076 N/A 1 MS-18 2001 Installed Yes
- 7. Description of Work Replaced valve with spare.
- 8. Tests Conducted:
Hydrostatic* n]
Pneumatic* ]
Nominal Operating Pressure N Exempt E]
Other F1 Pressure psi Test Temp.
°_F
- Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3210 RTL #A4.414A
- 9. Remarks Code Data Report attached. Previous NIS-2 Data Report No. 1725. Valve was supplied as ASME Applicable Manufacturer's Data Reports to be attached Section III 1971E-S'72A but is installed in an ANS B31.1 system.
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed T. White Staff Specialist Date November 17, 20 10 Owner or O0ner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period S-,,&/- a ?
to 1/- l-- /0
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
/,ýZ Commissions,JJ 7 1.,7 /4,1/C,41 Inspectoo Signature National Board, State, Province, and Endorsements Date
-/f- /7-
, 20 //1_
Page 2 of 2
FORM NPV-1 CERTIFICATE HOLDERS' DATA REPORT FOR NUCLEAR PUMPS OR VALVES*
As Required by the Provisions of the ASME Code,Section III. Division 1 Pg.l of 2
- 1. Manufactured and certified by Enertech, A Div. of Curtiss-Wright Flow Control Corp., 2950 Birch St., Brea, CA 92821 (name and address of N Certificate Holder)
- 2. Manufactured for First Energy Corp.; P.O. Box 3611; Akron, OH 44309-3611 (name and address of Purchaser)
- 3. Location of installation Beaver Valley Power Station; Route 168; Shippingport, PA 15077 (name and address)
- 4. Model No., Series No., or Type DRV-Z Drawing PD98401 Rev.
E CRN None
- 5. ASME Code,Section III, Division 1:
1971 S72 3
None (edition)
(addenda date)
(class)
(Code Case no.)
- 6. Pump or valve Nozzle Check Valve Nominal inlet size 3
Outlet size 3
(in.)
(in.)
- 7. Material:
Body SA-105 Bonnet N/A Disk SA-479 Type 316 Bolting N/A (a)
Cert.
Holder's Serial No.
11075 11076 (b)
Nat'l Board No.
None None (cl Body Serial No.
KEI-O01 KEI-002 (d)
Bonnet Serial No.
None None (e)
Disk Serial No.
JKT-023 JKT-024
- Supplemental information in form of lists, sketches, or drawings may be used provided (1) size is 8 %/ x 11, (2) information in items I through 4 on this Data Report is included on each sheet. (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
(12188)
This form (E00037} may be obtained from the Order Dept.. ASME. 22 Law Drive, Box 2300, Fairfield, NJ 07007-2300.
REPRINT 6/93
FORM NPV-1 (Back -
Pg. 2 of 2_ _
Certificate Holder's Serial No. 11075 & 11076 B. Design conditions 1100 psi 560
'F or valve pressure class 600 (1)
(pressure)
Itemperature)
- 9. Cold working pressure 1440 psi at 1001F
- 10. Hydrostatic test 2175 psi.
Disk differential test pressure 1600 psi
- 11. Remarks: Qty. 2, Enertech Job Number 24628V CERTIFICATION OF DESIGN Design Specification certified by Francis W. Gardner P.E. State PA Reg. no.
036614-E Design Report certified by Ira J, Silverman P.E. State CA Reg. no.
23241 CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this pump or valve conforms to the rules for construction of the ASME Code,Section III, Division 1.
N Certificate of Authorization No.
N-2826 Ex
~es 10/26/02 Date 1346101 Name Enertech IN Certificate Holder)
(authorized representativel CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of California and employed by Hartford Steam Boiler Insp. & Insur. Co.
of Connecticut have inspected the pump, or valve, described in this Data Report on L
47 z, 1 Z1
- and state that to the best of my knowledge and belief, the Certificate Holder has con-structed this pump, or valve, in accordance with the ASME Code,Section III, Division 1.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the component described in this Data Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
DateAuhorze Signed
[Nat
- 7.
dinl.e (Authorized Inspector)
[N~at'l. Bd. (inci. endorsements) and state or prov. and no.]
(1) For manually operated valves only.
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl NOP-CC-5703-02 Rev. 00 Report Number 3211 RTL #A4.414A
- 1. Owner F.E.N.O.C Date 12/02/2010 (NAME) 76 South Main Street-Akron, OH 44308 Sheet 1
of 1
(ADDRESS)
Unit No.
1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shippin.qport, PA 15077 WO# 200339325 (ADDRESS)
Repair/Replacement Organization P.O. No., Job No., etc.
- 3. Work Performed By BVPS - Construction Type Code Symbol Stamp N/A (NAME)
Shippincqport, PA 15077 Authorization No.
N/A (ADDRESS)
Expiration Date N/A
- 4. Identification of System River Water (Q3)
- 5. (a) Applicable Construction Code ANSI B31.1 1967 Edition, S'71 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c)
Applicable Section XI Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Expansion Garlock N/A N/A REJ-1 RW-2004 Removed No Joint 4A1 Expansion Garlock 10-791021-01 N/A REJ-1RW-2010 Installed No Joint 4A1 Stud Nova Machine N/A N/A HT# X573 2005 Installed No Nut Nova-Machine N/A N/A HT# 3697 1997 Installed No
- 7. Description of Work Replacement of REJ and Flangqe Studs/Nuts with like kind
- 8. Tests Conducted:
Hydrostatic* L]
Pneumatic* Li Nominal Operating Pressure [
Exempt LI Other F]
Pressure psi Test Temp.
°_F
-Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3211 RTL #A4.414A
- 9. Remarks Previous NIS-2 Data Report # 1744. Expansion Joint PO#45331376, Stud PO# 47117569 and Applicable Manufacturer's Data Reports to be attached Nut PO# 47121233 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed J. Sciulli k*
Nuclear Specialist Date December 1, 20 10 Owner or-6wner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period 2 /-
0 ?
to
// - L/
1 - / 0, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither-the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
'0', -,/. )"L-1, Commissions
/JW Z
7 Y
'ý JZ---
lnspect9o'signature National Board, State, Province, and Endorsements Date
,20
/0 Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3212 RTL #A4.414A
- 1. Owner F.E.N.O.C Date 10/27/2010 (NAME) 76 South Main Street-Akron, OH 44308 Sheet 1
of 1
(ADDRESS)
Unit No.
1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shippincport, PA 15077 Work Order #200375743 (ADDRESS)
Repair/Replacement Organization P.O. No., Job No., etc.
- 3. Work Performed By BVPS Construction Services Type Code Symbol Stamp N/A (NAME)
Shippincport, PA 15077 Authorization No.
N/A (ADDRESS)
Expiration Date N/A
- 4. Identification of System Recirculation Spray (C))
- 5. (a) Applicable Construction Code Section III 19 68 Edition, W'68 Addenda,
- Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section XI Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Heat Industrial 6301-1 3179 1RS-E-1A 1971 Corrected Yes Exchanger Process
- 7. Description of Work Replace seal welded diaphragms.
- 8. Tests Conducted:
Hydrostatic* ]
Pneumatic* LI Nominal Operating Pressure F]
Exempt 0 Other nI Pressure psi Test Temp.
_F
'Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3212 RTL #A4.414A
- 9. Remarks Copy of original Data Report in NIS-2 #1577. Previous NIS-2 Data Report No. 3065.
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed T. White Staff Specialist Date October 27, 20 10 Owner or Ownbr's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period
- --!/-
0 ?
to
/
5
-2?
