December 5, 2005

SUBJECT:

OYSTER CREEK NUCLEAR GENERATING STATION - NRC TRIENNIAL FIRE PROTECTION INSPECTION REPORT 05000219/2005008

Dear Mr. Crane:

On November 4, 2005, the NRC completed a triennial fire protection team inspection at the Oyster Creek Nuclear Generating Station. The enclosed report documents the inspection results which were discussed at an exit meeting on November 4, 2005, with Mr. B. Swenson and other members of your staff.

The inspection examined activities conducted under your license as they relate to safety and compliance with the Commissions rules and regulations and with the conditions of your license.

The purpose of the inspection was to evaluate your post-fire safe shutdown capability and fire protection program. The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel.

Based on the results of this inspection, the NRC identified one finding of very low safety significance (Green) that was a violation of NRC requirements. However, because of the very low safety significance and because it is entered into your corrective action program, the NRC is treating this finding as a non-cited violation (NCV) consistent with Section VI.A.1 of the NRC Enforcement Policy. If you contest the NCV in this report, you should provide a response within 30 days of the date of this inspection report, with the basis for your denial, to the Nuclear Regulatory Commission, ATTN.: Document Control Desk, Washington, DC 20555-0001; with copies to the Regional Administrator Region I; the Director, Office of Enforcement, United States Nuclear Regulatory Commission, Washington, DC 20555-0001; and the NRC Resident Inspector at the Oyster Creek Nuclear Generating Station.

Mr. Christopher In accordance with 10 CFR 2.390 of the NRC's "Rules of Practice," a copy of this letter, its enclosure, and your response (if any) will be available electronically for public inspection in the NRC Public Document Room or from the Publicly Available Records (PARS) component of NRCs document system (ADAMS). ADAMS is accessible from the NRC Web site at http://www.nrc.gov/reading-rm/ADAMS.html (the Public Electronic Reading Room).

Sincerely,

/RA/

John F. Rogge, Chief Engineering Branch 3 Division of Reactor Safety Docket No. 50-219 License No. DPR-16 Enclosure: NRC Inspection Report 05000219/2005008 cc w/encl:

Chief Operating Officer, AmerGen Site Vice President, Oyster Creek Nuclear Generating Station, AmerGen Plant Manager, Oyster Creek Generating Station, AmerGen Regulatory Assurance Manager, Oyster Creek, AmerGen Senior Vice President - Nuclear Services, AmerGen Vice President - Mid-Atlantic Operations, AmerGen Vice President - Operations Support, AmerGen Vice President - Licensing and Regulatory Affairs, AmerGen Director Licensing, AmerGen Manager Licensing - Oyster Creek, AmerGen Vice President, General Counsel and Secretary, AmerGen T. ONeill, Associate General Counsel, Exelon Generation Company J. Fewell, Assistant General Counsel, Exelon Nuclear Correspondence Control Desk, AmerGen J. Matthews, Esquire, Morgan, Lewis & Bockius LLP Mayor of Lacey Township K. Tosch, Interim Assistant Director of Radiation Programs, State of New Jersey Acting Manager, Bureau of Nuclear Engineering, NJ Dept. of Environmental Protection R. Shadis, New England Coalition Staff N. Cohen, Coordinator - Unplug Salem Campaign W. Costanzo, Technical Advisor - Jersey Shore Nuclear Watch E. Gbur, Chairwoman - Jersey Shore Nuclear Watch E. Zobian, Coordinator - Jersey Shore Anti Nuclear Alliance

Mr. Christopher

SUMMARY OF FINDINGS

IR 05000219/2005008; 10/17/2005 - 11/04/2005, Oyster Creek Nuclear Generating Station;

Triennial Fire Protection Team Inspection, Fire Protection.

The report covered a two-week triennial fire protection team inspection by five Region I specialist inspectors. One Green finding was identified. The significance of most findings is indicated by their color (Green, White, Yellow, Red) using Inspection Manual Chapter (IMC)0609, Significance Determination Process (SDP). Findings for which the SDP does not apply may be Green or be assigned a severity level after NRC management review. The NRCs program for overseeing the safe operation of commercial nuclear power reactors is described in NUREG-1649, Reactor Oversight Process, Revision 3, dated July 2000.

