Questionable Certification of Class IE Components| ML031150283 |
| Person / Time |
|---|
| Site: |
Beaver Valley, Millstone, Hatch, Monticello, Calvert Cliffs, Dresden, Davis Besse, Peach Bottom, Browns Ferry, Salem, Oconee, Mcguire, Nine Mile Point, Palisades, Palo Verde, Perry, Indian Point, Fermi, Kewaunee, Catawba, Harris, Wolf Creek, Saint Lucie, Point Beach, Oyster Creek, Watts Bar, Hope Creek, Grand Gulf, Cooper, Sequoyah, Byron, Pilgrim, Arkansas Nuclear, Braidwood, Susquehanna, Summer, Prairie Island, Columbia, Seabrook, Brunswick, Surry, Limerick, North Anna, Turkey Point, River Bend, Vermont Yankee, Crystal River, Haddam Neck, Ginna, Diablo Canyon, Callaway, Vogtle, Waterford, Duane Arnold, Farley, Robinson, Clinton, South Texas, San Onofre, Cook, Comanche Peak, Yankee Rowe, Maine Yankee, Quad Cities, Humboldt Bay, La Crosse, Big Rock Point, Rancho Seco, Zion, Midland, Bellefonte, Fort Calhoun, FitzPatrick, McGuire, LaSalle, 05000000, Zimmer, Fort Saint Vrain, Shoreham, Satsop, Trojan, Atlantic Nuclear Power Plant, Crane |
|---|
| Issue date: |
04/26/1988 |
|---|
| From: |
Rossi C Office of Nuclear Reactor Regulation |
|---|
| To: |
|
|---|
| References |
|---|
| IN-88-019, NUDOCS 8804220217 |
| Download: ML031150283 (5) |
|
Similar Documents at Beaver Valley, Millstone, Hatch, Monticello, Calvert Cliffs, Dresden, Davis Besse, Peach Bottom, Browns Ferry, Salem, Oconee, Mcguire, Nine Mile Point, Palisades, Palo Verde, Perry, Indian Point, Fermi, Kewaunee, Catawba, Harris, Wolf Creek, Saint Lucie, Point Beach, Oyster Creek, Watts Bar, Hope Creek, Grand Gulf, Cooper, Sequoyah, Byron, Pilgrim, Arkansas Nuclear, Braidwood, Susquehanna, Summer, Prairie Island, Columbia, Seabrook, Brunswick, Surry, Limerick, North Anna, Turkey Point, River Bend, Vermont Yankee, Crystal River, Haddam Neck, Ginna, Diablo Canyon, Callaway, Vogtle, Waterford, Duane Arnold, Farley, Robinson, Clinton, South Texas, San Onofre, Cook, Comanche Peak, Yankee Rowe, Maine Yankee, Quad Cities, Humboldt Bay, La Crosse, Big Rock Point, Rancho Seco, Zion, Midland, Bellefonte, Fort Calhoun, FitzPatrick, McGuire, LaSalle, 05000000, Zimmer, Fort Saint Vrain, Shoreham, Satsop, Trojan, Atlantic Nuclear Power Plant, Crane |
|---|
Category:NRC Information Notice
[Table view]The following query condition could not be considered due to this wiki's restrictions on query size or depth: <code> [[:Beaver Valley]] OR [[:Millstone]] OR [[:Hatch]] OR [[:Monticello]] OR [[:Calvert Cliffs]] OR [[:Dresden]] OR [[:Davis Besse]] OR [[:Peach Bottom]] OR [[:Browns Ferry]] OR [[:Salem]] OR [[:Oconee]] OR [[:Mcguire]] OR [[:Nine Mile Point]] OR [[:Palisades]] OR [[:Palo Verde]] OR [[:Perry]] OR [[:Indian Point]] OR [[:Fermi]] OR [[:Kewaunee]] OR [[:Catawba]] OR [[:Harris]] OR [[:Wolf Creek]] OR [[:Saint Lucie]] OR [[:Point Beach]] OR [[:Oyster Creek]] OR [[:Watts Bar]] OR [[:Hope Creek]] OR [[:Grand Gulf]] OR [[:Cooper]] OR [[:Sequoyah]] OR [[:Byron]] OR [[:Pilgrim]] OR [[:Arkansas Nuclear]] OR [[:Braidwood]] OR [[:Susquehanna]] OR [[:Summer]] OR [[:Prairie Island]] OR [[:Columbia]] OR [[:Seabrook]] OR [[:Brunswick]] OR [[:Surry]] OR [[:Limerick]] OR [[:North Anna]] OR [[:Turkey Point]] OR [[:River Bend]] OR [[:Vermont Yankee]] OR [[:Crystal River]] OR [[:Haddam Neck]] OR [[:Ginna]] OR [[:Diablo Canyon]] OR [[:Callaway]] OR [[:Vogtle]] OR [[:Waterford]] OR [[:Duane Arnold]] OR [[:Farley]] OR [[:Robinson]] OR [[:Clinton]] OR [[:South Texas]] OR [[:San Onofre]] OR [[:Cook]] OR [[:Comanche Peak]] OR [[:Yankee Rowe]] OR [[:Maine Yankee]] OR [[:Quad Cities]] OR [[:Humboldt Bay]] OR [[:La Crosse]] OR [[:Big Rock Point]] OR [[:Rancho Seco]] OR [[:Zion]] OR [[:Midland]] OR [[:Bellefonte]] OR [[:Fort Calhoun]] OR [[:FitzPatrick]] OR [[:McGuire]] OR [[:LaSalle]] OR [[:05000000]] OR [[:Zimmer]] OR [[:Fort Saint Vrain]] OR [[:Shoreham]] OR [[:Satsop]] OR [[:Trojan]] OR [[:Atlantic Nuclear Power Plant]] OR [[:Crane]] </code>. |
UNITED STATES
NUCLEAR REGULATORY COMMISSION
OFFICE OF NUCLEAR REACTOR REGULATION
WASHINGTON, D.C.
?0555
April 26, 1988
NRC INFORMATION NOTICE NO. 88-19: QUESTIONAELE CERTIFICATION OF
CLASS lE COMPONENTS
Addressees
All holders of operating licenses or construction permits for nuclear power
reactors.
Purpose
This information notice Is being provided to alert addressees to a possible
problem with the certification of Class lE components furnished by Planned
Maintenance Systems (PMS) of Mt. Vernon, Illinois. It is expected that
recipients will review the information for applicability to their facilities
and consider actions, as appropriate, to avoid similar problems. However, suggestions contained in this information notice do not constitute NRC
requirements; therefore, no specific action or written response is required.
Description of Circumstances
On April 1, 1988, Wolf Creek Nuclear Operating Corporation (WCNOC) submitted
a written 10 CFR Part 21 Notification to NRC Region IV concerning 60 Class lE
fuses that had been procured from PMS. One of the requirements of the purchase
order (PO) issued to PMS was that the PO Items were to be supplied in accord- ance with the requirements of a specific fuse qualification specification for
Class 1E equipment.
This specification contained detailed requirements including
materials, environmental qualification, seismic qualification, and inspection/
test requirements. The PMS Certificate of Compliance supplied with the order
certified that all of the procurement document requirements had been met and
no deviations from the requirements had been identified.
The fuses were placed on hold by WCNOC because a required Quality Department
surveillance had not been performed. A subsequent WCNOC surveillance revealed
that the records in PMS's possession did not support the statement on the PMS
Certificate of Compliance that all PO requirements had been met. Qualification
specification requirements were not covered by PMS quality assurance records
with respect to information on environmental qualification, radiation levels, and seismic qualification. In addition, it could not be established that a
required continuity/resistance check of each fuse had been performed before
the fuses were shipped.
IN 88-19
April 26, 1988
Page ? of 2 Discussion:
The WCNOC 10 CFR Part ?1 notification has brought into question the validity
of the Certificate of Compliance issued by PMS for Class IE fuses that they
supplied. Accordingly, licensees may wish to review Class IF component pro- curements from this vendor to ensure that appropriate bases exist for the use
of the components.