/0
,and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
)
/.-Commissions M y-'i,) r,fWA-zZ2 F
Inspector's,2' nature National Board, State, Province, and Endorsements Date
/(
~2--?-/D
, 20 /0 Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3213 RTL #A4.414A
- 1. Owner F.E.N.O.C Date 10/27/2010 (NAME) 76 South Main Street -Akron, OH 44308 Sheet 1
of 1
(ADDRESS)
Unit No.
1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shippincport, PA 15077 Work Order #200375745 (ADDRESS)
Repair/Replacement Organization P.O. No., Job No., etc.
- 3. Work Performed By BVPS Construction Services Type Code Symbol Stamp N/A (NAME)
Shippincqport, PA 15077 Authorization No.
N/A (ADDRESS)
Expiration Date N/A
- 4. Identification of System Recirculation Spray (C))
- 5. (a) Applicable Construction Code Section III 19 68 Edition, W'68 Addenda, - Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section XI Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Heat Industrial 6301-3 3181 1RS-E-1C 1971 Corrected Yes Exchanger Process
- 7. Description of Work Replace seal welded diaphragms.
- 8. Tests Conducted:
Hydrostatic* El Pneumatic* LI Nominal Operating Pressure F]
Exempt 0 Other E]
Pressure psi Test Temp.
o F
'Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3213 RTL #A4.414A
- 9. Remarks Copy of original Data Report in NIS-2 #1578. Previous NIS-2 Data Report No. 3066.
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed T. White Staff Specialist Date October 27, 20 10 Owner or Ow r's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period
.J-'-.2 O
to
/
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions d2 Y 4
/
Jnspector's`ý nature National Board, State, Province, and Endorsements Date
/ 0 -'A 20 /
Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3216
- 1. Owner F.E.N.O.C Date 10/10/2010 (NAME) 76 South Main Street -Akron, OH 44308 Sheet 1
of 1
(ADDRESS)
Unit No.
1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shippinqport, PA 15077 Work Order #200323026 (ADDRESS)
Repair/Replacement Organization P.O. No., Job No,, etc.
- 3. Work Performed By FENOC Maintenance Type Code Symbol Stamp N/A (NAME)
Shippingport, PA 15077 Authorization No.
N/A (ADDRESS)
Expiration Date N/A
- 4. Identification of System Ventilation / River Water (3)
- 5. (a) Applicable Construction Code Section VIli 19 71Edition, S'72 AddendaCode Case -
(b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c)
Applicable Section XI Code Case(s):
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Heat York 1-2239 46531 1VS-E-4B 1972 Corrected No Exchanger End Bell Dubose N/A N/A N/A 2009 Installed No National Energy
- 7. Description of Work Replaced heat exchanger end bells.
- 8. Tests Conducted.
Hydrostatic* El Pneumatic* El Nominal Operating Pressure Z Exempt El Other El Pressure psi Test Temp. ---
F Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3216
- 9. Remarks U-1 Data Report attached to previous NIS-2 No. 1590. The tube section of the heat exchanger was Applicable Manufacturer's Data Reports to be attached exempt to ASME Section VIII and was made to commercial grade. Serial numbers 1 through 4 were supplied under P.O. 45274468, however, the serial numbers installed were not recorded.
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed T. White Staff Specialist Date October 11
, 2010 Owner orO ner's besgnee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period I-k-I - ( 7 to
/ 0 -/.2 -/0
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions,ti,
,,-,/z A-f
.. 3 F Inspectxs Signature National Board, State, Province, and Endorsements Date
/0 20/0 Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3236 RTL #A4.414A
- 1. Owner F.E.N.O.C I Date 12/02/2010 (NAME) 76 South Main Street - Akron, OH 44308 (ADDRESS)
Beaver Valley Power Station (BVPS)
Sheet 1
of Unit No.
1
- 2. Plant (NAME)
Shippinciport, PA 15077 (ADDRESS)
- 3. Work Performed By BVPS - Maintenance (NAME)
ShiDDinoDort. PA 15077 WO# 200375747 Repair/Replacement Organization P.O. No., Job No., etc.
Type Code Symbol Stamp N/A Authorization No.
N/A Expiration Date N/A (ADDRESS)
- 4. Identification of System River Water (Q3)
- 5. (a) Applicable Construction Code ANSI B31.1 1967 Edition, S'71 Addenda, N/A Code Case (b) Applicable Edition of Section X1 Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section XI Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Nut Nova Machine N/A N/A N/A 2005 Installed No Stud Nova Machine N/A N/A HT# X573 2010 Installed No Check Valve C & S Valve 89-0929-01(Q)-Ol N/A 1 RW-1 06 N/A Removed No Check Valve C & S Valve 92-2019-06(Q)-1 N/A 1RW-106 N/A Installed No
- 7. Description of Work Replace valve and valve bolting with a spare valve and like kind bolting
- 8. Tests Conducted:
Hydrostatic* L]
Pneumatic*L]-
Nominal Operating Pressure [
Exempt LI Other l Pressure psi Test Temp.
°F
- Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3236 RTL #A4.414A
- 9. Remarks Previous NIS-2# 2027. Stud PO# 47117569, Nut PO/HT# 47082958/P921 and 4708563/A201 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed J. Sciulli Nuclear Specialist Date December 2, 20 10 Owner or &ner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period
-S--,d./- O F to
//J -
-/,39r, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
A a-I j Commissions ld
,*"K 6
Y.,7, T Inspectoq Signature National Board, State, Province, and Endorsements Date
, 20
/0 Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3239 RTL #A4.414A
- 1. Owner F.E.N.O.C Date 12/02/2010 (NAME) 76 South Main Street - Akron. OH 44308 (ADDRESS)
Sheet Unit No.
1 of 1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shippincqport, PA 15077 (ADDRESS)
- 3. Work Performed By BVPS - Maintenance (NAME)
Shippinqport, PA 15077 (ADDRESS)
WO# 200308441 Repair/Replacement Organization P.O. No., Job No., etc.
Type Code Symbol Stamp N/A Authorization No.
Expiration Date N/A N/A
- 4. Identification of System
- 5. (a) Applicable Construction Code ANSI B31.1 1967 Edition, S'71 Addenda,_ Code Case N/A (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c)
Applicable Section XI Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Valve N/A N/A N/A NRV-1MS-101B 1976 Corrected No Shaft Flowserve N/A N/A NRV-1MS-101B 2006 Installed No
- 4.
4 4
+
4 4
- 7. Description of Work Replace valve shaft bearing covers.
- 8. Tests Conducted:
Hydrostatic* D Pneumatic* L]
Nominal Operating Pressure [
Exempt []
Other nI Pressure psi Test Temp.
°_F
- Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl NOP-CC-5703-02 Rev. 00 Report Number 3239 RTL #A4.414A
- 9. Remarks No Previous NIS-2. Shaft PO# 45203895 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed J. Sciulli Nuclear Specialist Date December 2, 20 10 Owner or Owr's Degnee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period
"--j,./- 0 to
//
-_Y-0
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions,/I 4'*- r
,L2 PY Inspectge's Signature National Board, State, Province, and Endorsements Date
/,,-..?--
,20
/0 Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3248 RTL #A4.414A
- 1. Owner F.E.N.O.C Date 12/01/2010 (NAME) 76 South Main Street-Akron, OH 44308 Sheet 1
of 1
(ADDRESS)
Unit No.
1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shippingqport, PA 15077 WO# 200387923 (ADDRESS)
Repair/Replacement Organization P.O. No., Job No., etc.