NRC-Identified Findings

Cornerstone: Mitigating Systems

Green.

The team identified a non-cited violation of 10 CFR Part 50, Appendix R,

Section III.G.2. AmerGen Energy included unapproved manual actions in their fire safe shutdown analyses and safe shutdown procedure to operate equipment necessary for achieving and maintaining hot shutdown. Several of these manual actions did not meet the requirements of Appendix R,Section III.G.2 and the NRC had not granted exemptions to allow these actions.

In accordance with the guidance provided in inspection procedure 71111.05T,

Fire Protection, (issue dated: 02/18/05) this finding is greater than minor. The finding is of very low safety significance because the manual actions are reasonable and are expected to meet the criteria outlined in of inspection procedure 71111.05T. (Section 4OA5.01).

Licensee-Identified Violations

None

REPORT DETAILS

Background This report presents the results of a triennial fire protection inspection conducted in accordance with NRC Inspection Procedure (IP) 71111.05T, Fire Protection. The objective of the inspection was to assess whether AmerGen Energy Company, LLC, has implemented an adequate fire protection program and that post-fire safe shutdown capabilities have been established and are being properly maintained at the Oyster Creek Nuclear Generating Station (OCNGS). Four plant areas that included the following fire zones (FZs) and fire areas (FAs),were selected for detailed review based on risk insights from the Oyster Creek Individual Plant Examination (IPE)/Individual Plant Examination of External Events (IPEEE):

C Fire Zone OB-FZ-5 C Fire Zone TB-FZ-11C C Fire Area TB-FA-3A C Fire Area TB-FA-3B The inspection team evaluated the AmerGen Energys fire protection program (FPP) against applicable requirements which include plant Technical Specifications, Operating License Condition 2.C.3, NRC Safety Evaluations, 10 CFR 50.48 and 10 CFR 50 Appendix R. The team also reviewed related documents that include the Updated Final Safety Analysis Report Section 9.5.1, the Fire Hazards Analysis (FHA) and the Post-Fire Safe Shutdown

Analysis.

Specific documents reviewed by the team are listed in the attachment.

REACTOR SAFETY

Cornerstones: Initiating Events, Mitigating Systems

==1R05 Fire Protection

==

.01 Post-Fire Safe Shutdown From Outside Main Control Room (Alternative Shutdown) and

Normal Shutdown

a. Inspection Scope

Methodology The team reviewed the safe shutdown analysis, operating procedures, piping and instrumentation drawings (P&IDs), electrical drawings, the updated final safety analysis report (UFSAR) and other supporting documents to verify that hot and cold shutdown could be achieved and maintained from outside the control room for fires that rely on shutdown from outside the control room. This review included verification that shutdown from outside the control room could be performed both with and without the availability of offsite power. Plant walkdowns were also performed to verify that the plant configuration was consistent with that described in the post-fire safe shutdown and fire hazards analyses. These inspection activities focused on ensuring the adequacy of systems selected for reactivity control, reactor coolant makeup, reactor decay heat removal, process monitoring instrumentation and support systems functions. The team verified that the systems and components credited for use during this shutdown method would remain free from fire damage. The team verified that the transfer of control from the control room to the alternative shutdown location(s) would not be affected by fire-induced circuit faults (e.g., by the provision of separate fuses and power supplies for alternative shutdown control circuits).

Similarly, for fire areas that utilize shutdown from the control room, the team also verified that the shutdown methodology properly identified the components and systems necessary to achieve and maintain safe shutdown conditions.

Operational Implementation The team verified that the training program for licensed and non-licensed operators included alternative shutdown capability. The team also verified that personnel required for safe shutdown using the normal or alternative shutdown systems and procedures are trained and available onsite at all times, and exclusive of those assigned as fire brigade members.