No specific action or written response is required by this Information notice.
If you have any questions about this matter, please contact the technical
contact listed below or the Regional Administrator of the appropriate regional
office.
Charles E. Rossi, Director
Division of Operational Events Assessment
Office of Nuclear Reactor Regulation
Technical Contact:
Joseph J. Petrosino, NRR
(301) 492-0979 Attachment-,--ist of-Recently Issued-NRC Information Notices
Attachment
IN 88-19
April 26, 1988 LIST OF RECENTLY ISSUED
NPC INFORMATION NOTICES
Information
Date of
Notice No.
Subject
Issuance
Issued to
88-18
88-17
88-16
88-15
Malfunction of Lockbox on
Radiography Device
Summary of Responses to NPC
Bulletin 87-01, "Thinning of
Pipe Walls in Nuclear Power
Plants"
Identifying Waste Generators
in Shipments of Low-Level
Waste to Land Disposal
Facilities
Availability of U.S. Food
and Drug Administration
(FDA)-Approved Potassium
Iodide for Use in Emergencies
Involving Radioactive Iodine
Potential Problems with
Electrical Relays
Water Hammer and Possible
Piping Damage Caused by
Misapplication of Kerotest
Packless Metal Diaphragm
Globe Valves
Overgreasing of Electric
Motor Bearings
4/25/88
4/22/88
4/22/88
4/18/88
4/18/88
4/18/88
4/12/88
All NRC licensees
authorized to
manufacture, distribute, and/or operate radio- graphic exposure
devices.
All holders of OLs
or CPs for nuclear
power reactors.
Radioactive waste
collection and
service company
licensees handling
prepackaged waste, and licensees operating
low-level waste
disposal facilities.
Medical, Academic, and Commercial
licensees who possess
radioactive iodine.
All holders of OLs
or CPs for nuclear
power reactors.
All holders of OLs
or CPs for nuclear
power reactors.
All holders of OLs
or CPs for nuclear
power reactors.
88-14
88-13
88-12 OL = Operating License
CP = Construction Permit
IN 88-19 April 26, 1988 Discussion:
The WCNOC 10 CFR Part 21 notification has brought into question the validity
of the Certificate of Compliance Issued by PMS for Class 1E fuses that they
supplied. Accordingly, licensees may wish to review Class 1E component pro- curements from this vendor to ensure that appropriate bases exist for the use
of the components.
No specific action or written response is required by this information notice.
If you have any questions about this matter, please contact the technical
contact listed below or the Regional Administrator of the appropriate regional
office.
Charles E. Rossi, Director
Division of Operational Events Assessment
Office of Nuclear Reactor Regulation
Technical Contact:
Joseph J. Petrosino, NRR
(301) 492-0979 Attachment:
List of Recently Issued NRC Information Notices
-
Transmitted by
dated
Z::~z /e4 z151;
,1
'X
^w RkFX*C/OGCB: DOEA: NRR
C
ICHBerlinger
04/22/88
- OGCB:DOEA:NRR *VIB:DRIS:NRR
AC/VIB:DRIS:NRR
JERamsey
JJPetrosino
JStone
04/22/88
04/22/88
04/22/88
TechEd
04/22/88
BKGrimes
04/22/88
DDriskill
04/22/88
JGPartlow
04/22/88
IN 88-XX
April xx, 1988 Discussion:
The WCNOC 10 CFR Part 21 notification has brought into question the validity of
the Certificate of Compliance issued by PMS for Class 1E fuses that they
supplied.
Accordingly, licensees may wish to review Class 1E component pro- curements from this vendor to ensure that appropriate bases exist for the use
of the components.
No specific action or written response is required by this information notice.
If you have any questions about this matter, please contact the technical
contact listed below or the Regional Administrator of the appropriate regional
office.