- 3. Work Performed By BVPS - Maintenance Type Code Symbol Stamp N/A (NAME)
Shippinqport, PA 15077 Authorization No.
N/A (ADDRESS)
Expiration Date N/A
- 4. Identification of System Emergency Diesel (Q3)
- 5. (a) Applicable Construction Code ANSI 831.1 1967 Edition, S'71
- Addenda, Code Case N/A (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c)
Applicable Section XI Code Case(s): N/A
- 6. Identification of Components Corrected National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Valve Swagelok N/A N/A 1DLO-28 2010 Installed No Pipe Michigan N/A N/A HT#
2005 Installed No Seamless 3M50192 Pipe Cap Bonney Forge N/A N/A HT# 9438 2004 Installed No
- 7. Description of Work Install new drain on line
- 8. Tests Conducted:
Hydrostatic* ]
Pneumatic* L]
Nominal Operating Pressure E]
Exempt El Other I Pressure psi Test Temp.
-F
'Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3248 RTL #A4.414A
- 9. Remarks No Previous NIS-2. Valve PO# 45346904, Pipe Po#45233562 and Pipe Cap PO# 45332935 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed J. Sciulli 21*I Nuclear Specialist Date December 1, 20 10 Owner or Owrter's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period
"-- 2.- / - o 9 to
//-
V-/k0'
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
S-1 J
Commissions J-Z Y,,2 Inspector's n&ature National Board, State, Province, and Endorsements Date
-_"______,20
/O Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3252 RTL #A4.414A
- 1. Owner F.E.N.O.C I Date 12/02/2010 (NAME) 76 South Main Street-Akron, OH 44308 (ADDRESS)
Beaver Valley Power Station (BVPS)
Sheet 1
of Unit No.
1
- 2. Plant (NAME)
Shippincqport, PA 15077 (ADDRESS)
- 3. Work Performed By BVPS - Construction (NAME)
Shippincqport, PA 15077 (ADDRESS)
WO# 200383348 Repair/Replacement Organization P.O. No., Job No., etc.
Type Code Symbol Stamp N/A Authorization No.
N/A Expiration Date N/A
- 4. Identification of System River Water (Q3)
- 5. (a) Applicable Construction Code ANSI B31.1 1967 Edition, S'71 Addenda, N/A Code Case (b)
Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c)
Applicable Section Xl Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Elbow ATI N/A N/A HT# 6XN-2009 Installed No NVS001 Flange Western N/A N/A HT# 857B 2002 Installed No Forge and Flange Ball Valve BNL Industries B021016-1-8 N/A 1RW-132 2003 Corrected No End Piece BNL Industries N/A N/A HT# D4730 2010 Installed No
- 7. Description of Work Replace valve end pieces
- 8. Tests Conducted:
Hydrostatic* LI Pneumatic* []
Nominal Operating Pressure M Exempt [l Other [L Pressure psi Test Temp.
-F Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl NOP-CC-5703-02 Rev. 00 Report Number 3252 RTL #A4.414A
'Record test pressure and temperature
- 9. Remarks Previous NIS-2# 2076. End Piece PO# 45324230, Elbow PO# 47265422 and Flange PO# 7099495 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed J. Sciulli Nuclear Specialist Date December 2, 20 10 Owner or 0'ner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period 5----
/ -
?
to
//-
Y,-/T?
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
__2_
Commissions_-_,__9__________________
Inspe *yes Signature National Board, State, Province, and Endorsements Date
/<2_-
20 '0 Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3254 R7-L #A4.414A
- 1. Owner F.E.N.O.C I Date November2, 2010 (NAME) 76 South Main Street -Akron. OH 44308 (ADDRESS)
Beaver Vallev Power Station (BVPS)
Sheet Unit No.
1 of 1
- 2. Plant (NAME)
Shippincport, PA 15077 Work Order #200383347 (ADDRESS)
- 3. Work Performed By BVPS Construction Services (NAME)
Shioninonort, PA 15077 RepairlReplacement Organization P.O. No.. Job No., etc.
Type Code Symbol Stamp N/A Authorization No.
N/A Expiration Date N/A (ADDRESS)
- 4. Identification of System River Water (Q3)
- 5. (a) Applicable Construction Code ANSI B31.1 19 67 Edition, S'71 Addenda, -Code Case (b)
Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c)
Applicable Section XI Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Ball Valve BNL Industries B021016-1-6 N/A 1RW-130 2003 Corrected No End Cap BNL Industries B02101601-4 N/A 2003 Removed No End Cap BNL Industries N/A N/A Ht. #D4728 2010 Installed No
- 7. Description of Work Replaced valve end caps, pipe nipple, and flange.
- 8. Tests Conducted:
Hydrostatic* []
Pneumatic* El Nominal Operating Pressure Z Exempt LI Other Ln Pressure psi Test Temp.
o F Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl NOP-CC-5703-02 Rev. 00 Report Number 3254 RTL #A4.414A
- 9. Remarks No Code Data Reports available. Previous NIS-2 Data Report No. 1835. Replacement 6" NPS Pipe:
Applicable Manufacturer's Data Reports to be attached PO 47031899 / Ht. #811818M01; 6" NPS Flange: PO 7099495-15 / Ht. #857B.
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed T. White Staff Specialist Date November 12, 20 10 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period S&
-2o-(-
0 7 to
/
Y-1(0
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his~employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
_________Commissions d.'
4
/
i J-9-
Inspectorignature National Board, State, Province, and Endorsements Date
///.
, 20 ( 0 Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3256 RTL #A4.414A
- 1. Owner F.E.N.O.C f Date November 22, 2010 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1
of 1
(ADDRESS)
Unit No.
1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shippingport, PA 15077 Work Order 200373908 (ADDRESS)
Repair/Replacement Organization P.O. No-, Job No., etc.
- 3. Work Performed By BVPS Maintenance Type Code Symbol Stamp N/A (NAME)
Shippingport, PA 15077 Authorization No.
N/A (ADDRESS)
Expiration Date N/A
- 4. Identification of System Emergency Diesel (Q3)
- 5. (a) Applicable Construction Code ANSI B31.1 19 67_ Edition, S'71 Addenda, ---Code Case (b)
Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c)
Applicable Section XI Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Piping EMD-General 72-D1-1160 N/A 1EE-EG 1972 Corrected No Motors ENGINE
- 8. Tests Conducted:
Hydrostatic* F1 Pneumatic* []
Nominal Operating Pressure M Exempt [l Other L]
Pressure psi Test Temp.
o F Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3256 RTL #A4.414A
- 9. Remarks No Code Data Report available. Replacement Couplinqs: 3 ea. 4" - PO 45332534: 2 ea. 3" - PO Applicable Manufacturer's Data Reports to be attached 45126587 & PO 45119100: 1 ea. 6"- P0 45115781.
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed T. White Staff Specialist Date November 24, 20 10 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period
,. ( - 0 "
to 1/_ *_/0
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
________________L_"
Commissions ",J'
) -Y/, A'YS
/.4
,3 "Y
Inspector' ignature National Board, State, Province, and Endorsements Date
/_-__/--
, 20
/0 Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3257 RTL #A4.414A
- 1. Owner F.E.N.O.C Date November 22, 2010 (NAME) 76 South Main Street -Akron, OH 44308 Sheet 1
of 1
(ADDRESS)
Unit No.
I
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shippinqport, PA 15077 Work Order 200373909 (ADDRESS)
Repair/Replacement Organization P.O. No., Job No., etc.
- 3. Work Performed By BVPS Maintenance Type Code Symbol Stamp N/A (NAME)
Shippinqport, PA 15077 Authorization No.