The team reviewed the adequacy of procedures utilized for post-fire shutdown and performed an independent walk through of procedure steps to ensure the implementation and human factors adequacy of the procedures. The team also verified that the operators could be reasonably expected to perform specific actions within the time required to maintain plant parameters within specified limits. Time critical actions which were verified included restoration of AC electrical power, establishing the remote shutdown and local shutdown panels, establishing reactor coolant makeup using the control rod drive and isolation condenser systems and establishing decay heat removal.

Specific procedures reviewed for alternative shutdown, including shutdown from outside the control room included the following:

C ABN-29, Plant Fires, Rev. 5 C

ABN-30, Control Room Evacuation, Rev. 4 C

346, Operation of The Remote and Local Shutdown Panels, Rev. 11 The team reviewed manual actions to ensure that they had been properly reviewed and approved and that the actions could be implemented in accordance with plant procedures in the time necessary to support the safe shutdown method for each fire area. The team also reviewed the periodic testing of the alternative shutdown transfer capability and instrumentation and control functions to ensure the tests are adequate to ensure the functionality of the alternative shutdown capability.

b. Findings

No findings of significance were identified.

.02 Protection of Safe Shutdown Capabilities

a. Inspection Scope

The team reviewed the fire hazards analysis, safe shutdown analyses and supporting drawings and documentation to verify that safe shutdown capabilities were properly protected. The team ensured that separation requirements of Section III.G of 10 CFR 50, Appendix R were maintained for the credited safe shutdown equipment and their supporting power, control and instrumentation cables. This review included an assessment of the adequacy of the selected systems for reactivity control, reactor coolant makeup, reactor heat removal, process monitoring, and associated support system functions.

The team reviewed AmerGen Energys procedures and programs for the control of ignition sources and transient combustibles to assess their effectiveness in preventing fires and in controlling combustible loading within limits established in the FHA. A sample of hot work and transient combustible control permits were also reviewed. The team performed plant walkdowns to verify that protective features were being properly maintained and administrative controls were being implemented.

The team also reviewed AmerGen Energys design control procedures to ensure that the process included appropriate reviews and controls to assess plant changes for any potential adverse impact on the fire protection program and/or post-fire safe shutdown analysis and procedures.

b. Findings

No findings of significance were identified.

.03 Passive Fire Protection

a. Inspection Scope

The team walked down accessible portions of the selected fire areas to observe material condition and the adequacy of design of fire area boundaries (including walls, fire doors and fire dampers) to ensure they were appropriate for the fire hazards in the area.

Additionally, the team reviewed a fire wrap (Mecatiss) installation in fire zone TB-FZ-11C to ensure it met its installation and design requirements.

The team reviewed installation/repair and qualification records for a sample of penetration seals to ensure the fill material was of the appropriate fire rating and that the installation met the engineering design.

b. Findings

No findings of significance were identified.

.04 Active Fire Protection

a. Inspection Scope

The team reviewed the design, maintenance, testing and operation of the fire detection and suppression systems in the selected plant fire areas. This included verification that the manual and automatic detection and suppression systems were installed, tested and maintained in accordance with the National Fire Protection Association (NFPA) code of record, or as NRC approved deviations, and that they would control and/or extinguish fires associated with the hazards in the selected areas. A review of the design capability of suppression agent delivery systems was verified to meet the code requirements for the fire hazards involved. The team also performed a walkdown of accessible portions of the detection and suppressions systems in the selected areas as well as a walkdown of major system support equipment in other areas (e.g., fire protection pumps, Halon and/or Carbon Dioxide (CO2) storage tanks and supply system) and assess the material condition of the systems and components.

The team reviewed electric and diesel fire pump flow and pressure tests to ensure that the pumps were meeting their design requirements. The team also reviewed the fire main loop flow tests to ensure that the flow distribution circuits were able to meet the design requirements.

The team also assessed the fire brigade capabilities by reviewing training and qualification records, and drill critique records. The team also reviewed pre-fire plans and smoke removal plans for the selected fire areas to determine if appropriate information was provided to fire brigade members and plant operators to identify safe shutdown equipment and instrumentation, and to facilitate suppression of a fire that could impact post-fire safe shutdown. In addition, the team inspected the fire brigades protective ensembles, self-contained breathing apparatus (SCBA), and various fire brigade equipment (including smoke removal equipment) to determine operational readiness for fire fighting.

b. Findings

No findings of significance were identified.