Charles E. Rossi, Director
Division of Operational Events Assessment
Office of Nuclear Reactor Regulation
Technical Contact:
Joseph J. Petrosino, NRR
(301) 492-0979 Attachment:
Transmitted t
List of Recently Issued NRC Information Notices
by
dated
OG
- NRR
041-./88
CONCURRENCES
D/DOEA:NRR
CERossi
04/ /88 VIB:DRJM RR
JJPetrM
'no
04=/88 C/O OB
- NRR
CHBerlinger
04/-r?88 AC/V
JStone
04/%7/88
TechEd
04/23380j'
I/kI/RIV <^ow
DDriskill
04jRW/88 D/DRIS:NRFs i
JGPartlow
04$. /88
" Per
gV/3/ ray
/-1,Fex-"
W11/S2/ee
,S
,
-OJMcn= A"ztc
AI/V'd~
)
/
2
31g
|
|---|
|
| list | - Information Notice 1988-01, Safety Injection Pipe Failure (27 January 1988, Topic: Unidentified leak, Water hammer)
- Information Notice 1988-03, Cracks in Shroud Support Access Hole Cover Welds (2 February 1988, Topic: Intergranular Stress Corrosion Cracking, Stolen)
- Information Notice 1988-04, Inadequate Qualification and Documentation of Fire Barrier Penetration Seals (5 February 1988, Topic: Fire Barrier, Fire Watch, Stolen)
- Information Notice 1988-05, Fire in Annunciator Control Cabinets (12 February 1988, Topic: Stolen)
- Information Notice 1988-06, Foreign Objects in Steam Generators (29 February 1988, Topic: Eddy Current Testing, Stolen)
- Information Notice 1988-07, Inadvertent Transfer of Licensed Material to Uncontrolled Locations (7 March 1988, Topic: Stolen, Overexposure)
- Information Notice 1988-08, Chemical Reactions with Radioactive Waste Solification Agents (14 March 1988, Topic: Process Control Program, Stolen)
- Information Notice 1988-09, Reduced Reliability of Steam-Driven Auxiliary Feedwater Pumps Caused by Instability of Woodward PG-PL Type Governors (18 March 1988, Topic: Overspeed trip, Overspeed)
- Information Notice 1988-10, Memo of Understanding Between NRC and OSHA Relating to NRC-Licensed Facilities (53 FR 43950, October 31, 1988) (23 December 1988, Topic: Fatality, Overexposure)
- Information Notice 1988-10, Memo of Understanding Between NRC and OSHA Relating to NRC-Licensed Facilities (53 Fr 43950, October 31, 1988) (23 December 1988, Topic: Fatality, Overexposure)
- Information Notice 1988-10, Memorandum of Understanding Between NRC and Osha Relating to NRC-Licensed Facilities (53 Fr 43950, October 31, 1988. (23 December 1988, Topic: Fatality, Overexposure)
- Information Notice 1988-11, Potential Loss of Motor Control Center And/Or Switchboard Function Due to Faulty Tie Bolts (7 April 1988)
- Information Notice 1988-12, Overgreasing of Electric Motor Bearings (12 April 1988, Topic: Hardened grease)
- Information Notice 1988-13, Water Hammer & Possible Piping Damage Caused by Misapplication of Kerotest Packless Metal Diaphragm Globe Valves (18 April 1988, Topic: Water hammer)
- Information Notice 1988-14, Potential Problems with Electrical Relays (18 April 1988)
- Information Notice 1988-15, Availability of Us Food & Drug Administration (FDA) Approved Potassium Iodide for Use in Emergencies Involving Radioactive Iodine (18 April 1988, Topic: Water hammer, Potassium iodide)
- Information Notice 1988-15, Availability of Us Food & Drug Administration (Fda) Approved Potassium Iodide for Use in Emergencies Involving Radioactive Iodine (18 April 1988, Topic: Potassium iodide)
- Information Notice 1988-16, Identify Waste Generators in Shipments of Low-Level Waste to Land Disposal Facilities (22 April 1988)
- Information Notice 1988-17, Summary of Responses to NRC Bulletin 87-01, Thinning of Pipe Walls in Nuclear Power Plants (22 April 1988, Topic: Safe Shutdown, Weld Overlay, Feedwater Heater, Through-Wall Leak, Water hammer)
- Information Notice 1988-18, Malfunction of Lockbox on Radiography Device (25 April 1988, Topic: Overexposure)