N/A (ADDRESS)
Expiration Date N/A
- 4. Identification of System EmerqencV Diesel (Q3)
- 5. (a) Applicable Construction Code ANSI B31.1 19 67 Edition, S'71 Addenda, -- Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c)
Applicable Section XI Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Piping EMD-General 72-D1-1041 N/A 1EE-EG 1972 Corrected No Motors ENGINE
- 8. Tests Conducted:
Hydrostatic* E]
Pneumatic* EL Nominal Operating Pressure E Exempt []
Other F]
Pressure psi Test Temp.
°_F
- Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl NOP-CC-5703-02 Rev. 00 Report Number 3257 RTL #A4.414A
- 9. Remarks No Code Data Report available. Replacement Couplings: 4" - PO 45332534: 3" - PO 45126587.
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed T. White Staff Specialist Date November 24, 20 10 Owner or Owne,
- Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period
/--
- -/- 6 7 to
/( - Y -( 0
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
i9
,z J
I a
ýý'
C o m m is s io n sg
-1,I17*
/A 3T Inspector's nature National Board, State, Province, and Endorsements Date
/Z 20 /0 Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3273 RTL #A4.414A
- 1. Owner F.E.N.O.C Date December20, 2010 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1
of 1
(ADDRESS)
Unit No.
1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shippinaport, PA 15077 Work Order #200402653 (ADDRESS)
Repair/Replacement Organization P.O. No., Job No., etc.
- 3. Work Performed By BVPS Construction Services Type Code Symbol Stamp N/A (NAME)
Shippingport, PA 15077 Authorization No.
N/A (ADDRESS)
Expiration Date N/A
- 4. Identification of System River Water (Q3)
- 5. (a) Applicable Construction Code ANSI B31.1 19 67 Edition, S'71 Addenda, - Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section XI Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Piping Stone &
N/A N/A WR-610 1976 Corrected No Webster Piping First Energy N/A N/A WR-610 2010 Installed No
- 7. Description of Work Replaced pipe and fittings. Reworked supports.
- 8. Tests Conducted:
Hydrostatic* LI Pneumatic* El Nominal Operating Pressure [
Exempt [
Other LI Pressure psi Test Temp.
°F
- Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl NOP-CC-5703-02 Rev. 00 Report Number 3273 RTL #A4.414A
- 9. Remarks No Code Data Report available. Replaced following 1-1/2" pipe and fittings - Pipe: PO 45335570 / Ht.
Applicable Manufacturer's Data Reports to be attached
- 523562: Couplinq: PO 7049429 / Ht. #1488ANE2: Tee 7037275 / Ht. #1488ANE2: Reducer: 47084700 / Ht.#62741 Elbow: 45339154 / Ht.#E52, PO 45340452 / Ht. #18442. Additionally, the following supports were reworked: PS-1 13, PS-120. PS-128. PS-121, PS-107 (removed). PS-108, PS-109. PS-112. PS-114, PS-116, PS-118. PS-122, PS-114.
PS-117. PS-110. PS-111, PS-115, PS-119, PS-123. PS-124. PS-125. PS-126. PS-127, PS-129. PS-130 by addinq 2x2x1/4" anale: PO 47261319 / Ht. #JH1257: 5/8" Plate: PO 45337100: 3/8" Plate: PO 45151413 / Ht. # T4705:
'/" Plate: PO 45301005 / Ht. #A8T2701-02. PO 45189132 / Ht. #U8551/1A: 1" Plate: PO 47034423 / Ht. #W63733.
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section X1.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date Signed T. White ite.
Staff Specialist N/A
)ate January 12, 20 11 Owner or Owier's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania
- and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period J--/
- 0 o to
// - y-
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
CommssonsAe
ýýX d-2 o,
Inspecj;'
Signature National Board, State, Province, and Endorsements Date
/-/c?
,20
//
Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3275 RTL #A4.414A
- 1. Owner F.E.N.O.C Date December 3, 2010 (NAME) 76 South Main Street-Akron, OH 44308 Sheet 1
of 1
(ADDRESS)
Unit No.
1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shippinqport, PA 15077 Work Order #200412068 (ADDRESS)
RepairlReplacement Organization P.O. No., Job No., etc.
- 3. Work Performed By BVPS Maintenance Type Code Symbol Stamp N/A (NAME)
Shippinqport, PA 15077 Authorization No.
N/A (ADDRESS)
Expiration Date N/A
- 4. Identification of System Chemical and Volume Control (Q2)
- 5. (a) Applicable Construction Code ANSI B31.1 19 67 Edition, S'71 Addenda, -
Code Case (b)
Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c)
Applicable Section XI Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Check Valve Rockwell Int.
N/A N/A 1CH-84 1976 Corrected No
- 7. Description of Work Reseal welded canopy to body.
- 8. Tests Conducted:
Hydrostatic* LI Pneumatic* LI Nominal Operating Pressure El Exempt Z Other F1 Pressure psi Test Temp.
_F
- Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section.XI NOP-CC-5703-02 Rev. 00 Report Number 3275 RTL #A4.414A
- 9. Remarks No Code Data Report available.
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed T. White Staff Specialist Date December 3, 20 10 Owner or Onkr's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period S-- Z_/ - 0 ?
to
// - V-
/ 0, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
-cJ*-
..*-'* -'/*7.*
/JCo mmissions W2,?/994-..*.
Inspector's Ymgnature National Board, State, Province, and Endorsements Date
/w_-
( -
20 (C0 Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3286 RTL #A4.414A
- 1. Owner F.E.N.O.C Date 12/1512010 (NAME) 76 South Main Street - Akron, OH 44308 Sheet I
of 1
(ADDRESS)
Unit No.
1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shippinqport, PA 15077 WO# 200415220 (ADDRESS)
Repair/Reptacement Organization P.O. No., Job No., etc.
- 3. Work Performed By BVPS - Construction Type Code Symbol Stamp N/A (NAME)
Shippinqport, PA 15077 Authorization No.
N/A (ADDRESS)
Expiration Date N/A
- 4. Identification of System River Water (Q3)
- 5. (a) Applicable Construction Code ANSI B31.1 1967 Edition, S'71 Addenda, N/A Code Case (b)
Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section XI Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Piping Schneider Inc.
N/A N/A WR-560 1976 Corrected No
- 7. Description of Work Cut and reweld elbow and a section of pipe.
- 8. Tests Conducted:
Hydrostatic* El Pneumatic* E Nominal Operating Pressure Z Exempt []
Other []
Pressure psi Test Temp.
oF
- Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3286 RTL #A4.414A
- 9. Remarks No Previous NIS-2.
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed J. Sciulli Nuclear Specialist Date December 15, 20 10 Owner or (twner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period
,./-,'-
I-0 ?
to
/[-
V-/0
-, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
~~J j
,ý -
Commissions F~~y2
,*A14
,y~
Inspecto%
ignature National Board, State, Province, and Endorsements Date
/O-L. 0
, 20 /0 Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Reoort Number 3291 RTL #A4.414A
- 1. Owner F.E.N.O.C Date 12/14/2010 (NAME) 76 South Main Street -Akron. OH 44308 (ADDRESS)
Sheet Unit No.
1 of 1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
ShioDinaoort. PA 15077 WO# 200425159 (ADDRESS)
- 3. Work Performed By BVPS - Construction (NAME)
ShiDoinaDort. PA 15077 Repair/Replacement Organization P.O. No., Job No., etc.
Type Code Symbol Stamp N/A (ADDRESS)
Authorization No.