.05 Protection From Damage From Fire Suppression Activities

a. Inspection Scope

The team performed document reviews and plant walkdowns to verify that redundant trains of systems required for hot shutdown are not subject to damage from fire suppression activities or from the rupture or inadvertent operation of fire suppression systems. Specifically, the team verified that:

C A fire in one of the selected fire areas would not directly, through production of smoke, heat or hot gases, cause activation of suppression systems that could potentially damage all redundant trains.

C A fire in one of the selected fire areas (or the inadvertent actuation or rupture of a fire suppression system) would not directly cause damage to all redundant trains (e.g., sprinkler caused flooding of other than the locally affected train).

C Adequate drainage is provided in areas protected by water suppression systems.

b. Findings

No findings of significance were identified.

.06 Alternative Shutdown Capability

a. Inspection Scope

Alternative shutdown capability for the areas selected for inspection utilizes shutdown from outside the control room and is discussed in Section 1R05.01 of this report.

.07 Circuit Analyses

a. Inspection Scope

The team verified that the licensee performed a post-fire safe shutdown analysis for the selected fire areas and that the analysis appropriately identified the structures, systems and components important to achieving and maintaining post-fire safe shutdown.

Additionally, the team verified that AmerGen Energys analysis ensured that necessary electrical circuits were properly protected and that circuits that could adversely impact safe shutdown due to hot shorts, shorts to ground or other failures were identified, evaluated and dispositioned to ensure spurious actuations would not prevent safe shutdown.

The teams review considered fire and cable attributes, potential undesirable consequences and common power supply/bus concerns. Specific items included the credibility of the fire threat, cable insulation attributes, cable failure modes, multiple spurious actuations, actuations resulting in flow diversion or loss of coolant events.

The team also reviewed cable raceway drawings and routing lists for a sample of components required for post-fire safe shutdown to verify that cables were routed as described in the cable routing matrices.

Cable failure modes were reviewed for the following components:

C P-15-1B, Control Rod Drive Pump B C

V-14-32, Steam Line Valve - Train B (AC)

C V-14-33, Steam Line Valve - Train B (DC)

C V-14-35, Condensate Valve - Train B (DC)

C V-14-37, Condensate Valve - Train B (AC)

C LI-211-994 (ALT), Isolation Condenser B Shell Water Level C

LI-622-1028 & LI-622-1029, Fuel Zone Level Instruments The team reviewed circuit breaker coordination studies to ensure equipment needed to conduct post-fire safe shutdown activities would not be impacted due to a lack of coordination. The team confirmed that coordination studies had addressed multiple faults due to fire. Additionally, the team reviewed a sample of circuit breaker maintenance and records to verify that circuit breakers for components required for post-fire safe shutdown were properly maintained in accordance with procedural requirements.

b. Findings

No findings of significance were identified.

.08 Communications

a. Inspection Scope

The team reviewed safe shutdown procedures, the post-fire safe shutdown analysis and associated documents to verify an adequate method of communications would be available to plant operators following a fire. During this review, the team considered the effects of ambient noise levels, clarity of reception, reliability and coverage patterns.

The team also inspected the designated emergency storage lockers to verify the availability of portable radios for the fire brigade. The team also verified that communications equipment such as repeaters, transmitters, etc. would not be affected by a fire.

b. Findings

No findings of significance were identified.

.09 Emergency Lighting

a. Inspection Scope

The team observed the placement and coverage area of eight-hour emergency lights, and in specified locations permanent essential lighting, throughout the selected fire areas to evaluate their adequacy for illuminating access and egress pathways and any equipment requiring local operation and/or instrumentation monitoring for post-fire safe shutdown. The team also verified that the battery power supplies were rated for at least an 8-hour capacity. Preventive maintenance procedures and various documents, including the vendor manuals and completed surveillance tests were reviewed to ensure adequate surveillance testing and periodic battery replacements were in place to ensure reliable operation of the eight-hour emergency lights and that the emergency lighting units were being maintained consistent with the manufacturers recommendations and accepted industry practices.

b. Findings

No findings of significance were identified.