- Information Notice 1988-19, Questionable Certification of Class Ie Components (26 April 1988, Topic: Water hammer)
- Information Notice 1988-19, Questionable Certification of Class IE Components (26 April 1988)
- Information Notice 1988-20, Unauthorized Individuals Manipulating Controls and Performing Control Room Activities (5 May 1988)
- Information Notice 1988-21, Inadvertent Criticality Events at Oskarshamn and at U.S. Nuclear Power Plants (9 May 1988, Topic: Shutdown Margin)
- Information Notice 1988-22, Disposal of Sludge from Onsite Sewage Treatment Facilities at Nuclear Power Stations (12 May 1988, Topic: Sewage Treatment Plant)
- Information Notice 1988-23, Potential for Gas Binding of High-Pressure Safety Injection Pumps During a Loss-Of-Coolant Accident (12 May 1988)
- Information Notice 1988-24, Failures of Air-Operated Valves Affecting Safety-Related Systems (13 May 1988)
- Information Notice 1988-25, Minimum Edge Distance for Expansion Anchor Bolts (16 May 1988, Topic: Earthquake)
- Information Notice 1988-26, Falsified Pre-Employment Screening Records (16 May 1988)
- Information Notice 1988-27, Deficient Electrical Terminations Identified in Safety-Related Components (18 May 1988)
- Information Notice 1988-28, Potential for Loss of Post-Loca Recirculation Capability Due to Insulation Debris Blockage (19 May 1988, Topic: Coatings)
- Information Notice 1988-29, Deficiencies in Primary Containment Low-Voltage Electrical Penetration Assemblies (24 May 1988)
- Information Notice 1988-30, Target Rock Two-State SRV Setpoint Drift Update (25 May 1988)
- Information Notice 1988-31, Steam Generator Tube Rupture Analysis Deficiency (25 May 1988, Topic: Loss of Offsite Power)
- Information Notice 1988-32, Prompt Reporting to NRC of Significant Incidents Involving Radioactive Material (25 May 1988, Topic: Overexposure)
- Information Notice 1988-33, Recent Problems Involving the Model Spec 2-T Radiographic Exposure Device (27 May 1988, Topic: Depleted uranium)
- Information Notice 1988-34, Nuclear Material Control & Accountability of Non-Fuel Special Nuclear Material at Power Reactors (31 May 1988)
- Information Notice 1988-36, Possible Sudden Loss of RCS Inventory During Low Coolant Level Operation (8 June 1988)
- Information Notice 1988-37, Flow Blockage of Cooling Water to Safety System Components (14 June 1988, Topic: Ultimate heat sink)
- Information Notice 1988-38, Failure of Undervoltage Trip Attachment of General Electric Circuit Breakers (15 June 1988)
- Information Notice 1988-39, Loss of Recirculation Pumps with Power Oscillation Event (15 June 1988, Topic: Feedwater Heater)
- Information Notice 1988-40, Examiners Handbook for Developing Operator Licensing Examinations (22 June 1988)
- Information Notice 1988-41, Physical Protection Weaknesses Identified Through Regulatory Effectiveness Reviews (RERs) (22 June 1988)
- Information Notice 1988-41, Physical Protection Weaknesses Identified Through Regulatory Effectiveness Reviews (Rers) (22 June 1988)
- Information Notice 1988-42, Circuit Breaker Failures Due to Loose Charging Spring Motor Mounting Bolts (23 June 1988, Topic: Locktite)
- Information Notice 1988-43, Solenoid Valve Problems (23 June 1988, Topic: Stroke time)
- Information Notice 1988-44, Mechanical Binding of Spring Release Device in Westinghouse Type DS-416 Circuit Breakers (24 June 1988)
- Information Notice 1988-45, Problems in Protective Relay & Circuit Breaker Coordination (7 July 1988, Topic: Safe Shutdown)
- Information Notice 1988-46, Licensee Report of Defective Refurbished Circuit Breakers (8 July 1988)
- Information Notice 1988-47, Slower-than-Expected Rod-drop Times (14 July 1988)
... further results |
|---|