Expiration Date N/A N/A
- 4. Identification of System River Water (Q3)
- 5. (a) Applicable Construction Code ANSI B31.1 19 67 Edition, S'71 Addenda, N/A Code Case (b)
Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c)
Applicable Section XI Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Piping Schneider Inc.
N/A N/A WR-5 1976 Corrected No
- 7. Description of Work Weld repair a pin hole leak.
- 8. Tests Conducted:
Hydrostatic* E]
Pneumatic* L]
Nominal Operating Pressure H Exempt []
Other n]
Pressure psi Test Temp.
o F
- Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3291 RTL #A4.414A
- 9. Remarks No previous NIS-2.
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed J. Sciulli Nuclear Specialist Date December 14, 20 10 Owner or')wner's Dgsignee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period -,2- - 0 ?
to
//-
'/-/C
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
~~~
1Anaty-Commissions V' ý
'ZW4$2 2
/1 Inspector' National Board, State, Province, and Endorsements Date
/____,_______,20
/0 Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3293 RTL #A4.414A
- 1. Owner F.E.N.O.C Date 12/02/2010 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1
of 1
(ADDRESS)
Unit No.
1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shippingport, PA 15077 WO# 200429434 (ADDRESS)
Repair/Replacement Organization P.O. No., Job No., etc.
- 3. Work Performed By BVPS - Maintenance Type Code Symbol Stamp N/A (NAME)
Shippinqport, PA 15077 Authorization No.
N/A (ADDRESS)
Expiration Date N/A
- 4. Identification of System Residual Heat Removal (C)
- 5. (a) Applicable Construction Code AMSE Section III 19 68Edition, 72 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section XI Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Heat Joseph 1832-1 368 1RH-E-1A 1969 Corrected Yes Exchanger Oat.Co Stud Nova Machine N/A N/A HT# 2U88 2008 Installed No
- 7. Description of Work Remove and Inspect one flange bolt and replace is necessary.
- 8. Tests Conducted:
Hydrostatic* E]
Pneumatic* LI Nominal Operating Pressure [L Exempt E OtherLI Pressure psi Test Temp.
°_F
- Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3293 RTL #A4.414A
- 9. Remarks Previous NIS-2 Report No1581. Stud PO# 45297678 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed J. Sciulli 2
Nuclear Specialist Date December 1, 20 10 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period
.- '-- c.L /-
0 T to
/(-
-/
0
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
____CommissionsZ f '
V-1 AL--Z7-14 d*--3 ?y Inspector'signature National Board, State, Province, and Endorsements Date
____________,20
/0.
Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3294 RTL #A4.414A
- 1. Owner F.E.N.O.C Date October 31, 2010 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1
of 1
(ADDRESS)
Unit No.
1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shippincport, PA 15077 Work Order #200432353 (ADDRESS)
RepairtReplacement Organization P.O. No., Job No., etc.
- 3. Work Performed By BVPS Maintenance Type Code Symbol Stamp N/A (NAME)
Shippincqport, PA 15077 Authorization No.
N/A (ADDRESS)
Expiration Date N/A
- 4. Identification of System Residual Heat Removal (Q2)
- 5. (a) Applicable Construction Code ANSI B31.1 1967 Edition, S'71 Addenda, N/ACode Case (b)
Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section Xl Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Glove Valve Rockwell-N/A N/A 1RH-200 1976 Corrected No Edward
- 7. Description of Work Installed a mechanical clamping device and support to compensate for a cracked pipe to valve inlet socket weld.
- 8. Tests Conducted:
Hydrostatic* L]
Pneumatic* l]
Nominal Operating Pressure [
Exempt LI Other F1 Pressure psi Test Temp.
oF
- Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3294 RTL #A4.414A
- 9. Remarks No Code Data Report available. The mechanical clamping device was manufactured and installed by Applicable Manufacturer's Data Reports to be attached Team Inc. per ECP 10-0619-001 under the FENOC ASME Section Xl proaram. and the pipe suoDort was manufactured and installed by FENOC. Both the clamping device and the support were later removed per work Order 200199095 when the W" valve and inlet piping were replaced. Materials installed were: Team Clamp assembly PO 45352950: 14" Anvil Clamp - PO 45352934: Tube Steel-45210895: Plate - PO 47283331/ Ht. #BOR6303; 1/2A" Studs - PO 45333545 / Ht. #8898247; 1" Nuts - PO 45343125 / Ht. #4N88 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Da Signed T. White Staff Specialist Owner or Owners Designee, Title ite N/A Date November 12, 20 10 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period 5- -, /- 0 y to
//- Y--0
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
,9,,,j 2,1, Commissions
'*frY FAA/Ti-614A4,-? 9-(,
lnspectoýAignature National Board, State, Province, and Endorsements Date
//I-
,20
((
Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3295 RTL #A4.414A
- 1. Owner F.E.NO.C Date October3l,2010 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1
of 1
(ADDRESS)
Unit No.
1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shippinqport, PA 15077 Work Order #200368067 (ADDRESS)
Repair/Replacement Organization P.O. No., Job No., etc.
- 3. Work Performed By BVPS Valve Team Type Code Symbol Stamp N/A (NAME)
Shippincport, PA 15077 Authorization No.
N/A (ADDRESS)
Expiration Date N/A
- 4. Identification of System River Water (Q3)
- 5. (a) Applicable Construction Code ANSI B16.5 19 68 Edition, -- Addenda, -
Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section XI Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Butterfly Rodney Hunt 2
N/A MOV-1RW-103B 1993 Corrected No Valve A
F 4
F
+
+
t F
+/-
4 4
t
- 7. Description of Work Replaced valve flange bolts.
- 8. Tests Conducted:
Hydrostatic* []
Pneumatic* []
Nominal Operating Pressure El Exempt 0 Other D]
Pressure psi Test Temp.
oF Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3295 RTL #A4.414A
- 9. Remarks No Code Data Report available. Previous NIS-2 Data Report No. 451. Replacement 1-1/4" Bolts: PO Applicable Manufacturer's Data Reports to be attached 47167866 / Ht. #QQT.
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed T. White M)Ce2 Staff Specialist Date November 3, 20 10 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period J--d-. / - 0 ?
to
/1-'Y.
/0
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
7Commissions Inspector's cgnature National Board, State, Province, and Endorsements Date
//-
-/'-
, 20 / 0 Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3296 RTL #A4.414A
- 1. Owner F.E.N.O.C Date November 2, 2010 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1
of 1
(ADDRESS)
Unit No.
1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shippingport, PA 15077 Work Order #200432665 (ADDRESS)
Repair/Replacement Organization P.O. No., Job No., etc.
- 3. Work Performed By BVPS Maintenance Type Code Symbol Stamp N/A (NAME)
Shippingport, PA 15077 Authorization No.
N/A (ADDRESS)
Expiration Date N/A
- 4. Identification of System Feedwater (Q3)
- 5. (a) Applicable Construction Code ANSI B31.1 19 1967 Edition, S'71 Addenda, -Code Case (b)
Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c)
Applicable Section X1 Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Check Valve Rockwell N/A N/A 1 FW-627 1976' Corrected No International Cover Rockwell N/A N/A Ht. #5P9487 1983 Installed No International Disc Rockwell N/A N/A Ht. #F6702 1983 Installed No International
- 7. Description of Work Replaced valve disc, cover, and seal welded cover to body.