.10 Cold Shutdown Repairs

a. Inspection Scope

The team verified that AmerGen Energy had dedicated repair procedures, equipment, and materials to accomplish repairs of components required for cold shutdown which might be damaged by the fire to ensure cold shutdown could be achieved within the time frames specified in their design and licensing bases. The team verified that the repair equipment, components, tools and materials (e.g., precut cables with prepared attachment lugs) were available and accessible onsite. Repair procedures reviewed included M0344, Appendix R Repair Wide Range Level Transmitter LT-IA12 Replacement, Rev. 1, and alternative level instruments to provide wide range level indication.

b. Findings

No findings of significance were identified.

.11 Compensatory Measures

a. Inspection Scope

The team verified that compensatory measures were in place for out-of-service, degraded or inoperable fire protection and post-fire safe shutdown equipment, systems, or features (e.g., detection and suppression systems and equipment, passive fire barriers, or pumps, valves or electrical devices providing safe shutdown functions or capabilities). The team also verified that the short term compensatory measures compensated for the degraded function or feature until appropriate corrective action could be taken and that AmerGen Energy was effective in returning the equipment to service in a reasonable period of time.

b. Findings

No findings of significance were identified.

OTHER ACTIVITIES

4OA2 Identification and Resolution of Problems

.01 Corrective Actions for Fire Protection Deficiencies

a. Inspection Scope

The team verified that AmerGen Energy was identifying fire protection and post-fire safe shutdown issues at an appropriate threshold and entering them into the corrective action program. The team also reviewed a sample of selected issues to verify that AmerGen Energy had taken or planned appropriate corrective actions.

The team reviewed corrective actions associated with Appendix R circuit breaker coordination for instrument panel IP-4 (IR 00387804), which included review of a 1985 Burns and Roe Co. report number 3731-030, Appendix R Evaluation for Coordination of Circuit Breakers Located at MCCs or Power Panels. The report identified circuit breaker coordination deficiencies associated with instrument panel IP-4. The team also reviewed modifications that were implemented to resolve the identified deficiencies as documented in GPU report SDD-OC-730A, Modification to Circuit Breaker Coordination for Compliance with Appendix R, 1985. The modifications included adding a 200 ampere fuse in series with a 70 ampere circuit breaker in IP-4. The circuit breaker and fuse were not properly coordinated with the IP-4 supply breakers (upstream breakers).

A fire in the appropriate fire zones could cause the IP-4 supply breakers to trip, thus causing IP-4 to de-energize. AmerGen Energy did not provide a basis as to why the 200 ampere fuse was installed during the modification process.

Additionally, the team reviewed a March 2002, Engineering Planning and Management (EPM), Inc., letter (EL6642002-006) which identified several circuit breaker coordination enhancements. The recommended enhancements did not include resolution of the IP-4 circuit breaker coordination issues.

On October 19, 2005, AmerGen Energy identified lack of coordination for breakers at instrument panel IP-4 and issued IR 00387804.

b. Findings

No findings of significance were identified.

The team determined that the corrective actions in 1985 were not effective in resolving circuit breaker coordination issues because the issue for instrument panel IP-4 remained after modifications were incorporated. The 2002 evaluation and recommended enhancements, was an opportunity for AmerGen Energy to identify and correct the IP-4 lack of circuit breaker coordination issue. When AmerGen Energy identified the issue in October 2005, they entered it into their corrective action program and implemented compensatory measures (hourly fire watch) pending resolution.

4OA5 Other Activities

.01 (Closed) Unresolved Item (URI)05000219/2002011-01, Spurious Operation of an

Electromatic Relief Valve (EMRV) and Manual Operation of Core Spray.

During a previous triennial fire protection inspection (NRC IR 05000319/2002005, January 24, 2003) the team identified an unresolved item concerning the acceptability of AmerGen Energys use of manual actions to remotely operate equipment necessary for achieving and maintaining hot shutdown, in lieu of providing protection to the cables associated with that equipment, as a method of complying with 10 CFR Part 50, Appendix R, Section III.G.2. Specifically, the team found that OCNGS relied on a manual operator actions, without an approved exemption from the regulations, to defeat the spurious operation of an EMRV for fire conditions in fire zone RB-FZ-1D.