- 8. Tests Conducted:
Hydrostatic* L]
Pneumatic* LI Nominal Operating Pressure M Exempt El Other l]
Pressure psi Test Temp.
o F Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR. REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl NOP-CC-5703-02 Rev. 00 Report Number 3296 RTL #A4.414A
- 9. Remarks No Code Data Report available. *Year installed.
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed T. White Staff Specialist Date November 12, 20 10 Owner or OWnies Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National.Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period
.S-- dL/- 0 ?
to
// - '
(
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
__J-_
_ý'nec nu Commissions J
,R9",4-/.-
-4 *? dtY Inspector's.Vnature National Board, State, Province, and Endorsements Date
/(d(_
20 /(
Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section X1 NOP-CC-5703-02 Rev. 00 Report Number 3297 RTL #A4.414A
- 1. Owner F.E.N.O.C I Date November 15, 2010 (NAME) 76 South Main Street -Akron, OH 44308 Sheet 1
of 1
(ADDRESS)
Unit No.
1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shippinqport, PA 15077 Work Order #200432381 (ADDRESS)
Repair/Replacement Organization P.O. No., Job No.. etc.
- 3. Work Performed By BVPS Valve Team Type Code Symbol Stamp N/A (NAME)
Shippinqport, PA 15077 Authorization No.
N/A (ADDRESS)
Expiration Date N/A
- 4. Identification of System Safety Injection (Q1)
- 5. (a) Applicable Construction Code ANSI B16.5 19 68 Edition, -- Addenda, -- Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section XI Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Check Valve Velan N/A N/A 1SI-22 1976 Corrected No Cover Velan 5375 N/A Ht. #H4069 1990 Installed No
- 7. Description of Work Replaced valve cover and cover studs/nuts.
- 8. Tests Conducted:
Hydrostatic* []
Pneumatic* EL Nominal Operating Pressure M Exempt [L Other i]
Pressure psi Test Temp.
OF
- Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3297 RTL #A4.414A
- 9. Remarks No Code Data Report available. Installed 1-1/4" Studs: PO 47117569 / Ht. #X573: Nuts: PO 47121233 Applicable Manufacturer's Data Reports to be attached Ht. #S697.
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed T. White Staff Specialist Date December 2, 20 10 Owner or O0 er's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period
..f '- f - 0 7 to
//
/ 0, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
& 2 Commissions~
IýJ 1
,4~o;?
InspectoySignature National Board, State, Province, and Endorsements Date
/- -
, 20/
0 Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3303 I TL #A4.414A
- 1. Owner F.E.N.O.C I Date December 3, 2010 (NAME) 76 South Main Street - Akron, OH 44308
- 2. Plant (ADDRESS)
Beaver Valley Power Station (BVPS)
(NAME)
Shippinarort. PA 15077 Sheet Unit No.
1 of 1
4.
5.
6.
(ADDRESS)
Repair/Replacement Organization P.O. No., Job No., etc.
Work Performed By BVPS Maintenance Type Code Symbol Stamp N/A (NAME)
Shippincqport, PA 15077 Authorization No.
NIA (ADDRESS)
Expiration Date N/A Identification of System Chemical and Volume Control (Q2)
(a) Applicable Construction Code Section VIII 19 68 Edition,-
Addenda, -
Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section XI Code Case(s): N/A Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Relief Valve Crosby N69972-00-0016 N/A RV-1CH-203 2003 Removed No Relief Valve Crosby 61680-003 N/A RV-1CH-203 1990 Installed No
- 7. Description of Work Replaced valve with spare and flangqe studs/nuts.
- 8. Tests Conducted:
Hydrostatic* E]
Pneumatic* L]
Nominal Operating Pressure Z Exempt LI OtherF]
Pressure psi Test Temp.
oF
- Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section X1 NOP-CC-5703-02 Rev. 00 Report Number 3303 RTL #A4.414A
- 9. Remarks No Code Data Report available. Previous NIS-2 Data Report No. 1622. Replacement 5/8" Studs: PO Applicable Manufacturer's Data Reports to be attached 45314223 / Ht. #3N12; Nuts: PO 45343125 / Ht. #4P86.
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed T. White Staff Specialist Date December 9, 20 10 Owner or Wn`er's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period j--
./0 f'
to
//-
V-/ / '
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
___._Commissions,
,A1 5/9 o
,,.J Z-2*
A /,,-2?V/
InspectorI'Signature National Board, State, Province, and Endorsements Date
/2---/3
,20 /
0 Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3304 RTL #A4.414A
- 1. Owner F.E.N.O.C Date November 15, 2010 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1
of 1
(ADDRESS)
Unit No.
1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shippingport, PA 15077 Work Order # 200296268 (ADDRESS)
Repair/Replacement Organization P.O. No., Job No., etc.
- 3. Work Performed By BVPS Maintenance Type Code Symbol Stamp N/A (NAME)
Shippinqport, PA 15077 Authorization No.
N/A (ADDRESS)
Expiration Date N/A
- 4. Identification of System Residual Heat Removal (Q2)
- 5. (a) Applicable Construction Code ANSI B31.1 19 67 Edition, S'71 Addenda, -
Code Case (b)
Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c)
Applicable Section Xl Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Relief Valve Crosby N69973-01-0001 N/A RV-1 RH-721 1988 Removed No Relief Valve Crosby 53237M1 N/A RV-1 RH-721 1976 Installed No
- 7. Description of Work Replaced valve with spare for testing purposes.
- 8. Tests Conducted:
Hydrostatic* LI Pneumatic* E]
Nominal Operating Pressure LI Exempt [
Other L]
Pressure psi Test Temp.
o F
- Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3304 RTL #A4.414A
- 9. Remarks No Code Data Report available. Previous NIS-2 Data Report No. 1868 Applicable Manufacturers Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed T. White Staff Specialist Date November 15, 20 10 Owner or Ow er's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period 3- -
-/-
(
CJ to d/ -
0
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Insp" r's Signature National Board, State, Province.. an::E~ndorsements Date
//-/
_,20
/0 Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3305 RTL #A4.414A
- 1. Owner F.E.N.O.C Date October31, 2010 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1
of 2
(ADDRESS)
Unit No.
1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shippinqport, PA 15077 Work Order #200369665 (ADDRESS)
Repair/Replacement Organization P.O. No., Job No., etc.
- 3. Work Performed By BVPS Maintenance Type Code Symbol Stamp N/A (NAME)
Shippincqport, PA 15077 Authorization No.
N/A (ADDRESS)
Expiration Date N/A
- 4. Identification of System Chemical and Volume Control (Q2)
- 5. (a) Applicable Construction Code ASME Section III 19 71 Edition, W'72 Addenda, -Code Case (b)
Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section XI Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Relief Valve Crosby N56900-00-0029 194 RV-1CH-382B 1976 Corrected Yes
- 7. Description of Work Replaced valve inlet flanqe studs/nuts.
- 8. Tests Conducted:
Hydrostatic* LI Pneumatic* LI Nominal Operating Pressure El Exempt M Other R Pressure psi Test Temp.
oF
- Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3305 RTL #A4.414A
- 9. Remarks Code Data Report attached. Previous NIS-2 Data Report No. 1867. Replaced 5/8" Studs: PO Applicable Manufacturer's Data Reports to be attached 45275451 / Ht. #258262: 5/8" Nuts: PO 45203316 / Ht. #Z726. This is an ASME Section III valve installed into an ANSI B31.1 system.