During this inspection, the team reviewed CAP Number 02003-0035 and associated corrective actions, document number R0467050033.04, Oyster Creek Fire Risk Analysis Updated Project - Compartment Fire Scenario Development Report, Rev. 1, calculation C-1302-810-5450-004, Appendix R - Stuck Open EMRV, Rev. 1, document number C-1302-911-E120-005, Fire Area/zones RB-FZ-1D and RB-FZ-1G - Fire Safe Shutdown Analysis and various fire protection safety evaluation reports. The team determined that the likelihood of a fire in fire zone RB-FZ-1D to challenge EMRV operation is very small.

However, AmerGen Energys continued to implement unapproved manual actions to open the Core Spray System II, parallel path injection valve (V-20-21), in the unlikely event that a fire caused the spurious operation of an EMRV. The results of this review are described in the following paragraphs.

Introduction.

The team identified a Green non-cited violation (NCV) because AmerGen Energy used manual actions to operate equipment necessary for achieving and maintaining hot shutdown in lieu of providing protection for the cables associated with that equipment, as required by 10 CFR Part 50, Appendix R, Section III.G.2.

Description.

The team reviewed safety evaluation reports and did not identify any NRC reviews that approved manual actions for fire zone RB-FZ-1D (Appendix R, III.G.2. fire area). However, the post-fire safe shutdown analyses described the fire areas and the required manual actions to achieve and maintain safe shutdown. The actions included removing fuses, tripping or closing circuit breakers and manual operation of motor-operated valves (MOVs) from motor control centers.

During this inspection, the team reviewed post fire safe shutdown analyses for fire zones RB-FZ-1D and TB-FZ-11C. The team also reviewed the post-fire safe shutdown analyses for fire areas TB-FA-3A and TB-FA-3B. The team found that these analyses identified manual actions necessary for post fire safe shutdown and that these actions were incorporated into the post-fire safe shutdown procedure. These additional manual actions did not meet the requirements of Appendix R,Section III.G.2 and the NRC had not granted exemptions to allow these actions. The manual actions that were identified in the post-fire safe shutdown analyses but not approved by the NRC included removing fuses, tripping or closing circuit breakers and operating MOVs. Discussions with AmerGen Energy revealed that other Appendix R, III.G.2. areas of OCNGS also implement unapproved manual actions.

Analysis.

Inspection procedure 71111.05T (issue date February 18, 2005) states that, If the inspectors determine that manual actions are reasonable and are expected to meet the criteria outlined in Enclosure 2, then the inspection report will identify this issue as a green finding pending the Commissions acceptance of the proposed staff initiative to incorporate the use of manual actions into Section III.G.2 of the code. (The green finding is an indicator that while compensatory measures in the form of manual actions have been implemented and are acceptable, the licensee continues to be in violation of the code requirements). If the inspectors determine that the manual actions are not reasonably accomplishable and, therefore, implementation may not lead to a safe plant condition, the preliminary finding will be identified as potentially greater than green and entered into the significance determination process (SDP).

The team determined that,

(1) adequate diagnostic instrumentation was provided to detect spurious actuation of equipment and accomplishment of manual actions;
(2) the environmental conditions potentially encountered by the operator(s) while accessing and performing the manual actions were reasonable;
(3) staffing was sufficient and training adequate;
(4) procedures were available for performing the planned manual action; (5)communication means had been provided;
(6) when necessary, special tools had been dedicated and made available for use;
(7) the equipment requiring manipulation was accessible; and
(8) the AmerGen Energy fire protection team had confirmed their ability to perform the required manual actions within the specified time. Therefore, the team concluded that the manual actions were reasonable and were expected to meet the criteria of Enclosure 2.
Enforcement.