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed T. White Staff Specialist Date December 10, 2010 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period 5:--^ Z. / - 0 7 to
/ (-
-/o 0
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions -Jd Vo,--
,A"T3F-Inspector'50"gnature National Board, State, Province, and Endorsements Date
/1--
, 20 Page 2 of 2
/_?.f_7*_Corrected Report 1/28/87 C:s Pa CGROSBY VALVE
& GAGE COM PANY WR ENTHAM, MASS FORM NV-I FOR SAFETY AND SAFETY KELIEF VALVES Q.C.-44C As required by the Prov,2ions of Ehe ASLDE Code Rules DATA REPORT Safbety And Safety Relief Valves I. Manufactured By Crosby Vaye_&_g.
Company, 43 Kendrick Street, Wrentham.
Ma, 02093 JB Name and Addr,3es model NO.TD-1R Order No N302954 Contract Date.3/30/73 iNational Board No.
194 Westinghouse Electric Corp.,
- 2. Manufactured ForP. 0. Box 355. Pittsburgh, Pa.
15230 OrderNo.
546-CCK-183426-BN Name and Address
- 3. Owner Duquesne Light Cgmipany., Beaver *Valley P*ower Station, 13eaver Valley Unit #2 Name and Address
- 4. Location of plant Shippingport, Beaver County, Pennsylvania
- 5. Valve ldentification RV-8121 DMW.
Serial No.
N56900-00-0029 Drawing Nio.
DS-C-56900 Rev.
A Type
,PJei *P Orifice Size-I Pipe Size
. Inlet.
- 2. Outlet 3
SafetySafety Relief. Pilot. Power Actuated Inch Inch Inch Inch
- 6. Set Pressure (PSIC) 0 2500 F
Rated Temperature Stamped Capacity 225
,Pm W*ater i10I.Overpressure Blowdown cnbo*
IQ%'/_ of 1; P Outlet Hydrostatic Test (PSIG) Inlet_
425 2
eeVr 425
- 7. The material, design, constructiea and wockrnanship comply with ASU(E Code, Section III-Clae Edition---9-2-L-,Addenda Date Winter 1972
,Case No.
PIe6tsura Containing or Pressut Rotiining Components Serial No.
Material Specification
- a. CastingL Identification Including Type or Grade ASTM-A351-72 Gr.
CF8M Body N90135-34-0028 ASME-SA351 Gr.
CF8M ASTM-A216-70 Gr.
WCB Bonnet HN0449-31-0010 ASME-SA216 Gr.
WCB
- b. Bar Stock and Forglgs Soppot Ends Nozzle Disc Insert Spring Washero A~dios ing Bolt Spindle N90137-40-0098 N90448-33-0069 Ng~b34 -421--t)L35 gO~tom N88634-42-019a NS8 6 15-4 ZzDLr67 N88669-4Q-0101 AqfP-qA&7Q ASTM-A479-71 Type 316 ASME-SA193 rr. B6 ASTM-A193-70 Gr.
B6 ASNE-SAI93 (rT. R6 ASTM-A193-73 Gr.
B6 AqMP-qAII qC-Rr
kRemarks:
Report corrected to add the date to the Certificate of Shop Inspection after verification to the component route sheet.
Orig-inal--ANI Signeee is no longer in the employment of Factory Mutual.
/&~/~/
/?9/i9'
/J
~XV13-5fr11-/
A,-7U0
/1-1
/,g-4 C__
_/
ý,
Crosb
ý uality Assurance Date Factory Mutual Af Date Serial No. or Identification Material Specification Including Type or Grade ASTM-A313 Type 316
- c. Spring NX~-2605-0060
- d. Bolting
- e. Other Parts such as Pilot Components ASTM-A453-70 Gr. 660
'onnet Stud 89289 ASME-SA453 Gr, 660 ASTM-AI93-71 Gr. B6 Bonnet Stud Nut 89293 AS4FP-SA193 Cr-R6 We certify that the statements made in this report are corect.
D"ate
!i-!
9gned C
srobv Valve & Ga.ge Co, Manufacturer QA Manager Certificate of Authorization No.
926 expires October 28, 1977 CERTIFICATE OF SHOP INSPECTION.
I. the undersigned, holding a valid commission issued by thp National Board of Boiler and Pressure Vessel Inspectors and the State or Province of M.aSS and employed by Facto2ry Mutual Svstems*,
Nor!.ocod, Masls.
have inspected the equipment described in this Data Report on
- eEE1-
/"-
!9.Z7-and state that to the best of my knowledge and bejief. the Manufacturer has constructed this equip-ment in accordance with the applica.ble Subsections of ASME Section Ill.
By signing this certificate, neither the Inspector nor his employer makes any warranty. ex-pressed or implied. concerning the equipment described in this Data Report.Furthermore. neither the Inspector nor his employer shall he liable in any manner for any personal injury or property damage or a lossj f any kind arising from or connected with this inspection.
/"
Date p6
ý`nspe~cttir./
Commissions
,National Brard, Sia:e. province,:nd "ro.)
- Ark/right-Boston Manufacturers Mutual Insuraince Company -
Mutual Bocer & Machinery Divisicn.
FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3306 RTL#A4.41A
- 1. Owner F.E.N.O.C Date 12/16/10 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1
of 1
(ADDRESS)
Unit No.
1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shippinqport, PA 15077 WO# 200371901 (ADDRESS)
Repair/Replacement Organization P.O. No., Job No., etc.
- 3. Work Performed By BVPS - Construction Type Code Symbol Stamp N/A (NAME)
Shippincqport, PA 15077 Authorization No.
N/A (ADDRESS)
Expiration Date
- 4. Identification of System Reactor Coolant (Class 1)
- 5. (a) Applicable Construction Code ANSI B31.1 19 67 Edition S'71 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E - 2003A (c) Applicable Section Xl Code Case(s): None
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed es or No)
Snubber Bergen Paterson 1858 N/A BV-RC-HC-10C Removed No Snubber Bergen Paterson 1842 N/A BV-RC-HC-10C Installed No
- 7. Description of Work Replaced snubber with a spare because of seal leakaqe
- 8. Tests Conducted:
Hydrostatic* L]
Pneumatic* L]
Nominal Operating Pressure L]
Exempt 0 Other n]
Pressure psi Test Temp.
oF
- Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3306 RTL#A4.41A
- 9. Remarks The snubber was replaced with a used spare rotated from stock. but the removed but the removed Applicable Manufacturer's Data Reports to be attached snubber was not tested (IWA-4132(h)).
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed J.Sciulli Nuclear Specialist Date December 1 7th, 2010 Owneror Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period
.. 7-
/. - 0?
to
//'- q -K 0
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
L~-/-
~
Commissions W/d 7 '-V X
/Vrd
/"fL-,3 t9 InspectoZ,,OSignature National Board, State, Province, and Endorsements Date
/,L - '17-
, 20 /0 Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3309 RTL #A4.414A
- 1. Owner F.E.N.O.C Date November 18, 2010 (NAME) 76 South Main Street-Akron, OH 44308 Sheet 1
of 1
(ADDRESS)
Unit No.
1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME).
Shippincport, PA 15077 Work Order #200432540 (ADDRESS)
Repair/Replacement Organization P.O. No., Job No., etc.
- 3. Work Performed By BVPS Valve Team Type Code Symbol Stamp N/A (NAME)
Shippincport, PA 15077 Authorization No.
N/A (ADDRESS)
Expiration Date N/A
- 4. Identification of System Quench Spray (Q2)
- 5. (a) Applicable Construction Code ANSI B16.5 1968 Edition, -
Addenda,-- Code Case (b)
Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section Xl Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Check Valve Schutte &
700480 N/A 1QS-4 1976 Corrected No Koerting Disd Flowserve N/A N/A N/A 2001 Installed No
- 7. Description of Work Replaced valve disc.
- 8. Tests Condtcted:
Hydrostatic* L]
Pneumatic* E]
Nominal Operating Pressure LI Exempt H Other L]
Pressure psi Test Temp.
_F Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3309 RTL #A4.414A
- 9. Remarks No Code Data Report available.
Applicable Manufacturef's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed T. White
/1 Staff Specialist Date November 24, 20 10 Owner or Own, 's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period 3-- d_- (- 0 7 to
//-
e/- / 0
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
spe*_s SgaueCommissions gf J--
InspecK/s Signature National Board, State, Province, and Endorsements Date
/,_/-__
_, 20 /0 Page 2 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3312 RTL #A4.414A
- 1. Owner F.E.N.O.C I Date 10/29/2010 (NAME) 76 South Main Street-Akron, OH 44308 (ADDRESS)
Sheet 1
of 2
Unit No.
1
- 2. Plant Beaver Valley Power Station (BVPS)
(NAME)
Shiooinaoort PA 15077 (ADDRESS)
- 3. Work Performed By BVPS Maintenance (NAME)
Shippincjport, PA 15077 (ADDRESS)
Work Order #200372724 Repair/Replacement Organization P.O. No., Job No., etc.
Type Code Symbol Stamp Authorization No.
Expiration Date N/A N/A N/A
- 4. Identification of System Quench Spray (Q3)
- 5. (a) Applicable Construction Code Section III 19 89 Edition, 1991 Addenda, __Code Case (b)
Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c)
Applicable Section Xl Code Case(s): N/A
- 6. Identification of Components Corrected, National
- Removed, ASME Name of Name of Manufacturer Board Other Year or Code Stamped Component Manufacturer Serial No.
No.
Identification Built Installed (Yes or No)
Relief Valve Farris NC-1506-A15 N/A RV-1QS-100B 2004 Corrected Yes Engineering
- 7. Description of Work Replaced valve inlet studs/nuts.
- 8. Tests Conducted:
Hydrostatic* El Pneumatic* E]
Nominal Operating Pressure El Exempt M Other F]
Pressure psi Test Temp. ---
oF Record test pressure and temperature Page 1 of 2
FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI NOP-CC-5703-02 Rev. 00 Report Number 3312 RTL #A4.414A
- 9. Remarks Code Data Report attached. Previous NIS-2 Data Report No. 1556. Replacement Y2" Studs: PO Applicable Manufacturer's Data Reports to be attached 45301001 / Ht. #2Y31: Nuts: PO 45321040 / Ht. #3T97, PO 45318842 / Ht. #3T44, PO 45297319 / 2U09.
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No.
N/A Expiration Date N/A Signed T. White k týý Staff Specialist Date November24, 20 10 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period
(-
0 9 to
//-
and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
-j
?Commissions CIA
,r
,J-'J d-3 V
Inspe Signature National Board, State, Province, and Endorsements Date
/,-
1 20 /0 Page 2 of 2
FORM NV-1 CERTIFICATE HOLDERS' DATA REPORT FOR PRESSURE OR VACUUM RELIEF VALVES*
As Required by the Provisions of the ASME Code,Section III Division 1 Pg. 1 f Farris Engineering Division of Curtiss-Wright Flow Control Corporation 15 Shaver Street Brantford, Ontario Canada N3T 5T3
.. Manufactured and certified by.
First Energy Beaver Valley Main Ro (name and address o0 NV Certtifcate Holder) ute Shippingport PA USA 15077
- 2. Manufactured for (name and address of Purchaser)
- 3. Location of installation BEAVER VALLEY POWER STATION (name and address)
- 4. Valve 26GB10L120/S4/SP Orifice size G
Nom. inlet size 1.5 Outlet size 2.5 (model no., series no.)
(in.)
(in.)
un.)
- 5. ASME Code,Section III, Division 1 1989 1991 3
N/A (edition)
(addenda data)
(class)
(Code Case no.)
- 6. Type Spring 150 70 F 225 at Min. 50
-F (spring, pilot or power operated)
(set pressure, psig)
(blowdown. psi)
Irated temp.)
(hydro. test., psig., inlet)
- 7. Identification NC-1506-A15 20046217 27531 REV -
N/A 2004 (Cert. Holder's serial no.)
(Mat'l Code)
(drawing no.)
(Na'l. Bd. no.)
(year built) 4
- 8. Control ring settings
- 9. Pressure retaining items:
Serial No. or Identification Mat'). Spec., Including Type or Grade Body Bonnet or Yoke Support Rods Nozzle Disk Spring Washers A,':;sting Screws I le Spring Bolting Other Items Hex Nuts
- 10. Relieving capacity 6-6083-CF4-1 SA351 GRADE CF8M SOLUTION ANNEALED CASTING J857-1 SA351 GRADE CF8M SOLUTION ANNEALED CASTING N/A N/A 0777744-1A-18 SA479 GRADE 316 SOLUTION ANNEALED BAR 9N236-L20-1--4 SA479 GRADE 316 SOLUTION ANNEALED BAR J9051-2-45 J9051-2-46 150504-1-26 150504-1-25 SA479 GRADE 316 SOLUTION ANNEALED BAR Tensile Strength (KSI) 70 70 75 75 75 75 75 171 140 75 80 SA479 GRADE 316 SOLUTION ANNEALED BAR SA479 GRADE 316 SOLUTION ANNEALED BAR DHT3 A 313 Type 316 STAINLESS STEEL SPRING 723541 SA564 GRADE 630 COND. H1100 FINISHED PART DISC HOLDER: 9P101-L20-1-11 SA479 GRADE 316 SOLUTION ANNEALED BAR SA194 GRADE 8M FINISHED PART 30257 160 USGPM WATER 10%
(15) overpressure as certified by the National Board (steam or fluid, lb/hr)
(psi) 7/28/2003 (date)
- 11. Remarks:
CERTIFICATION OF DESIGN Design Specification certified by P.E. State Reg. no.
Design Report certified by Jang Sun Ahn P.E. State Ontario Reg. no.
100052462 CERTIFICATE OF COMPUANCE We certify that the statements made in this report are correct and that this valve conforms to the rules for construction of the ASME Code, Section Ill, Division 1.
11,Dvso
.N-3061 November 2, 2004 NV Certificate of Authorization No.
Expires Date f
N a me Farris Engineering, Division Of Curtiss-Wright Flow Control Corporation
(
/
I (NV Certificate Holder)
Sauthorization representative) olemental information in the form of lists, sketches, or drawings may be used provided (1) size is 81/2 x 11, (2) information in items 1 through 4 on this Data
. is included on each sheet, (3) each sheet is-numbered and the number of sheets is recorded at the top of this form.
(7/98)
This form (E000421 may be obtained from the Order Dept., ASME, 22 Law Drive, Box 2300, Fairfield, NJ 07007-2300.
I EI0llilln 21111 IIlll E00042
FORM NV-i (Back -
Pg. 2. of
- - I NC-1506-A15 Certificate Holder's Serial No.
CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the.State or Province of ONTARIO and employed by TECHNICAL STANDARDS AND SAFETY AUTHORITY (TSSA) of ONTARIO have inspected the valve described in this Data Report on 7'
60 and state that to the best of my knowledge and belief, the Certificate Holder has constructed this valve in accordance with the ASME Code,Section III, Division 1.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the component described in this Data Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Date Si nd lAuthc*/d Nuclear inspector '"
INat'I. Bd. lind. endorsements) and state or prov. and no.)