Title 10 of the Code of Federal Regulations (CFR), Part 50.48, Fire Protection, and 10 CFR Part 50, Appendix R, Fire Protection Program for Nuclear Power Facilities Operating Prior to January 1, 1979," establish specific fire protection features required to satisfy 10 CFR Part 50, Appendix A, General Design Criterion 3, Fire Protection. Appendix R applies to licensed nuclear power stations that were operating prior to January 1, 1979, which includes OCNGS.Section III.G.2 of Appendix R to 10 CFR Part 50 requires that, where cables or equipment, including associated non-safety circuits that could prevent operation or cause maloperation due to hot shorts, open circuits, or shorts to ground, of redundant trains of systems necessary to achieve and maintain hot shutdown conditions are located within the same fire area outside of primary containment, one of the following means of ensuring that one of the redundant trains is free of fire damage shall be provided:

a.

Separation of cables and equipment and associated non-safety circuits of redundant trains by a fire barrier having a 3-hour rating. Structural steel forming a part of or supporting such fire barriers shall be protected to provide fire resistance equivalent to that required of the barrier; b.

Separation of cables and equipment and associated non-safety circuits of redundant trains by a horizontal distance of more than 20 feet with no intervening combustible or fire hazards. In addition, fire detectors and an automatic fire suppression system shall be installed in the fire area; or c.

of cable and equipment and associated non-safety circuits of one redundant train in a fire barrier having a 1-hour rating. In addition, fire detectors and an automatic fire suppression system shall be installed in the fire area.

Contrary to the above, the team found that, at OCNGS, AmerGen Energy included manual actions in the fire protection safe shutdown analysis for Appendix R, III.G.2, fire areas, to operate equipment necessary for achieving and maintaining hot shutdown.

Several of these manual actions did not meet the requirements of Appendix R,Section III.G.2. and the NRC had not granted exemptions to allow these actions. This issue was determined to be of very low safety significance because OCNGS application of manual actions met the criteria established in IP 71111.05T, Enclosure 2, and was entered into the OCNGS corrective action program (IR 00394035). This violation is being treated as an NCV, consistent with Section VI.A of the NRC Enforcement Policy:

NCV 05000219/2005008-01, Failure to Provide Protection in Accordance with 10 CFR Part 50, Appendix R, Section III.G.2. This unresolved item is closed.

4OA6 Meetings, Including Exit

Exit Meeting Summary

The team presented their preliminary inspection results to Mr. B. Swenson, Site Vice President, and other members of the site staff at an exit meeting on November 4, 2005.

No proprietary information was included in this inspection report.

ATTACHMENT:

SUPPLEMENTAL INFORMATION

KEY POINTS OF CONTACT

AmerGen Energy Personnel

B. Swenson, Site Vice President
M. Button, Site Engineering Director
J. ORouke, Site Engineering Director (Assistant)
A. Aggarwal, Electrical Engineer
H. Behrens, HR Manager
R. Brown, Operations
J. Camire, BOP Systems Manager (Acting)
M. Carlson, Fire Protection Program Engineer
J. Dontal, Shift Operations Superintendent
M. Heck, ELU System Engineer
S. Hutchins, Electrical and I&C Manager
J. ORouke, Assistant Site Engineering Director
R. Milos, Reg. Assurance Engineer
T. Powell, Engineering Programs Manager
C. Pragman, Corporate Fire Protection Program Manager
T. Prosser, Fire Marshal
H. Sharma, Electrical Design Engineer
B. Sullivan, Operator
T. Trettel, Fire Protection System Manager

NRC

J. Rogge, Chief, Engineering Branch 3, Division of Reactor Safety
M. Ferdas, Senior Resident Inspector, Oyster Creek Nuclear Generating Station

LIST OF ITEMS OPENED, CLOSED, AND DISCUSSED

Opened

NONE Open and

Closed

05000219/2005008-01 NCV Failure to Provide Protection in Accordance with 10 CFR Part 50, Appendix R, Section III.G.2. (Section 4OA5.01)

Closed

05000219/2002011-01 URI Spurious Operation of an Electromatic Relief Valve (EMRV) and Manual Operation of Core Spray (Section 4OA5.01)

Discussed

NONE

LIST OF DOCUMENTS REVIEWED